Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO MICRON Fab 10A Project Sequence of Operations For Heat Recovery Water System (Phase A1) Document Reference: 86165 2 ENG 8608 SOO 005 Engineer Responsible for System Vynus Engineer Responsible for SOO & P&ID Vynus / Palani Rev. 0 Comment Initial Release for Review By Vynus Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Date 24 Sep 2018 Page 1 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO CONTENTS 1 REFERENCE DOCUMENTS.................................................................................................................. 4 1.1 1.2 1.3 1.4 2 GENERAL INFORMATION .......................................................................................................................... 4 SYSTEM PROCESS AND INSTRUMENTATION DRAWINGS (P&ID’S) .............................................................. 4 OTHER RELEVANT DOCUMENTS................................................................................................................ 4 GENERAL................................................................................................................................................ 4 KEY EQUIPMENT AND INSTRUMENTS ............................................................................................ 5 2.1 KEY EQUIPMENT ITEMS............................................................................................................................ 5 2.1.1 Heat Exchangers .......................................................................................................................... 5 2.1.2 Pumps ........................................................................................................................................... 5 2.1.3 Valves (ON/OFF) .......................................................................................................................... 5 2.1.4 Valves (Modulating)...................................................................................................................... 5 2.1.5 Other key equipment items ............................................................................................................ 6 2.2 KEY INSTRUMENTS.................................................................................................................................. 6 2.2.1 Pressure instruments ..................................................................................................................... 6 2.2.2 Flow instruments........................................................................................................................... 6 2.2.3 Temperature instruments .............................................................................................................. 6 2.2.4 Analytical instruments .................................................................................................................. 7 2.2.5 Miscellaneous other instruments ................................................................................................... 7 3 OVERALL SYSTEM DESCRIPTION .................................................................................................... 8 3.1 3.2 4 SYSTEM OVERVIEW ................................................................................................................................. 8 SUB-SYSTEMS ......................................................................................................................................... 8 SUB-SYSTEM FUNCTIONAL DESCRIPTIONS ................................................................................ 10 4.1 SUB-SYSTEM 1 – HRW DISTRIBUTION PUMPS......................................................................................... 10 4.1.1 General description .................................................................................................................... 10 4.1.2 Key equipment items ................................................................................................................... 10 4.1.3 Key instruments .......................................................................................................................... 10 4.1.4 Start-Up...................................................................................................................................... 10 4.1.5 Normal operation (“Auto”)......................................................................................................... 11 4.1.6 Shut-Down .................................................................................................................................. 12 4.1.7 Interlocks.................................................................................................................................... 12 4.1.8 Interfaces with other systems ...................................................................................................... 12 4.1.9 FMCS parameter displays........................................................................................................... 12 4.1.10 Switching between “Manual” and “Auto” .............................................................................. 13 4.1.11 “Local” control ..................................................................................................................... 13 4.1.12 Set-points / Warnings / Alarms ............................................................................................... 13 4.2 SUB-SYSTEM 2 – HRW HEAT EXCHANGERS ........................................................................................... 14 4.2.1 General description .................................................................................................................... 14 4.2.2 Key equipment items ................................................................................................................... 14 4.2.3 Key instruments .......................................................................................................................... 15 4.2.4 Start-Up...................................................................................................................................... 15 4.2.5 Normal operation (“Auto”)......................................................................................................... 15 4.2.6 Shut-Down .................................................................................................................................. 16 4.2.7 Interlocks.................................................................................................................................... 16 4.2.8 Interfaces with other systems ...................................................................................................... 16 4.2.9 FMCS parameter displays........................................................................................................... 16 4.2.10 Switching between “Manual” and “Auto” .............................................................................. 17 4.2.11 “Local” control ..................................................................................................................... 17 4.2.12 Set-points / Warnings / Alarms ............................................................................................... 17 4.3 SUB-SYSTEM 3 – MINIMUM FLOW .......................................................................................................... 18 Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 2 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.3.1 General description .................................................................................................................... 18 4.3.2 Key equipment items ................................................................................................................... 18 4.3.3 Key instruments .......................................................................................................................... 18 4.3.4 Start-Up...................................................................................................................................... 18 4.3.5 Normal operation (“Auto”)......................................................................................................... 18 4.3.6 Shut-Down .................................................................................................................................. 19 4.3.7 Interlocks.................................................................................................................................... 19 4.3.8 Interfaces with other systems ...................................................................................................... 19 4.3.9 FMCS parameter displays........................................................................................................... 19 4.3.10 Switching between “Manual” and “Auto” .............................................................................. 20 4.3.11 “Local” control ..................................................................................................................... 20 4.3.12 Set-points / Warnings / Alarms ............................................................................................... 20 4.4 SUB-SYSTEM 4 – HRW HEAT-LOAD CALCULATIONS .............................................................................. 21 4.4.1 General description .................................................................................................................... 21 4.4.2 Key equipment items ................................................................................................................... 21 4.4.3 Key instruments .......................................................................................................................... 22 4.4.4 Start-Up...................................................................................................................................... 23 4.4.5 Normal operation (“Auto”)......................................................................................................... 23 4.4.6 Shut-Down .................................................................................................................................. 23 4.4.7 Interlocks.................................................................................................................................... 23 4.4.8 Interfaces with other systems ...................................................................................................... 23 4.4.9 FMCS parameter displays........................................................................................................... 23 4.4.10 Switching between “Manual” and “Auto” .............................................................................. 24 4.4.11 “Local” control ..................................................................................................................... 24 4.4.12 Set-points / Warnings / Alarms ............................................................................................... 24 Appendix 1 Set-points / Warnings / Alarms Appendix 2 P&ID’s Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 3 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 1 Reference Documents 1.1 General Information Document F10A-SOO-000 – “General Information” contains generic information and guidelines that relate to all SOO’s for this project. If there is any contradiction between this document and F10A-SOO-000 – “General Information”, this document shall take precedence. 1.2 System Process and Instrumentation Drawings (P&ID’s) The following P&ID’s describe the Process Cooling Water system. Drawing Number Sht Rev. F10A-SCH-C1-01-MCHWT-003 1 2 F10A-SCH-C1-00-MCHWT-001 F10A-SCH-F0-00-MCHWT-003 1 1 3 2 1.3 Description CUP A1 Building Level 1 Chiller Plant Room Heat Recovery Water Schematic CUP A1 Building Chilled Water Schematic FAB1 Building Heat Recovery System Schematic Other relevant documents The following documents are related to the distribution of services from this system but do not contain any controls directly affecting this system. As such are not included in this systems boundary. Document Number Rev. Description N/A N/A 1.4 N/A General The sequence of operation and logic provided in this document is a general summary of the sequence and logic requirements. Preparation and updating of the detailed logic sequence for proper and efficient functioning of the respective systems and subsystems is within the full turnkey scope of the system integrator. If the intent of any part of the document is not clear, it is the responsibility of the system integrator to obtain clarification before commencing work. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 4 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 2 Key equipment and instruments The specific equipment items and instruments applicable to this system are tabulated below. 2.1 Key equipment items 2.1.1 Heat Exchangers Tag Descriptor C10A1-01-C161D-HRW-HX-01 (Future) C10A1-01-C161D-HRW-HX-02 (Phase 2) C10A1-01-C161D-HRW-HX-03 (Phase 1) C10A1-01-C171D-HRW-HX-04 (Phase 1) Function / Description Heat Recovery System Heat Exchangers 2.1.2 Pumps Tag Descriptor C10A1-01-C171D-HRW-PMP-01 (Future) C10A1-01-C171D-HRW-PMP-02 C10A1-01-C171D-HRW-PMP-03 C10A1-01-C181D-HRW-PMP-04 Function / Description Heat Recovery Water Pumps 2.1.3 Valves (ON/OFF) Tag Descriptor Function / Description C10A1-1-Cxxx-HRW-HX-01-FCV01 (Future) Cup Level 1 Heat Recovery Heat Exchanger 1 On/Off Valve Cup Level 1 Heat Recovery Heat Exchanger 2 On/Off Valve Cup Level 1 Heat Recovery Heat Exchanger 3 On/Off Valve Cup Level 1 Heat Recovery Heat Exchanger 4 On/Off Valve C10A1-1-Cxxx-HRW-HX-02-FCV01 C10A1-1-Cxxx-HRW-HX-03-FCV01 C10A1-1-Cxxx-HRW-HX-04-FCV01 2.1.4 Valves (Modulating) Tag Descriptor Function / Description C10A1-1-Cxxx-HRW-HX-01-TCV-01 (Future) C10A1-1-Cxxx-HRW-HX-02-TCV-01 Cup Level 1 Heat Recovery Heat Exchanger 1 Temperature Control Valve Cup Level 1 Heat Recovery Heat Exchanger 2 Temperature Control Valve Cup Level 1 Heat Recovery Heat Exchanger 3 Temperature Control Valve Cup Level 1 Heat Recovery Heat Exchanger 4 Temperature Control Valve C10A1-1-Cxxx-HRW-HX-03-TCV-01 C10A1-1-Cxxx-HRW-HX-04-TCV-01 Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 5 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO C10A1-1-Cxxx-HRW-HDR-PCV-01 Cup Level 1 Heat Recovery By-pass Safety Relief Pressure Control Valve 2.1.5 Other key equipment items Tag Descriptor Function / Description None 2.2 Key instruments 2.2.1 Pressure instruments Tag Descriptor Function / Description C10A1-1-Cxxxx-HRW-HDR01-PIT-01 C10A1-1-Cxxxx-HRW-HDR02-PIT-01 F10A1-x-Fxxx-HRW-HDR-PDIT-01 F10A1-x-Fxxx-HRW-HDR-PDIT-02 F10A2-x-Fxxx-HRW-HDR-PDIT-01 F10A2-x-Fxxx-HRW-HDR-PDIT-02 C10A2-x-Fxxx-HRW-HDR-PDIT-01 C10A2-x-Fxxx-HRW-HDR-PDIT-01 CUPA1-L-1 HRW SUPPLY HDR. PR.- Monitoring CUPA1-L-1 HRW RETURN HDR. PR.- Monitoring FABA1-L-x HRW Diff. PR. 01 - Pump Control FABA1-L-x HRW Diff. PR. 02 - Pump Control FABA2-L-x HRW Diff. PR. 01 - Pump Control FABA2-L-x HRW Diff. PR. 02 - Pump Control CUPA2-L-x HRW Diff. PR. 01 - Pump Control CUPA2-L-x HRW Diff. PR. 02 - Pump Control 2.2.2 Flow instruments Tag Descriptor Function / Description C10A1-1-Cxxx-CW-HDR-02-FIT-01 CUPA1-LEVEL 1 Condenser water return flowmeter from HRW CUPA1-LEVEL 1 HRW Supply header flow-meter to FabA1 FABA2-LEVEL x HRW Supply header flow-meter to FabA2 Level x CUPA2-LEVEL x HRW Supply header flow-meter to CupA2 Level x CUPA2-LEVEL x Condenser water return flowmeter from HRW C10A1-1-Cxxx-HRW-HDR-01-FIT-01 F10A2-x-Fxxx-HRW-HDR-01-FIT-01 C10A2-x-Cxxx-HRW-HDR-01-FIT-01 C10A2-x-Cxxx-CW-HDR-02-FIT-01 2.2.3 Temperature instruments Tag Descriptor C10A1-1-Cxxx-CW-HDR-01-TIT-01 C10A1-1-Cxxx-CW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 Function / Description CUPA1 LEVEL 1 Condenser water supply header temperature from HRW CUPA1 LEVEL 1 Condenser water return header temperature to HRW CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1-Control CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1-Control Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 6 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-CW-HDR-01-TIT-01 C10A2-x-Cxxx-CW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 C10A2-x-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 C10A2-x-Cxxx-HRW-HDR-02-TIT-01 CUPA1 LEVEL 1 HRW Return header temperature from CUPA1 CUPA1 LEVEL 1 HRW Supply header temperature to FABA1-Control CUPA1 LEVEL 1 HRW Supply header temperature from FABA1-Control CUPA1 LEVEL 1 HRW Return header temperature from FABA1 CUPA2 LEVEL x Condenser water supply header temperature from HRW CUPA2 LEVEL x Condenser water return header temperature to HRW CUPA2 LEVEL x HRW Supply header temperature to CUPA1-Control CUPA2 LEVEL x HRW Return header temperature from CUPA1 CUPA2 LEVEL x HRW Supply header temperature to FABA2-Control CUPA2 LEVEL x HRW Return header temperature from FABA2 2.2.4 Analytical instruments Tag Descriptor Function / Description None 2.2.5 Miscellaneous other instruments Tag Descriptor Function / Description None Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 7 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 3 Overall System Description 3.1 System Overview Four (4) heat exchangers are employed in parallel to transfer heat from the Condenser Water and into the Heat Recovery Water. The heat exchangers are sized to be 4 x 33.3% capacities. Design conditions are: Condenser water entering HEX Condenser water leaving HEX Heat Recovery water entering HEX Heat Recovery water leaving HEX : 35.0 oC 2.0 oC : 25.0 oC 2.0 oC : 20.0 oC 2.0 oC : 30.0 oC 2.0 oC The control system objective is to maintain the Heat Recovery Water discharged from the circulation pumps at 30.0 oC at all times. The Heat Recovery Water system is a closed system. A minimum flow is maintained through the heat exchangers via a Pressure control valve located between the Heat Recovery Water circulation pump discharge and return headers. The Heat Recovery water circulation pumps are VFD controlled with the pump frequency set using differential pressure between the supply and return pipes at endof-line, FAB level 1. Equipment Heat Recovery Heat Exchangers Heat Recovery Water Pumps 3.2 3 Equipment Quantity Standby Phase 1 3 1 2 4 3 Total Duty 1 Phase 2 1 Future 1 1 2 1 Sub-Systems The following Table identifies the sub-systems that the Overall system can be broken down into. Each sub-system will then be described in detail in Section 4.0 of this SOO document. No. 1 2 3 Sub-System Name Sub-System 1 – HRW Distribution Pumps Sub-System 2 – HRW Heat Exchangers Sub-System 3 – Minimum flow Functional Description Distribution of HRW to facilities Transfer condenser water heat to heat recovery fluid Provides minimum flow condition to pumps Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 8 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4 Sub-System 4 – HRW Heat-Load Calculations HRW heat load calculation Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 9 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4 Sub-system Functional Descriptions 4.1 Sub-System 1 – HRW Distribution Pumps 4.1.1 General description The Heat Recovery Water system is a closed loop circulated through 3 VFD driven pumps. The pump frequency is controlled by one of following options. End of line pressure transmitters located at FABA1 Level 1. End of line pressure transmitters located at FABA2 Level x. End of line pressure transmitters located at CUPA2 Level x. The above said options can be selected from FMCS SCADA. 4.1.2 Key equipment items 4.1.2.1 Pumps Tag Descriptor C10A1-01-C171D-HRW-PMP-01 (Future) C10A1-01-C171D-HRW-PMP-02 C10A1-01-C171D-HRW-PMP-03 C10A1-01-C181D-HRW-PMP-04 Function / Description Heat Recovery Water Pumps 4.1.3 Key instruments 4.1.3.1 Pressure instruments Tag Descriptor C10A1-1-Cxxxx-HRW-HDR01-PIT-01 C10A1-1-Cxxxx-HRW-HDR02-PIT-01 F10A1-x-Fxxx-HRW-HDR-PDIT-01 F10A1-x-Fxxx-HRW-HDR-PDIT-02 F10A2-x-Fxxx-HRW-HDR-PDIT-01 F10A2-x-Fxxx-HRW-HDR-PDIT-02 C10A2-x-Fxxx-HRW-HDR-PDIT-01 C10A2-x-Fxxx-HRW-HDR-PDIT-01 4.1.4 Function / Description CUPA1-L-1 HRW SUPPLY HDR. PR.- Monitoring CUPA1-L-1 HRW RETURN HDR. PR.- Monitoring FABA1-L-x HRW Diff. PR. 01 - Pump Control FABA1-L-x HRW Diff. PR. 02 - Pump Control FABA2-L-x HRW Diff. PR. 01 - Pump Control FABA2-L-x HRW Diff. PR. 02 - Pump Control CUPA2-L-x HRW Diff. PR. 01 - Pump Control CUPA2-L-x HRW Diff. PR. 02 - Pump Control Start-Up With no pumps running, the FMCS operator will normally initiate a HRW system start-up by clicking on a “HRW START BUTTON” on the HRW system graphic display. The FMCS will then execute the following start-up sequence: i) Heat Exchanger On/Off valves would be opened automatically. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 10 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO ii) Once valve open status confirmed, temperature control PID loop will be active and controlled by HRW supply temperature. iii) Pump Starts at minimum frequency. Pump would be controlled by end-of-line differential pressure transmitter. Ref above point no.4.1.1 4.1.5 Normal operation (“Auto”) 4.1.5.1 PID control In “Auto” mode, the frequency output of the VFD Driven Pumps maintains the end-of-line differential pressure. Two pressure differential transmitters located at FAB Level 1 between the Heat Recovery Water supply and return pipes is the primary instrument that controls the Heat Recovery Water pumps. Options also provided at FMCS SCADA for selecting the end-of-line differential pressure transmitter located at A2 area. Refer above point no. 4.1.1 4.1.5.2 Control logic The automatic control algorithm shall determine the number of pumps that need to run to satisfy the demand using the header pressure as the criteria for controlling pump speeds and starting / stopping additional pumps. However, the operator selected “minimum number of pumps running” shall take precedence over the automatic control algorithm. Demand control shall be based on the following description: i) The FMCS uses the pressure value as PV to a PID loop, the output of which is used to regulate the VFD speeds. ii) The speed of all the operating pumps is raised and lowered in unison. iii) If the pressure is not maintained as per the required PID set point then operator shall decide to increase to the number of pumps by increasing the minimum demand value in the Duty standby faceplate. Then the FMCS will start the next available pump that is in “Auto” mode and with the lowest accumulated run hours. iv) The new pump will be started at minimum speed, and slowly ramped up until its speed matches that of the other running pumps. v) The FMCS then includes the new pump under the control of the pressure PID loop, adjusting the speed to maintain the pressure set-point. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 11 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO vi) Similarly, if the speed of the operating pumps falls below a set level, then the FMCS will automatically slowly ramp down the speed of the pump and will continue to run at PID low clamp output value. If required operator shall decide to decrease the number of pumps by decreasing the minimum demand value in the Duty standby faceplate. Then the FMCS will stop the pump that is in “Auto” mode, which is having the highest accumulated run hours. In “Local” mode, the operator at the field shall be able to operate the pumps from the VFD panels and the end of line differential pressure transmitter at FAB level 1 will have no control over the frequency. In case of analogue signal failure to the VFD’s, the Variable Frequency Drive shall be programmed to fail at Last Operational Frequency configuration. 4.1.6 Shut-Down 4.1.6.1 Normal Shut-Down Shutdown of the system will be manual. An automatic shutdown sequence is not required. 4.1.6.2 Emergency Shut-Down No emergency shutdown procedure is required. 4.1.7 Interlocks If all four Heat Exchanger On/Off valves are closed or encounter FTO alarm then pump will be stopped, if pump already running and temperature control valve will be fully closed. 4.1.8 Interfaces with other systems This system does not interface with any other systems. 4.1.9 FMCS parameter displays 4.1.9.1 Operator Interface The FMCS screen shall display the status of each pump, and the pump frequency in Hertz. Another screen accessible from the main Heat Recovery Water screen shall display run hours for each of the pumps. The end-of-line pressure differential value shall be displayed continuously along with the PID loop set-point value. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 12 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO The PID loop set-point values shall be operator adjustable. 4.1.9.2 Logging / Trending Trending available for instruments mentioned in table 4.1.3. 4.1.10 Switching between “Manual” and “Auto” The FMCS operator can, at any time, manually start and stop a pump by firstly clicking on the “Auto” / “Manual” icon on the FMCS monitor, to place the device into “Manual” mode. The “Start” / “Stop” icon can then be chosen. In “Manual” mode, frequency shall be able to be adjusted on the FMCS screen. The minimum and maximum frequency shall correspond to the programmed VFD minimum and maximum frequency. The motor frequency shall be shown in Hertz. Switching a running piece of equipment from “Auto” to “Manual” and vice-versa will be feasible without disruption to this piece of equipment or the overall control scheme. The system will continue to control in “Auto” (Taking the benefit of the equipment running in “Manual”) 4.1.11 “Local” control All motors [including VFD controlled motors] can be switched into local control mode at the MCC. If the pump is selected to “Local” at the MCC / VFD, then the FMCS no longer has any control over the device, which will come under the control of the electrical MCC. When selected to “Local”, the device can be started and stopped only from “Start” / “Stop” buttons on the MCC / VFD. Similarly, frequency adjustment can be done only manually from raise / lower buttons on the VFD unit, the HRW end-of-line pressure PID loop having no control over this frequency. During this period FMCS shall be tracking the actual frequency of the locally operated pump and adjusting the frequency reference such that once the drive is put to “Auto” mode, the transfer is “bumpless” and VFD will not be subjected to a sudden increase /decrease of frequency. 4.1.12 Set-points / Warnings / Alarms A table of set points, warnings and alarms for all equipment and instruments is included in Appendix 1. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 13 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.2 Sub-System 2 – HRW Heat Exchangers 4.2.1 General description The Heat Recovery Water system utilizes four (4) plate heat exchangers to raise the temperature of the Heat Recovery Water using waste heat from the chiller condenser water system. The heat exchangers are piped in parallel with the flow being split between them. The flow of condenser water through the plate heat exchangers is controlled by a modulating valve fitted to each unit. Each of the modulating valve on the heat exchangers is controlled using a single PID loop where the average temperature of the heat recovery water supply temperature is calculated from the two temperature transmitters on the two outgoing supply pipes. 4.2.2 Key equipment items 4.2.2.1 Heat Exchangers Tag Descriptor C10A1-01-C161D-HRW-HX-01 (Future) C10A1-01-C161D-HRW-HX-02 C10A1-01-C161D-HRW-HX-03 C10A1-01-C171D-HRW-HX-04 4.2.2.2 Valves (ON/OFF) Tag Descriptor Function / Description Heat Recovery System Heat Exchangers Function / Description C10A1-1-Cxxx-HRW-HX-01-FCV-01(Future) Cup Level 1 Heat Recovery Heat Exchanger 1 On/Off Valve C10A1-1-Cxxx-HRW-HX-02-FCV-01 Cup Level 1 Heat Recovery Heat Exchanger 2 On/Off Valve C10A1-1-Cxxx-HRW-HX-03-FCV-01 Cup Level 1 Heat Recovery Heat Exchanger 3 On/Off Valve C10A1-1-Cxxx-HRW-HX-04-FCV-01 Cup Level 1 Heat Recovery Heat Exchanger 4 On/Off Valve 4.2.2.3 Valves (Modulating) Tag Descriptor C10A1-1-Cxxx-HRW-HX-01-TCV-01(Future) C10A1-1-Cxxx-HRW-HX-02-TCV-01 C10A1-1-Cxxx-HRW-HX-03-TCV-01 C10A1-1-Cxxx-HRW-HX-04-TCV-01 C10A1-1-Cxxx-HRW-HDR-PCV-01 Function / Description Cup Level 1 Heat Recovery Heat Exchanger 1 Temperature Control Valve Cup Level 1 Heat Recovery Heat Exchanger 2 Temperature Control Valve Cup Level 1 Heat Recovery Heat Exchanger 3 Temperature Control Valve Cup Level 1 Heat Recovery Heat Exchanger 4 Temperature Control Valve Cup Level 1 Heat Recovery By-pass Safety Relief Pressure Control Valve Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 14 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.2.3 Key instruments 4.2.3.1 Temperature instruments Tag Descriptor C10A1-1-Cxxx-CW-HDR-01-TIT-01 C10A1-1-Cxxx-CW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-CW-HDR-01-TIT-01 C10A2-x-Cxxx-CW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 C10A2-x-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 C10A2-x-Cxxx-HRW-HDR-02-TIT-01 Function / Description CUPA1 LEVEL 1 Condenser water supply header temperature from HRW CUPA1 LEVEL 1 Condenser water return header temperature to HRW CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1-Control CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1-Control CUPA1 LEVEL 1 HRW Return header temperature from CUPA1 CUPA1 LEVEL 1 HRW Supply header temperature to FABA1-Control CUPA1 LEVEL 1 HRW Supply header temperature from FABA1-Control CUPA1 LEVEL 1 HRW Return header temperature from FABA1 CUPA2 LEVEL x Condenser water supply header temperature from HRW CUPA2 LEVEL x Condenser water return header temperature to HRW CUPA2 LEVEL x HRW Supply header temperature to CUPA1-Control CUPA2 LEVEL x HRW Return header temperature from CUPA1 CUPA2 LEVEL x HRW Supply header temperature to FABA2-Control CUPA2 LEVEL x HRW Return header temperature from FABA2 4.2.4 Start-Up There is no start-up procedure for this sub-system. 4.2.5 Normal operation (“Auto”) 4.2.5.1 PID control Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 15 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO In “Auto” mode, the temperature control valves for both heat exchangers will modulate to maintain temperature at the discharge header at set-point (operator adjustable between 20.0 oC and 32.0 oC). In the case of an analogue card failure, the Temperature Control Valves shall “Fail at Last Operational Position” In case of failure of the pneumatic supply, the Temperature Control Valves shall stay last position. 4.2.5.2 Control logic It shall be possible to isolate each Heat Recovery Heat Exchanger using the solenoid operated Flow Control Valves. These valves shall be able to be selected from the FMCS screen and manually set to “Open” or “Closed”. 4.2.6 Shut-Down 4.2.6.1 Normal Shut-Down There is no shut-down procedure for this system. 4.2.6.2 Emergency Shut-Down There is no Emergency shut-down procedure for this system. 4.2.7 Interlocks There are no interlocks associated with this sub-system. 4.2.8 Interfaces with other systems This system does not interface with any other systems. 4.2.9 FMCS parameter displays 4.2.9.1 Operator Interface The Heat Recovery Heat Exchanger temperature control valve opening (0100%) shall be continuously displayed on the FMCS screen along with the discharge header Temperature Set-Point and Present Value. 4.2.9.2 Logging / Trending The Heat Recovery Water supply and return discharge header temperature values shall be logged with date and time stamp. These values shall be Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 16 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO displayed on a historical trend graphs along with the respective set-point value and valve-opening signal. 4.2.10 Switching between “Manual” and “Auto” Selecting “Manual” mode in the FMCS, the operator shall be able to “stroke” the full range (0-100%) of the Temperature Control Valve. Switching a running piece of equipment from “Auto” to “Manual” and vice-versa will be feasible without disruption to this piece of equipment or the overall control scheme. The system will continue to control in “Auto” (Taking the benefit of the equipment running in “Manual”) 4.2.11 “Local” control There is no “Local” control of the Temperature Control Valves. 4.2.12 Set-points / Warnings / Alarms A table of set-points, warnings and alarms for all equipment and instruments is included in Appendix 1. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 17 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.3 Sub-System 3 – Minimum Flow 4.3.1 General description The Heat Recovery Water pump system has a Pressure Control Valve that operates to provide a minimum flow at times of low demand. 4.3.2 Key equipment items 4.3.2.1 Valves (Modulating) Tag Descriptor C10A1-1-Cxxx-HRW-HDR-PCV-01 Function / Description Cup Level 1 Heat Recovery By-pass Safety Relief Pressure Control Valve 4.3.3 Key instruments 4.3.3.1 Pressure instruments Tag Descriptor Function / Description F10A1-x-Fxxx-HRW-HDR-PDIT-01 FABA1-L-x HRW Diff. PR. 01 - By-pass Safety Relief Pressure Control Valve FABA1-L-x HRW Diff. PR. 02 - By-pass Safety Relief Pressure Control Valve FABA2-L-x HRW Diff. PR. 01 - By-pass Safety Relief Pressure Control Valve FABA2-L-x HRW Diff. PR. 02 - By-pass Safety Relief Pressure Control Valve CUPA2-L-x HRW Diff. PR. 01 - By-pass Safety Relief Pressure Control Valve CUPA2-L-x HRW Diff. PR. 02 - By-pass Safety Relief Pressure Control Valve F10A1-x-Fxxx-HRW-HDR-PDIT-02 F10A2-x-Fxxx-HRW-HDR-PDIT-01 F10A2-x-Fxxx-HRW-HDR-PDIT-02 C10A2-x-Fxxx-HRW-HDR-PDIT-01 C10A2-x-Fxxx-HRW-HDR-PDIT-01 4.3.4 Start-Up There is no start-up procedure for this sub-system. 4.3.5 Normal operation (“Auto”) 4.3.5.1 PID control The Heat Recovery Water Pressure Control Valve (PCV) is used to maintain the end-of line differential pressure set point while maintaining a minimum flow condition when there is low demand for Heat Recovery Water. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 18 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO At times of low demand there will only be one Heat Recovery Water pump operating at the minimum frequency (operator set on the FMCS) and the endof-line pressure differential is above the set-point, then the Heat Recovery Pressure Control Valve shall open to bleed water from the discharge manifold into the return pipe to achieve the end-of-line pressure differential and maintain a minimum flow through the pump and heat exchangers. The Pressure Control Valve shall only open when the pump is at minimum frequency. The FMCS uses the end of line differential pressure value as PV to a PID loop, the output of which is used to regulate the Pressure Control Valve opening. If demand for Heat Recovery Water increases, the Pressure Control Valve shall progressively closed off until it is fully shut. When the valve is fully shut, the Heat Recovery pump frequency can be increased to provide the required end-of-line differential pressure. 4.3.5.2 Control logic Refer to PID control above. 4.3.6 Shut-Down 4.3.6.1 Normal Shut-Down There is no shut-down procedure for this system. 4.3.6.2 Emergency Shut-Down There is no Emergency shut-down procedure for this system. 4.3.7 Interlocks The Pressure Control Valve PID control shall be interlocked so that the Heat Recovery pump shall not be able to be sped up until the Pressure Control Valve is fully shut. 4.3.8 Interfaces with other systems This system does not interface with any other systems. 4.3.9 FMCS parameter displays 4.3.9.1 Operator Interface The FMCS screen shall continuously display the Pressure Control valve percentage open. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 19 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.3.9.2 Logging / Trending No logging or trending is required. 4.3.10 Switching between “Manual” and “Auto” In “Manual” mode, the operator shall be able to manually open the Pressure Control Valve irrespective of the end-of-line pressure differential value. 4.3.11 “Local” control There is no “Local” control of the Pressure Control Valve. 4.3.12 Set-points / Warnings / Alarms A table of set-points, warnings and alarms for all equipment and instruments is included in Appendix 1. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 20 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.4 Sub-System 4 – HRW Heat-Load Calculations 4.4.1 General description The heat-load on each side of the Heat Recovery heat exchangers (Condenser Water and Heat Recovery Water) will be calculated and displayed on the FMCS. The FMCS will calculate heat load demand for both sides of the Heat Recovery Water heat exchangers using temperature transmitters in the Condenser and Heat Recovery Water supply and return headers, together with the flow transmitters in the supply pipes, in accordance with the formula CW Heat-Load (kW) = [(Q1 x x CP x (T2-T1)] / 3,600 Where: Q1 CP T1 T2 is the HRW flow rate (header 1) in m3/hour is the density of water (1,000 kg/m3) is the constant where the value is 4.184 KJ/kgK is the HRW return header temperature (header 1) (oC) is the HRW discharge header temperature (header 2) (oC) Overall HRW Heat-Load (kW) = [(Q1 x x CP x (T2-T1)) + (Q2 x x CP x (T4-T3))] / 3,600 Where: Q1 Q2 CP T1 T2 T3 T4 is the HRW flow rate (header 1) in m3/hour is the HRW flow rate (header 2) in m3/hour is the density of water (1,000 kg/m3) is the constant where the value is 4.184 KJ/kgK is the HRW return header temperature (header 2) (oC) is the HRW supply header temperature (header 1) (oC) is the HRW return header temperature (header 2) (oC) is the HRW supply header temperature (header 1) (oC) The flow meter is used for monitoring only and will be displayed on the FMCS screens. 4.4.2 Key equipment items Tag Descriptor Function / Description None Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 21 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.4.3 Key instruments 4.4.3.1 Flow instruments Tag Descriptor Function / Description C10A1-1-Cxxx-CW-HDR-02-FIT-01 CUPA1-LEVEL 1 Condenser water return flowmeter from HRW CUPA1-LEVEL 1 HRW Supply header flow-meter to FabA1 FABA2-LEVEL x HRW Supply header flow-meter to FabA2 Level x CUPA2-LEVEL x HRW Supply header flow-meter to CupA2 Level x CUPA2-LEVEL x Condenser water return flowmeter from HRW C10A1-1-Cxxx-HRW-HDR-01-FIT-01 F10A2-x-Fxxx-HRW-HDR-01-FIT-01 C10A2-x-Cxxx-HRW-HDR-01-FIT-01 C10A2-x-Cxxx-CW-HDR-02-FIT-01 4.4.3.2 Temperature instruments Tag Descriptor C10A1-1-Cxxx-CW-HDR-01-TIT-01 C10A1-1-Cxxx-CW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-CW-HDR-01-TIT-01 C10A2-x-Cxxx-CW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 C10A2-x-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 C10A2-x-Cxxx-HRW-HDR-02-TIT-01 Function / Description CUPA1 LEVEL 1 Condenser water supply header temperature from HRW CUPA1 LEVEL 1 Condenser water return header temperature to HRW CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1-Control CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1-Control CUPA1 LEVEL 1 HRW Return header temperature from CUPA1 CUPA1 LEVEL 1 HRW Supply header temperature to FABA1-Control CUPA1 LEVEL 1 HRW Supply header temperature from FABA1-Control CUPA1 LEVEL 1 HRW Return header temperature from FABA1 CUPA2 LEVEL x Condenser water supply header temperature from HRW CUPA2 LEVEL x Condenser water return header temperature to HRW CUPA2 LEVEL x HRW Supply header temperature to CUPA1-Control CUPA2 LEVEL x HRW Return header temperature from CUPA1 CUPA2 LEVEL x HRW Supply header temperature to FABA2-Control CUPA2 LEVEL x HRW Return header temperature from FABA2 Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 22 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO 4.4.4 Start-Up There is no start-up procedure for this sub-system. 4.4.5 Normal operation (“Auto”) 4.4.5.1 PID control There is no PID control for this system. 4.4.5.2 Control logic There is no control logic for this system. 4.4.6 Shut-Down 4.4.6.1 Normal Shut-Down There is no shut-down procedure for this system. 4.4.6.2 Emergency Shut-Down There is no Emergency shut-down procedure for this system. 4.4.7 Interlocks There are no interlocks associated with the various analogue signals and equipment for this system. 4.4.8 Interfaces with other systems This system does not interface with any other systems. 4.4.9 FMCS parameter displays 4.4.9.1 Operator Interface The temperature values at both Condenser Water and Heat Recovery Water supply and return headers shall be continuously displayed on the FMCS screen. The calculated instantaneous Heat-Load for each side of the heat exchangers shall also be continuously displayed on the FMCS screen. 4.4.9.2 Logging / Trending Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 23 of 27 Project Name: FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM (PHASE A1) SOO The Condenser Water heat load calculation and Heat Recovery water flowrates and Supply/Return temperatures shall be logged with date and time stamp. The Condenser Water heat load calculation and Heat Recovery water flow-rates and Supply/Return temperatures values shall be displayed on a historical trend graph. 4.4.10 Switching between “Manual” and “Auto” There is no “Manual” or “Auto” option available. 4.4.11 “Local” control There is no “Local” control. 4.4.12 Set-points / Warnings / Alarms Not applicable. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Revision Date: 24 Sep 2018 Create Date: 24 Sep 2018 Revision: 0 Page 24 of 27 Project Name:FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM - SOO APPENDIX 1: Set points / Warnings / Alarms Pressure Instruments Tag Number Description C10A1-1-Cxxxx-HRW-HDR01-PIT-01 CUPA1-L-1 HRW SUPPLY HDR. PR.- Monitoring CUPA1-L-1 HRW RETURN HDR. PR.- Monitoring FABA1-L-x HRW Diff. PR. 01 Pump Control FABA1-L-x HRW Diff. PR. 02 Pump Control FABA2-L-x HRW Diff. PR. 01 Pump Control FABA2-L-x HRW Diff. PR. 02 Pump Control CUPA2-L-x HRW Diff. PR. 01 Pump Control CUPA2-L-x HRW Diff. PR. 02 Pump Control C10A1-1-Cxxxx-HRW-HDR02-PIT-01 F10A1-x-Fxxx-HRW-HDR-PDIT-01 F10A1-x-Fxxx-HRW-HDR-PDIT-02 F10A2-x-Fxxx-HRW-HDR-PDIT-01 F10A2-x-Fxxx-HRW-HDR-PDIT-02 C10A2-x-Fxxx-HRW-HDR-PDIT-01 C10A2-x-Fxxx-HRW-HDR-PDIT-01 Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Create Date: 24 Sep 2018 Units Set-point Set-point (NOTE 1) Low-Low Value Action Warning and Alarm switching points Low High Value Action Value Action High-High Value Action Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Note 2 N/A Note 2 Alarm Note 2 Warning Note 2 Warning Note 2 Alarm Bar Revision Date: 24 Sep 2018 Revision: 0 Page 25 of 27 Project Name:FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM - SOO Temperature Instruments Tag Number C10A1-1-Cxxx-CW-HDR-01-TIT-01 C10A1-1-Cxxx-CW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-01 C10A1-1-Cxxx-HRW-HDR-01-TIT-02 C10A1-1-Cxxx-HRW-HDR-02-TIT-01 C10A2-x-Cxxx-CW-HDR-01-TIT-01 C10A2-x-Cxxx-CW-HDR-02-TIT-01 C10A2-x-Cxxx-HRW-HDR-01-TIT-01 Description CUPA1 LEVEL 1 Condenser water supply header temperature from HRW CUPA1 LEVEL 1 Condenser water return header temperature to HRW CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1Control CUPA1 LEVEL 1 HRW Supply header temperature to CUPA1Control CUPA1 LEVEL 1 HRW Return header temperature from CUPA1 CUPA1 LEVEL 1 HRW Supply header temperature to FABA1Control CUPA1 LEVEL 1 HRW Supply header temperature from FABA1-Control CUPA1 LEVEL 1 HRW Return header temperature from FABA1 CUPA2 LEVEL x Condenser water supply header temperature from HRW CUPA2 LEVEL x Condenser water return header temperature to HRW CUPA2 LEVEL x HRW Supply header temperature to CUPA1Control Units °C Set-point Set-point (NOTE 1) Low-Low Value Action Warning and Alarm switching points Low High Value Action Value Action High-High Value Action 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 N/A N/A Alarm 19 Warning N/A Warning N/A Alarm 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 N/A N/A Alarm 19 Warning N/A Warning N/A Alarm 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 N/A N/A Alarm 19 Warning N/A Warning N/A Alarm 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A 20 N/A N/A Alarm 19 Warning N/A Warning N/A Alarm 35 N/A N/A N/A N/A N/A N/A N/A N/A N/A General Note: Set-points and values are nominal and may be altered either during commissioning or alternatively by operator adjustment via FMCS (see notes below). Set points value to be discussed and determined during SAT. Note1: Set-point 2 is only required where a dead-band is used. Note2: Value to be determined during commissioning. Note3: Value to be operator adjustable via FMCS. Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Create Date: 24 Sep 2018 Revision Date: 24 Sep 2018 Revision: 0 Page 26 of 27 Project Name:FAB10A PN: S86165 HEAT RECOVERY WATER SYSTEM - SOO APPENDIX 2: P&ID’s Document: 86165 2 ENG 8608 SOO 005 – Heat Recovery Water System Prepared By: Vynus Create Date: 24 Sep 2018 Revision Date: 24 Sep 2018 Revision: 0 Page 27 of 27