STRUCTURAL NOTES GENERAL NOTES FOUNDATION NOTES REINFORCED CONCRETE NOTES STRUCTURAL STEEL NOTES CONTRACTORS DESIGN RESPONSIBILITY 1. THE STRUCTURAL PLANS AND SPECIFICATIONS, TO THE BEST OF OUR KNOWLEDGE, COMPLY WITH THE APPLICABLE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE 2003 WITH STATE OF CONNECTICUT AMENDMENTS. 1. FOUNDATION DESIGN PARAMETERS FROM GEOTECHNICAL INVESTIGATION REPORT PREPARED BY LOBDELL CONSULTANTS, P.C. DATED AUGUST 31, 2009. 1. 1. 1. THE LISTED BELOW PROJECT ITEMS ASSOCIATED WITH FABRICATION, ERECTION AND CONTRACTORS MEANS AND METHODS AND REQUIRING STRUCTURAL DESIGN ARE THE RESPONSIBILITY OF THE CONTRACTOR. 2. FOUNDATIONS SHALL BE DESIGNED FOR 4,000 PSF STATIC BEARING CAPACITY. THE CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE 2003 WITH STATE OF CONNECTICUT AMENDMENTS AND ALL APPLICABLE FEDERAL AND SATE CODES, STANDARDS, REGULATIONS AND LAWS. 3. CONTRACTOR SHALL BE FAMILIAR WITH THE SUBSURFACE CONDITIONS AND GEOTECHNICAL REPORT BEFORE COMMENCING EXCAVATION. 4. DOWELS FROM FOOTINGS INTO PIERS AND WALLS ABOVE SHALL BE THE SAME SIZE AND NUMBER AS VERTICAL REBAR IN PIERS AND WALLS, AND SHALL BE EXTENDED "LTE" INTO FOOTINGS AND "LTS" INTO PIERS AND WALLS UNLESS OTHERWISE SHOWN. 2. 3. WORK NOT INDICATED ON A PART OF THE DRAWINGS BUT REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE REPEATED. 5. IN ANY CASE OF CONFLICT BETWEEN THE NOTES, DETAILS AND SPECIFICATIONS, THE MOST RIGID REQUIREMENTS SHALL GOVERN. CONTRACTOR SHALL MAKE NO DEVIATION FROM CONTRACT DOCUMENTS WITHOUT WRITTEN APPROVAL OF THE ENGINEER. 6. 5. DROP BOTTOM OF WALLS AND PIERS TO TOP OF FOOTINGS TO OBTAIN FULL EXTENT OF CONTACT, UNLESS OTHERWISE SHOWN. 6. CENTERLINE OF FOOTINGS SHALL BE CENTERLINE OF WALLS, PIERS AND COLUMNS, UNLESS OTHERWISE SHOWN. 7. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AND COORDINATE WITH ARCHITECTURAL DRAWINGS, DRAWINGS FROM OTHER CONSULTANTS, PROJECT SHOP DRAWINGS AND FIELD CONDITIONS. 8. 7. THE CONTRACTOR SHALL PROTECT EXISTING FACILITIES, STRUCTURES AND UTILITY LINES FROM ALL DAMAGE. 8. JOB SAFETY AND CONSTRUCTION PROCEDURES ARE THE RESPONSIBILITY OF THE CONTRACTOR. 9. THE STRUCTURES ARE DESIGNED FOR THE FOLLOWING UNIFORMLY DISTRIBUTED LIVE LOADS: NO BACKFILLING SHALL BE DONE AGAINST FOUNDATION AND RETAINING WALLS UNTIL CONCRETE HAS ATTAINED AT LEAST 75% OF ITS DESIGN STRENGTH. BEFORE BACKFILLING, PROVIDE BRACING FOR WALLS SUSTAINING MORE THAN 3 FEET OF EARTH PRESSURE. THIS BRACING SHALL REMAIN IN PLACE UNTIL ALL SLABS AND BEAMS FRAMING INTO WALL HAVE BEEN PLACED AND SET. IN NO CASE SHALL BULLDOZERS OR OTHER HEAVY EQUIPMENT BE PERMITTED CLOSER THAN 5 FEET FROM ANY FOUNDATION WALL. IF IT IS NECESSARY TO OPERATE SUCH EQUIPMENT CLOSER THAN 8 FEET TO THE WALL, THE CONTRACTOR SHALL BE THE SOLE RESPONSIBLE PARTY AND AT THEIR OWN EXPENSE SHALL PROVIDE ADEQUATE SUPPORTS OR BRACE THE WALL TO WITHSTAND THE ADDITIONAL LOADS SUPERIMPOSED FROM SUCH EQUIPMENT. 100 LBS./SQ.FT. 150 LBS./SQ.FT. 6 LBS./SQ.FT. 100 LBS./SQ.FT. 30 LBS./SQ. FT. + DRIFTING SEISMIC LOADS 1. 2. THE BUILDING STRUCTURAL FRAMES/WALLS ARE DESIGNED USING THE EQUIVALENT LATERAL FORCE METHOD IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE 2003 W/ CONNECTICUT AMENDMENTS. 9. 2. A. SPECTRAL ACCELERATIONS IMPORTANCE FACTOR B. SEISMIC DESIGN CATEGORY B. C. D. ALL EXPOSED CONCRETE SHALL HAVE AN AIR ENTRAINING AGENT. 4. ALL REINFORCING BARS SHALL CONFORM TO ASTM A615, GRADE 60 UNLESS REQUIRED TO BE WELDED AS SHOWN ON PLANS. ALL REINFORCING BARS REQUIRED TO BE WELDED SHALL CONFORM TO ASTM A706, GRADE 50. 5. 6. C. "R=3" LIGHT FRAMED WALLS SHEATHED WITH WOOD STRUCTURAL PANELS RATED FOR SHEAR RESISTANCE "R=6" CONTROLING RESPONSE FACTOR USED FOR ENTIRE BUILDING STRUCTURE (PER ASCE-7 SECTION 9.5.2) WIND LOADS "R=3" WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185. SUPPORT WIRE FABRIC WITH CHAIRS OR LIFTS, DURING CONCRETE PLACEMENT TO INSURE PROPER POSITION IN SLAB. % PASSING (BY WEIGHT) 100% 50-100% 25-75% 13. STRUCTURAL FILL MATERIAL SHOULD BE PLACED IN UNIFORM 12" THICK LOOSE LIFTS AND COMPACTED TO 95% OF ITS MAXIMUM DRY DENSITY, AT OPTIMUM MOISTURE CONTENT, IN ACCORDANCE WITH ASTM D1557-93. IN RESTRICTED AREAS WHERE ONLY HAND-OPERATED EQUIPMENT IS PERMITTED, THE MAXIMUM LOOSE LIFT SHALL BE 8". 14. SOIL COMPACTION SHALL BE CONTROLLED BY A QUALIFIED TESTING LABORATORY OR GEOTECHNICAL ENGINEER. TAKE A MINIMUM OF ONE FIELD DENSITY TEST FOR EACH LAYER. LOCATION OF TEST SHALL BE DETERMINED BY THE TESTING AGENCY. 2. 3. 4. DESIGN AND ERECT FORMS AND SHORES IN ACCORDANCE WITH ACI-347. DESIGN FORMS AND SHORES FOR HORIZONTAL CONCRETE MEMBERS FOR NOT LESS THAN DEAD LOAD PLUS 50 PSF CONSTRUCTION LOAD AND FOR THE CUMULATIVE LOADS OF SUPPORTING FLOOR SLABS. DESIGN SHORES WITH A MIN. FACTOR OF SAFETY OF 3. PROVIDE TEMPORARY BRACING AS NEEDED TO ENSURE STABILITY OF STRUCTURE DURING CONSTRUCTION. FORMING, SHORING AND RE-SHORING SHALL BE INSPECTED BY THE PROFESSIONAL ENGINEER WHO PREPARES THE SAID DRAWINGS. THEY SHALL SUBMIT A STATEMENT TO THE ENGINEER THAT THIS WORK WAS PERFORMED IN ACCORDANCE WITH PLANS AND SPECIFICATIONS. LAP GRADE BEAM AND WALL TOP HORIZONTAL REINFORCEMENT AT CENTER OF SPAN. LAP GRADE BEAM AND WALL BOTTOM HORIZONTAL REINFORCEMENT AT SUPPORT. LAP INSIDE FACE WALL VERTICAL REINFORCEMENT AT SUPPORT. LAP OUTSIDE FACE VERTICAL WALL REINFORCEMENT AT MID-HEIGHT OF WALL. UNLESS OTHERWISE NOTED, TERMINATE BARS AT DISCONTINUOUS ENDS WITH STANDARDS HOOKS. ALL HOOKED BARS NOT DIMENSIONED SHALL BE STANDARD HOOKS. MINIMUM CONCRETE COVER SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE ON THE DRAWINGS: A. B. C. D. E. SLABS: WALLS: COLUMNS: ALL CONCRETE EXPOSED TO WEATHER OR EARTH: ALL CONCRETE PLACED AGAINST EARTH: 3/4 INCH 1 INCH 1-1/2 INCHES 2 INCHES 3 INCHES PROVIDE CONSTRUCTION JOINTS IN ACCORDANCE WITH ACI-318, CHAPTER 6.4. SUBMIT SHOP DRAWINGS SHOWING CONSTRUCTION JOINT DETAILS, LOCATIONS AND THE SEQUENCE OF POURS FOR THE STRUCTURAL ENGINEER'S REVIEW PRIOR TO BEGINNING WORK. 10. WALL AND GRADE BEAM CONSTRUCTION JOINTS SHALL BE LOCATED TO PROVIDE A 60 FOOT MAXIMUM LENGTH OF CONCRETE PLACEMENT. 11. VERTICAL CONSTRUCTION JOINTS IN GRADE BEAMS AND WALLS SHALL BE USED ONLY WITH PRIOR APPROVAL OF THE ENGINEER, SEE NOTE 9 ABOVE, AND SHALL BE LOCATED AS FOLLOWS: B. SHORES SHALL BE DESIGNED AND DETAILED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF CONNECTICUT. DRAWINGS ILLUSTRATING THE SHORING SYSTEM AND SEQUENCING SHALL BE SIGNED AND SEALED BY SAID ENGINEER. 4. ALL CONNECTION MATERIAL AND BASE PLATES SHALL CONFORM TO ASTM STANDARD A-36 (36KSI), WITH 50-KSI STEEL PLATE WHERE NOTED. 5. ALL BOLTS SHALL CONFORM TO ASTM A325 OR A490, NUTS SHALL CONFORM TO ASTM A563 AND WASHERS SHALL CONFORM TO ASTM A-F436. 9. F. 9. B. C. ALL ROLLED SHAPES AND CHANNELS: ASTM A-572 OR A-992, MIN. YIELD STRENGTH OF 50 KSI MISCELLANEOUS ANGLES: ASTM A-36, MIN YIELD STRENGTH OF 36 KSI HOLLOW STRUCTURAL STEEL SECTIONS, (TUBES AND PIPES): ASTM A500 GRADE B, MIN YIELD STRENGTH OF 42 KSI FOR PIPES AND 46 KSI FOR TUBES. A. E. 8. A. OVERSIZED OR SLOTTED HOLES SHALL NOT BE USED FOR ANY CONNECTIONS UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR APPROVED IN WRITING BY THE ENGINEER. EXPOSURE = "C" 1. CALCULATIONS FOR ITEMS MARKED THUS (*) SHALL BE SUBMITTED FOR REVIEW AND APPROVAL TO THE ENGINEER OF RECORD, OTHERWISE THE ITEMS SHALL ONLY BE SUBMITTED FOR THE OWNERS RECORD: 8. 2. GROUND SNOW LOAD = 30 PSF & DRIFTING, PER ASCE 7-02. 3. ALL REINFORCING BARS SHALL BE LAPPED AS SPECIFICALLY DETAILED ON THE DRAWINGS. SPLICING & EMBEDMENTS SHALL BE IN ACCORDANCE W/ ACI 318 WHERE NOT SPECIFICALLY INDICATED ON THE DRAWINGS, ALL REINFORCING BARS SHALL BE LAPPED USING THE TENSION SPLICE LENGTHS IN THE LAP SPLICE SCHEDULE: A. 1. STEEL MATERIALS SHALL CONFORM TO THE FOLLOWING UNLESS OTHERWISE NOTED ON THE DRAWINGS: ALL SHOP OR FIELD BOLTED CONNECTIONS, SHALL BE BOLTED CONNECTIONS USING 3/4 INCH DIAMETER A325 N BOLTS IN STANDARD HOLES, UNLESS SPECIFICALLY NOTED OTHERWISE. BASIC WIND SPEED (3 SECOND GUST) = 110 MPH. FORMWORK AND SHORING NOTES 3. 7. ALL REINFORCEMENT SHALL BE SECURELY HELD IN PLACE WHILE PLACING CONCRETE. IF REQUIRED, ADDITIONAL BARS OR STIRRUPS SHALL BE PROVIDED BY THE CONTRACTOR TO FURNISH SUPPORT FOR ALL BARS. 1. SNOW LOADS THE CONTRACTOR SHALL RETAIN THE SERVICES OF STRUCTURAL PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF CONNECTICUT TO PERFORM THE DESIGN OF THESE ITEMS. ALL ANCHOR BOLTS/RODS SHALL CONFORM TO ASTM F-1554 GRADE 36 WITH WELD ABILITY SUPPLEMENT S1, UNLESS OTHERWISE NOTED. SUBMIT GRADE CERTIFICATIONS FOR RECORD. STEEL SUPPLIER SHALL SUPPLY RIGID STEEL TEMPLATES FOR ANCHOR ROD INSTALLATION. C. D. THE FRACTION PASSING THE NO. 200 SIEVE SHALL BE LESS THAN 15% OF THE FRACTION PASSING THE NO. 4 SIEVE. 12. ON-SITE EXCAVATED MATERIAL MAY ONLY BE SUITABLE FOR USE AS GRANULAR FILL IF IT CONFORMS TO THE SPECIFICATIONS NOTED AND IS APPROVED FOR USE BY THE GEOTECHNICAL ENGINEER. REFER TO GEOTECHNICAL REPORT FOR MORE INFORMATION. 2. 6. B. I=1.00 "B" STEEL NOT SPECIFICALLY DETAILED FOR SEISMIC CONTRACTOR SHALL BE RESPONSIBLE TO ADEQUATELY PROTECT ALL EXCAVATION SLOPES. WHERE NECESSARY, SHEETING AND SHORING OF EXCAVATION SHALL BE PROVIDED WITH ALL REQUIRED TIEBACKS AND BRACING. SIEVE SIZE 3-1/2" 3/4" #4 ALL STEEL DETAILS AND CONNECTIONS SHALL BE IN ACCORDANCE WITH THE FOUNDATIONAL WALLS, BUTTRESSES, SLAB ON GRADE: 4000 PSI, NORMAL WEIGHT FOOTINGS AND PIERS: 4000 PSI, NORMAL WEIGHT CONCRETE ON METAL DECK: 4000 PSI, NORMAL WEIGHT ALL OTHER CONCRETE: 4000 PSI, NORMAL WEIGHT 3. 11. MATERIAL FOR CONTROLLED FILL SHALL MEET THE FOLLOWING CRITERIA: SELECT EXCAVATED GRAVEL OR STONE MATERIALS FREE OF ORGANIC MATERIAL, LOAM, TRASH, SNOW, ICE, FROZEN SOIL, AND OTHER OBJECTIONABLE MATERIAL, CONFORMING TO THE GRADATION REQUIREMENTS AS FOLLOWS: Ss = 0.279 S1 = 0.064 SEISMIC RESISTING SYSTEM CONCRETE SHALL HAVE A MIN. COMPRESSIVE STRENGTH AT 28 DAYS AS FOLLOWS UNLESS OTHERWISE NOTED ON THE DRAWINGS: A. 10. METHODS EMPLOYED IN ALL SHEETING AND SHORING SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF CONNECTICUT. SEISMIC PARAMETERS: 2. REQUIREMENTS FOR HOT AND COLD WEATHERING CONCRETING MUST BE ADHERED TO. 7. PUBLIC ROOMS, STAIRS & CORRIDORS KITCHENS PARTITIONS GATHERING ROOM ROOF FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO THE CONSTRUCTION, ASD (LATEST EDITION). ALL REFERENCED STANDARDS REFER TO THE EDITION IN FORCE AT THE TIME THESE PLANS AND SPECIFICATIONS ARE ISSUED FOR PERMIT. 4. STRUCTURAL CONCRETE AND CONCRETING PRACTICES SHALL CONFORM WITH FOUNDATION WALLS: OPENING. GRADE BEAMS: ERECTION: GUIDING, BRACING, CONSTRUCTION LOADS, SCAFFOLDING, RIGGING CONSTRUCTION HOISTS AND CRANES, TEMPORARY SUPPORTS AND THEIR CONNECTIONS. SPECIAL INSPECTIONS THE FOLLOWING CONTROLLED INSPECTIONS ARE REQUIRED TO BE PERFORMED IN ACCORDANCE THE BUILDING CODE OF THE STATE OF CONNECTICUT, LATEST EDITION: ITEM: CONCRETE CONSTRUCTION REINFORCED MASONRY CONSTRUCTION STEEL CONSTRUCTION SOILS SPRAYED FIRE RESISTANT MATERIALS TIMBER CONSTRUCTION TIMBER FRAMING NOTES 1. ALL TIMBER FRAME CONSTRUCTION SHALL BE DONE IN STRICT CONFORMANCE TIMBER CONSTRUCTION MANUAL, LATEST EDITION. 2. ALL TIMBER SHALL BE KILN-DRIED, #2 OR BETTER, DOUGLAS FIR WITH A MINIMUM ALLOWABLE BENDING STRESS OF 1000 PSI OR AN APPROVED EQUIVALENT. ALL WOOD IN CONTACT WITH SOIL, WEATHER OR CONCRETE SURFACES SHALL BE PRESERVATIVELY TREATED. (P.T.) 10. ALL WELD BACK UP BARS SHALL BE REMOVED AND GROUND SMOOTH AFTER WELD IS COMPLETED, UNLESS NOTED OTHERWISE. 3. ALL PLYWOOD DECKING OR SHEATHING SHALL BE APA RATED C-D GRADE WITH EXTERIOR GLUE. 11. ALL WELDS INDICATED SHALL MEET THE MINIMUM WELD SIDE SPECIFIED BY THE AISC MANUAL OF STEEL DESIGN. (SINGLE PASS AS REQUIRED) 4. 12. ALL WELDS SHALL BE PERFORMED BY QUALIFIED WELDERS IN ACCORDANCE WITH A.W.S. SPECIFICATIONS, LATEST EDITIONS. ALL WELDING ELECTRODES SHALL CONFORM TO A.W.S. A5.1 GRADE E-70. BARE ELECTRODES AND GRANULAR FLUX SHALL CONFORM TO A.W.S. A5.17, F70 A.W.S. FLUX CLASSIFICATION. EXTERIOR PLYWOOD WALL SHEATHING SHALL BE FASTENED WITH 10d COMMON NAILS SPACED AT 4" O.C. AT PANEL EDGES AND 12" O.C. INTERMEDIATE. EXTERIOR PLYWOOD ROOF SHEATHING SHALL BE FASTENED WITH 10d COMMON NAILS SPACED AS FOLLOWS: AT AT THE PERIMETER OF THE ROOF 4" O.C., AT PANEL EDGES AND 12" O.C. INTERMEDIATE. (BLOCKING IS REQUIRED). 5. ALL LAG BOLT CONNECTIONS SHALL BE PRE-DRILLED WITH THE PROPER SIZE DIAMETER IN ACCORDANCE WITH THE AITC TIMBER MANUAL. 6. ALL TIMBER FRAMING CLIPS AND FASTENERS SHALL BE HOT DIP GALVANIZED AFTER FABRICATION. ALL SIMPSON STRONG TIE CONNECTORS SHALL HAVE ZMAX G185 GALVANIZED COATINGS. 7. ALL STRUCTURAL COMPOSITE LUMBER (SCL) SHALL BE MICROLAM LVL's WITH A MINIMUM MODULUS OF ELASTICITY OF 1900 KSI, AS MANUFACTURED BY THE TRUS JOIST CO. OR AN APPROVED EQUIVALENT. 14. SHOP AND FIELD CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS SHALL BE BOLTED OR WELDED. 8. ALL PARALLAM POST (PSL) SHALL HAVE A MINIMUM MODULUS OF ELASTICITY OF 1800 KSI, AS MANUFACTURED BY THE TRUS JOIST CO. OR AN APPORVED EQUIVALENT. 15. WHEN NOT SPECIFICALLY DETAILED ELSEWHERE ON THE DRAWINGS, ALL BEAM TO BEAM AND BEAM TO COLUMN CONNECTIONS SHALL BE DETAILED AS SHOWN IN THE TYPICAL BEAM CONNECTION DETAILS. 9. INSTALLATION OF LVL's SHALL BE IN ACCORDANCE WITH MANUFACTURERS RECOMMENDED PROCEDURES. DO NOT DRILL OR CUT ANY STRUCTURAL HEADER OR BEAM WITHOUT APPROVAL OF ARCHITECT/ENGINEER. LAMINATE MULITPLE-PLY LVL'S WITH 3/8" DIAMETER CARRIAGE BOLTS, TWO ROWS 16" ON CENTER. ALL BUTT AND FULL PENETRATION WELDS SHALL BE MADE USING RUN OFF TABS WHICH SHALL BE REMOVED AND GROUND SMOOTH AFTER WELD IS COMPLETED. 13. ALTERNATE CONNECTIONS WILL BE ACCEPTED ONLY WITH THE WRITTEN APPROVAL OF THE ENGINEER. HOWEVER, THE ENGINEER SHALL BE THE SOLE JUDGE OF THE ACCEPTABILITY AND THE CONTRACTOR'S BID SHALL ANTICIPATE THE USE OF THOSE SPECIFIC DETAILS SHOWN ON THE DRAWINGS. IN ANY EVENT THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN OF SUCH ALTERNATE DETAILS WHICH THEY PROPOSE. 16. ALL BEAM AND GIRDERS SHALL BE CONNECTED FOR 115% OF THE REACTION DENOTED BY THE SYMBOL V ON THE PLAN. PROVIDE A MINIMUM 2 BOLT CONNECTION. IF NO REACTION IS GIVEN PROVIDE CONNECTION FOLLOWING NOTE 17 BELOW. AT CENTERLINES BETWEEN SUPPORTS. 13. NO CONCRETE TEST WILL BE ACCEPTED IF CONCRETE IS TAMPERED WITH IN ANY WAY AFTER SAID TEST IS PERFORMED. REPEAT TEST IF WATER IS ADDED AFTER INITIAL SAMPLING. 17. ALL BEAM AND GIRDER CONNECTIONS SHALL BE AT LEAST CAPABLE OF DEVELOPING THE UNIFORMLY DISTRIBUTED LOAD CAPACITY OF THE MEMBER USING THE REACTION FROM THE ALLOWABLE LOAD OF BEAM AS TABULATED IN THE AISC MANUAL OF STEEL CONSTRUCTION LATEST EDITION UNLESS NOTED OTHERWISE. FOR COMPOSITE BEAMS MULTIPLY THE REACTION BY THE RATIO Str/S WHERE Str = SECTION MODULUS OF THE TRANSFORMED COMPOSITE CROSS SECTION WITH RESPECT TO THE BOTTOM FLANGE, AND S= SECTION MODULUS OF THE STRUCTURAL STEEL ALONE. 14. THE CONTRACTOR SHALL PROVIDE REINFORCING STEEL ERECTOR WITH A SET OF APPROVED SHOP DRAWINGS FOR FIELD USE. 18. FILLER BEAMS SHOULD BE SPACED EQUALLY BETWEEN THE SUPPORTS UNLESS OTHERWISE NOTED ON THE DRAWINGS. 15. ALL ADJOINING SURFACES NOT CAST MONOLITHICALLY SHALL BE ROUGHENED 19. ALL HOLES AND CUTS SHALL BE SHOWN ON THE SHOP DRAWINGS AND MADE IN THE SHOP. CUTS OR BURNING OF HOLES IN STRUCTURAL STEEL MEMBERS IN THE FIELD WILL NOT BE PERMITTED. 12. NO HORIZONTAL CONSTRUCTION JOINTS WILL BE PERMITTED IN BEAMS, WALLS AND SLABS UNLESS SPECIFICALLY SHOWN ON THE DRAWINGS OR APPROVED IN WRITING PRIOR TO CONSTRUCTION BY THE ENGINEER. A. WITH THE AITC STRESS LEVEL S-2 LEAD HOLE 10. ENGINEERED METAL-PLATE-CONNECTED WOOD TRUSSES SHALL BE DESIGNED BY A LICENSED PROFESSIONAL ENGINEER. THE CONTRACTOR SHALL SUBMIT ENGINEERED TRUSS SHOP DRAWINGS TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW AND APPROVAL. TRUSS SHOP DRAWINGS SHALL BEAR THE SEAL AND SIGNATURE OF A LICENSED DESIGN PROFESSIONAL CURRENTLY REGISTERED FOR PRACTICE IN THE STATE OF CT. SHOP DRAWINGS SHALL INDICATE ALL LOADING CASES CONSIDERED, MAXIMUM DEFLECTIONS AND MAXIMUM END REACTIONS FOR EACH TYPICAL TRUSS CONFIGURATION. TRUSS SHOP DRAWINGS SHALL INDICATE COMPRESSION MEMBERS REQUIRING ADDITIONAL FIELD-INSTALLED LATERAL BRACING. REFER TO DRAWINGS S-002 AND S-003 FOR LOAD DIAGRAMS. TRUSS DEFLECTIONS SHALL BE LIMITED TO 1360 OF SPAN. 11. PROVIDE TORQUE LOCKING NUTS AT ALL BOLTED CONNECTIONS. 12. LAMANITED BEAMS SHALL BE 24FV3 SOUTHERN YELLOW PINE AND SHALL BE PRESERVATIVE TREATED (P.T.). TIMBER FRAMING FASTENING SCHEDULE TO ACI RECOMMENDATIONS AND APPLY A BONDING AGENT AS REQUIRED. 16. CONTRACTOR SHALL FIELD VERIFY DIMENSIONS AND LOCATIONS OF ALL OPENINGS, PIPE SLEEVES, CURBS, ETC., AS REQUIRED BY OTHER TRADES BEFORE CONCRETE IS PLACED. 17. CONTRACTOR SHALL COORDINATE SLAB DEPRESSIONS FOR FLOOR FINISHES WITH THE ARCHITECTURAL DRAWINGS. 18. CONTRACTOR SHALL COORDINATE LOCATION OF FLOOR DRAINS, CURBS, CONCRETE PADS AND FLOOR DEPRESSIONS, ETC., WITH THE ARCHITECTURAL AND MECHANICAL DRAWINGS. 19. CONTRACTOR SHALL COORDINATE LOCATION OF INSERTS, WELDED PLATES AND OTHER ITEMS TO BE EMBEDDED IN CONCRETE WITH ARCHITECTURAL AND MECHANICAL DRAWINGS. 20. HORIZONTAL PIPES OR CONDUITS PLACED IN SLABS SHALL NOT BE SPACED CLOSER THAN 3 X THE DIAMETER OF CENTER. PIPE AND CONDUITS PLACED IN SLABS SHALL NOT HAVE AN OUTSIDE DIAMETER LARGER THAN 1/3 OF SLAB THICKNESS. ALUMINUM CONDUITS SHALL NOT BE PLACED IN CONCRETE. NO CONDUITS SHALL BE PLACED IN THE SLAB WITHIN 12 INCHES OF ANY COLUMN FACE. 21. CONTRACTOR SHALL USE RIGID STEEL TEMPLATES (SUPPLIED BY THE STEEL FABRICATOR) TO INSTALL ANCHOR RODS. 22. ALL STEEL MEMBERS TO BE ENCASED IN CONCRETE SHALL BE WRAPPED WITH A MINIMUM W.W.F. 6 X 6 - W2.9 X W2.9 REINFORCING, UNLESS OTHERWISE NOTED. 23. ALL SLABS SHALL BE FLAT AND LEVEL PER THE CONCRETE SPECIFICATIONS. THE CONCRETE CONTRACTOR SHALL INCLUDE IN THEIR BID ANY EXCESS CONCRETE REQUIRED DUE TO SUPPORT MEMBER DEFLECTION TO POUR SLABS FLAT AND LEVEL. THE CONCRETE PLACING PROCEDURE SHALL BE CONTROLLED TO MINIMIZE SUPPORT MEMBER DEFLECTION. NO. CONNECTION FASTENING LOCATION 1. FLOOR JOIST TO SILL OR WALL PLATE 4 - 8d COMMON TOENAIL 2. BOTTOM PLATE TO JOIST, RIM, OR BLOCKING (2) ROWS OF 1 4x 4 1 2 SDS SCREWS @ 12" O.C. FACE 3. TOP PLATE TO STUD 2 - 16d COMMON END NAIL 4. STUD TO BOTTOM PLATE 2 - 16d COMMON + SIMPSON SP4 STUD TIE END NAIL 5. DOUBLE STUD 16d COMMON @ 16" O.C. FACE NAIL 6. DOUBLE TOP PLATES 16d COMMON@ 16" O.C. FACE NAIL 7. DOUBLE TOP PLATES LAP SPLICE 8 - 16d COMMON FACE NAIL 8. BLOCKING BETWEEN JOIST OR RAFTER TO TOP PLATE 3 - 8d COMMON TOENAIL 9. RIM JOIST TO TOP PLATE 10d COMMON @ 6" O.C. TOENAIL 10. FLOOR TRUSS TO RIM JOIST 2 - 10d COMMON FACE NAIL, ONE EACH TOP AND BOTTOM CHORD 11. CEILING JOIST TO TOP PLATE 3 - 10d COMMON TOENAIL 25. ALL STRUCTURAL STEEL EXPOSED TO WEATHER SHALL BE GALVANIZED. 12. CEILING JOIST - LAPS OVER PARTITIONS 4 - 16d COMMON FACE NAIL 26. ALL TUBE & PIPE SECTIONS EXPOSED TO WEATHER SHALL HAVE OPEN ENDS CAPPED WITH 1/4" PLATE. 13. CEILING JOIST TO PARALLEL RAFTERS 4 - 16d COMMON FACE NAIL 14. COLLAR TIE TO RAFTER 4 - 16d COMMON FACE NAIL 15. RAFTER TO PLATE 4 - 8d COMMON TOENAIL 16. LEDGER TO RIM JOIST 3 - 16d COMMON 24" O.C. FACE NAIL 17. LEDGER TO WALL STUD 3 - 16d COMMON EA. STUD FACE NAIL 18. 2X4 GYPSUM NAILER 8d COMMON 16" O.C. FACE NAIL 19. HEADER TO STUD 4 - 8d COMMON TOENAIL 20. STEEL MEMBERS INDICATED ON THE DRAWINGS TO BE ENCASED IN CONCRETE SHALL BE UNPAINTED ON THE CONTACT SURFACES AND SHALL BE WRAPPED WITH A MINIMUM W.W.F. 6 X 6 - W2.9 X W2.9 REINFORCING UNLESS OTHERWISE NOTED. 21. THE STRUCTURAL STEEL CONTRACTOR SHALL COORDINATE THE BOTTOM OF BASE PLATE ELEVATION WITH THE TOP OF CONCRETE ELEVATION. 22. THE MAXIMUM LOAD HUNG FROM ANY BEAM FOR MEP DUCTWORK, PIPING ETC SHALL BE DISTRIBUTED TO THE BEAM'S TRIBUTARY AREA IN A WAY THAT THE ALLOWABLE DESIGN LOADS LISTED IN THE GENERAL NOTES ARE NOT EXCEEDED. THE CONTRACTOR SHALL COORDINATE THE LOADS OF ALL TRADES AND PROVIDE ADDITIONAL SUPPORT OR DISTRIBUTION FRAMING AS REQUIRED TO ACHIEVE THESE LOADS. 23. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS, MECHANICAL DRAWINGS AND DRAWINGS RELATED TO OTHER TRADES. THE GENERAL CONTRACTOR IS RESPONSIBLE TO CHECK AND COORDINATE DIMENSIONS, CLEARANCES, ETC., WITH THE WORK OF THE OTHER TRADES. 24. PROVIDE ANY TEMPORARY BRACING OR GUYS TO PROVIDE LATERAL SUPPORT OF THE STRUCTURES AND INDIVIDUAL ELEMENTS UNTIL PERMANENT FRAME IS COMPLETELY INSTALLED. 27. ALL STRUCTURAL STEEL TO RECEIVE SPRAY APPLIED FIRE PROTECTION SHALL BE LEFT UNCOATED. 28. FOR EXPOSED INTERIOR STRUCTURAL STEEL, REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR SURFACE PREPARATION AND FINISH REQUIREMENTS. 29. STEEL FABRICATOR SHALL COORDINATE ALL HOLE LOCATIONS FOR SIMPSON TIE DOWN ANCHORS. ALL HOLES SHALL BE SHOP DRILLED THROUGH BEAM FLANGES. 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz 1" 17'-34 11'-27 8" 3'-0" 21'-9" 9'-113 8" 11'-17 8" 43'-6" 21'-9" 11'-6" 10'-0" 10'-0" 9'-105 8" 11'-7" 9'-6" 12'-71" 8 1'-2" 4'-9" 6'-8" 11'-83 8" 15'-0" 1" 6'-92 11'-83 8" 10'-10" 1" 1'-44 1" 6'-118 1" 4'-112 5'-8" 7'-23" 8 4'-9" 11'-05" 8 3'-9" 1" 6'-92 13'-0" 10'-93 8" 4'-117 8" 6'-25 8" 11'-73 8" 6'-10" 11'-83 8" 1" 6'-42 15'-0" 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz 1" 17'-34 11'-27 8" 11'-17 8" 43'-6" 3'-0" 21'-9" 21'-9" 4'-9" 9'-113 8" 11'-05 8" 11'-6" 10'-0" 10'-0" 9'-105" 8 11'-7" 1" 12'-78 9'-6" 1'-2" 4'-9" 6'-0" 7'-23" 8 5'-8" 1" 4'-112 1" 4'-112 5'-8" 6'-0" 7'-23 8" 6'-0" 1" 6'-118 6'-0" 5'-6" 11'-83" 8 11'-73" 8 6'-25 8" 4'-117 8" 6'-0" 10'-93" 8 10'-93 8" 4'-117 8" 6'-25" 8 6'-0" 11'-73 8" 11'-83 8" 5'-113" 8 11'-83 8" 5'-9" 6'-23 4" 11'-83 8" 5'-6" 6'-33" 8 1" 6'-92 10'-10" 4'-7" 6'-0" 6'-0" 1" 1'-44 6'-0" 1" 6'-118 6'-0" 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz 1" 17'-34 TYP. 11'-27 8" 11'-17 8" 43'-6" 3'-0" 21'-9" 21'-9" 3' W. X 12" TH. CONC. SLAB AT BASE OF STAIRS 4'-9" 9'-113 8" 11'-05 8" 11'-6" 10'-0" 10'-0" 9'-105" 8 11'-7" 12'-71" 8 9'-6" 1'-2" 4'-9" 7'-23 8" 5'-8" 1" 4'-112 1" 6'-118 1" 6'-92 6'-33 8" 10'-10" SW 3' W. X 12" TH. CONC. SLAB AT BASE OF STAIRS TYP. 11'-83 8" 4'-7" 1" 1'-44 1" 6'-118 1" 4'-112 5'-8" 7'-23" 8 3' W. X 12" TH. CONC. SLAB AT BASE OF STAIRS 3' W. X 2' TH. GRADE BEAM 5'-9" SW SW 6'-23 4" TOP OF PIERS AND FND. WALL [+8'-3 1/2"] 5'-113 8" 11'-83 8" 3' W. X 2' TH. GRADE BEAM 3' W. X 2' TH. GRADE BEAM 11'-73 8" 6'-25 8" 4'-117 8" SW 10'-93 8" LINE OF WALL FRAMING, ABOVE, SEE S102 10'-93 8" 4'-117 8" 6'-25 8" 11'-73 8" SW SW SW TOP OF PIERS AND FND. WALL [+8'-3 1/2"] SW 11'-83 8" SW 11'-83 8" 3' W. X 2' TH. GRADE BEAM, REINF. WITH (4) #6 BARS TOP & BOT., & #4 TIES @ 12" O.C. EXTEND INTO FTG. TYP. FACE OF EX. BUILDING, DO NOT UNDERMINE EXISTING FOUNDATIONS. VERIFY EXISTING BOTTOM OF FTG. ELEVATION IN THE FIELD AND SET A.1 LINE FOOTINGS TO MATCH RAMP CONSTRUCTION, SEE ARCH. DRAWINGS FOR LAYOUT. TOP OF PIERS TO FOLLOW PROFILE OF RAMP, TYP. 3' W. X 12" TH. CONC. SLAB AT BASE OF STAIRS TYP . TYP. 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz 7 11'-27 8" 3'-0" 9'-113 8" 11'-17 8" 43'-6" 21'-9" 11'-05" 8 21'-9" 11'-6" 10'-0" 10'-0" 4'-9" 2X12 STAIR STRINGERS @ 12" O.C., TYP. 10 5 CANT. 5"X18" G.L.B. 5"X18" G.L.B. (2) 2X12 5"X18" G.L.B. 5"X18" G.L.B. 4 5 S-501 S-501 5"X18" G.L.B. 2X12 @ 16" O.C. 2X12 @ 16" O.C. 4'-7" 00 10 X1 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. 68 10 X W 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. SW 8 X6 10 4 S-202 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. 68 5"X18" G.L.B. SW 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. W 8 X6 10 X 10 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 2 5"X18" G.L.B. (2) 2X12 P.T. FLUSH GIRDER 5"X18" G.L.B. S-202 3 S-201 10'-93" 8 4X4 P.T. POST, TYP. (2) 2X12 P.T. DROP GIRDER AT PIERS, TYP. 2X12 STAIR STRINGERS @ 12" O.C., TYP. TYP. (2) 2X12 DROP GIRDER 4'-117 8" 5"X18" G.L.B. CONTRACTOR SHALL COORDINATE LOCATION OF FRAMING WITH PLUMBING PENETRATIONS AT ALL BATHROOM AND KITCHEN LOCATIONS, TYP. (4) 2X12 2X12 @ 12" O.C. (4) 2X12 2X12 @ 12" O.C. (4) 2X12 5"X18" G.L.B. (4) 2X12 (2) 2X12 5"X18" G.L.B. 2X12 JOISTS @ 12" O.C., TYP. (2) 2X12 JOISTS @ EDGE, TYP. 2X12 @ 16" O.C. 5"X18" G.L.B. 2X12 @ 12" O.C. (4) 2X12 1 S-202 5"X18" G.L.B. 2X12 @ 12" O.C. 5"X18" G.L.B. (4) 2X12 (4) 2X12 5"X18" G.L.B. 4X4 P.T. POST, TYP. 5"X18" G.L.B. P.A. 2X12 @ 16" O.C. 2X12 P.T. @ 16" O.C. (2) 2X12 P.T. DROP GIRDER AT PIERS, TYP. 5"X18" G.L.B. (4) 2X12 5"X18" G.L.B. 5"X18" G.L.B. W 5"X18" G.L.B. SW 5"X18" G.L.B. 5'-113" 8 5"X18" G.L.B. 68 5"X18" G.L.B. W (2) 2X12 5"X18" G.L.B. 2X12 @ 16" O.C. SW 5"X18" G.L.B. SW 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. X 10 (2) 2X12 PROVIDE BLOCK-OUT FOR SHOWER UNIT 5"X18" G.L.B. 68 10 X W 5"X18" G.L.B. W 5"X18" G.L.B. 5"X18" G.L.B. (2) 2X12 P.T. FLUSH GIRDERS 68 5"X18" G.L.B. 2X12 @ 16" O.C. 5"X18" G.L.B. 5"X18" G.L.B. X 10 5"X18" G.L.B. 2X12 @ 16" O.C. 4'-117 8" 5"X18" G.L.B. 2X12 @ 16" O.C. 2X12 @ 16" O.C. 8"X18" G.L.B. PROVIDE 2X8 BLOCKING @ 16" O.C. AT CHANGE IN DECKING ORIENTATION, SEE ARCH. DWGS. 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. 1" 6'-92 1 SW 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. S-201 2X12 @ 16" O.C. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. SW 5"X18" G.L.B. 2X12 @ 16" O.C. PROVIDE 1" JOINT BETWEEN THE PROPOSED AND EXISTING STRUCTURES 5"X18" G.L.B. W (2) 2X12 5"X18" G.L.B. TYP. 8 X6 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 11'-83" 8 2X12 @ 16" O.C. 5"X18" G.L.B. 2X12 @ 16" O.C. TYP. 10 (2) 2X12 5"X18" G.L.B. 6'-33" 8 5"X18" G.L.B. 6'-23 4" 8 10 X6 W SW 8 X6 5"X18" G.L.B. W (2) 2X12 2X12 STAIR STRINGERS @ 12" O.C., TYP. 10 (2) 2X12 2X12 @ 16" O.C. W 5"X18" G.L.B. SIM. W (2) 2X12 8"X18" G.L.B. P.A. 2X12 @ 16" O.C. 0 (2) 2X12 0 X1 (2) 2X12 10 11'-73 8" 5"X18" G.L.B. 5"X18" G.L.B. 2X12 @ 16" O.C. 5"X18" G.L.B. 6'-25 8" 5"X18" G.L.B. P.A. 5"X18" G.L.B. 10'-93" 8 5"X18" G.L.B. 5'-9" 5"X18" G.L.B. 5"X18" G.L.B. 11'-73" 8 1" 1'-44 5"X18" G.L.B. 5"X18" G.L.B. 11'-83 8" CANT. 5"X18" G.L.B. 2X12 @ 16" O.C. 5'-8" W 10 X1 00 S-401 5"X18" G.L.B. P.A. 11'-83" 8 OUTLINE OF PROPOSED DECK 12 1" 4'-112 CANT. 1" 6'-118 2X12 @ 16" O.C. 2X12 @ 16" O.C. . .B 5'-8" 7 S-201 .L 1" 4'-112 6 S-201 "G 1" 6'-118 4 S-201 8 X1 5"X18" G.L.B. W 10'-10" 5" 5"X18" G.L.B. 2X12 @ 16" O.C. 5"X18" G.L.B. 11'-83" 8 2X12 @ 16" O.C. 5"X18" G.L.B. 5"X18" G.L.B. 5"X18" G.L.B. 00 X1 . .L G " 18 X 2X12 @ 5" 16" O.C. CANT. G.L.B AT "A.1" LINE TO "A," TYP. 5"X18" G.L.B. 10 W 7'-23 8" 5"X18" G.L.B. S-401 2X12 STAIR STRINGERS @ 12" O.C., TYP. CANT. 7'-23" 8 S-401 S-201 11 12'-71" 8 9'-6" 11'-7" 1'-2" 4'-9" B. 9'-105 8" 6'-25 8" 1" 17'-34 S-401 4X4 P.T. POST, TYP. TYP . (2) 2X12 P.T. DROP GIRDER AT PIERS, TYP. 2X12 JOISTS @ 12" O.C., TYP. 2X12 JOISTS @ 12" O.C., TYP. (2) 2X12 JOISTS @ EDGE, TYP. (2) 2X12 JOISTS @ EDGE, TYP. 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz 1" 17'-34 11'-27" 8 3'-0" 21'-9" 7'-23 8" (CANT.) 5'-8" 1" 4'-112 1" 6'-118 1" 6'-92 (2) 2x6 6'-33 8" 5K 3. LV L 1 4" x9 4" (2 )1 K 3. 8 (3) 1 34 x 18 LVL 6'-23 4" 5'-9" SW 5'-113 8" SLOPE (2)2x8 (2)2x8 1.9K (3)2x8 PWT @ 24" O.C. MULTI-PLY PWT's (2)2x8 4'-7" (2) 2x8 (2) 2x8 x 1 WP7 (3)2x8 (3)134"x1141"LVL 11'-83 8" WP2 3. 5K 11'-73 8" (2) 2x8 WP2 SKY-LIGHT) WP2 6'-25 8" WP2 (2) 2x8 SPACE TRUSSES FURTHER APART (2) 2x6 B MULTI-PLY PWT's 4.7K SLOPE 6.2K (3)134"x1141"LVL WP5 WP6 WP1 (2) 2x8 (2)2x8 MULTI-PLY PWT's 2x8 (2) 2x8 1.2K 1.2K (2)2x8 2x8 SW 1.1K 1.1K B .85K .85K 2x8 2x8 2x8 2x8 1.1K 1.1K 4 S-202 WP7 WP6 BM HSS10x6x3/8 6x10 6x10 (2)134"X1141" LVL (2)2x10 LOW @16"o.c. 1.9K 5 4 1 (2) 2x6 (2) 2x6 4 L LV 1 1 4" 3 4" WP6 WP6 6x10 6x10 6x10 6x10 6x10 134"X921" LVL (2)2x10 LOW (3)134"X20" LVL @16"o.c. 134"X921" LVL (2)2x10 LOW WP1 WP2 4'-117" 8 L LV 7 8" x1 1 (2 ) (2)134"X1141" LVL WP2 BM 3 S-201 WP2 PROVIDE 2x8 @ 16" O.C. AT ROOF CORNERS TYP. 1 S-202 WP2 (2)2x8 [ELEV. -] SLOPE 2 NOTE: TRUSS MANUFACTURER TO DESIGN TRUSSES FOR CONCENTRATED LOADS AROUND SKYLIGHTS AND AT HIP OR VALLEY RAFTERS FOR LOADS SHOWN ON PLANS. LOADS ARE IN KIPS (1000 LBS.) ALL HEADERS SHOWN TO BE TOP AND BOTTOM. SEE NOTE 7, THIS SHEET. TYPICAL 10'-93 8" L LV 4" 1 9 3 "x 3 4" (3)134"x16"LVL [ELEV. -] WP2 B 2X6@12"OC. BEARING WALL D-FIR. No 2 (2) 2x6 1 4 (2 )1 (2 )1 6x10 6x10 6x10 6x10 VL "L 6'-25 8" (2) 2x6 1 WP2 2 VL (2)2x8 [ELEV. -] PA S-201 S-201 L 1 " 94 WP2 WP1 (2)134"x741"LVL WP2 SLOPE B WP2 SLOPE 1 3 "x )1 4 WP2 SLOPE (2)2x6(L) (3) 1 34 x 18 LVL WP2A SLOPE (2 WP2 BOX BM LOW (2)134"X921" LVL (2)2x6(L) VL (2)134"x741"LVL VL WP1 WP1 SLOPE "L WP1 8 WP1 WP2 7 11 4 2X8@16"OC. TYP. WP2 BM SLOPE 2X8@16"OC. TYP. 1.1K 1.1K B WP2 L 1 " 94 (2)2x6 WP2 (2)134"x741"LVL 3 "x )1 4 (2 WP2 WP2 (2)134"x1141"LVL (2)134"x1141"LVL (2)2X8 (2)2X8 WP3 WP2 1.1K 1.1K SLOPE 94 (2)2x8 OUTLINE OF PARAPET WALL ABOVE (TYP.) WP2 3 "x )1 4 (2 "x 3 WP1 SLOPE (2)2x8 SLOPE WP4 4x8 2X6@12"OC. BEARING WALL D-FIR. No 2 VL 4x8 2X8@16"oc WP1 HEAVY TIMBER TRUSS TYPE 1 L 1 " 94 (3)134x16" LVL REFER TO NOTE 8 FOR FRAMING AROUND MECH. EQUIPMENT (TYP.) WP2 2x8 2x8 @ 16" O.C. 3 WP1 B SLOPE (2)2x8 PA (3) 1 34 x 18 LVL 3 "x )1 4 B 4x8 (2 1k 1k WP2 4x8 (3)2X10 (3)134x18 LVL (2) 2x8 8K 1k 1k .5k .5k (2)2x8 PROVIDE 1" JOINT BETWEEN PROPOSED AND EXISTING STRUCTURES PROVIDE 2x8 @ 16" O.C. AT ROOF CORNERS TYP. 6x10 4x8 OUTLINE OF ROOF TOP EQUIPMENT. CONTRACTOR TO COORDINATE FINAL LOCATION (TYP) HEAVY TIMBER TRUSS TYPE 1 HSS10x6x3/8 (2)2x8 WP1 (3)2X10 WP1 (3) 1 34 x 18 LVL 3. WP7 (2)2x8 .6k .6k WP1 6x10 6x10 6x10 6x10 4x8 SW RP B 4x8 (2)2x8 B WP6 B 2x8 WP2 RD TYPICAL SKYLIGHT OPENING 4x8 HSS10x6x3/8 1k 1k HSS10x6x3/8 1k 1k WP6 WP7 B (2)2x8 SW .6k .6k (2)2x8 B (2 )1 SW RD RP DENOTES POST MARK SEE POST SCHEDULE THIS SHEET. (TYP) BM REFER TO NOTE 8 FOR FRAMING AROUND MECH. EQUIPMENT (TYP.) HEAVY TIMBER TRUSS TYPE 1 PWT @ 24" O.C. WP6 SW 6x10 6x10 6x10 6x10 6x10 PWT @ 24" O.C. SLOPE WP4 WP2A BOLT LVL TOGETHER W=1100 PLF SW B (3)2x8 1.6 1.6k RD 4x8 WP2A WP6 8K 3. MULTI-PLY PWT's 1.1k1.2k B 4x8 WP7 (2)2x8 WP2 (3)134x16 LVL HSS10x6x3/8 (2)2x8 6x10 1k 1k 4x8 6x10 RP 4x8 6x10 HSS10x6x3/8 1k 1k RD (2)2x8 " 4 (3) 1 34 x 18 LVL (3) 1 34 x 18 LVL x9 X5 X SS 5 H (3)134x16 LVL (3)134x16 LVL X X5 5 SS H H SS H " 4 HEAVY TIMBER TRUSS TYPE 1 (2)2x8 (2)134x941" LVL 8K (3) 1 34 x 18 LVL 1k 1k 1.1k1.2k 3. 5K L (2) 2x8 LV 1 4" 3 4 SLOPE 3. 4x8 4 SS 5 5X 5 6x10 HSS10x6x3/8 4x8 6x10 6x10 6x10 6x10 6x10 4x8 6x10 6x10 4x8 1 " 1 4 X5 X X " 1 PROVIDE SIMPSON HUCQ412-SDS HANGER AT EACH END OF LVL WP2 VL PWT @ 24" O.C. "x ( HEAVY TIMBER TRUSS TYPE 1 HSS10x6x3/8 1k 1k SLOPE SLOPE HSS10x6x3/8 6x10 6x10 6x10 6x10 6x10 6x10 WP6 WP6 (2)2x8 9 1 2) (2)134x941" LVL SLOPE 6x10 6x10 6x10 6x10 6x10 6x10 6x10 6x10 6x10 S-301 PWT @ 24" O.C. S-201 L PS 5 HSS12x8x3/8 6x10 6x10 6x10 6x10 6x10 6x10 6x10 6x10 6x10 6x10 6x10 1 (2) 2x8 WP2 6 PROVIDE SIMPSON HUCQ412-SDS HANGER AT EACH END OF LVL 2x8 @ 16" O.C. L 1 " 94 11'-83" 8 HSS5X5X1 4" S-201 L K LV 3.8 1 " 94 WP8 2 FRAMING AT SKYLIGHT TO BE TOP AND BOTTOM. SEE NOTE 7. (TYPICAL) GIRT [ELEV. +20'-0"] 7 HSS5X5X1 4" 3 "x )1 4 (2 (3)134"x1178"LVL WP2 PROVIDE 2x8 @ 16" O.C. AT ROOF CORNERS TYP. 3 "x )1 4 (2 WP1 WP2 8 REFER TO 6/S501 FOR STEEL TUBE CONNECTION (TYP. EACH END) 5K (3)134"x1178"LVL (2)2x10 HSS10x6x3/8 WP1 SW WP2 5 4 S-201 REFER TO S-102 FOR COLUMN SIZE TYP. HEAVY TIMBER TRUSS TYPE 1 (2)2x8 S-402 HSS 12x4x3 8 COLUMN REFER TO SECTION 3/S-501 FOR HEAD DETAIL 3. 10'-10" HSS 20x12x (2)134"x1178"LVL LVL SUPPORT BEAMS AND POSTS TO BE CONCEALED IN PARTITION WALLS, SEE S102 WP8 HEAVY TIMBER TRUSS TYPE 2 (3)134"x18" LVL WP8 PA 4 S-402 5 S-201 (3)2X8 HDR. WP6 2x8@16"o.c. TYPICAL HSS 12x4x3 8 COL. REFER TO SECTION 3/S-501 FOR HEAD DETAIL HSS12x8x3/8 LVL STRUC. RIDGE 1" 1'-44 6'-111" 8 12'-71" 8 9'-6" 11'-7" 6x10 OUTRIGGER AT GABLE END, TYP. PROVIDE OUTRIGGERS AT EACH END OF GATHERING ROOM. (CANT.) 7'-23" 8 5'-8" 1" 4'-112 S-402 134"x941" 11'-83 8" 9'-105" 8 10'-0" S-302 3 11'-83 8" 10'-0" 4'-9" HEAVY TIMBER TRUSS TYPE 2 11'-73 8" 11'-6" 1'-2" 6 4'-117 8" 11'-05" 8 21'-9" 4'-9" 10'-93 8" 9'-113 8" 11'-17" 8 43'-6" S-202 3 S-202 POST SCHEDULE LINE OF EXISTING BUILDING, TYP. MARK WP1 SIZE (2) 2X6 WP2 541"X541" PSL WP2A 541"X541" WP3 WP4 NAILING 16d COMMON FACE NAILS AT 24" O.C. POST CAP/BASE (2) SIMPSON ACE4 T&B. GRADE D.FIR No. 2 --- (2) SIMPSON ACE4 T&B. ENGINEERED --- --- (2) SIMPSON AC6 (14-16d) T&B. ENGINEERED --- 7"X7" PSL --- (2) SIMPSON ACE4 T&B. ENGINEERED --- --- (2) SIMPSON ACE4 T&B. ENGINEERED --- WP5 541"X7" PSL 321"X541" PSL --- (2) SIMPSON ACE4 T&B. ENGINEERED --- WP6 (3) 2X6 16d COMMON FACE NAILS AT 16" O.C. EACH FACE (2) SIMPSON ACE4 TOP; HDQ8-SDS3 HOLD DOWN D.FIR No. 2 WP7 (3) 2X4 16d COMMON FACE NAILS AT 16" O.C. EACH FACE (2) SIMPSON ACE4 T&B. D.FIR No. 2 WP8 321"X321" PSL (2) SIMPSON ACE4 TOP. HDQ8-SDS3 HOLD DOWN ENGINEERED PSL --- TYPICAL HANGER AND STRAP/HURRICANE TIE SCHEDULE ROOF FRAMING PLAN SCALE: 1/8"= 1'-0" ELEMENT FACE MOUNT HANGER TOP FLANGE HANGER STRAP/HURRICANE TIE (AT WALL SUPPORT) ROOF TRUSS --- --- SIMPSON HTS-20 WITH (24) 10d COMMON NAILS LVL GIRDERS/ RAFTERS --- --- SIMPSON HTS-20 WITH (24) 10d COMMON NAILS 2X12 JOIST SIMPSON LUS210 HU212TF (2) SIMPSON H2.5A 2X10 JOIST SIMPSON LUS210 HU210TF (2) SIMPSON H2.5A 2X8 JOIST SIMPSON LUS28 HU28TF (2) SIMPSON H2.5A 2X6 JOIST SIMPSON LUS26 HU26TF (2) SIMPSON H2.5A 4X8 JOIST SIMPSON HUCQ4-10 SDS --- --- 6X10 JOIST SIMPSON HUCQ6-10 SDS --- --- COMMENTS --- SEE 1/S402 FOR HOLD DOWN ANCHOR DETAILS --SEE 1/S402 FOR HOLD DOWN ANCHOR DETAILS 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz S501 5 8" PLYWOOD WITH EXTERIOR GLUE P.T. WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS 1" 11'-42 9'-6" 7 S501 2x6 NON-LOAD BEARING WALL LVL 10'-0" (P.T.) 3 T&G PLYWOOD SHEATHING 2 S401 2x12's AT 16" O.C. SOLID BLOCKING BEWTEEN JOISTS AT MIDSPAN AND AT SUPPORT LOCATIONS TRUSS CONNECTION TO BE DESIGNED BY TRUSS MANUFACTURER. MULTI-PLY WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS HSS14x4x5 8 WITH 12 THREADED ROD WELDED TO TOP AND BOTTOM AT 16" O.C. TO ATTACH BLOCKING (COUNTERSINK NUTS) 2x4 NON-LOAD BEARING WALL 4" P.T. 2X6 CONT. (TYP) SEE ARCH'L. PLANS FOR MOLDING (3)134"x16" LVL 6 S401 TYP. P.T. 2X6 CONT. (TYP) SEE ARCH'L. PLANS FOR MOLDING COMPOSITE DECKING, SEE ARCH. DWGS. GLUE LAMINATED BEAM SEE PLANS FOR SIZE P.T. LVL BEAM SEE PLAN FOR SIZE. 16'-1" TOP OF PARAPET (3)134"x18" 10'-0" P.T. DOUBLE 2X6 TOP PLATE 4'-0" NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. HIP RAFTERS TO FRAME IN AT PANEL POINT. (FAR SIDE) SEE PLAN FOR SIZE. MULTI-PLY PREFAB. WOOD TRUSSES TO BE DESIGNED BY OTHERS. 5 8" PLYWOOD WITH EXTERIOR GLUE NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. CONCRETE PIER AND FOOTING SEE PLANS FOR TYPE AND SIZE 8 S501 (2)134"x941" LVL (P.T.) VALLEY BEAM (2)134"x941" 2x8 (P.T.) @16" OC. SLOPING JOISTS LVL (P.T.) HIP BEAM 3 4" T&G PLYWOOD SHEATHING 2 S401 2x12's AT 16" O.C. TYP. 6 S401 GLUE LAMINATED BEAM SEE PLANS FOR SIZE 8" PLYWOOD WITH EXTERIOR GLUE 541"x541" PSL POST TO SUPPORT VALLEY BEAM SUSPENDED CEILING SEE ARCH. DWGS. (3)134"x18" LVL BEAM (P.T.) SEE PLAN FOR SIZE LVL NON-LOAD BEARING WALL 7 S501 TRUSS BEARING LINE (P.T.) (3)134"x16" LVL (P.T.) 3 COMPOSITE DECKING, SEE ARCH. DWGS. 4 S401 T&G PLYWOOD SHEATHING SOLID BLOCKING BEWTEEN JOISTS AT MIDSPAN AND AT SUPPORT LOCATIONS 4" 2 S401 6 S401 TYP. HSS14x4x5 8 WITH 12 THREADED ROD WELDED TO TOP AND BOTTOM AT 16" O.C. TO ATTACH BLOCKING (COUNTERSINK NUTS) 2X6 CONT. (TYP) SEE ARCH'L. PLANS FOR MOLDING COMPOSITE DECKING, SEE ARCH. DWGS. 2x12's AT 16" O.C. GLUE LAMINATED BEAM SEE PLANS FOR SIZE CONCRETE WALL AND FOOTING SEE PLANS FOR TYPE AND SIZE 16'-1" TOP OF PARAPET P.T. DOUBLE 2X6 TOP PLATE 2x6 BEARING WALL NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. CONCRETE PIER AND FOOTING SEE PLANS FOR TYPE AND SIZE 16'-1" TOP OF PARAPET P.T. WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS 10'-0" TRUSS CONNECTION TO BE DESIGNED BY TRUSS MANUFACTURER. 5 2x8 (P.T.) @16" OC. ROOF JOISTS P.T. 2X6 CONT. (TYP) SEE ARCH'L. PLANS FOR MOLDING MULTI-PLY PREFAB. WOOD TRUSSES TO BE DESIGNED BY OTHERS. P.T. WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS 10'-0" PROVIDE (2) 2X6 BEAMS BELOW PARAPET (TYP) 5 8" PLYWOOD WITH EXTERIOR GLUE NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. SKY-LIGHT SEE ARCHITECTURAL PLANS. 2X8 FRAMING AROUND SKY-LIGHT. SEE PLAN 5 P.T. WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS 3 4" T&G PLYWOOD SHEATHING 2x12's AT 16" O.C. GLUE LAMINATED BEAM SEE PLANS FOR SIZE TRUSS CONNECTION TO BE DESIGNED BY TRUSS MANUFACTURER. 2 S401 TYP. LVL BEAM (P.T.) SEE PLAN FOR SIZE 2x6 BEARING WALL BEYOND 5 8" PLYWOOD WITH EXTERIOR GLUE 4'-0" 10'-0" MULTI-PLY P.T. PREFAB. WOOD TRUSSES TO BE DESIGNED BY OTHERS. 10'-0" P.T. 2X6 CONT. (TYP) 16'-1" TOP OF PARAPET P.T. WOOD TRUSS, TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz P.T. 2x6 FACIA NAIL TO EA. TRUSS (TYP) BEARING WALL 2X6@12"O.C. D-FIR No. 2 (3)134"x18" LVL (P.T.) BEARING WALL 2X6@12"O.C. D-FIR No. 2 2 S401 TYP. 3 4" T&G PLYWOOD SHEATHING 2x12's AT 16" O.C. NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. 6 S401 SOLID BLOCKING BEWTEEN JOISTS AT MIDSPAN AND AT SUPPORT LOCATIONS 16'-1" TOP OF PARAPET PLYWOOD WITH EXTERIOR GLUE 8" PLYWOOD WITH EXTERIOR GLUE 8" 10'-0" 5 HIP RAFTERS BEYOND TO FRAME IN AT PANEL POINT OF TRUSS. SEE PLAN FOR SIZE. PROVIDE TOP MOUNT JOIST HANGER FOR SLOPING MEMBER. TYP COMPOSITE DECKING, SEE ARCH. DWGS. P.T. 2x8@16" OC. P.T. 2x6 @16" O.C. GLUE LAMINATED BEAM SEE PLANS FOR SIZE CONCRETE PIER AND FOOTING SEE PLANS FOR TYPE AND SIZE CONCRETE PIER AND FOOTING SEE PLANS FOR TYPE AND SIZE NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. P.T. 2X6 CONT. (TYP) SEE ARCH'L. PLANS FOR MOLDING MULTI-PLY P.T. WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS LVL BEAM (P.T.) SEE PLAN FOR SIZE. PROVIDE (2) 2X6 BEAMS BELOW PARAPET (TYP) F 5 8" PLYWOOD WITH EXTERIOR GLUE H P.T. 2X6 CONT. (TYP) SEE ARCH'L. PLANS FOR MOLDING SEE ARCH. PLANS FOR FLASHING DETAILS. PROVIDE JOIST HANGER AT EACH RAFTER TYP. CONTINUE MULTI-PLY PREFAB. WOOD TRUSSES OR PROVIDE SOLID BLOCKING BETWEEN TRUSSES BEARING ON WALL 134"x921" LVL @16" O.C. TRUSS CONNECTION TO BE DESIGNED BY TRUSS MANUFACTURER. 2x4 SHEAR WALL 134"x921" LVL @16" O.C. ROOFING ON 5 8" PLYWOOD JOIST HANGER TYP. CEILING JOIST 2x6 @ 16" O.C. 3 T&G PLYWOOD SHEATHING SEE ARCH. PLANS FOR FLASHING DETAILS. (2)2x10 (2)2x10 MULTI PLY GLUED PLYWOOD BEAM @ 16"OC. CUT PER ARCH. RADIUS. SEE ARCH. PLANS H1 TYPE HURRICANE ANCHOR BY SIMPSON TYP. AT EACH RAFTER (2)134"x1141" JOIST HANGER TYP. 4" 2x12's AT 16" O.C. 2 S401 TYP. 6 S401 2x6 BEARING WALL COMPOSITE DECKING, SEE ARCH. DWGS. 2x6 FACIA BOARD CONT. CEILING JOIST 2x6 @ 16" O.C. (2)2x10 H1 TYPE HURRICANE ANCHOR BY SIMPSON TYP. AT EACH RAFTER SIMPSON LUSC28-2 JOIST HANGER. TYP. LVL D P.T. WOOD TRUSS TO BE DESIGNED BY OTHERS. REFER TO LOADING DIAGRAMS 10'-0" 1" 28 (3)134"x20" LVL 16'-1" TOP OF PARAPET D (2)134"x1141" F LVL GLUE LAMINATED BEAM SEE PLANS FOR SIZE CONCRETE PIER AND FOOTING SEE PLANS FOR TYPE AND SIZE NOTE: REFER TO STRAP/HURRICANE TIE SCHEDULE ON DRAWING S-103 FOR ROOF FRAMING TIE DOWN INFORMATION. H SEE ARCH. PLANS FOR FLASHING DETAILS. 21" 8 (3)134"x20" LVL PROVIDE JOIST HANGER AT EACH RAFTER TYP. (3)134"x16" LVL 134"x921" LVL @16" O.C. ROOFING ON 5 8" PLYWOOD 134"x921" LVL @16" O.C. (2) 2x8 (2)2x10 BEAM TYP. (2)2x10 BEAM TYP. 2x6 FACIA BOARD CONT. TYP. MULTI PLY PLYWOOD BM SEE SECTION 1 THIS SHEET (2) 2x8 (2)134"x1141" LVL (2)2x10 BEAM TYP. SIMPSON LUSC28-2 JOIST HANGER. TYP. 541"x541" PSL POST TYP. 541"x541" PSL POST TYP. SEE ARCH. PLANS FOR FLASHING DETAILS. H1 TYPE HURRICANE ANCHOR BY SIMPSON TYP. AT EACH RAFTER (2)134"x1141" LVL 541"x541" PSL POST TYP. 4.8 1 CENTER LINE OF 2x6 WALL 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz SEE ARCH. PLANS FOR FACIA AND FLASHING DETAILS (3)134"x16" LVL RIDGE BEAM (3)134"x20" LVL 541"x541" PSL 2x6 STUD WALL @ 16" OC. PROVIDE DOUBLE TOP PLATE BOTTOM OF LVL (2)2x10 BEAM WOOD BOX BEAM (2)2x12 WEB 2x6 TOP AND BOTTOM ARCHEDWINDOW SEE ARCH. PLANS . (2)2x8 BEAM BEYOND 541"x541" PSL POST BEYOND (2)2x10 BEYOND MULTI PLY GLUED PLYWOOD BEAM @ 16"OC. CUT PER ARCH. RADIUS. SEE ARCH. PLANS 541"x541" PSL POST BEYOND 2x6 STUD WALL @ 16" OC. PROVIDE DOUBLE TOP PLATE WOOD BOX BEAM (2)2x12 WEB 2x6 TOP AND BOTTOM DOOR SEE ARCH. PLANS +12'-0" FINISHED FLOOR 7"x7" PSL W10 COL. (GALV.) 1 1 4" DIAMETER ASTM F1554 GR. 55 ANCHOR RODS (GALV.) 1 x 4 12" x 4" TALL STIFFENER PLATES GALV. (3 PER SIDE) 2" 1" TOP PLATE GALV. 1"x12"x1'-8" BASE PLATE PLAN VIEW W10 COL. (GALV.) 1 1 4" DIAMETER ASTM F1554 GR. 55 ANCHOR RODS (GALV.) 1" TOP PLATE GALV. 1 x 4 12" x 4" TALL STIFFENER PLATES GALV. (3 PER SIDE) 2" 1"x12"x1'-8" BASE PLATE DOUBLE NUTS FOR LEVELING 2 12" NON-SHRING GROUT CONCRETE PIER SEE PIER SCH. FOR SIZE AND REINFORCING CONCRETE FOOTING SEE FOOTING SCH. FOR SIZE AND REINFORCING PROVIDE 12"x3"x3" FISH PLATE WITH NUT TOP AND BOTTOM AT BOTTOM OF EACH ANCHOR ROD TYP. SECTION TYPICAL BASE PLATE DETAIL AT W10 COLUMNS HEAVY TIMBER TRUSS TYPE 1 WORK POINT SEE ARCH. DWGS. FOR ROOFING AND FLASHING DETAILS SEE ARCH. DWGS. FOR ROOFING AND FLASHING DETAILS 3 8" GALV. STEEL SIDE PLATES WITH 1" DIAMETER A-325 THRU BOLTS (GALV.) TYP. 6X10 TIMBER BEAM 12X12 TOP CHORD 12X12 TOP CHORD WORK POINT 12X12 TOP CHORD 3 LINE OF 2X6 FULL-SAWN TONGUE-AND-GROOVE DECKING, SEE 4/S302 8" GALV. STEEL SIDE PLATES WITH 1" DIAMETER A-325 THRU BOLTS (GALV.) TYP. CENTERLINE OF TIMBER HSS10x6x3 8 WITH 1 4" BENT PLATE WELDED TO TOP SEE ARCH. DWGS. FOR ROOFING AND FLASHING DETAILS LINE OF 2X6 FULL-SAWN TONGUE-AND-GROOVE DECKING, SEE 4/S302 6X10 TIMBER BEAM LINE OF 2X6 FULL-SAWN TONGUE-AND-GROOVE DECKING, SEE 4/S302 WORK POINT CENTERLINE OF TIMBER 12X12 BOTTOM CHORD 12X12 WEB CENTERLINE OF TIMBER WORK POINT 5" W10 STEEL COLUMN GALV. STEEL SIDE PLATES WITH 1" DIAMETER A-325 THRU BOLTS (GALV.) TYP. 12X12 WEB 8" 4" 3 CENTERLINE OF TIMBER 12X12 TIMBER DIAGONAL 7" N. MI 7" YP. T 12X12 TIMBER DIAGONAL 12X12 BOTTOM CHORD CENTERLINE OF TIMBER 6" 4" 1 2" 2 CENTERLINE OF TIMBER P. TY T 4" . YP N. MI . P TY 1 1/2" 4'-6" 1" DIAMETER A-325 THRU BOLTS (GALV.) TYP. N. MI 1 2" 1 . YP T 4" WORK POINT 3 8" GALV. STEEL SIDE PLATES WITH 1" DIAMETER A-325 THRU BOLTS (GALV.) TYP. 3 CENTERLINE OF COLUMN 8" GALV. STEEL SIDE PLATES WITH 3 8" GALV. SEAT PLATE CENTERLINE OF TIMBER 12X12 TIMBER DIAGONAL 3 8" GALV. STEEL SIDE PLATES WITH 1" DIAMETER A-325 THRU BOLTS (GALV.) TYP. 12X12 BOTTOM CHORD SECTION SECTION SECTION 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz SECTION SECTION HEAVY TIMBER TRUSS TYPE 2 GATHERING ROOM STRUCTURAL ROOF DECKING TYP. PURLIN CONNECTION DETAIL TYP. PURLIN OUTRIGGER CONNECTION DETAIL 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz SECTION A-A TYP. PIER AND FOOTING DETAIL A GLU-LAM BEAM SEAT DETAIL TYP. PIER AND FOOTING DETAIL SHEAR WALL FND. DETAIL A.1 FOUNDATION DETAIL AT EX. BUILDING TYP. DETAIL AT FRAMED WALL EXTERIOR STAIR FRAMING DETAIL RAMP TO FINISHED GRADE TRANSITION DETAIL 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz TYP. RAMP FRAMING DETAIL GLUE LAM FRAMING DETAIL GLUE LAM FRAMING DETAIL GLUE LAM FRAMING DETAIL A TYPICAL SHEAR WALL HOLD DOWN DETAIL TYPICAL STEEL TUBE BASE PLATE DETAIL 4 3 S402 S402 A.1 FRAMING SECTION AT EX. BUILDING FRAMING SECTION AT OFFICE 117 FRAMING SECTION AT OFFICE 117 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz TYP. DETAIL AT HEAD OF TUBE POST TYP. SHEAR WALL DETAIL TYP. DETAIL AT ROOF TRANSITION ROOF FRAMING NOT SHOWN FOR CLARITY HURRICANE TIE/STRAP REFER TO SCHEDULE ON DWG. S-103 DOUBLE 2x6 PLATE 1 4"x3"x8" (GALV.) LONG TOP PLATE. WELD PLATE TO TOP OF POST AND TUBE WITH 1 4" FILLET WELD ALL AROUND. SIMPSON HUCQ410 HEAVY DUTY JOIST HANGER. FASTEN TO STEEL POST WITH (10) 1/4-14 SELF DRILLING SCREWS 1 HSS5x5x 4 STEEL POST WITH 1 4" CAP PLATE HSS14x4X12 WITH 12" DIA. THREADED ROD WELDED TO TOP AND BOTTOM TO ATTACH BLOCKING. WELD TUBE TO SEAT WITH 1 4" FILLET WELD ALL AROUND. L4x4x1 4x0'-5" (GALV.) LONG SEAT WITH 3 8" FITTED STIFFENER AT CENTER. WELD SEAT TO POST WITH 1 4" FILLET WELD ALL AROUND. SECTION SECTION SECTION CABLE BARRIER. SEE ARCH. DRAWINGS FOR DETAILS AND LOCATION. DOUBLE 2X4 (P.T.) TOP PLATE PROVIDE SOLID (2) 2X4 BLOCKING BETWEEN 2X4 AT BARRIER POST LOCATIONS. ATTACH BLOCKING TO STUDS WITH A23 SIMPSON CLIPS 1 PROVIDE (4) 4x3 SDS SCREWS EACH SIDE PER CLIP PROVIDE 2X6 TOP CHORD EXTENSION AT 24" O.C. TO FRAME ROOF. CONTRACTOR HAS OPTION TO PANELIZE OR STICK FRAME PEAK OF TRUSS L4x4x1 4x0'-4" LONG (GALV.) CLIP EACH SIDE TYP. 2X4 (P.T.) AT 24" O.C. 5 8" PLYWOOD WITH EXTERIOR GLUE 2X4 (P.T.) CONT. BOTTOM PLATE SEE ARCH. DWGS. FOR ROOFING AND FLASHING DETAILS (2) 2X6 SOLID BLOCKING BETWEEN TRUSSES UNDER PARAPET PRE-ENGINEERED WOOD TRUSS SECTION BOTTOM CHORD OF PREFAB TRUSS PROVIDE (8) 1 4x3 SIMPSON SDS SCREWS EACH SIDE (STAGGER LOCATION) (3) 13 4x16 LVL. PROVIDE PLYWOOD SPACERS ON EACH SIDE OF LVL'S TO MAINTAIN REQUIRED WALL THICKNESS 1 4"x8"x12" TALL SIDE PLATES WELDED TO POST CAP PLATE WITH 3 16" FILLET WELD ALL AROUND HSS5x5x1 4 STEEL POST WITH 1 4" CAP PLATE SECTION 64 Thompson Street, Suite A101 East Haven, CT 06513 Tel: 203.467.4370 Fax: 203.468.6172 Web: www.iesllc.biz