Modbus Register Map: MGE Galaxy 300/ MGE Galaxy 7000
Notes:
1. 16-bit registers are transmitted MSB first (i.e. big-endian).
2. UINT16 and UINT32 are most-significant word in n+0, least significant word in n+1 (i.e. big-endian).
3. Function codes 3 and 4 are supported
4. Modbus serial RTU and TCP is supported.
5. Signed numbers are twos-compliment
6. Status bits are atomic within a single Modbus register. User should not look for consistency across multiple registers, only within a single register.
7. For ASCII strings less than the maximum length, the unused characters are filled with nulls.
8. Single-register reads of reserved or undefined registers will return an error. Block reads which begin with a valid register will return zeros for undefined registers.
9. Strings are two characters per register, first character in high-order byte, second character in low-order byte. Printable ASCII only.
10. Bit #0 is least significant bit.
11. Data Type column: "INT16"=signed 16-bit integer, "UINT16" = unsigned 16-bit integer, "INT32" = signed 32-bit integer, "UINT32" = unsigned 32-bit integer, "ENUM" is a UINT16 value which
maps to a defined list of states, "ASCII" = the printable ASCII subset from 0x20 - 0x7E. BOOLEAN= a single bit, 0 or 1.
12. "Absolute Starting Register Address" = 0 (the column heading used in this table) is equivalent to "Register 40001" in Modicon terminology, which is address zero when transmitted over the
wire.
13. The number of word by frame should not exceed 26 words.
14. Register 40072 is only to be used in Parallel Configurations and is not supported for Unitary Configurations.
990-4329B-001
06/2021
© 2021 Schneider Electric. All Rights Reserved.
Note 1: For detailed modbus configuration settings please refer to the AP9635 User’s Guide. Note 2: SSC for Static Switch Cabinet.
Modicon
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
mal)
Absolute
Starting
Register
Address,
(Decimal)
40001
0x0000
0
40002
40011
40020
40028
40037
40046
40051
40057
40065
0x0001
0x000A
0x0013
0x001B
0x0024
0x002D
0x0032
0x0038
0x0040
1
10
19
27
36
45
50
56
64
Data Point
Bit
Over all status of the UPS. 0 = Status unknown
2 = No alarms present
4 = Warning alarms present 8 = Critical alarms present
NMC application name
NMC card model number
NMC card serial number
NMC card hardware revision
NMC card firmware revision
Reserved for future use
NMC card manufactruing date
Reserved for future use
Alarm/Status Register
0
Load powered (protected or not)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
40066
0x0041
65
0
1
2
3
990-4329B
Length
# registers
Data Type
1
ENUM
9
9
8
9
9
5
6
8
1
ASCII
ASCII
ASCII
ASCII
ASCII
UINT16
BOOLEAN
BOOLEAN
Internal UPS hardware fault exists
NA
Battery usage status
Battery low warning
Low battery
Operation on static switch
Modbus data Invalid
Communication fault
UPS overload
Emergency stop
UPS Temperature Fault
Battery to be checked or External battery monitoring fault
Device ventilation fault
Load Alarm Violation Fault
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1 - Unitary 3: 3 (Galaxy 7000 & Galaxy 300)
2 - Modular 3: 3 (Galaxy 7000 & Galaxy 300) 3 - Galaxy 7000 parallel
with SSC
4 - Galaxy 7000 SSC
5 - Galaxy 300 unitary 3:1
6 - Galaxy 300 modular 3:1
1
Divide
Reading
By:
Valid Response
Supported Modules
ASCII
Load Protected (UPS coupled)
Alarm/Status Register
Run in Frequency converter
Multiply
Reading By:
UINT16
BOOLEAN
BOOLEAN
Modus Register Map
0: Output is not powered.
1: Output is powered.
0: Inverter is not used
1: Inverter is used
1 - An internal UPS hardware fault exists
Not supported by Galaxy 7000 SSC
1 - On battery power in response to an input power problem
1 - Low battery
1 - Ups is in shutdown state
1 - (In bypass) Bypass AC Input is used as source of power
1 - Modbus Data Not valid
1 - UPS serial communication fault exists
1 - UPS output overload
1 - Emergency stop in progess
1 - UPS temperature fault
1 - Battery Replacement needed
1 - System level fan fault exists
1 - Alarm violation present
0 - Alarm violation not present
Not supported by Galaxy 7000 SSC
Not supported by Galaxy 7000 SSC
0 - Power converter currently works on auto ranging
1 - Power converter currently works on frequency converter
0 0 1 - Galaxy 7000 Unitary
0 1 0 - Galaxy 7000 Modular
0 1 1 - Galaxy 7000 Parallel with SSC
1 0 0 - Galaxy 7000 SSC
0 0 1 - Galaxy 300 Unitary 33
1 0 1 - Galaxy 300 Unitary 31
0 1 0 - Galaxy 300 Redundant 33
1 1 0 - Galaxy 300 Redundant 31
Not supported by Galaxy 7000 SSC
Galaxy 7000 parallel SSC
Not supported by Galaxy 7000 SSC
1
Modicon
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
mal)
40067
40069
40070
990-4329B
0x0042
0x0044
0x0045
Absolute
Starting
Register
Address,
(Decimal)
66
68
69
Data Point
Bit
Length
# registers
Data Type
4
5
6
7
8
9
10
NA
NA
Maintenance bypass switch status
NA
NA
Rectifier internal fault status
Load protection status in parallel installation
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
11
UPS Power Saving Mode status
BOOLEAN
12
UPS environnement fault
BOOLEAN
13
ECO mode status
BOOLEAN
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
NA
NA
Alarm/Status Register
Installed battery status
NA
Battery test result
NA
NA
NA
NA
NA
Battery test in progress
NA
Internal battery temperature status
NA
NA
NA
NA
Battery switch status
Alarm/Status Register
NA
NA
NA
Main AC switch status
NA
NA
NA
NA
Main AC voltage status
Main AC fuse status
NA
Main AC frequency status
NA
NA
NA
NA
Alarm/Status Register
NA
NA
NA
NA
NA
Status of the input contact 1
Status of the input contact 2
UPS Redundancy status
NA
K2S fault status
K2S switch on/off status
Overlap transfert on SSC status
NA
NA
NA
NA
Multiply
Reading By:
Divide
Reading
By:
BOOLEAN
BOOLEAN
1
1
1
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Modus Register Map
Valid Response
Supported Modules
1 - Maintenance bypass switch closed
1 - Rectifier internal fault exists
0 - Load protection is restored
1 - Load protection is lost due to less number of good power modules
0 - UPS not in Power Saving Mode (Efficiency Booster Mode)
1 - UPS is running in Power Saving Mode (EBM)
0 - No UPS environnental fault
1 - UPS environnemntal fault or ups minor fault
0 - UPS not in ECO Mode
1 - UPS is running in ECO Mode
Not supported by Galaxy 7000 SSC
Only on G7000
Only on G7000
Only on G7000
1 - Battery present
1 - Battery test failed (Done and Error)
1 - Test in progress
1 - The internal battery temperature exceeds the critical threshold
Not supported by Galaxy 7000 SSC
1 - Battery switch closed
Not supported by Galaxy 7000 SSC
1 - Main AC switch closed
Not supported by Galaxy 300
1 - Main AC is not OK/Voltage out of range
1 - Main AC fault (open)
Not supported by Galaxy 7000 SSC
Not supported by Galaxy 7000 SSC
1 - Main AC frequency out of range
Not supported by Galaxy 7000 SSC
1 - Input contact 1 fault exist
1 - Input contact 2 fault exist
1 - Power modules redundancy is lost
1 - K2S fault exist
1 - K2S swtich on (close)
1 - Overlap transfert fault exists
Only Galaxy 7000 SSC supported
Only Galaxy 7000 SSC supported
Only Galaxy 7000 SSC supported
2
Modicon
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
mal)
40071
0x0046
Absolute
Starting
Register
Address,
(Decimal)
70
Data Point
Bit
0
1
0x0047
71
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
6
Bypass thermal overload status
BOOLEAN
7
Bypass swtich fault status
BOOLEAN
8
9
NA
Bypass frequency status
BOOLEAN
BOOLEAN
Bypass voltage status
BOOLEAN
11
12
13
14
15
NA
NA
NA
Bypass switch status
NA
Alarm/Status Register
0
Internal bypass hardware fault exists
990-4329B
0x0048
72
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
Multiply
Reading By:
Divide
Reading
By:
UINT16
BOOLEAN
BOOLEAN
NA
NA
NA
Bypass overload status
1
40073
1
Data Type
2
3
4
5
10
40072
Alarm/Status Register
NA
UPS maintenance bypass status
Length
# registers
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
Inverter and AC bypass desynchronisation
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
0
1
2
3
4
5
6
7
8
NA
NA
NA
NA
NA
NA
NA
NA
NA
Output switch status
NA
NA
NA
NA
Alarm/Status Register
Input contact 1 status
Input contact 2 status
NA
NA
NA
NA
NA
NA
Input Contact 1 COSIT
9
Input Contact 2 COSIT
BOOLEAN
10
Input Contact 3 COSIT
BOOLEAN
11
Input Contact 4 COSIT
BOOLEAN
12
13
14
15
NA
NA
NA
NA
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1
Modus Register Map
Valid Response
Supported Modules
0 - UPS is not in maintenance bypass
1 - UPS is in maintenance bypass
Galaxy 7000 parallel with SSC
0 - Bypass input power not overload
1 - Bypass input power overload
0 - No thermal overload on bypass input
1 - Thermal overload exists on bypass input
0 - No fault in bypass swtich
1 - Bypass swtich is in fault condition
Galaxy 7000 parallel with SSC
0 - Bypass frequency in range
1 - Bypass frequency out of range
0 - Bypass voltage in range
1 - Bypass voltage out of range
Galaxy 7000 parallel with SSC
1 - Bypass switch closed
Galaxy 7000 parallel with SSC
Galaxy 7000 parallel with SSC
Galaxy 7000 parallel with SSC
Galaxy 7000 parallel with SSC
Parallel configurations only
0 - Hardware fault no longer exist
1 - Hardware fault due to Bypass internal fault (fuse, relay, …)
0 - Ups synchronised with AC bypass,
1 - Ups is not synchronised with the AC bypass
1 - Output switch closed
1 - input contact 1 closed
1 - input contact 2 closed
1 - Input contact 1 closed
0 - Input contact 1 open
1 - Input contact 2 closed
0 - Input contact 2 open
1 - Input contact 3 closed
0 - Input contact 3 open
1 - Input contact 4 closed
0 - Input contact 4 open
Not supported by Galaxy 300
Not supported by Galaxy 300
Not supported by Galaxy 300
Not supported by Galaxy 300
3
Modicon
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
mal)
40074
0x0049
Absolute
Starting
Register
Address,
(Decimal)
73
40075
0x004A
74
40076
0x004B
75
40077
0x004C
76
Data Point
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
990-4329B
Alarm/Status Register
Charger hardware fault exists
NA
NA
Battery charging status
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Alarm/Status Register
EBM setting
ECO setting
ECO Scheduling setting
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Reserved for future use
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Alarm/Status Register
NA
Inverter major fault
Inverter overload status
Inverter thermal overload status
Inverter limitation status
Length
# registers
1
1
1
Data Type
Multiply
Reading By:
Divide
Reading
By:
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
UPS fuse fault
BOOLEAN
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Modus Register Map
Valid Response
Supported Modules
1- Hardware fault due to charger malfunction
Not present for Galaxy 7000 SSC
1 - Battery is charging
Not present for Galaxy 7000 SSC
1 - Efficiency Booster Mode feature is available
1 - ECO mode feature is available
1 - Scheduled ECO mode feature is available
Only on G7000
Only on G7000
Only on G7000
1 - Failure due to inverter malfunction
1 - Inverter Overload
1 - Thermal overload
0 - No current limitation
1 - Current limitation
0 - No fuse or fuse closed
1 - Fuse open
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
4
Modicon
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
mal)
Absolute
Starting
Register
Address,
(Decimal)
40078
40080
0x004D
0x004F
77
79
40081
40225
40227
40229
40231
40233
40234
40235
40236
40238
40241
40243
40245
40247
40249
40250
40251
40252
40254
40255
40257
40258
40259
40260
40263
40264
40265
40266
40267
40268
40269
40271
40272
40278
40279
40280
40281
40287
40288
40289
40290
40291
40292
40293
40294
40295
40296
40297
40298
40299
40300
40301
40302
40303
40305
40306
40307
40308
0x0050
0x00E0
0x00E2
0x00E4
0x00E6
0x00E8
0x00E9
0x00EA
0x00EB
0x00ED
0x00F0
0x00F2
0x00F4
0x00F6
0x00F8
0x00F9
0x00FA
0x00FB
0x00FD
0x00FE
0x0100
0x0101
0x0102
0x0103
0x0106
0x0107
0x0108
0x0109
0x010A
0x010B
0x010C
0x010E
0x010F
0x0115
0x0116
0x0117
0x0118
0x011E
0x011F
0x0120
0x0121
0x0122
0x0123
0x0124
0x0125
0x0126
0x0127
0x0128
0x0129
0x012A
0x012B
0x012C
0x012D
0x012E
0x0130
0x0131
0x0132
0x0133
990-4329B
80
224
226
228
230
232
233
234
235
237
240
242
244
246
248
249
250
251
253
254
256
257
258
259
262
263
264
265
266
267
268
270
271
277
278
279
280
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
304
305
306
307
Data Point
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Reserved for future use
Alarm/Status Register
NA
Short circuit on output status
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
Reserved for future use
Time on ECO mode since commissionning
Time on ECO mode since reset
Time OnLine since commissionning ECO
Time OnLine since reset ECO
Percent time spent on ECO since commissionning
Percent time spent on ECO since reset
Number time running in ECO mode
Monthly time in ECO mode
Reserved for future use
Time on PSM since commissionning
Time on PSM since reset
Time OnLine since commissionning PSM
Time OnLine since reset PSM
Percent time spent on PSM since commissionning
Percent time spent on PSM since reset
Number time running in PSM
Monthly time in PSM
Number of G7000 in PSM
Reserved for future use
Mains input phase 1 current
Mains input phase 2 current
Mains input phase 3 current
Reserved for future use
Bypass input phase 1current
Bypass input phase 2 current
Bypass input phase 3 current
Output phase 1 current
Output phase 2 current
Output phase 3 current
Reserved for future use
Battery current
Reserved for future use
Mains input phase 1 to phase 2 voltage
Mains input phase 2 to phase 3 voltage
Mains input phase 3 to phase 1 voltage
Reserved for future use
Bypass input phase 1 to neutral voltage
Bypass input phase 2 to neutral voltage
Bypass input phase 3 to neutral voltage
Bypass input phase 1 to phase 2 voltage
Bypass input phase 2 to phase 3 voltage
Bypass input phase 3 to phase 1 voltage
Output phase 1 to neutral voltage
Output phase 2 to neutral voltage
Output phase 3 to neutral voltage
Output phase 1 to phase 2 voltage
Output phase 2 to phase 3 voltage
Output phase 3 to phase 1 voltage
Reserved for future use
UPS Temperature in deg F
UPS Temperature in deg C
Battery voltage
Reserved for future use
Output phase 1 active power
Output phase 2 active power
Output phase 3 active power
Output phase 1 apparent power
Length
# registers
2
1
Data Type
Multiply
Reading By:
Divide
Reading
By:
Supported Modules
UINT16
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
48
2
2
2
2
1
1
1
2
3
2
2
2
2
1
1
1
2
1
2
1
1
1
3
1
1
1
1
1
1
2
1
6
1
1
1
6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
Valid Response
1 - Short circuit fault exixts
UINT32
UINT32
UINT32
UINT32
UINT16
UINT16
UINT16
UINT32
Second
Second
Second
Second
%
%
UINT32
UINT32
UINT32
UINT32
UINT16
UINT16
UINT16
UINT32
UINT16
Second
Second
Second
Second
%
%
UINT16
UINT16
UINT16
Amps
Amps
Amps
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
Amps
Amps
Amps
Amps
Amps
Amps
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
INT16
Amps
Not present for Galaxy 7000 SSC
UINT16
UINT16
UINT16
Volts
Volts
Volts
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Volts
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
Not present for Galaxy 7000 parallel with SSC
UINT16
UINT16
UINT16
°F
°C
Volts
Not present for Galaxy 7000 SSC
UINT16
UINT16
UINT16
UINT16
kW
kW
kW
kVA
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Modus Register Map
Second
Second
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
5
Modicon
Standard
Register
Number
Absolute
Starting
Register
Address,
(Hexadeci
mal)
Absolute
Starting
Register
Address,
(Decimal)
40309
40310
40311
40312
40313
40314
40315
40316
0x0134
0x0135
0x0136
0x0137
0x0138
0x0139
0x013A
0x013B
308
309
310
311
312
313
314
315
Output phase 2 apparent power
Output phase 3 apparent power
Total Output active power
Total Output apparent power
Reserved for future use
Total output percent load
Output phase 1 peak factor
Output phase 2 peak factor
1
1
1
1
1
1
1
1
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
40317
0x013C
316
Output phase 3 peak factor
1
UINT16
40318
40319
0x013D
0x013E
317
318
Output power factor
Mains input frequency
1
1
UINT16
UINT16
dHz
40320
40321
0x013F
0x0140
319
320
Reserved for future use
Bypass input frequency
1
1
UINT16
UINT16
dHz
40322
40323
40324
40325
40326
40330
40331
40332
40333
40337
40338
40339
40340
40341
40342
40343
40344
40345
40346
40385
40386
40387
40389
40390
40392
40393
40394
40396
40397
40417
40425
40433
40441
40449
40522
40523
40530
40531
40532
0x0141
0x0142
0x0143
0x0144
0x0145
0x0149
0x014A
0x014B
0x014C
0x0150
0x0151
0x0152
0x0153
0x0154
0x0155
0x0156
0x0157
0x0158
0x0159
0x0180
0x0181
0x0182
0x0184
0x0185
0x0187
0x0188
0x0189
0x018B
0x018C
0x01A0
0x01A8
0x01B0
0x01B8
0x01C0
0x0209
0x020A
0x0211
0x0212
0x0213
321
322
323
324
325
329
330
331
332
336
337
338
339
340
341
342
343
344
345
384
385
386
388
389
391
392
393
395
396
416
424
432
440
448
521
522
529
530
531
Output frequency
Output phase 1 power factor
Output phase 2 power factor
Output phase 3 power factor
Reserved for future use
Battery remaining runtime
Battery temperature
Battery remaining capacity
Reserved for future use
Mains input phase 1 to neutral voltage
Mains input phase 2 to neutral voltage
Mains input phase 3 to neutral voltage
Total number of battaries count
Total battery capacity
Battery temperature in Deg F
UIO sensor port 1 temperature in deg F
UIO sensor port 1 maximum temperature threshold in deg F
UIO sensor port 1 minimum temperature threshold in deg F
Reserved for future use
UIO sensor port 1 temperature in deg C
UIO sensor port 1 maximum temperature threshold in deg C
Reserved for future use
UIO sensor port 1 minimum temperature threshold in deg C
Reserved for future use
UIO sensor port 1 humidity
UIO sensor port 1 maximum humidity threshold
Reserved for future use
UIO sensor port 1 minimum humidity threshold
Reserved for future use
UPS manufacturere name
UPS product name
UPS model number
UPS serial number
UPS firmware release
Nominal output apparent power
Reserved for future use
UPS number in parallel installation
Nominal Battery Backup time
Nominal battery voltage
1
1
1
1
4
1
1
1
4
1
1
1
1
1
1
1
1
1
39
1
1
2
1
2
1
1
2
1
20
8
8
8
8
15
1
7
1
1
1
UINT16
UINT16
UINT16
UINT16
dHz
%
%
%
UINT16
UINT16
UINT16
minutes
°C
%
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
Volts
Volts
Volts
UINT16
UINT16
°C
°C
UINT16
°C
UINT16
UINT16
%
%
UINT16
%
ASCII
ASCII
ASCII
ASCII
ASCII
UINT16
kVA
UINT16
UINT16
UINT16
minutes
Volts
990-4329B
Data Point
Bit
Length
# registers
Data Type
Multiply
Reading By:
Divide
Reading
By:
Modus Register Map
Valid Response
kVA
kVA
kW
kVA
%
Amp-Hour
°F
°F
°F
°F
Supported Modules
Not present for Galaxy 300 3:1
Not present for Galaxy 300 3:1
Peak factor will be in multiples of 100
Peak factor will be in multiples of 100
(Not present for Galaxy 300 3:1)
Peak factor will be in multiples of 100
(Not present for Galaxy 300 3:1)
Power factor will be in multiples of 100 (0 to 100)
Frequency value will be in multiples of 10
Not present for Galaxy 7000 SSC
Frequency value will be in multiples of 10
Not present for Galaxy 7000 parallel with SSC
Frequency value will be in multiples of 10
Only on G7000
Only on G7000
Only on G7000
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
Only on G7000
Only on G7000
Not present for Galaxy 7000 SSC
Not present for Galaxy 7000 SSC
6
UPS in
Power
Saving
Mode (EBM)
UPS in ECO
Mode
Comm lost
On Manual
Bypass
On Bypass
End of
battery
runtime
Low Battery
Warning
UPS on
Battery
Modbus
Address (word
+ bit) Hexa
format
UPS on
Normal AC
input
Global Overview MGE Galaxy 300/ MGE Galaxy 7000
Main UPS status
Load Powered
400
1
1
1
1
1
1
X
1
1
Load on inverter
401
1
1
1
0
0
0
X
0
1
UPS on battery
404
0
1
1
0
0
0
X
0
0
0
Load on AC Bypass
407
0
0
0
1
1
0
X
0
UPS in maintenance position
461
0
0
0
0
0
1
X
0
0
Battery Charging
493
X
0
0
0 X
X
X
X
UPS in ECO mode
41D
0
0
0
0
0
0
X
1
0
UPS in Power Saving Mode (EBM)
41B
0
0
0
0
0
0
X
0
1
X
Breaker status
Output switch status (QOP or Q5N)
47B
1
1
1
1
1
0
X
1
1
Main AC switch status (Q1 or QM1)
443
1
1
1
1
1
1
X
1
1
Bypass switch status (QM2 or Q4S)
46E
1
1
1
1
1
1
X
1
1
Battery switch status (QB or QF1)
42F
1
1
1
1
1
1
X
1
1
Maintenance Bypass switch status (Q3BP)
416
0
0
0
0
0
1
X
0
0
Internal UPS fault - Red Led on UPS interface
402
0
0
0
1
1
1
X
0
0
Load not protected
41A
0
0
0
1
1
1
X
0
0
UPS Internal Communication Fault
409
0
0
0
0
0
0
1
0
0
Rectifier fault
419
0
0
0
0
0
0
X
0
0
Inverter fault
4C1
0
0
0
0
0
0
X
0
0
Charger fault
490
0
0
0
0
0
0
X
0
0
Battery temperature fault
42A
0
0
0
0
0
0
X
0
0
End of battery runtime
406
0
0
0
1
0
0
X
0
0
Emergency Power Off
40B
0
0
0
0
0
0
X
0
0
Fan Faillure
40E
0
0
0
0
0
0
X
0
0
Environment fault - Orange Led on UPS
41C
0
1
1
1
0
0
X
0
0
UPS Fault
UPS Warning
Overload
40A
0
0
0
0
0
0
X
0
0
Low Battery Warning
405
0
0
1
1
0
0
X
0
0
Inverter Overload
4C2
0
0
0
0
0
0
X
0
0
Static switch overload
465
0
0
0
0
0
0
X
0
0
AC Normal Frequency Out Of Tolerance
44B
0
1
1
1
0
0
X
0
0
AC Normal Voltage Out Of Tolerance
448
0
1
1
1
0
0
X
0
0
AC bypass Out of tolerance
467
0
0
0
0
0
0
X
0
0
Characteristics for UPS in Online operation
Characteristics value for the current UPS operational mode
990-4329B
Modus Register Map