CURRENT IN MULTIPLES OF RATING PLUG AMPERES .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 600 0.022 seconds at 8,727 A 0.025 seconds at 8,727 A 500 500 0.018 seconds at 200,000 A 400 400 300 300 200 0.01 10000 1000 100000 Current in Amps Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 3 Amperes 200 7 Amperes 100 90 80 70 100 90 80 70 40 50 2 2 30 60 MIN MIN 50 40 30 3 3 20 20 4 4 10 9 8 7 5 5 6 6 6 4 10 9 8 7 5 6 5 4 MAX 3 3 MAX 2 K215-181B TIME IN SECONDS 60 TIME IN SECONDS 1000 900 800 700 2 1 .9 .8 .7 .9 .8 .7 .6 MIN .6 .5 MIN .4 .2 .5 .4 2 2 .3 1 .3 3 3 4 4 .1 .09 .08 .07 .2 5 .06 .06 6 6 .05 .1 .09 .08 .07 5 .04 MAX MAX .03 .05 .04 .03 NOTE 2 APPLIES .02 NOTE 2 APPLIES NOTE 2 APPLIES .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 7 Rating Plug Amperes 3, 7 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip K215-181B Instantaneous with Tracking Short-time Delay Time-current Curves Adjustments Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient Note 2: Current limiting range, please refer to inset curve. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. K215-181B 1000 900 800 700 CURRENT IN MULTIPLES OF RATING PLUG AMPERES .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 600 0.022 seconds at 8,727 A 0.025 seconds at 8,727 A 500 500 0.018 seconds at 200,000 A 400 400 300 300 200 0.01 10000 1000 100000 Current in Amps Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 15 Amperes 200 20 Amperes 100 90 80 70 TIME IN SECONDS 1000 900 800 700 100 90 80 70 60 60 50 50 40 40 30 MIN 20 30 MIN 2 2 3 10 9 8 7 20 3 10 9 8 7 4 4 6 TIME IN SECONDS 1000 900 800 700 6 5 5 4 5 5 4 3 3 6 6 2 2 MAX MIN .9 .8 .7 .6 MIN .6 2 2 .5 1 .5 .4 .4 3 3 .3 .3 .2 4 5 .1 .09 .08 .07 .06 .2 4 5 6 6 .05 .04 .06 .05 MAX .03 .1 .09 .08 .07 .04 MAX .03 NOTE 2 APPLIES .02 NOTE 2 APPLIES .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 30 Rating Plug Amperes 15, 20 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip K215-182B Instantaneous with Tracking Short-time Delay Time-current Curves Adjustments Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient Note 2: Current limiting range, please refer to inset curve. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. K215-182B K215-182B MAX 1 .9 .8 .7 CURRENT IN MULTIPLES OF RATING PLUG AMPERES .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 600 0.022 seconds at 8,727 A 0.025 seconds at 8,727 A 500 500 0.018 seconds at 200,000 A 400 200 0.01 10000 1000 100000 Current in Amps Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 25 Amperes 200 30 Amperes 100 90 80 70 100 90 80 70 60 60 50 50 40 40 30 MIN MIN 20 30 2 2 3 3 10 9 8 7 20 10 9 8 7 4 4 6 6 5 5 5 5 4 3 4 3 6 6 2 MAX 1 .9 .8 .7 .5 .9 .8 .7 .6 MIN 2 2 .4 2 MAX MIN .6 1 .5 .4 3 3 .3 .2 .3 4 .2 4 5 .1 .09 .08 .07 5 .1 .09 .08 .07 6 6 .06 .05 .04 .06 .05 MAX MAX .03 .04 NOTE 2 APPLIES .02 NOTE 2 APPLIES .03 .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 30 Rating Plug Amperes 25, 30 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 TIME IN SECONDS TIME IN SECONDS 400 300 300 K215-183B 1000 900 800 700 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip Instantaneous with Tracking Short-time Delay Time-current Curves Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient K215-183B Adjustments Long-time delay; not adjustable. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. Note 2: Current limiting range, please refer to inset curve. K215-183B 1000 900 800 700 CURRENT IN MULTIPLES OF RATING PLUG AMPERES .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 600 0.022 seconds at 8,727 A 0.025 seconds at 8,727 A 500 500 0.018 seconds at 200,000 A 400 400 300 300 200 0.01 100 90 80 70 TIME IN SECONDS 1000 900 800 700 10000 1000 100000 Current in Amps Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 100 90 80 70 50 Amperes 40 Amperes 200 60 60 50 50 40 40 30 30 MIN MIN 20 3 3 10 9 8 7 20 2 2 10 9 8 7 4 4 6 6 5 5 5 5 4 TIME IN SECONDS 1000 900 800 700 4 3 3 6 6 2 2 MAX MIN .6 .5 MIN 1 .5 2 .4 .9 .8 .7 .6 2 .3 .4 .3 3 3 .2 .2 4 4 5 5 .1 .09 .08 .07 6 6 .06 .1 .09 .08 .07 .05 .05 MAX MAX .04 .06 .03 .04 NOTE 2 APPLIES .02 NOTE 2 APPLIES .03 .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 60 Rating Plug Amperes 40, 50 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip Instantaneous with Tracking Short-time Delay Time-current Curves Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient K215-184B Adjustments Long-time delay; not adjustable. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX. Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. Note 2: Current limiting range, please refer to inset curve. K215-184B K215-184B MAX 1 .9 .8 .7 CURRENT IN MULTIPLES OF RATING PLUG AMPERES 1000 900 800 700 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 1000 900 800 700 600 500 500 400 400 300 300 0.025 seconds at 8,727 A 0.022 seconds at 8,727 A 200 200 0.018 seconds at 200,000 A 100 90 80 70 100 90 80 70 0.01 50 60 1000 10000 Current in Amps 100000 Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 40 MIN 30 60 Amperes 40 30 2 20 50 20 TIME IN SECONDS TIME IN SECONDS 60 3 10 9 8 7 10 9 8 7 4 6 6 5 5 4 4 3 3 6 K215-185B 2 2 MAX 1 .9 .8 .7 .9 .8 .7 .6 MIN .6 .5 .5 2 .4 1 .4 .3 .3 3 .2 .2 4 5 .1 .09 .08 .07 .1 .09 .08 .07 6 .06 .06 MAX .05 .05 .04 .04 .03 .03 NOTE 2 APPLIES .02 .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 60 Rating Plug Amperes 60 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip K215-185B Instantaneous with Tracking Short-time Delay Time-current Curves Adjustments Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient Note 2: Current limiting range, please refer to inset curve. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. K215-185B 5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 600 0.022 seconds at 8,727 A 0.025 seconds at 8,727 A 500 500 0.018 seconds at 200,000 A 400 400 300 300 100 90 80 70 10000 1000 100000 Current in Amps Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 100 90 80 70 80 Amperes 70 Amperes 200 60 60 50 50 40 40 30 MIN 20 20 2 2 3 3 10 9 8 7 30 MIN 10 9 8 7 4 4 6 6 5 5 5 4 5 3 4 3 6 6 2 1 .9 .8 .7 .5 1 .5 2 .4 .9 .8 .7 .6 MIN MIN .6 2 MAX MAX K215-186B TIME IN SECONDS 0.01 200 TIME IN SECONDS 1000 900 800 700 2 .3 .4 3 .3 3 .2 .2 4 4 5 .1 .09 .08 .07 5 .1 .09 .08 .07 6 6 .06 MAX .05 .06 .05 MAX .04 .03 .04 NOTE 2 APPLIES .02 NOTE 2 APPLIES .03 .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 100 Rating Plug Amperes 70, 80 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip K215-186B Instantaneous with Tracking Short-time Delay Time-current Curves Adjustments Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient Note 2: Current limiting range, please refer to inset curve. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. K215-186B 1000 900 800 700 CURRENT IN MULTIPLES OF RATING PLUG AMPERES .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT LIMITING PERFORMANCE AT HIGH S/C VALUES 0.1 600 600 0.022 seconds at 8,727 A 0.025 seconds at 8,727 A 500 500 0.018 seconds at 200,000 A 400 0.01 100 90 80 70 10000 1000 100000 Current in Amps Applies at < 480 Vac. >480 Vac Curve Extends to Application at 0.025 Seconds 100 90 80 70 100 Amperes 90 Amperes 200 60 60 50 50 40 40 MIN MIN 30 20 20 2 2 3 10 9 8 7 30 3 4 10 9 8 7 4 6 5 6 5 4 5 5 3 4 6 2 2 .4 .9 .8 .7 .6 MIN MIN .5 2 MAX MAX .6 3 6 2 1 .9 .8 .7 1 .5 .4 3 3 .3 .2 .3 4 4 .2 5 5 .1 .09 .08 .07 6 .1 .09 .08 .07 6 MAX .06 MAX .06 .05 .05 .04 .04 .03 .03 NOTE 2 APPLIES .02 NOTE 2 APPLIES .02 .01 .01 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 1 2 3 4 5 6 7 8 9 10 20 30 40 CURRENT IN MULTIPLES OF RATING PLUG AMPERES GE Consumer & Industrial Electrical Distribution Current Ratings Frame Amperes 100 Rating Plug Amperes 90, 100 Voltage Ratings 2 Pole — 480 Vac max. 3 Pole — 600 Vac max. 05.10 MAG-BREAK® Motor Circuit Protector Type SE with Spectra RMS® Solid-state Trip TIME IN SECONDS 200 TIME IN SECONDS 400 300 300 K215-187B 1000 900 800 700 K215-187B Instantaneous with Tracking Short-time Delay Time-current Curves Adjustments Curves apply at 50 to 400 Hertz and from -20°C to 70°C breaker ambient Note 2: Current limiting range, please refer to inset curve. Instantaneous pick-up settings in multiples of rating plug rating: MIN, 2, 3, 4, 5, 6, MAX Note 1: Operation above 60 Hertz and 50°C play require thermal and interrupting derating of the circuit breaker. Refer to Selection and Application manual. K215-187B 1000 900 800 700