Modbus Register Map: MGE Galaxy 300/ MGE Galaxy 7000 Notes: 1. 16-bit registers are transmitted MSB first (i.e. big-endian). 2. UINT16 and UINT32 are most-significant word in n+0, least significant word in n+1 (i.e. big-endian). 3. Function codes 3 and 4 are supported 4. Modbus serial RTU and TCP is supported. 5. Signed numbers are twos-compliment 6. Status bits are atomic within a single Modbus register. User should not look for consistency across multiple registers, only within a single register. 7. For ASCII strings less than the maximum length, the unused characters are filled with nulls. 8. Single-register reads of reserved or undefined registers will return an error. Block reads which begin with a valid register will return zeros for undefined registers. 9. Strings are two characters per register, first character in high-order byte, second character in low-order byte. Printable ASCII only. 10. Bit #0 is least significant bit. 11. Data Type column: "INT16"=signed 16-bit integer, "UINT16" = unsigned 16-bit integer, "INT32" = signed 32-bit integer, "UINT32" = unsigned 32-bit integer, "ENUM" is a UINT16 value which maps to a defined list of states, "ASCII" = the printable ASCII subset from 0x20 - 0x7E. BOOLEAN= a single bit, 0 or 1. 12. "Absolute Starting Register Address" = 0 (the column heading used in this table) is equivalent to "Register 40001" in Modicon terminology, which is address zero when transmitted over the wire. 13. The number of word by frame should not exceed 26 words. 14. Register 40072 is only to be used in Parallel Configurations and is not supported for Unitary Configurations. 990-4329B-001 06/2021 © 2021 Schneider Electric. All Rights Reserved. Note 1: For detailed modbus configuration settings please refer to the AP9635 User’s Guide. Note 2: SSC for Static Switch Cabinet. Modicon Standard Register Number Absolute Starting Register Address, (Hexadeci mal) Absolute Starting Register Address, (Decimal) 40001 0x0000 0 40002 40011 40020 40028 40037 40046 40051 40057 40065 0x0001 0x000A 0x0013 0x001B 0x0024 0x002D 0x0032 0x0038 0x0040 1 10 19 27 36 45 50 56 64 Data Point Bit Over all status of the UPS. 0 = Status unknown 2 = No alarms present 4 = Warning alarms present 8 = Critical alarms present NMC application name NMC card model number NMC card serial number NMC card hardware revision NMC card firmware revision Reserved for future use NMC card manufactruing date Reserved for future use Alarm/Status Register 0 Load powered (protected or not) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 40066 0x0041 65 0 1 2 3 990-4329B Length # registers Data Type 1 ENUM 9 9 8 9 9 5 6 8 1 ASCII ASCII ASCII ASCII ASCII UINT16 BOOLEAN BOOLEAN Internal UPS hardware fault exists NA Battery usage status Battery low warning Low battery Operation on static switch Modbus data Invalid Communication fault UPS overload Emergency stop UPS Temperature Fault Battery to be checked or External battery monitoring fault Device ventilation fault Load Alarm Violation Fault BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN 1 - Unitary 3: 3 (Galaxy 7000 & Galaxy 300) 2 - Modular 3: 3 (Galaxy 7000 & Galaxy 300) 3 - Galaxy 7000 parallel with SSC 4 - Galaxy 7000 SSC 5 - Galaxy 300 unitary 3:1 6 - Galaxy 300 modular 3:1 1 Divide Reading By: Valid Response Supported Modules ASCII Load Protected (UPS coupled) Alarm/Status Register Run in Frequency converter Multiply Reading By: UINT16 BOOLEAN BOOLEAN Modus Register Map 0: Output is not powered. 1: Output is powered. 0: Inverter is not used 1: Inverter is used 1 - An internal UPS hardware fault exists Not supported by Galaxy 7000 SSC 1 - On battery power in response to an input power problem 1 - Low battery 1 - Ups is in shutdown state 1 - (In bypass) Bypass AC Input is used as source of power 1 - Modbus Data Not valid 1 - UPS serial communication fault exists 1 - UPS output overload 1 - Emergency stop in progess 1 - UPS temperature fault 1 - Battery Replacement needed 1 - System level fan fault exists 1 - Alarm violation present 0 - Alarm violation not present Not supported by Galaxy 7000 SSC Not supported by Galaxy 7000 SSC 0 - Power converter currently works on auto ranging 1 - Power converter currently works on frequency converter 0 0 1 - Galaxy 7000 Unitary 0 1 0 - Galaxy 7000 Modular 0 1 1 - Galaxy 7000 Parallel with SSC 1 0 0 - Galaxy 7000 SSC 0 0 1 - Galaxy 300 Unitary 33 1 0 1 - Galaxy 300 Unitary 31 0 1 0 - Galaxy 300 Redundant 33 1 1 0 - Galaxy 300 Redundant 31 Not supported by Galaxy 7000 SSC Galaxy 7000 parallel SSC Not supported by Galaxy 7000 SSC 1 Modicon Standard Register Number Absolute Starting Register Address, (Hexadeci mal) 40067 40069 40070 990-4329B 0x0042 0x0044 0x0045 Absolute Starting Register Address, (Decimal) 66 68 69 Data Point Bit Length # registers Data Type 4 5 6 7 8 9 10 NA NA Maintenance bypass switch status NA NA Rectifier internal fault status Load protection status in parallel installation BOOLEAN BOOLEAN BOOLEAN BOOLEAN 11 UPS Power Saving Mode status BOOLEAN 12 UPS environnement fault BOOLEAN 13 ECO mode status BOOLEAN 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 NA NA Alarm/Status Register Installed battery status NA Battery test result NA NA NA NA NA Battery test in progress NA Internal battery temperature status NA NA NA NA Battery switch status Alarm/Status Register NA NA NA Main AC switch status NA NA NA NA Main AC voltage status Main AC fuse status NA Main AC frequency status NA NA NA NA Alarm/Status Register NA NA NA NA NA Status of the input contact 1 Status of the input contact 2 UPS Redundancy status NA K2S fault status K2S switch on/off status Overlap transfert on SSC status NA NA NA NA Multiply Reading By: Divide Reading By: BOOLEAN BOOLEAN 1 1 1 BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN Modus Register Map Valid Response Supported Modules 1 - Maintenance bypass switch closed 1 - Rectifier internal fault exists 0 - Load protection is restored 1 - Load protection is lost due to less number of good power modules 0 - UPS not in Power Saving Mode (Efficiency Booster Mode) 1 - UPS is running in Power Saving Mode (EBM) 0 - No UPS environnental fault 1 - UPS environnemntal fault or ups minor fault 0 - UPS not in ECO Mode 1 - UPS is running in ECO Mode Not supported by Galaxy 7000 SSC Only on G7000 Only on G7000 Only on G7000 1 - Battery present 1 - Battery test failed (Done and Error) 1 - Test in progress 1 - The internal battery temperature exceeds the critical threshold Not supported by Galaxy 7000 SSC 1 - Battery switch closed Not supported by Galaxy 7000 SSC 1 - Main AC switch closed Not supported by Galaxy 300 1 - Main AC is not OK/Voltage out of range 1 - Main AC fault (open) Not supported by Galaxy 7000 SSC Not supported by Galaxy 7000 SSC 1 - Main AC frequency out of range Not supported by Galaxy 7000 SSC 1 - Input contact 1 fault exist 1 - Input contact 2 fault exist 1 - Power modules redundancy is lost 1 - K2S fault exist 1 - K2S swtich on (close) 1 - Overlap transfert fault exists Only Galaxy 7000 SSC supported Only Galaxy 7000 SSC supported Only Galaxy 7000 SSC supported 2 Modicon Standard Register Number Absolute Starting Register Address, (Hexadeci mal) 40071 0x0046 Absolute Starting Register Address, (Decimal) 70 Data Point Bit 0 1 0x0047 71 BOOLEAN BOOLEAN BOOLEAN BOOLEAN 6 Bypass thermal overload status BOOLEAN 7 Bypass swtich fault status BOOLEAN 8 9 NA Bypass frequency status BOOLEAN BOOLEAN Bypass voltage status BOOLEAN 11 12 13 14 15 NA NA NA Bypass switch status NA Alarm/Status Register 0 Internal bypass hardware fault exists 990-4329B 0x0048 72 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 Multiply Reading By: Divide Reading By: UINT16 BOOLEAN BOOLEAN NA NA NA Bypass overload status 1 40073 1 Data Type 2 3 4 5 10 40072 Alarm/Status Register NA UPS maintenance bypass status Length # registers BOOLEAN BOOLEAN BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN Inverter and AC bypass desynchronisation BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN 0 1 2 3 4 5 6 7 8 NA NA NA NA NA NA NA NA NA Output switch status NA NA NA NA Alarm/Status Register Input contact 1 status Input contact 2 status NA NA NA NA NA NA Input Contact 1 COSIT 9 Input Contact 2 COSIT BOOLEAN 10 Input Contact 3 COSIT BOOLEAN 11 Input Contact 4 COSIT BOOLEAN 12 13 14 15 NA NA NA NA BOOLEAN BOOLEAN BOOLEAN BOOLEAN 1 Modus Register Map Valid Response Supported Modules 0 - UPS is not in maintenance bypass 1 - UPS is in maintenance bypass Galaxy 7000 parallel with SSC 0 - Bypass input power not overload 1 - Bypass input power overload 0 - No thermal overload on bypass input 1 - Thermal overload exists on bypass input 0 - No fault in bypass swtich 1 - Bypass swtich is in fault condition Galaxy 7000 parallel with SSC 0 - Bypass frequency in range 1 - Bypass frequency out of range 0 - Bypass voltage in range 1 - Bypass voltage out of range Galaxy 7000 parallel with SSC 1 - Bypass switch closed Galaxy 7000 parallel with SSC Galaxy 7000 parallel with SSC Galaxy 7000 parallel with SSC Galaxy 7000 parallel with SSC Parallel configurations only 0 - Hardware fault no longer exist 1 - Hardware fault due to Bypass internal fault (fuse, relay, …) 0 - Ups synchronised with AC bypass, 1 - Ups is not synchronised with the AC bypass 1 - Output switch closed 1 - input contact 1 closed 1 - input contact 2 closed 1 - Input contact 1 closed 0 - Input contact 1 open 1 - Input contact 2 closed 0 - Input contact 2 open 1 - Input contact 3 closed 0 - Input contact 3 open 1 - Input contact 4 closed 0 - Input contact 4 open Not supported by Galaxy 300 Not supported by Galaxy 300 Not supported by Galaxy 300 Not supported by Galaxy 300 3 Modicon Standard Register Number Absolute Starting Register Address, (Hexadeci mal) 40074 0x0049 Absolute Starting Register Address, (Decimal) 73 40075 0x004A 74 40076 0x004B 75 40077 0x004C 76 Data Point Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 990-4329B Alarm/Status Register Charger hardware fault exists NA NA Battery charging status NA NA NA NA NA NA NA NA NA NA NA NA Alarm/Status Register EBM setting ECO setting ECO Scheduling setting NA NA NA NA NA NA NA NA NA NA NA NA NA Reserved for future use NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Alarm/Status Register NA Inverter major fault Inverter overload status Inverter thermal overload status Inverter limitation status Length # registers 1 1 1 Data Type Multiply Reading By: Divide Reading By: UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN UPS fuse fault BOOLEAN NA NA NA NA NA NA NA NA NA NA BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN Modus Register Map Valid Response Supported Modules 1- Hardware fault due to charger malfunction Not present for Galaxy 7000 SSC 1 - Battery is charging Not present for Galaxy 7000 SSC 1 - Efficiency Booster Mode feature is available 1 - ECO mode feature is available 1 - Scheduled ECO mode feature is available Only on G7000 Only on G7000 Only on G7000 1 - Failure due to inverter malfunction 1 - Inverter Overload 1 - Thermal overload 0 - No current limitation 1 - Current limitation 0 - No fuse or fuse closed 1 - Fuse open Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC 4 Modicon Standard Register Number Absolute Starting Register Address, (Hexadeci mal) Absolute Starting Register Address, (Decimal) 40078 40080 0x004D 0x004F 77 79 40081 40225 40227 40229 40231 40233 40234 40235 40236 40238 40241 40243 40245 40247 40249 40250 40251 40252 40254 40255 40257 40258 40259 40260 40263 40264 40265 40266 40267 40268 40269 40271 40272 40278 40279 40280 40281 40287 40288 40289 40290 40291 40292 40293 40294 40295 40296 40297 40298 40299 40300 40301 40302 40303 40305 40306 40307 40308 0x0050 0x00E0 0x00E2 0x00E4 0x00E6 0x00E8 0x00E9 0x00EA 0x00EB 0x00ED 0x00F0 0x00F2 0x00F4 0x00F6 0x00F8 0x00F9 0x00FA 0x00FB 0x00FD 0x00FE 0x0100 0x0101 0x0102 0x0103 0x0106 0x0107 0x0108 0x0109 0x010A 0x010B 0x010C 0x010E 0x010F 0x0115 0x0116 0x0117 0x0118 0x011E 0x011F 0x0120 0x0121 0x0122 0x0123 0x0124 0x0125 0x0126 0x0127 0x0128 0x0129 0x012A 0x012B 0x012C 0x012D 0x012E 0x0130 0x0131 0x0132 0x0133 990-4329B 80 224 226 228 230 232 233 234 235 237 240 242 244 246 248 249 250 251 253 254 256 257 258 259 262 263 264 265 266 267 268 270 271 277 278 279 280 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 304 305 306 307 Data Point Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Reserved for future use Alarm/Status Register NA Short circuit on output status NA NA NA NA NA NA NA NA NA NA NA NA NA NA Reserved for future use Time on ECO mode since commissionning Time on ECO mode since reset Time OnLine since commissionning ECO Time OnLine since reset ECO Percent time spent on ECO since commissionning Percent time spent on ECO since reset Number time running in ECO mode Monthly time in ECO mode Reserved for future use Time on PSM since commissionning Time on PSM since reset Time OnLine since commissionning PSM Time OnLine since reset PSM Percent time spent on PSM since commissionning Percent time spent on PSM since reset Number time running in PSM Monthly time in PSM Number of G7000 in PSM Reserved for future use Mains input phase 1 current Mains input phase 2 current Mains input phase 3 current Reserved for future use Bypass input phase 1current Bypass input phase 2 current Bypass input phase 3 current Output phase 1 current Output phase 2 current Output phase 3 current Reserved for future use Battery current Reserved for future use Mains input phase 1 to phase 2 voltage Mains input phase 2 to phase 3 voltage Mains input phase 3 to phase 1 voltage Reserved for future use Bypass input phase 1 to neutral voltage Bypass input phase 2 to neutral voltage Bypass input phase 3 to neutral voltage Bypass input phase 1 to phase 2 voltage Bypass input phase 2 to phase 3 voltage Bypass input phase 3 to phase 1 voltage Output phase 1 to neutral voltage Output phase 2 to neutral voltage Output phase 3 to neutral voltage Output phase 1 to phase 2 voltage Output phase 2 to phase 3 voltage Output phase 3 to phase 1 voltage Reserved for future use UPS Temperature in deg F UPS Temperature in deg C Battery voltage Reserved for future use Output phase 1 active power Output phase 2 active power Output phase 3 active power Output phase 1 apparent power Length # registers 2 1 Data Type Multiply Reading By: Divide Reading By: Supported Modules UINT16 BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN BOOLEAN 48 2 2 2 2 1 1 1 2 3 2 2 2 2 1 1 1 2 1 2 1 1 1 3 1 1 1 1 1 1 2 1 6 1 1 1 6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 Valid Response 1 - Short circuit fault exixts UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT32 Second Second Second Second % % UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT32 UINT16 Second Second Second Second % % UINT16 UINT16 UINT16 Amps Amps Amps Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 Amps Amps Amps Amps Amps Amps Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 INT16 Amps Not present for Galaxy 7000 SSC UINT16 UINT16 UINT16 Volts Volts Volts Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 Volts Volts Volts Volts Volts Volts Volts Volts Volts Volts Volts Volts Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC Not present for Galaxy 7000 parallel with SSC UINT16 UINT16 UINT16 °F °C Volts Not present for Galaxy 7000 SSC UINT16 UINT16 UINT16 UINT16 kW kW kW kVA Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Modus Register Map Second Second Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 5 Modicon Standard Register Number Absolute Starting Register Address, (Hexadeci mal) Absolute Starting Register Address, (Decimal) 40309 40310 40311 40312 40313 40314 40315 40316 0x0134 0x0135 0x0136 0x0137 0x0138 0x0139 0x013A 0x013B 308 309 310 311 312 313 314 315 Output phase 2 apparent power Output phase 3 apparent power Total Output active power Total Output apparent power Reserved for future use Total output percent load Output phase 1 peak factor Output phase 2 peak factor 1 1 1 1 1 1 1 1 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 40317 0x013C 316 Output phase 3 peak factor 1 UINT16 40318 40319 0x013D 0x013E 317 318 Output power factor Mains input frequency 1 1 UINT16 UINT16 dHz 40320 40321 0x013F 0x0140 319 320 Reserved for future use Bypass input frequency 1 1 UINT16 UINT16 dHz 40322 40323 40324 40325 40326 40330 40331 40332 40333 40337 40338 40339 40340 40341 40342 40343 40344 40345 40346 40385 40386 40387 40389 40390 40392 40393 40394 40396 40397 40417 40425 40433 40441 40449 40522 40523 40530 40531 40532 0x0141 0x0142 0x0143 0x0144 0x0145 0x0149 0x014A 0x014B 0x014C 0x0150 0x0151 0x0152 0x0153 0x0154 0x0155 0x0156 0x0157 0x0158 0x0159 0x0180 0x0181 0x0182 0x0184 0x0185 0x0187 0x0188 0x0189 0x018B 0x018C 0x01A0 0x01A8 0x01B0 0x01B8 0x01C0 0x0209 0x020A 0x0211 0x0212 0x0213 321 322 323 324 325 329 330 331 332 336 337 338 339 340 341 342 343 344 345 384 385 386 388 389 391 392 393 395 396 416 424 432 440 448 521 522 529 530 531 Output frequency Output phase 1 power factor Output phase 2 power factor Output phase 3 power factor Reserved for future use Battery remaining runtime Battery temperature Battery remaining capacity Reserved for future use Mains input phase 1 to neutral voltage Mains input phase 2 to neutral voltage Mains input phase 3 to neutral voltage Total number of battaries count Total battery capacity Battery temperature in Deg F UIO sensor port 1 temperature in deg F UIO sensor port 1 maximum temperature threshold in deg F UIO sensor port 1 minimum temperature threshold in deg F Reserved for future use UIO sensor port 1 temperature in deg C UIO sensor port 1 maximum temperature threshold in deg C Reserved for future use UIO sensor port 1 minimum temperature threshold in deg C Reserved for future use UIO sensor port 1 humidity UIO sensor port 1 maximum humidity threshold Reserved for future use UIO sensor port 1 minimum humidity threshold Reserved for future use UPS manufacturere name UPS product name UPS model number UPS serial number UPS firmware release Nominal output apparent power Reserved for future use UPS number in parallel installation Nominal Battery Backup time Nominal battery voltage 1 1 1 1 4 1 1 1 4 1 1 1 1 1 1 1 1 1 39 1 1 2 1 2 1 1 2 1 20 8 8 8 8 15 1 7 1 1 1 UINT16 UINT16 UINT16 UINT16 dHz % % % UINT16 UINT16 UINT16 minutes °C % UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 Volts Volts Volts UINT16 UINT16 °C °C UINT16 °C UINT16 UINT16 % % UINT16 % ASCII ASCII ASCII ASCII ASCII UINT16 kVA UINT16 UINT16 UINT16 minutes Volts 990-4329B Data Point Bit Length # registers Data Type Multiply Reading By: Divide Reading By: Modus Register Map Valid Response kVA kVA kW kVA % Amp-Hour °F °F °F °F Supported Modules Not present for Galaxy 300 3:1 Not present for Galaxy 300 3:1 Peak factor will be in multiples of 100 Peak factor will be in multiples of 100 (Not present for Galaxy 300 3:1) Peak factor will be in multiples of 100 (Not present for Galaxy 300 3:1) Power factor will be in multiples of 100 (0 to 100) Frequency value will be in multiples of 10 Not present for Galaxy 7000 SSC Frequency value will be in multiples of 10 Not present for Galaxy 7000 parallel with SSC Frequency value will be in multiples of 10 Only on G7000 Only on G7000 Only on G7000 Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC Only on G7000 Only on G7000 Not present for Galaxy 7000 SSC Not present for Galaxy 7000 SSC 6 UPS in Power Saving Mode (EBM) UPS in ECO Mode Comm lost On Manual Bypass On Bypass End of battery runtime Low Battery Warning UPS on Battery Modbus Address (word + bit) Hexa format UPS on Normal AC input Global Overview MGE Galaxy 300/ MGE Galaxy 7000 Main UPS status Load Powered 400 1 1 1 1 1 1 X 1 1 Load on inverter 401 1 1 1 0 0 0 X 0 1 UPS on battery 404 0 1 1 0 0 0 X 0 0 0 Load on AC Bypass 407 0 0 0 1 1 0 X 0 UPS in maintenance position 461 0 0 0 0 0 1 X 0 0 Battery Charging 493 X 0 0 0 X X X X UPS in ECO mode 41D 0 0 0 0 0 0 X 1 0 UPS in Power Saving Mode (EBM) 41B 0 0 0 0 0 0 X 0 1 X Breaker status Output switch status (QOP or Q5N) 47B 1 1 1 1 1 0 X 1 1 Main AC switch status (Q1 or QM1) 443 1 1 1 1 1 1 X 1 1 Bypass switch status (QM2 or Q4S) 46E 1 1 1 1 1 1 X 1 1 Battery switch status (QB or QF1) 42F 1 1 1 1 1 1 X 1 1 Maintenance Bypass switch status (Q3BP) 416 0 0 0 0 0 1 X 0 0 Internal UPS fault - Red Led on UPS interface 402 0 0 0 1 1 1 X 0 0 Load not protected 41A 0 0 0 1 1 1 X 0 0 UPS Internal Communication Fault 409 0 0 0 0 0 0 1 0 0 Rectifier fault 419 0 0 0 0 0 0 X 0 0 Inverter fault 4C1 0 0 0 0 0 0 X 0 0 Charger fault 490 0 0 0 0 0 0 X 0 0 Battery temperature fault 42A 0 0 0 0 0 0 X 0 0 End of battery runtime 406 0 0 0 1 0 0 X 0 0 Emergency Power Off 40B 0 0 0 0 0 0 X 0 0 Fan Faillure 40E 0 0 0 0 0 0 X 0 0 Environment fault - Orange Led on UPS 41C 0 1 1 1 0 0 X 0 0 UPS Fault UPS Warning Overload 40A 0 0 0 0 0 0 X 0 0 Low Battery Warning 405 0 0 1 1 0 0 X 0 0 Inverter Overload 4C2 0 0 0 0 0 0 X 0 0 Static switch overload 465 0 0 0 0 0 0 X 0 0 AC Normal Frequency Out Of Tolerance 44B 0 1 1 1 0 0 X 0 0 AC Normal Voltage Out Of Tolerance 448 0 1 1 1 0 0 X 0 0 AC bypass Out of tolerance 467 0 0 0 0 0 0 X 0 0 Characteristics for UPS in Online operation Characteristics value for the current UPS operational mode 990-4329B Modus Register Map 7