Comment on structure shop drawing
station
29+831.626
30+358.99
Comment
1. Please correct the flow direction of the out let paved water way and main
pipe
2. The out let needs channelization and please indicate the channelization limit
1. Based on the profile natural ground .5 percent slope is not sufficient to
drain out the discharge flow and it needs to raise up in the inlet
2. The channel slope is reversed which is-1.89
3. The printed station is not the same as the soft copy