See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/261055151 Transformer Tertiary Stabilizing Windings. Part I: Apparent power rating Conference Paper · September 2012 DOI: 10.1109/ICElMach.2012.6350213 CITATIONS READS 7 3,209 3 authors: Patricia Penabad-Duran Xose M. Lopez-Fernandez University of Vigo University of Vigo 10 PUBLICATIONS 116 CITATIONS 45 PUBLICATIONS 414 CITATIONS SEE PROFILE SEE PROFILE C. Alvarez-Marino University of Vigo 13 PUBLICATIONS 165 CITATIONS SEE PROFILE Some of the authors of this publication are also working on these related projects: Efecto del desequilibrio de tensiones en el desempeño energético del motor de inducción View project All content following this page was uploaded by Xose M. Lopez-Fernandez on 14 December 2020. The user has requested enhancement of the downloaded file. Transformer Tertiary Stabilizing Windings. Part I: Apparent Power Rating Patricia Penabad-Duran, Xose M. Lopez-Fernandez, Casimiro Alvarez-Mariño Abstract -- This paper presents a calculation method for the apparent power rating of Tertiary Stabilizing Winding (TSW) of power transformers, which is scarcely discussed in the literature. The objetive of the work is to offer an appoach for the dimensioning of TSWs from the knowledge of expected unbalanced load conditions. For that purpose, the equivalent circuit model of a three-winding transformer for single-phase load and single phase-to-ground fault study is discussed, where zero sequence impedances are determined by means of several proposed tests. A practical application is presented and the equivalent circuit model is validated with Finite Element Method (FEM) computations. A companion paper which complements this work evaluates the influence of TSWs on the overheating hazard on tank walls under unbalanced load conditions. Index Terms-- Leakage flux, Zero sequence current, Threephase transformer, Core type, Symmetrical components, Equivalent circuit, Tertiary stabilizing winding. 1 I. INTRODUCTION W ITH the advent of the three-phase system, two alternative methods of transformer windings connection were offered (ie. the Delta and Wye connections). The Wye connection offers some advantages such as it provides two different values secondary voltages, and it makes possible to ground all three phases symmetrically at a common point. However, it did not take long to the industry to discover one problem after another arising from the Yy-connected transformers [1]. For many years it has been a common practice to include a Tertiary Stabilizing Winding (TSW), particularly in Yy-connected transformers. The TSW, which is not intended to connect any load, is meant instead for purposes such as stabilizing the neutral point of the fundamental frequency voltages, to protect the transformer and system from a excessive thirdharmonic, and to provide an internally closed circuit for zero sequence currents [2]. This practice has been followed so closely for so many years that it is generally taken for granted that the stabilizing winding is a necessary part of such transformers [3]. Whether it is necessary or even desirable to include a stabilizing winding in all cases, regardless of the system characteristics and conditions is discussed in [4]. Nevertheless, it has been generally accepted never making any winding of a multi-winding transformer smaller than 35% of the rating of the largest winding [5]. An efficient dimensioning and even the decision on the actual need of TSW require an appropriate knowledge of expected unbalanced load conditions on the main windings and their consequences. The authors purpose is to contribute P. Penabad-Duran is with Dept. of Electrical Engineering, University of Vigo, ETSEI, 36210 Vigo, Spain. X. M. Lopez-Fernandez is with Dept. of Electrical Engineering, University of Vigo, ETSEI, 36210 Vigo, Spain (e-mail: xmlopez@uvigo.es). C. Alvarez-Mariño is with Dept. of Electrical Engineering, University of Vigo, ETSEI, 36210 Vigo, Spain. 978-1-4673-0142-8/12/$26.00 ©2012 IEEE with this paper (Part I), as the first part of a work presenting an approach for the dimensioning TSWs on Yy-connected transformers. In the second part of the work (Part II), presented on a companion paper [6], the thermal overheating hazard in tank walls due to the presence of the zero sequence flux, arising under unbalanced load conditions, is evaluated with and without the presence of TSW. Delta-connected TSWs of Yy-connected transformers are referred to illustrate the above discussion, and deserve further attention, not only because of their inherent importance, but also because they are not covered specifically by the standards. The aim of this paper is to clearly describe calculation strategies for the dimensioning of TSW apparent power rating. For that, two alternatives of calculation are presented in the following sections. One is the use of an Equivalent Circuit (EC) based on symmetrical components and the second is based on the FEM. A practical application which illustrates the dimensioning of TSWs is presented where both methods are compared for validating the results. II. TERTIARY STABILIZING WINDINGS DIMENSIONING When used in three-phase systems, transformer windings are usually Y-connected. For Y-connected main windings it has become axiomatic to add in each three phase unit a deltaconnected TSW of 35% of the equivalent size of one of the other two windings (usually the larger). If a delta-connected TSW is to be used, its size is an important consideration. The 35% rule is much overworked in many cases and may set a trap for the unsuspecting user. Then, two questions arise to be considered: Is the tertiary winding needed? If it is needed, what should be the size? The purpose of the TSW might be firstly to stabilize the neutral when unbalanced line-to-neutral single-phase loads are supplied, and secondly to suppress third-harmonic voltages. If these last were the only reasons for the TSW its size could be very small. But in the case of accidental fault a large current would flow in TSW with disastrous results. Strictly, there is no definite relation between the thermal and the short-circuit rating of windings, based on their ability to store heat and withstand mechanical stresses respectively. In addition to the short circuit duty, TSWs shall be designed to withstand the thermal duty of the circulating current resulting from continuous and temporary load or voltage unbalance on the main windings. In case no continuous thermal duty can be established from the users specification, the manufacturer should design TSWs to be large enough to carry zero sequence currents caused by a full single-phase load in the secondary winding. Since the TSW is not intended to supply any load, then the possibility of three-phase fault disappears and the TSW would need to be large enough only to carry zero sequence currents caused by line-to-neutral faults [3]. Therefore, to safely attain this economy of establishing the minimum permissible TSW apparent power rating requires the 2362 prediction of zero sequence currents and it should be based on the short-circuit duration time. The final size should withstand the thermal duty for the specified dimensioning criteria and should be capable of withstanding the short circuit forces. Based on this, an amount of copper (or A/mm2 or Watts/kg) and the apparent power rating can be assigned to the TSW. In this paper single-phase load and single phase-to-ground fault currents are calculated on core type transformers by means of an EC as well as FEM. On the next step, the thermal performance under these conditions is calculated and based on the maximum permitted windings temperature an approach to the dimensioning of TSW is presented. Moreover, in the particular case of a well-grounded system, that is one having low zero sequence impedance, will relieve to some extent the zero sequence current on the tertiary of the transformer. For this reason it is also necessary to know the maximum zero sequence impedance characteristics of the systems that are to be connected to the transformer if an exact prediction of the necessary size of the tertiary winding is to be calculated [3]. The real impact of the zero sequence flux, arising in unbalanced conditions, is scarcely discussed and relevant information is difficult to find [4]. Authors presented in [9] a method for the calculation of zero sequence flux over the tank wall and cover, and discuss its overheating hazard consequences on a companion paper [6]. III. ZERO SEQUENCE PERFORMANCE The solution of unbalanced conditions in three-phase systems can be obtained applying the symmetrical components. Thus, any unbalanced three-phase currents or voltages can be formulated in terms of positive, negative and zero sequence components. In the particular case of transformers supporting asymmetric faults and loads, significant zero sequence current might occur for some threephase connections. This current induces a zero sequence flux in the core resulting in two relevant consequences. The first one is that unless a magnetic return path for this flux is provided, the zero sequence flux returns outside the core, closing its path over tank walls and cover, inducing eddy currents and causing the heating of those structural metal elements [4]. The second one is the risk of induced phase overvoltage. The existence of zero sequence flux either within or outside the core does not only depend on the winding connections but also on the core configuration and the system characteristics. A delta-connected TSW has little impact on the positive and negative sequence impedance network. However, it has large impact on the zero sequence network as it can effectively cancel or diminish the zero sequence flux (ie. a circulating current around the delta winding provides compensating zero sequence ampere-turns). Therefore, transformer TSW is directly related with the zero sequence performance, and it is classically modelled by its zero sequence impedance. Regarding the magnetic core, three-legged three-phase core type transformers present a special problem with respect to zero sequence impedance characteristics. For Yyconnected transformers, the magnetic circuit can be considered as open circuit, since there is no circuit for the induced zero phase currents to flow. Three-legged transformer cores are open magnetic circuits to zero sequence magnetizing flux, as opposed to five-legged cores (closed circuits) on which the outer legs provide a return path for zero sequence flux [8]. Hence, the zero sequence magnetizing impedances on three-legged cores are comparatively small and zero sequence magnetizing currents cannot be assumed to be insignificant. But if a deltaconnected TSW is added to any Yy-connected transformer, the differences in characteristics due to the two types of core practically disappear. Because a delta-connected winding forms a comparatively low short-circuit impedance to zero sequence and third-harmonic voltages, it makes little difference whether the magnetic circuit is open or closed, as long as the delta connection is present [4], [8]. IV. TSW UNDER UNBALANCED CONDITIONS FROM EC To analyse the normal operation, the symmetrically supplied and loaded three-phase transformer is fully described by positive-phase sequence system. Under unbalanced conditions the transformer operation can be advantageously analysed using a transformation into symmetrical components [5]. For this, the single-phase EC of the zero sequence system is additionally needed. The particular study of interest of this paper is focused on Yy-connected transformers with delta-connected TSW. The positive, negative and zero sequence ECs, as well as the proposed tests for their impedance calculation are described in this section. Thus, positive, negative and zero sequence ECs interconnection for single-phase load and single phaseto-ground fault currents calculation is presented. Note that the magnetising reactance is neglected in the three sequences due to the presence of the delta-connected TSW [4], [8]. A. Zero Sequence Impedance Tests for YNyn Transformers The zero sequence impedance is different depending on the transformer construction. It is dependent upon the path available for the flow of flux generated by equal and inphase currents in the three phases. Zero sequence impedance for transformer banks is equal to the positive and negative sequence and it is the transformer leakage impedance. It does not occur the same in the case of three phase core type transformers, where the core does not provide an iron flux path for zero sequence. A three-winding transformer has zero sequence impedance for the primary, secondary, and tertiary windings. The equivalent circuit for the zero sequence impedance of a YNyn-connected transformer with delta-connected TSW is illustrated in Fig. 1. In this EC, Z0P, Z0S and Z0T are the zero sequence impedances in p.u. values of the primary, secondary and tertiary windings respectively. The zero sequence impedance characteristics of a transformer can be determined by means of a set of impedance tests [10]. Thus, to calculate the three unknown zero sequence impedances (Z0P, Z0S and Z0T) at least three equations stated from three tests are needed. Figures 2a to 5a show four possible connection schemes for testing, though only three are actually needed. Figures 2b to 5b show the zero sequence ECs for the connection schemes in Figures 2a to 5a. Table I shows the relationship between zero sequence impedances from each test. The described tests provide sufficient information for determining the branch values of the three-terminal zero sequence EC shown in Fig. 1. 2363 Fig. 1. Equivalent circuit for zero sequence impedance in p.u. values. (a) (a) (b) Fig. 4. a) Test 3 and b) equivalent zero sequence circuit for test 3. (b) Fig. 2. a) Test 1 and b) equivalent zero sequence circuit for test 1. (a) (b) Fig. 5. a) Test 4 and b) equivalent zero sequence circuit for test 4. (a) TABLE I RELATIONSHIP BETWEEN ZERO SEQUENCE IMPEDANCES FOR EACH TEST (b) Fig. 3. a) Test 2 and b) equivalent zero sequence circuit for test 2. The test source can be connected either at the primary or secondary windings. Tests are supplied by a single phase AC source, and there is no need for a three phase AC source for the measurement of the zero sequence impedance. It should be noted that in the case of three-legged core type construction transformers, the zero sequence impedances of the primary and secondary windings are influenced by the presence of the transformer tank. The tank, which encloses the complete core and coil structure, acts as a magnetically coupled short-circuited turn as far as zero sequence quantities are concerned. B. TEST ZERO SEQUENCE IMPEDANCE TEST 1 Z0P + Z0T TEST 2 Z0P + (Z0S || Z0T ) TEST 3 (Z0S + Z0T) TEST 4 Z0S + (Z0T || Z0P) Positive/Negative Sequence Impedance Test The zero sequence impedance tests have to be completed with the positive and negative sequence tests as shown in Fig. 6a. In this EC, Z1P, Z1S and Z1T are the positive/negative impedance of the primary, secondary and tertiary windings respectively, all of them in p.u. values. The positive/negative sequence EC and the measured impedance can be seen in Fig. 6b and Table II. The measurement of the positive sequence impedance requires a three phase AC source. 2364 (a) (b) Fig. 6. a) Test 5 and b) positive/negative sequence equivalent circuit. Fig. 7. Positive, Negative, and Zero sequence networks interconnected to represent a single line-to-ground fault on the low voltage side or singlephase load condition. TABLE II POSITIVE/NEGATIVE SEQUENCE IMPEDANCE FOR TEST 5 TEST POSITIVE/NEGATIVE IMPEDANCE 5 Z1CC= Z2CC= Z1P + Z1S Thus, for the reference phase Va = Va1 + Va 2 + Va 0 (3) and Note that the impedance to negative sequence current is always equal to the impedance to positive sequence currents, and the ECs are similar except that the phase shift, if any is involved, will always be of the same magnitude for both sequences voltages and currents but in opposite directions. ECs Interconnection for Single Phase Faults and Loads This work is prompted by the need to correctly model and simulate the unbalanced operation of power transformers for the apparent power rating of TSWs. Three-phase currents can be already solved into three sets of symmetrical component vectors [11] as in (1) Va = I a Z F (4) where ZF is either the fault impedance in the case of single phase-to-ground short circuit or the phase impedance in the case of single-phase load in p.u. values. From (2) and (4), yields C. Va = I a 0 3 Z F = I a1 3 Z F = I a 2 3 Z F (5) Therefore, under the above conditions, it can be easily seen from (2) and (5) that suitable positive, negative, and zero sequence equivalent circuits are interconnected in series, as shown in Fig. 7. D. I a = I a1 + I a 2 + I a 0 = I1 + I 2 + I 0 2 I b = I b1 + I b 2 + I b 0 = α I1 + α I 2 + I 0 (1) Zero Sequence Current in TSW From the conditions described in the previous section and the circuit shown in Fig. 7, the current thought the reference phase equivalent circuit in p.u. values is calculated as 2 I c = I c1 + I c 2 + I c 0 = α I1 + α I 2 + I 0 where Ia, Ib and Ic are the vectors of the phase currents, the subscripts 0, 1 and 2 refer respectively to the zero, positive, and negative sequence components, and the operator α=e2/3πi is the phase shift vector. For their representation in single-phase faults and load current calculations, where a is the reference phase (short-circuited phase or loaded phase), the current through the other phases Ib and Ic are equal to zero. Therefore from (1) I a1 = I a 2 = I a 0 1 = 3 I a1 = I a 2 = I a 0 = Va Z 1cc+ Z 2cc+ Z 0+3 Z F where Z 0 = Z 0 S + (Z 0T || Z 0 P ) (7) The current in the primary side in the reference phase a is then calculated as I P = I a1 + I a 2 + I 0 P Ia (6) (2) A three phase set of unbalanced voltage vectors Va, Vb and Vc can be solved into three balanced or symmetrical sets of vectors in a manner analogous to that just given for the resolution of currents [11]. 2365 (8) The current in the secondary side is calculated as I S = 3 I a1 (9) And the current in the tertiary winding is I T = I 0T (10) In the case of full single-phase load on the secondary side the equivalent circuit is that shown in Fig. 7, being ZF the value of the nominal single-phase load impedance, and Va the rated voltage, being both in p.u. value equal to 1. For a single phase-to-ground fault if we ignore earth fault resistors, reactors or system impedances, ZF=0 in Fig. 7 and the current flowing through the circuit is then calculated as from (6). When working with the equivalent circuit, calculated currents are in p.u. values and have to be multiplied by the base currents IN of each winding (either for the primary P or the secondary S) in order to obtain their real values IN = SN (11) 3U N Fig. 8. Modeled fictitious transformer geometry. In the case of the tertiary winding, the p.u. current I0T is calculated referred to the primary winding and then multiplied by the transformation ratio in order to calculate the real value of the current IT in Amperes as I T = I 0T ·I PN NP NT (12) where IPN is the base current of the primary winding and NP and NT are the turns number of the primary and tertiary windings, respectively. V. TSW UNDER UNBALANCED CONDITIONS FROM FEM Fig. 9. Electric Circuit to be coupled in the FEM model. As an alternative way to the EC described in Section IV, the FEM is also used to build the model of the considered transformer to determine phase currents under unbalanced conditions, and calculate the TSW apparent power rating. In this paper, the FEM transformer model also serves to compare and validate the results obtained from the EC. The representative transformer geometry to be modeled is shown in Fig. 8, where each phase windings (U, V and W) are wounded around a core leg. For current calculations under unbalanced conditions, electromagnetic coupled analyses are carried out. The coupled circuit is shown in Fig. 9. Each winding region in the FEM model is associated to a coil conductor in the electric circuit. Taking into account that the model is a plane model, each winding is represented by two regions (IN and OUT), and therefore two associated coils. This proposed model includes the series inductances to incorporate the presence of the real 3D leakage flux. The leakage inductances can be previously assessed by comparing a plane with an axisymmetric model of one of the transformer phases. R_LV are the load resistances for each phase, and R_TW are resistances which act as switches, either to connect or disconnect the tertiary windings. In the case of TSW apparent power rating, the current flowing through the tertiary winding IT is computed under full single-phase load condition. For that, the resistance value R_LV connected on the loaded phase (the reference phase) is the rated phase load, being open-circuited on the other two phases. In the case of current calculation under single phaseto-ground fault, the resistance value on the reference phase R_LV is set to zero (short-circuited). The resistance values R_TW are set to zero in order to have the tertiary winding connected and allow the flow of zero sequence currents. VI. THERMAL RATING OF TERTIARY STABILIZING WINDINGS Transformer TSWs shall be designed to withstand the thermal duty of carrying zero sequence unbalanced currents caused either by permanent load or temporary fault in the secondary winding. The worst case of permanent load would be a full single-phase load, and of temporary fault a single phase-to-ground fault with its duration taken into account. Once the TSW current IT is computed under full singlephase load condition either from EC (12) or FEM simulations, the apparent power ST of the TSW can be calculated as ST = 3 I T U NT = 3 I T U NP NT NP (13) where UNP and UNT are the rated voltages of the primary winding and TSW respectively. Moreover, the TSW current IT from (12) can be written in terms of the current density JT (A/m2) yielding to J T s cu N T = I 0T I PN N P (14) where scu is the cross section of the winding copper conductors. In the case of thermal apparent power rating of TSW, its dimensioning consists on assigning volume of copper Vcu (acting either on scu or NT), so that the winding is capable to store the generated heat during temporary single phase-to-ground fault or continuous full single-phase load conditions, protecting the tertiary against destructive overheating that can damage the windings insulation [2]. This procedure permits to asses average temperatures for the TSW and dimensioning its apparent power to comply with maximum allowable temperatures. 2366 TABLE III COMPUTED LEAKAGE INDUCTANCE OF EACH WINDING SYMBOL WINDING TABLE V TEST MEASUREMENTS INDUCTANCE (H) HV L_HV 0.27307735 LV L_LV -0,0000325 TW L_TW 0,00086858 TEST V0 - TEST VOLTAGE (V) I0 - CURRENT FROM FEM TESTS (A) CALCULATED IMPEDANCE (OHM) CALCULATED IMPEDANCE IN P.U. VALUES 1 100 0.487 204.95 0.183 2 100 0.608 164.44 0.147 3 100 154.7 0.646 0.046 4 100 196.5 0.508 0.037 5 100 0.557 179.46 0.160 TABLE IV FEM MODEL VALIDATION OPEN CIRCUIT TEST V1 V2 V3 Nameplate rated values 224250 V 24900 V 13800 V FEM computation 224250 V 24921 V 13757 V RATED LOAD CONDITION I1 I2 I3 Nameplate rated values 115.9 A 1043.5 A ≈0A FEM computation 113.1 A 1029.3 A 8.05 A VII. TABLE VI EQUIVALENT CIRCUIT IMPEDANCES PRACTICAL APPLICATION AND RESULTS As practical application of the problem described in the previous sections a 45 MVA YNyn0 (d1) transformer of 224.25 kV / 24.9 kV / 13.8 kV is considered. The turns number for the primary or High Voltage (HV) winding is 1250, for the secondary or Low Voltage (LV) winding 139 and for the Tertiary Winding (TW) 133 turns. The HV and LV windings, are both Wye connected with neutral points accessible. The HV winding is connected to the local grid, while the LV is connected to the consumer load. It has a delta-connected TSW, not connected to any load, with the purpose to allow the flow of the zero sequence current during unbalanced conditions. Since there are not available any transformer test values to calculate the sequence impedances of the EC, impedance tests are performed by means of a FE model. Therefore, the FE transformer model described in Section V serves on one hand to carry out impedance tests, and also to validate the transformer EC. Table III shows the calculated leakage inductance of each winding, according to Section V. R_LV are resistances which perform the double role of being load resistances for each phase, or together with R_TW are resistances which act as switches, either to connect or disconnect the secondary and tertiary windings respectively during the sequence impedance tests, according to IV.A and IV.B subsections. In order to validate the FEM transformer model, the open circuit test is carried out and measured voltage values are compared to the transformer nameplate rated values. Moreover, computed currents when a balanced three-phase load is connected to the transformer are compared to the transformer nameplate rated values. Results are shown in Table IV and validate the accuracy of the FE model. A. Impedance Test Results Tests for the calculation of equivalent circuit impedances are performed by means of FEM simulations, as already mentioned. The model geometry is described in Section V and shown in Fig. 8. The coupled electrical circuit varies depending on each test as shown from Fig. 2b to 6b. SYMBOL IMPEDANCE IN P.U. VALUES Z0P 0.1421 Z0S 0.0056 Z0T 0.0412 Z1CC=Z2CC 0.1605 Results from Tests 1 to 5 are shown in Table V, where test impedances are calculated in Ohms and also in p.u. value dividing by the base impedance value of each winding. The base impedances are ZPN=13.78 Ohm in the HV side and ZSN=1117.51 Ohm in the LV side. By solving the impedance equations from Table I and Table II, the equivalent circuit impedances are calculated and results are shown in Table VI. B. TSW Current Calculation and Apparent Power Rating Fault currents are calculated in three winding, three-limb, core type YNyn connected transformers by means of the equivalent circuit shown in Fig. 7. Single phase-to-ground fault (ZF=0) and full single-phase load (ZF= ZPN=13.78 Ohm) unbalanced conditions are computed. Primary, secondary and tertiary currents are calculated from (8)-(12) under both conditions and results are shown in Table VII. Computed currents by means of EC are compared to those numerically calculated by FEM, as seen in Table VII. The relative error is indicated, showing there is good agreement between results obtained from EC and FEM. Proved the accuracy of the EC method, it serves as an useful approach to current calculation under unbalanced conditions for the estimation of the TSW apparent power rating. Therefore, from the calculated current values under full single phase load condition shown in Table VII, the apparent power of the TSW is calculated from (13). In the case of the TSW current calculated from EC, IT=252.33 A and being the TSW rated voltage UNT=13.8 kV, the required TSW apparent power is 6.03 MVA, far lower from the 35% of the MVA apparent power of the main windings (15.75 MVA). C. TSW Dimensioning TSW dimensioning consists on assigning volume of copper Vcu (acting either on scu or NT), so that the winding is capable to store the generated heat during temporary single phase-to-ground fault or continuous full single-phase load conditions, so that the windings temperature does not exceed the maximum permitted of 80ºC that can damage the windings insulation [12]. For that, coupled magneto-thermal FEM simulations are carried out, to estimate the windings 2367 TABLE VII WINDINGS CURRENT UNDER UNBALANCED LOAD CONDITIONS UNBALANCED CONDITION Single phase load Single phaseto-neutral fault CALCULATED VALUE FROM EC CALCULATED VALUE FROM FEM RELATIVE ERROR (%) HV 77.05 A 84.74 A -9.98 % LV 935.51 A 1033.87 A -10.51 % TSW 252.33 A 239.28 A 5.17 % HV 718.62 A 724.5 A -0.82 % LV 8724.29 A 8847.85 A -1.4 % TSW 2353.14 A 2045.4 A 13.08 % WINDING TABLE VIII WINDINGS TEMPERATURE UNDER UNBALANCED LOAD CONDITIONS UNBALANCED CONDITION Continuous single phase load (time t=2s) REDUCED COPPER VOLUME MODEL VCU 71.5% VCU HV 66.73 ºC LV 79.72 ºC TSW Temporary single phase-to-neutral fault MODEL ORIGINAL WINDING 51.68 ºC 56.12 ºC HV 70.14 ºC LV 85.55 ºC TSW 68.26 ºC designed to withstand the thermal duty of the circulating current resulting from continuous and temporary load or voltage unbalance on the main windings. In this paper the apparent power rating of TSW is calculated by means of a transformer EC. For that, several tests are proposed for the calculation of the equivalent circuit positive/negative and zero sequence impedances. Moreover a FEM transformer model is also described for the same purpose, which serves also to validate the EC results. The TSW apparent power rating is then calculated from the knowledge of expected unbalanced currents. Moreover, the TSW thermal dimensioning is based on the maximum allowable windings temperature, so that the overheating caused under those unbalanced conditions does not damage the windings insulation. A practical application for the TSW thermal dimensioning of a 45 MVA Yy-connected three-phase three-limb core form power transformer is presented in this paper. From the thermal performance under unbalanced continuous and temporary load conditions, the dimensioning of copper volume has been reduced a 28.5 % from a proposed original model. IX. ACKNOWLEDGMENT The authors would like to thank Luis Sanchez Lago, student from University of Vigo, for performing equivalent circuit and finite element simulations useful in this paper. 79.27 ºC X. [1] temperature under the above conditions. Results are shown in Table VIII, where the original model is referred as the studied transformer model with given turns number NT=133, and a given copper volume Vcu. Though authors are aware that transformer thermal performance requires complicated fluid dynamic models [13], an estimation of equivalent convection coefficients hc, and mean oil temperature Toil is performed, such as the LV winding temperature is around the maximum permitted of 80ºC [12]. With the estimated thermal parameters (hc and Toil), TSW temperature reaches 51.68 ºC under continuous full single-phase load for its given copper volume. Therefore, the copper volume on the TSW can be reduced while the maximum permitted temperature of 80ºC is not reached. A new steady state temperature computation is carried out with a reduced TSW copper volume of Vcu'=71.5%Vcu increasing up to 56.12ºC, still lower from the maximum permitted. Moreover, the temperature reached at temporary single phase-to-ground fault, before protection mechanisms act (at about 2s) must also comply with maximum allowable temperatures. As seen in Table VIII, the values of TSW temperature reached at single phase-to-ground fault for the reduced copper volume model Vcu' is still within the limit of maximum permitted temperature. The next step in the TSW dimensioning would be to check whether the strength of conductors chosen for the reduced copper volume model Vcu' from the thermal rating withstand the short circuit forces. [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] VIII. CONCLUSION Historically transformer TSWs are designed to be 35% of the rated transformer power, but stabilizing windings shall be [13] 2368 View publication stats Powered by TCPDF (www.tcpdf.org) REFERENCES "The whys of the Wyes. The behavior of transformer connections", General Electric, Pittsfield, Massachusetts, 1957. J. Mini, L. J. Moore and R. Wilkins, "Performance of Auto Transformers with Tertiaries Under Short-Circuit Conditions", Pacific Coast Convection of the AIEE, Del Monte, Cal., October 2-5, 1923. O. T. Farry, "Tertiary Windings in Autotransformers," Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers, vol. 80, no. 3, pp. 78-82, Apr. 1961. B. A. Cogbill, "Are stabilizing windings necessary in all Y-connected transformers?", Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers, vol. 78, no. 3, pp. 963-970, Apr. 1959. A. N. Garin, "Short-Circuit Requirements for Transformers" American Institute of Electrical Engineers, vol.66, no.1, pp.710-713, Jan. 1947. P. Penabad-Duran, C. Alvarez-Mariño, X. M. Lopez-Fernandez, "Transformer TSWs: Part II: Overheating hazard on tank walls", to be presented in: International Conference on Electrical Machines (ICEM2012), Marseille, France, 2012. R. Allcock, S. Holland and L. Haydock, "Calculation of zero phase sequence impedance for power transformers using numerical methods," Magnetics, IEEE Transactions on , vol. 31, no. 3, pp. 2048-2051, May 1995. B. A. Cogbill, "Phasor-Power Method of Determining Transformer Sequence Impedances", Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers, vol. 78 (3), pp. 112-119, April 1959. X. M. Lopez-Fernandez, C. Alvarez-Mariño, P. Penabad-Duran and J. Turowski, "RNM2D_0 Fast Stray Losses Hazard Evaluation on Transformer Tank Wall & Cover due to Zero Sequence", Proc. of 3rd Advanced Research Workshop on Transformers (ARWtr2010), Santiago de Compostela, Spain, 3-6 October 2010, pp. 338-343. L. W. Meng, "Measurement of zero sequence impedance for threewinding transformers", The Singapore Engineer, The magazine of the Institution of Engineers, Singapore (IES), pp. 26-28, Jan. 2010. "Electrical Transmission and Distribution Reference Book", Westinghouse Electric Corporation, Fourth edition, East Pittsburgh, Pennsylvania, 1964. M. J. Heathcote, "The J&P Transformer Book", Newnes, Twelfth edition, Oxford, 1998. J. Zhang, X. Li and M. Vance, "Experiments and modeling of heat transfer in oil transformer winding with zigzag cooling ducts", Applied Thermal Engineering, vol. 28, pp. 36-48, 2008.