THE DURABILITY AND PERFORMANCE OF POLYMER HOUSED METAL OXIDE SURGE ARRESTERS UNDER IMPULSE CURRENT STRESSES K Lahti, K Kannus and K Nousiainen Tampere University of Technology, Finland Unexpectedly, many failures of modern MOA types have occurred in some laboratory tests where arresters are stressed with either multipulses or series of impulse current stresses. In this paper the effects of internal humidity content on the internal flashover failure tendency were studied. The test results are discussed and compared to the results of a dry impulse current stress series conducted earlier on arresters of the same types at Tampere University of Technology Test procedures and failure cases A total of eight different types of commercially available, new, distribution class, gapless polymer housed metal oxide surge arresters were used in the tests. In addition to this two older specimens, previously used in networks, were also tested. The arresters were from seven manufacturers from both Europe and North America. The total number of test specimens was 20. The procedures of the cyclic test series are described in Fig. 1 (total duration of the test was 100 weeks). Every week the MOAs were subjected to a +50°C water bath for 6 days. Every week accurate internal leakage current (e.g. LC) measurements were performed to check the water content penetrated into the MOAs. Between every humidity stress period an impulse current stress series was applied to the MOAs. Internal flashover occurred during the test in 12 (out of 20) of the arresters tested. Three of the other eight specimens failed (short circuited) during the test due to heavy moisture ingress, in three of the arresters some moisture ingress was measured but the test could be completed and in two of the arresters no humidity + 50oC water immersion, 6 days LC (dc) measurements + impulse current stress + 50oC water immersion, 6 days Fig. 1. One cycle of the test series TABLE 1 −Flashover failure cases Failure at Arrester Power losses before failure at Uc [W] Even very stringent environmental factors may stress metal oxide surge arresters (MOAs) during their fairly long desired life time (20 – 50a). For example, a large number of impulses, ambient humidity and rain will cause remarkable stresses on MOAs especially in regions of high lightning activity. Detailed data on the effects of different stresses on MOA performance are difficult to obtain from field experiences because these experiences are often based on failure cases and failed arresters are normally burned with power arcs to such a condition that only general assumptions of the initial reason of the failure can be made. Either exhaustive laboratory tests or instrumentation of arresters in field service is needed to gather thorough information. PD + LC (ac+dc) measurements + impulse current stress Arrester structure SUMMARY week impulse no 4.3 I 376 38 A1 10.3 I 951 96 B1 1.0, 0.9, 1.0 III 2, 4, 50 C1 − C3 1, 1, 5 >100, >200 F1, F2 46, 46 ~460, ~460 III 0.7, 0.7, 1.4 II I1 − I3 2, 2, 2 20, 12, 14 19.6 I* 244 25 A3o 3.8 II* 145 15 E3o *Older model of the type A or E arrester. ingress was measured. No internal flashovers occurred in these eight specimens. Some details of the flashover incidences are given in Table 1. Conclusions The internal moisture contents caused by the ca. two year test series in stringent conditions had clear effects on the internal flashover tendency in only one arrester type (F) which has considerable internal air spaces. Arrester types with tight glass fibre reinforced epoxy tube around the MO discs did not exhibit this tendency even in cases of very high internal power losses. The types with housing moulded directly on the arrester inner parts had only moderate internal power loss increases and no clear effects of this to failure cases could be shown. Surprisingly, many internal flashover failures occurred during the test series with only moderate impulse current stresses (12 out of 20 arresters failed). Almost all the failure cases were flashovers over one or more MO discs and failures occurred for most of the arrester types tested. The main reason for the failures must be related to the voltage stress caused by longer duration of the test impulses (2.5/70µs) compared to typical standard current impulse (8/20µs). LA DURABILITE ET LA PERFORMANCE DES PARAFOUDRES A OXYDE DE ZINC A ENVELOPPE SYNTHETIQUE SOUS CHOCS DE SURTENSIONS K Lahti, K Kannus and K Nousiainen Université de Technologie de Tampere, Finlande De façon inattendue, beaucoup de cas de défaillance des types modernes de POZ ont eu lieu pendant les tests en laboratoire lorsque les parafoudres ont été soumis à des multipulsions ou aux chocs de surtension. Dans ce document, l’impact du contenu de l’humidité intérieure sur la tendance de défaillance des arcs est étudié. Les résultats des tests sont énoncés et comparés aux résultats d’une série d’impulsions de surtension à sec conduite sur des parafoudres du même type antérieurement à l’Université de Technologie de Tampere. Procédures de tests et cas de défaillance Au total, huit différents types de parafoudres à oxyde de zinc sans trou, disponibles dans le commerce, neufs et de classe de distribution ont été utilisés dans les tests. De plus, on a testé deux spécimens plus âgés précédemment utilisés dans le réseau. Les parafoudres provenaient de sept fabricants d‘Europe et d’Amérique du Nord. Le nombre total de spécimens de test était 20. Les procédures des séries de tests cycliques sont durée totale 100 semaines. Chaque semaine, les POZ étaient immergés dans une eau à +50ºC pendant six jours. Chaque semaine, le courant continu (CC) était mesuré pour vérifier le contenu de l’eau pénétrée dans les POZ. Entre chaque période d’agression d’humidité, des séries d’agressions de courants continus ont été appliquées sur les POZ. A1 B1 C1 − C3 F1, F2 I1 − I3 A3o E3o Défaillance à semaine Nombre d’impulsions 38 96 1, 1, 5 46, 46 2, 2, 2 25 15 376 951 2, 4, 50 ~460, ~460 20, 12, 14 244 145 I I III III II I II Baisse de tension avant défaillance à Uc [W] TABLEAU 1 – Cas de défaillance d’arcs Structure de parafoudre Même les conditions environmentales très rigoureuses peuvent avoir un impact sur les parafoudres à oxyde de zinc (POZ) pendant la durée d’utilisation souhaitée (20 – 50 ans). Par example, le nombre élevé d’impulsions de choc, l’humidité ambiante et la pluie exercent des agressions importantes sur les POZ, surtout dans les régions d’intenses activités de foudres. Il est difficile d’obtenir, à partir des expériences de terrain, des données précises sur l’impact de différentes aggressions sur les POZ, parce que ces expériences sont souvent basées sur les cas de défaillance et parce que les parafoudres défaillis sont d’habitude brûlés avec les arcs de telle sorte qu’il n’est possible d’avancer que des hypothèses générales sur la raison originale de défaillance. Pour obtenir des informations approfondies, on a besoin de faire soit des tests minutieux en laboratoire soit des études de mécanismes des parafoudres sur le terrain. L’arc interne a eu lieu dans 12 (des 20) parafoudres testés. Trois des huit autres spécimens ont défailli (court-circuités) pendant le test à cause de la formation importante d’humidité, dans trois des parafoudres certaine formation d’humidité était mesurée mais le test pouvait être poursuivi jusqu’à la fin, et dans deux des parafoudres aucune humidité n’était mesurée. Il n’y a pas eu d’arcs internes dans ces huit spécimens. Certains détails sur les incidences d’arcs sont donnés dans le Tableau 1. Parafoudre RÉSUMÉ 4.3 10.3 1.0, 0.9, 1.0 >100, >200 0.7, 0.7, 1.4 19.6 3.8 Conclusions La formation d’humidité intérieure causée par les séries de tests pendant près de deux ans, dans des conditions rigoureuses, a eu un impact net sur la tendance des arcs internes seulement dans un type de parafoudres (F), qui a des espaces d’air internes importants. Les types de parafoudres munis d’un solide tube époxy renforcé de fibre de verre autour des disques d’OZ n’ont pas présenté cette tendance même en cas de baisses de courant internes très élevées. Les types ayant l’enveloppe attachée directement sur les parties internes de parafoudres avaient seulement des augmentations modérées de baisses de courant internes, et il n’était pas possible de démontrer l’impact clair de cela sur les cas de défaillance. Étonnamment, beaucoup de défaillances d’arcs internes ont eu lieu pendant les séries de tests lorsque les chocs de surtensions étaient modérés (12 des 20 parafoudres ont défailli). Presque toutes les défaillances étaient des arcs sur une ou plusieurs disques d’OZ, et les défaillances sont arrivées à la plupart des types de parafoudres testés. La raison principale de défaillance doit être liée aux chocs de tension causés par la durée plus longue d’impulsions de test (2.5/70µs) comparées à des impulsions typiques de courant standard (8/20µs). THE DURABILITY AND PERFORMANCE OF POLYMER HOUSED METAL OXIDE SURGE ARRESTERS UNDER IMPULSE CURRENT STRESSES K Lahti, K Kannus and K Nousiainen Tampere University of Technology, Finland ARRESTERS TESTED A total of eight different types of commercially available, new, distribution class, gapless polymer housed metal oxide surge arresters were used in the tests. In addition to this, two older specimens previously used in networks, were also used. The arresters were from seven manufacturers in both Europe and North America. The total number of test specimens was 20. The eight commercial arrester types cover a wide range of polymer arrester technology available today. Some properties of the arresters tested are listed in Table 1. The exact housing material recipes are not known to the authors. ‘Moulded housing’ in the table refers to a housing moulded directly onto the arrester body. The The internal gas space was evaluated by dismantling the arresters and checking the interfacial area between housing and inner structure visually. The types with ‘moulded housings’ could not be checked because the housings could not be dismantled without destroying them. 20 20 18 18 17 19.5 24.4 19.5 Uc EPDM EPM X X X X X X X 5 4 6 4 4 4 3 3 Test specimens Nos. Silicone Silicone EPDM EPDM EPDM EPM Silicone Silicone Thickness of housing between sheds [mm] A B C D E F H I Moulded housing Internal gas spaces or voids TABLE 1 -ARRESTER TYPES TESTED Uc [kV] Unexpectedly many failures of modern MOA types have happened in some laboratory tests where arresters are stressed with either multipulses [1] or series of impulse current stresses [2]. The typical failure mode in these tests was an internal flashover over one or more metal oxide discs in an MOA. In this paper the effects of internal humidity content on the internal flashover failure tendency are reported. The polymer housed arresters tested were exposed to a humidity stress in such a way that internal humidity content in the arresters gradually increased. At the same time impulse current stress series were regularly applied to the specimens. The test results are discussed and compared to the results obtained in a similar impulse current stress series [2] conducted earlier on arresters of the same types at Tampere University of Technology. In that test series only impulse current stresses were applied on arresters without any other stresses. The two older specimens, A3o and E3o, were 1991 models of the arrester types A and E. The data given in Table 1 are also valid for these arresters with the exceptions that the Uc –value of specimen E3o is 18 kV and A3o has an internal gas space. Nominal discharge current (In) of all the arresters was 10 kA. Housing material Metal oxide surge arresters (MOAs) can be exposed even to very stringent environmental conditions during their fairly long desired life time (20 – 50a). For example, a large number of impulses, ambient humidity and rain will cause remarkable stresses on MOAs especially in regions of high lightning activity. Detailed data of the effects of different stresses on MOA performance are difficult to obtain from field experiences because these experiences are often based on occasional failure cases. Failed arresters are normally burned with power arcs in such a way that only general assumptions of the initial reason of the failure can be made. Either exhaustive laboratory tests or instrumentation of arresters in field service are needed to gather thorough information. arrester types marked in the ‘internal gas space’ column have a mechanical structure allowing an internal air space. The arresters of type F have a considerable internal gas space (total 5-10 cm3 ), while the arresters of types E and I have smaller voids inside (some mm3 or less). In type D arresters the interface between the housing and the arrester body is sealed using an elastic sealing paste. Arrester type INTRODUCTION A1, A2, A3o B1, B2 C1, C2, C3 D1, D2 E1, E2, E3o F1, F2 H1, H2 I1, I2, I3 Max. continuous operating voltage according to IEC 60099-4 Ethylene-propylene diene monomer Ethylene-propylene monomer Mechanical Structure of the Specimens Moisture can penetrate polymer housed arresters by diffusion through polymer material or by capillary effect because of leaks/cracks in the end cap sealings or housing. Interfaces between different materials are the potential areas where moisture can form a conducting layer along the arrester. The area into which the humidity will first form a conducting layer inside an arrester depends on the mechanical structure of the arrester. In this paper we report internal flashovers in arresters and the probability of moisture in the flashover path is of great interest. The arrester types are divided PD + LC (ac+dc) measurements + impulse current stress + 50oC water immersion, 6 days LC (dc) measurements + impulse current stress TEST ARRANGEMENTS AND PROCEDURES The total testing time was ca. 2 years and arresters which did not fail during the test gathered thus totally 1000 impulses. As an exception the arresters of type H were taken later on the test series and they were tested for ca. 20 months (800 impulses). TABLE 2 – ARRESTER TYPES ACCORDING TO INTERNAL STRUCTURE. Fig. 1 One cycle of the test series RESULTS AND DISCUSSION General Results and Failure Cases Internal flashover occurred during the test in 12 (out of 20) of the arresters tested. Three of the other eight specimens failed (short circuited) during the test due to heavy moisture ingress (D1, D2, E2), in three of the arresters some moisture ingress was measured but the test could be carried out to the end (A2, B2, E1) and in two of the arresters no humidity ingress was measured (H1, H2). No internal flashovers occurred in these eight specimens. Some details of the flashover incidences are given in Table 3. AC power loss and residual voltage curves for all the arresters (except arresters of type C and I) are given in Figs 2 – 8. These parameters give an indication of the internal humidity content inside an MOA and the impulse current behaviour of an MOA. The arresters of type C and I failed during the first two test weeks and power loss or residual voltage trends were thus not gathered before the failures. Considerable partial discharge activity was measured in MOAs D1, D2, B1, E2 and E3o during the test and some activity also in MOAs A2, B2 and A3o [3]. TABLE 3 −Flashover failure cases Failure at Arrester week impulse no 4.3 A1 38 376 I 10.3 B1 96 951 I 1.0, 0.9, 1.0 2, 4, 50 III C1 − C3 1, 1, 5 >100, >200 F1, F2 46, 46 ~460, ~460 III 0.7, 0.7, 1.4 2, 2, 2 20, 12, 14 II I1 − I3 19.6 244 I* 25 A3o 3.8 II* 15 145 E3o *Older model of the type A or E arrester. MOA types I A, B II D, E, I III C, F IV H Housing moulded directly on MO disc surfaces, mechanical support strips inside housing material Tight glass fibre reinforced epoxy tube on the surface of MO discs, separately manufactured housing Untight glass fibre reinforced epoxy support (net) on the surface of MO discs Housing moulded directly on MO disc surfaces, glass fibre reinforced epoxy tube with openings inside housing material 100 AC losses, A1 AC losses, A2 Residual voltage, A1 Residual voltage, A2 45 AC power loss at Uc (W) Group 50 Description Power losses before failure at Uc [W] Between every humidity stress period an impulse stress series was applied to the MOAs. The impulse current test procedure was the following: The MOA was stressed with five positive current impulses followed by five negative current impulses. The time interval between the current impulses was on average 1.5 minutes and a total of 10 current impulses were applied to an arrester in approximately 20 minutes. The peak value of the current impulses varied from 1.7 to 2.7 kA depending on the type of the MOA tested. The wave shape of the current impulses with MOAs was approximately 2.5 / 70 µs defined according to IEC 60060-1. The front steepness of the voltage curve during the current impulses with MOAs (measured from the residual voltage recordings) was 400 − 480 kV/µs. The energy stress of one impulse to an arrester was approximately 10 kJ. + 50oC water immersion, 6 days Group (Table 2) In this test the arresters are subjected to a humidity stress due to which internal moisture in MOAs gradually increases. The content of the test series is described in Fig. 1. Every week the MOAs were subjected to a +50°C water bath for 6 days in order to cause a relatively fast moisture diffusion inside the test specimens. Every second week accurate AC power loss (Leakage Current, e.g. LC) measurements were performed (at Uc voltage) to check the water content penetrated into the MOAs. Internal DC leakage current, partial discharge and electro magnetic radiation measurements were also performed. These results are presented in [3]. The DC leakage current measurements were performed both before and after the impulse current stressings to find out possible changes caused by that stress. Residual voltages were measured each week to check the impulse current performance of the MOAs. 40 35 90 80 70 30 60 25 50 20 40 15 30 10 20 5 10 0 Residual voltage (kV) into groups according to their internal structure in Table 2. 0 0 20 40 60 80 100 Test time (weeks) Fig. 2. Residual voltage and AC power loss measurements for MOAs A1 and A2 during the test. 30 60 25 50 20 40 15 30 10 20 5 10 0 0 0 20 40 60 Test time (weeks) 80 35 50 90 45 80 40 60 25 50 20 40 15 30 10 20 5 0 20 40 60 Test time (weeks) 80 40 35 70 60 20 10 0 0 0 0 70 50 20 40 15 30 10 20 5 10 0 100 Fig. 5. Residual voltage and AC power loss measurements for MOAs E1 and E2 during the test. 20 40 60 Test time (weeks) 80 100 Fig. 8. Residual voltage and AC power loss measurements for MOAs A3o and E3o during the test. MOA A1 failed at the 376th impulse. An internal flashover occurred over one (lowest) MO disc (Fig. 9A). Power losses rose slightly during the test from the initial value of 2.1W to 4.3W before the failure and some internal humidity was thus present inside the MOA when the flashover happened. MOA B1 failed at 951st impulse. An internal flashover happened over the whole length of the arrester along the surface of a glass fibre reinforced epoxy strip. The strip was inside silicone housing material. Power losses rose during the test from the initial value of 1.2W to 10.3W. A change of power losses occurred few weeks before the final failure (Fig. 3) and a prefailure may thus have occurred then. Some moisture was, at least, present inside the MOA during the failure. 100 90 40 80 AC losses, F1 AC losses, F2 Residual voltage, F1 Residual voltage, F2 35 30 25 70 60 50 20 40 15 30 10 20 5 10 0 Residual voltage (kV) 45 AC power loss at Uc (W) 30 80 5 100 50 35 10 80 80 90 30 60 40 60 Test time (weeks) 100 AC losses, A3o AC losses, E3o Residual voltage, A3o Residual voltage, E3o 10 25 20 0 100 40 30 0 80 15 90 0 40 60 Test time (weeks) 50 Residual voltage (kV) AC power loss at Uc (W) 45 20 20 100 AC losses, E1 AC losses, E2 Residual voltage, E1 Residual voltage, E2 20 25 Fig. 4. Residual voltage and AC power loss measurements for MOAs D1 and D2 during the test. 50 30 Fig. 7. Residual voltage and AC power loss measurements for MOAs H1 and H2 during the test. 100 70 40 5 0 30 0 10 50 10 Residual voltage (kV) AC power loss at Uc (W) 40 60 AC losses, H1 AC losses, H2 Residual voltage, H1 Residual voltage, H2 15 100 AC losses, D1 AC losses, D2 Residual voltage, D1 Residual voltage, D2 45 70 0 Fig. 3. Residual voltage and AC power loss measurements for MOAs B1 and B2 during the test. 50 80 20 Residual voltage (kV) 70 25 Residual voltage (kV) 80 AC power loss at Uc (W) 35 90 90 AC power loss at Uc (W) AC power loss at Uc (W) 40 100 30 100 AC losses, B1 AC losses, B2 Residual voltage, B1 Residual voltage, B2 45 Residual voltage (kV) 50 0 0 20 40 60 Test time (weeks) 80 100 Fig. 6. Residual voltage and AC power loss measurements for MOAs F1 and F2 during the test. Arresters of types C and I failed very soon after the test was started (Table 3). In all the cases the failures were internal flashovers over one or more MO discs. The power losses were at initial level before the failures and failure processes were thus not affected by internal humidity. Arresters F1 and F2 degraded gradually during the test. The final internal flashovers occurred after ca. 460 impulses. Partial degradation started much earlier as can be seen in the residual voltage curves in Fig. 6. Flashovers over MO discs have thus happened much earlier than after the 460 impulses. A very high internal leakage current caused by internal humidity flowed inside the arresters, which very obviously affected the flashover events. A flashover over one MO disc in MOA F1 can be seen in fig. 9B. A B Fig. 9. Flashover failure over one MO disc in MOA A1 (A) and in MOA F1 (B). MOA A3o failed at 244th impulse when an internal flashover occurred over several MO discs in the hole inside of the MO discs where a mechanical support bar is assembled. Power losses of the arrester increased during the last few weeks before the failure. The final losses were 19.6W while the initial level was 2.8W. MOA E3o failed at 145th impulse. In this case an internal flashover also occurred between MO discs and glass fibre reinforced epoxy tube around the discs. The power losses increased during the test from the initial level of 0.5W to 3.8W. Internal Humidity vs. Flashover Failures Similar impulse current stress series without any moisture stress have been conducted earlier at Tampere University of Technology [2] for most of the arrester types studied in this test. In that test series exactly similar impulse current stresses (5+5 impulses of ~2kA, 2.5/70µs in 20 minutes) were applied to the test specimens once a day or less frequently. No other stresses were applied to those arresters. Nine arresters out of 48 specimens studied failed during the test series. Failure cases of arrester types similar to the types in this test series are indicated in Table 4. All the failure cases (except one) were internal flashovers over the MO disc(s) of an arrester. In one case (type A, failure at 14th impulse) a current channel was found in one MO disc after the failure. The possible effects of internal moisture on internal flashover failure probability are discussed in the following based on the results of the two test series. TABLE 4 –Failures due to impulse current stress without any other stresses conducted [2]. MOA type / type No of specimens / Failed at index at [2] No of failure cases impulse A / 300* + 350 18 / 2 9th, 14th C / 900 2/1 9th D / 100 6/0 E / 500 6/2 121st, 527th I / 950 2/2 51st, 93rd A3o / 390 2/1 882nd *Same as type A but Uc=22kV, type 350 same as type A Type A: 1 out of 2 MOAs failed in these tests with moisture stress and 2 of 18 in the dry test series. The failure of MOA A1 was an internal flashover failure over one MO disc similar to the other failure case in the ‘dry test series’. The internal power losses due to humidity ingress were moderate (max total losses ~10W). The arrester A1 failed already when the internal power losses were ca. 5W while the other test specimen, A2, stood up the whole test series without a failure with power losses over 10W during the last half of the testing period (ca. 1 year and 500 impulses). The mechanical structure of type A is such that the conductivity formed by internal moisture is most likely located in the interface between the housing material and MO discs, which is also the area where the flashovers occurred. In any case, according to these results the moderate amounts of internal moisture did not notable affect the flashover probability of this type. Older type A: The arrester A3o failed in the ‘wet test’ and one MOA out of two failed in the ‘dry test series’. Both failure cases were totally similar internal flashovers but A3o failed after a much lower number of impulses than the MOA in ‘dry series’. Some moisture was inside MOA A3o during the failure and this may have had a slight effect on the failure if it was on the area where the arc burned. Type B: 1 out of 2 MOAs of this type failed in these tests. This type was not studied in the ‘dry test series’. Internal power losses for this type were at a moderate level during the test. The one failure case was different from all the other cases in these tests. Humidity may have partially caused this failure because humidity most likely first penetrates the interface between the housing and mechanical support strip where the flashover also occurred. Clear evidence of this, however, cannot be evinced. Types C and I: Internal flashovers occurred in all the arresters of these types with only one exception (in the ‘dry test series’). The failures were all similar flashovers over MO discs in both test series and occurred typically almost immediately after the impulse stress was started. No remarkable increases of internal power losses were measured for these MOAs. The flashover cases were thus typical for these MOA types and these failure cases were not affected by any internal moisture in the arresters. Type D: No flashovers occurred in either of the test series. Power losses caused by internal moisture reached very high levels in MOAs D1 and D2 but the moisture did not cause any problems for the impulse current behaviour of the arresters. In any case, the conducting layer formed by the moisture was most likely at the interface between housing and the tight glass fibre reinforced epoxy tube and not between the tube and the MO discs where the flashovers are most likely. Type E: Two failures out of six specimens occurred in the ‘dry test series’. No flashovers occurred in the two MOAs in the tests with moisture stressing but the older arrester E3o had a flashover. These three cases were similar flashovers over MO discs. Not even very high internal moisture content (E2) caused problems in the impulse current behaviour of the arrester. The structure of this type is similar to the type D above and also in this case the humidity was most probably not in the area where flashovers typically occur. even high conductivities caused by internal humidity will typically cause such effects when MO discs are covered by tight glass fibre epoxy tube and the moisture remains outside the tube (types D and E). In structures with housing moulded directly on the inner parts of the MOA very high internal conductivity is not typically reached and internal humidity will thus not cause flashover problems. Type F: Internal flashovers occurred in these arresters when high internal humidity content was measured. The flashover events were very probably caused by the moisture but power losses of 50W or more were needed (see Fig. 6) to start the problems. Even much lower power losses would fail an arrester immediately under service AC stress. The internal structure of the type has considerable internal air space and humidity penetrating this space would be in contact with the MO disc surfaces. CONCLUSIONS Type H: No flashovers occurred for this type and nor did any measurable humidity penetrate inside the arrester structure during the stringent humidity stress. Thus the effect of internal moisture cannot be evaluated but the service behaviour of this type under these stresses appears excellent. The number of test specimens was limited and only major effects of moisture could thus be seen in the results. According to the results the internal moisture seemed to have a clear effect on the internal flashover probability only in case of type F arresters, when a considerable amount of moisture was present on the surface of the MO discs where the flashover probability is highest. The amount of moisture needed for those immediate reactions was so high that the MOAs would have failed much earlier under normal service AC stress. Such a high number of internal flashover failures in both tests is in any case astonishing and must be related to the long impulse (2.5/70µs). Peak values (~2kA) and energy (~10kJ) of the impulses should be easily handled with these In=10kA MOAs. The parameters of these impulses are also quite normal compared to real lightning surges [4]. The test with longer impulse actually acts as a voltage stress for the whole MOA structure. This kind of stress is not included in the IEC 60099-4 standard and it should be considered whether voltage stress using long current impulse should be included there. Similar flashover failures have also occurred with multipulse stresses [1] which introduce also a long voltage stress as the impulses used in our tests. Arrester Internal Structure vs. Flashover Failures Arresters with internal air space(s) between the internal parts and housing are problematic with respect to seal integrity [5]. When the air space also reaches the surfaces of the MO discs possible internal moisture may also cause internal flashover problems (type F). Not The internal moisture contents caused by the ca. twoyear test series in stringent conditions had clear effects on the internal flashover tendency only in one arrester type. High internal power losses due to the humidity was, anyhow, needed to cause the effects. Arrester types with tight glass fibre reinforced epoxy tube around the MO discs did not show this tendency even in case of very high internal power losses. The types with housing moulded directly on the arrester inner parts had only moderate internal power loss increases and no clear effects of this on failure cases could be shown. Surprisingly, many internal flashover failures occurred during the test series with only moderate impulse current stresses (12 out of 20 arresters failed). Almost all the failure cases were flashovers over one or more MO discs and failures occurred for most of the arrester types tested. The main reason for the failures must be related to the voltage stress caused by the longer duration of the test impulses (2.5/70µs) compared to typical standard current impulse (8/20µs). REFERENCES [1] Darveniza M., Tumma L. R., Richter B. and Roby D.A.,1997, ”Multipulse lightning currents and metal-oxide arresters”, IEEE Transactions on Power Delivery, 12, 1168-1175. [2] Kannus K., Lahti K., Nousiainen K., 1999, ”Effects of impulse current stresses on the durability and protection performance of metal oxide surge arresters”, ISH’99, vol 2, London, UK, 4 p. [3] Lahti K., Pakonen P., Kannus K., Nousiainen K., 1999, ”Possibilities to reveal internal moisture in polymeric surge arresters by means of PD and EMR measurements”, IEEE Power Tech’99, Budapest, Hungary, 6 p. [4] Anderson R. B., Eriksson A. J., 1980, ”Lightning parameters for engineering application”, Electra, No 69, 65 – 102. [5] Lahti, K., Richter, B., Kannus, K., Nousiainen, K., 1999, ”Internal degradation of polymer housed metal oxide surge arresters in very humid ambient conditions”. ISH’99, vol. 2, London, UK, 4 p.