POWER OPTIMIZER SPECIFICATIONS SolarEdge P850 Rated Input DC Power = 850 W Max Input Voltage = 125 V Max Output Current = 18 A Max Allowed System Voltage = 1000 Vdc LABEL TO BE INSTALLED ADJACENT TO DISCONNECTS: LABEL TO BE INSTALLED ADJACENT TO DISCONNECTS: PHOTOVOLTAIC AC DISCONNECT PHOTOVOLTAIC AC DISCONNECT MAXIMUM AC OPERATING CURRENT: 208.2 AMPS MAXIMUM AC OPERATING VOLTAGE: 208 VOLTS MAXIMUM AC OPERATING CURRENT: 124.9 AMPS MAXIMUM AC OPERATING VOLTAGE: 208 VOLTS 400/5 AMP Class 0.2S PV ARRAY 1 CT CABINET String # 1 (28) Q-Cell 485 W PV MODULES (14) SolarEdge P850 Power Optimizers DC SYSTEM LABEL FOR 40KW INVERTER NOMINAL OPERATING VOLTAGE = 840 Vdc MAX OPERATING VOLTAGE = 980 Vdc MAX DC CURRENT = 48.25 Adc NOMINAL DC OPERATING CURRENT = 48.25 Adc PV STRING COMBINER Rated 1000 VDC Use 20A Fuses (Positive and Negative Conductors) THREE PHASE INVERTER SolarEdge SE40KUS Rated 40,000W STC / 480Vac Transformerless, Ungrounded Max Output Current (per phase) = 48.25A Integrated DC Disconnect DC + N L1 L2 L3 G AC + - String #2 (28) Q-Cell 485 W PV MODULES (14) SolarEdge P850 Power Optimizers Inverter # 1 + String #3 (28) Q-Cell 485 W PV MODULES (14) SolarEdge P850 Power Optimizers 52IT-M-1 OVERCURRENT PROTECTION DEVICE 300A Breaker G 4/0 AWG Cu Wire (Rated 75 Deg C) L1, L2, L3 Insulated #4 AWG EGC + PV Wire in Free Air or THHN-2/XHHW-2 in Conduit #10 AWG Cu wire (Rated 1000Vdc / 90 deg C) (Positive, Negative and EGC) #6 AWG Bare Copper EGC in Free Air (keep under 2% voltage drop @ Imp for entire DC Run) #3 AWG Cu Wire (Rated 75 Deg C) L1, L2, L3 & N Insulated #6 AWG EGC (2) THWN-2 or XHHW-2 in EMT Raceway (Positive and Negative) #6AWG Cu wire (1000Vdc / 90 deg C Rated) (4) #6 AWG Cu Wire (75 deg rated) Line 1, Line 2, Line 3 and Neutral #6 AWG EGC (keep under 2% voltage drop @ Imp for entire DC Run) #6 AWG EGC Minimum G (See PV ARRAY 1 for Wiring Details) 30kW Inverter #2 with 3 Strings, 2 String each: (30) Q-Cell 485 W PV MODULES (15) SolarEdge P850 Power Optimizers And one string: (28) Q-Cell 485 W PV MODULES (14)SolarEdge P850 Power Optimizers TRANSFORMER 45 kVA Dry-Type 480/277 Wye - 208 Delta #6 AWG GEC #6 AWG GEC N G #6 AWG Cu Wire (Rated 75 Deg C) L1, L2, L3 & N Insulated #6 AWG EGC PV SUBPANEL #1 480Vac Load Center Rated 120 A minimum N L1 L2 L3 G PV SUBPANEL #2 480Vac Load Center Rated 70 A minimum 52IT 1 70A 3-P Circuit Breakers 52IT 2 50A 3-P Circuit Breakers Neutral Bus Ground Bus 480V System Bonding Jumper #6 AWG GEC Neutral Bus 52IT 3 70A 3-P Circuit Breaker 480V System Bonding Jumper Ground Bus #6 AWG GEC LABEL TO BE INSTALLED ADJACENT TO PANEL: PHOTOVOLTAIC SUB PANEL MAXIMUM AC OPERATING CURRENT: 88.25 AMPS MAXIMUM AC OPERATING VOLTAGE: 208 VOLTS PV ARRAY 3 (See PV ARRAY 1 for Wiring Details) BEP #1 AWG Cu Wire (Rated 75 Deg C) L1, L2, L3 Insulated #6 AWG EGC #1 AWG Cu Wire (Rated 75 Deg C) L1, L2, L3 Insulated #6 AWG EGC DC SYSTEM CONDUCTORS ARE RATED 1000Vdc LABEL PER NEC REQUIREMENTS ALL EQUIPMENT TO BE WIRED WITH EQUIPMENT GROUNDING CONDUCTOR AS REQUIRED BY THE NEC AND LOCAL CODE G TRANSFORMER 75 kVA Dry-Type 480/277 Wye - 208 Delta THREE PHASE INVERTER SolarEdge SE30KUS Rated 30,000W STC / 480Vac Transformerless, Ungrounded Max Output Current (per phase) = 40A Integrated DC Disconnect THIS SYSTEM IS COMPOSED OF AN UNGROUNDED DC SYSTEM THEREFORE NO DC SYSTEM GROUND IS REQUIRED 52IT-M-2 OVERCURRENT PROTECTION DEVICE 175A Breaker PV Generator disconnect switch 89L-2 FUSED AC DISCONNECT Lockable, Visible 200A 3-Pole 208Vac 175A Fuses (4) #8 AWG Cu Wire (75 deg rated) Line 1, Line 2, Line 3 and Neutral #6 AWG EGC Minimum PV ARRAY 2 UTILITY SERVICE GRID 208 Vac 3 phase Trough PV Generator disconnect switch 89L-1 FUSED AC DISCONNECT 400A 3-Pole 208Vac Lockable, Visible 4/0 AWG Cu Wire 300A Fuses (Rated 75 Deg C) L1, L2, L3 Insulated #4 AWG EGC + String #4 (28) Q-Cell 485 W PV MODULES (14) SolarEdge P850 Power Optimizers UTILITY METER Drawing Name: (4) #6 AWG Cu Wire (75 deg rated) Line 1, Line 2, Line 3 and Neutral #6 AWG EGC Minimum 40kW Inverter #4 with 4 Strings each: (28) Q-Cell 485 W PV MODULES (14) SolarEdge P850 Power Optimizers N L1 L2 L3 G Project Name and Location: Richwood Realry Co. 35-35 75th Street Queens, NY LABEL TO BE INSTALLED ADJACENT TO PANEL: PHOTOVOLTAIC SUB PANEL MAXIMUM AC OPERATING CURRENT: 48.25 AMPS MAXIMUM AC OPERATING VOLTAGE: 208 VOLTS Drawn By : Tal Studio Date: 11/22/2022 Revision : 11/25/2022 (PS) Revision : 12/19/2022 (PS) Revision : To Street