Revision: 01A BGC Insulation Specification BGC Insulation Specification Project Originating Company Document Title Basrah Gas Company BGC BGC Insulation Specification Document Number 0000-BGC-G000-GE00-G00000-CX-7755-00002 Document Revision 01A Version Code Document Status Document type Originator / Author Security Classification ECCN Issue Date Approved for Use Specification BGC Civil TA2 Restricted EAR 99 01-05-2019 Revision History Rev Date of Issue Status Originator Description 01A 01-05-2019 AFU BGC Civil TA2 Checker Approver Nilesh Bushari Piyushkumar Raninga Ramsanker Natarajan Brett Scull Marcel Kuipers 1 BGC Insulation Specification 1. Revision: 01A Table of Contents 2. INTRODUCTION ..................................................................................................................................................................4 2.1. PURPOSE .............................................................................................................................................................................4 2.2. SAFETY & ENVIRONMENT ...................................................................................................................................................4 2.3. DEFINITIONS ........................................................................................................................................................................5 2.4. ACRONYMS AND ABBREVIATIONS .....................................................................................................................................5 3. LEGISLATION, CODES, STANDARDS AND REFERENCES ....................................................................................................6 3.1. LEGISLATION, CODES, STANDARDS AND REFERENCES .......................................................................................................6 3.2. RESPONSIBILITIES ................................................................................................................................................................7 3.3. ORDER OF PRECEDENCE ......................................................................................................................................................7 4. QUALITY ASSURANCE AND QUALITY CONTROL ...............................................................................................................8 5. TECHNICAL REQUIREMENTS ..............................................................................................................................................8 5.1. GENERAL ..............................................................................................................................................................................8 5.2. Table 5-1: INSULATION CODE .................................................................................................................................10 5.3. GUIDELINES FOR THE SELECTION OF INSULATION MATERIAL ..............................................................................10 5.4. UNINSULATED SURFACES ........................................................................................................................................11 5.5. EXTENT OF INSULATION FOR PIPING AND EQUIPMENT........................................................................................12 6. INSULATION REQUIREMENTS ..........................................................................................................................................12 6.1. A MINERAL WOOL PIPE, SLAB AND MATTRESS INSULATION ................................................................................12 6.2. PREFORMED FOAM FOR COLD INSULATION ..........................................................................................................14 6.3. PROTECTIVE COVERING / CLADDING / JACKETING ................................................................................................14 6.4. FASTENERS AND MISCELLANEOUS INSULATION ACCESSORIES ............................................................................17 6.5. FABRICATION ADHESIVES, MASTICS AND METAL SEALANTS ................................................................................17 6.6. REMOVABLE INSULATION COVERS .........................................................................................................................17 6.7. PREFORMED HD PIR/PUR FOAM FOR PIPE SUPPORTS IN COLD INSULATION SYSTEM: ......................................17 7. INSTALLATION, HOT INSULATION (Heat conservation, Personnel Protection & Electric traced) ...............................18 7.1. GENERAL ..................................................................................................................................................................18 7.2. PIPING INSULATION .................................................................................................................................................18 7.3. EQUIPMENT INSULATION .......................................................................................................................................19 7.3.1. Shell ..........................................................................................................................................................................20 7.3.2. Bottom .....................................................................................................................................................................20 7.3.3. Heads .......................................................................................................................................................................20 7.3.4. Miscellaneous (Special Items, Manholes, Nozzles, etc ..........................................................................................21 7.4. MACHINERY INSULATION ........................................................................................................................................21 7.5. INSTRUMENT INSULATION......................................................................................................................................21 7.6. VAPOUR BARRIER ....................................................................................................................................................21 7.7. INSULATION FINISH JACKETING ..............................................................................................................................21 7.8. REQUIREMENTS FOR PERSONNEL PROTECTION INSULATION ..............................................................................27 2 BGC Insulation Specification 7.9. Revision: 01A ADDITIONAL REQUIREMENTS FOR ELECTRICAL TRACED INSULATION .................................................................27 8. INSTALLATION, COLD INSULATION .................................................................................................................................27 8.1. PIPING INSULATION .................................................................................................................................................27 8.2. EQUIPMENT INSULATION .......................................................................................................................................28 9. STORAGE AND HANDLING OF INSULATION MATERIALS ...............................................................................................28 10. INSPECTION ......................................................................................................................................................................29 10.1. CONTROL PRIOR TO THE APPLICATION ..................................................................................................................29 10.2. CONTROL DURING APPLICATION ............................................................................................................................29 10.3. INSPECTION CRITICAL ..............................................................................................................................................30 10.4. FINAL CONTROL .......................................................................................................................................................30 10.5. IN SERVICE INSPECTION ..........................................................................................................................................30 11. WARRANTY AND PERFORMANCE GUARANTEE ..............................................................................................................30 12. DOCUMENTATION ............................................................................................................................................................30 13. INSULATION ATTACHMENT METHODS, INSULATION FINISH REQUIREMENT AND INSULATION THICKNESS TABLE 31 13.1. Table 13-1: INSULATION ATTACHMENT METHODS AND MATERIALS (Mineral wool)...........................................31 13.2. Table 13-2: INSULATION FINISH REQUIREMENTS ..................................................................................................32 13.3. Table 13-3: INSULATION FINISH REQUIREMENTS (continued) ............................................................................33 13.4. Table 13-4: INSULATION THICKNESSES (mm) FOR PIPING AND EQUIPMENT ........................................................35 13.5. Table 13-5: INSULATION THICKNESSES (mm) FOR PIPING AND EQUIPMENT .........................................................36 13.6. Table 13-6: INSULATION THICKNESSES (mm) ELECTRICAL HEAT TRACING (ET)- ...................................................37 13.7. Table 13-7: INSULATION THICKNESSES (mm) FOR PIPING AND EQUIPMENT .........................................................38 13.8. Table 13-8: REFERENCE TABLE FOR THE LAYERING OF COLD INSULATION.........................................................40 3 BGC Insulation Specification 2. 2.1. Revision: 01A INTRODUCTION PURPOSE This document defines the minimum technical requirements for insulation of vessels, equipment, piping and pipe fittings, including preparation and application. The insulation may be for energy conservation, heat tracing and / or for personnel protection. Insulation for personnel protection applies to surface temperatures above 60°C during normal operation. Insulation for energy conservation may apply at lower temperatures. It is intended that insulation shall require only minimum maintenance during the 25-year design life of the project. In general, SUPPLIER’s scope of work for insulation systems shall include, but not be limited to, the following: • Design of specific details of insulation jacketing / fastening; • Quality assurance and control; • Procurement / supply of all materials; • Provision of all required test equipment, utilities and consumables necessary to perform the work. SUPPLIER shall supply all materials as necessary to complete the successful insulation of the schedule of items contained within the project. Equipment and piping belonging to a package unit shall be insulated in accordance with this specification under the scope of work of the package equipment SUPPLIER. SUPPLIER shall guarantee the proper functioning of their materials, application, protection coatings and work for the guarantee period. During the guarantee period, SUPPLIER shall repair any defects in his work to the satisfaction of COMPANY. SUPPLIER shall complete the work in accordance with this specification and to the satisfaction of COMPANY. CONTRACTOR shall fully comply with COMPANY standards and specifications requirements, listed in section 3.1 of this specification, and shall not use any other conflicting specification. In case of any conflict, COMPANY Standards & Specifications shall prevail. 2.2. SAFETY & ENVIRONMENT Safety shall be of paramount importance at all times throughout the fulfilment of the requirements of this specification. SUPPLIER shall observe good working practice and ensure that all activities are carried out in such a way that all risks are as low as reasonably practicable. SUPPLIER shall comply with all industry and country based regulatory requirements to ensure a safe working environment. Following Purchase Order (PO) award CONTRACTOR is to provide detailed policies, plans and procedures for ensuring that all safety requirements, laws, regulations, ordinances, etc., of the place or country pertaining to the work being performed are strictly maintained. The supplied COMPANY based safe working practices and requirements shall also be utilized and complied with throughout the execution of the contract. 4 BGC Insulation Specification Revision: 01A Further details relating to the particular safety and safety documentation requirements shall be found in the project specific documentation. All the correct PP (personal protection) should be made available to the operator before the work commences. Checks should be made to ensure that the operator is suitably qualified to carry out the necessary work. No insulation materials to contain Asbestos. 2.3. DEFINITIONS General Definitions used for this specification: Name 2.4. Definition COMPANY The COMPANY shall mean BASRAH GAS COMPANY (BGC) MANUFACTURE Manufacturer is the party that manufactures the insulation product(s) and Supplies to Supplier/INSULATION CONTRACTOR to perform the duties specified by the COMPANY. VENDOR/SUPPLIER Supplier is the party that supplies equipment and services to perform the duties specified by the COMPANY. INSULATION CONTRACTOR Any person or persons, firm, partnership, corporation or combination thereof, including vendors who perform the insulation work SUB-CONTRACTOR Any other party appointed by CONSTRUCTION/INSULATION CONTRACTOR for supply of ant work / services SHALL Is to be understood as mandatory in relation to the requirements of this specification SHOULD Is to be understood as recommendation in relation to the requirements of this specification ACRONYMS AND ABBREVIATIONS AIV Acoustic Induced Vibration ASTM American Society for Testing of Material bbls Barrels BGC Basrah Gas Company CC Cold Conservation CPT Coating Procedure Testing CRA Corrosion Resistant Alloy DFT Dry Film Thickness HC Heatt Conservation ISO International Standards Organisation ITP Inspection and Test Plan KAZ KHOR AL ZUBAIR MoO Ministry of Oil MRB Manufacturing Record Book MMscf/d Million Standard Cubic Feet per Day NACE National Association of Corrosion Engineers 5 BGC Insulation Specification NCR Non-conformance Report NORSOK 3. 3.1. Revision: 01A the Norwegian Shelf’s Competitive Position PIR Polyisocyanurate PO Purchase Order PP Personnel Protection PQT Procedure Qualification Testing PUF Polyurethane Foam QC Quality Control SI The International System of Units SSPC The Society for Protective Coatings Tcf Trillion Cubic Feet LEGISLATION, CODES, STANDARDS AND REFERENCES LEGISLATION, CODES, STANDARDS AND REFERENCES This specification will be used in conjunction with the latest edition (at the date of Contract award) of the following codes, standards and specifications and shall establish the minimum requirement for the execution of the work. VENDOR/CONTRACTOR may use alternate standards that meet or exceed those listed upon COMPANY’s approval. Document Number Title ASTM C795 Thermal Insulation for Use on Contact Austenitic Stainless Steel ASTM C871 Chemical Analysis of Thermal Insulation Materials for Leachable Chloride, Fluoride, Silicate, and Sodium Ions ASTM C1335 Measuring Non-Fibrous Content of Man-Made Rock and Slag Mineral Fiber Insulation ASTM C692 Standard Test Method for Evaluating the Influence of Thermal Insulations on External Stress Corrosion Cracking Tendency of Austenitic Stainless Steel Standard Specification for Mineral Fiber Pipe Insulation ASTM C547 ASTM A463 Standard Specification for Steel Sheet, Aluminium Coated, by the Hot-Dip Process. ASTM A480 General Requirements for Flat-Rolled Stainless Steel Plate, Sheet and Strip. ASTM A526 Standard Specification for Steel Sheet, Zinc Coated (Galvanized), by the Hot- Dip Process, Commercial Quality. Standard Specification for Mineral Fibre Pipe Insulation. ASTM A592 ASTM A792 Standard Specification for Steel Sheet, 55% Aluminium-Zinc Alloy, Coated by the Hot Dip Process. ASTM B209 Standard Specification for Aluminium and Aluminium-Alloy Sheet and Plate. 6 BGC Insulation Specification ASTM C612 Standard Specification for Mineral Fiber Block and Board Thermal Insulation. ASTM C647 Standard Guide to Properties and Tests of Mastics and Coating Finishes for Thermal Insulation. ASTM C680 Standard Practice for Estimate of the Heat Gain or Loss and the Surface Temperatures of Insulated Flat, Cylindrical, and Spherical Systems by Use of Computer Programs. Standard Specification for Spray-Applied Rigid Cellular Polyurethane Thermal Insulation. ASTM C1029 ASTM E84 Standard Test Method for Surface Burning Characteristics of Building Materials. BS - 9585 Thermal insulating materials specification for bonded man-made mineral fiber slabs CINI Stichting Commissie Isolatie Nederlandse Industrie EN 13468 Thermal Insulating Products for Building Equipment and Industrial Installations. Determination of Trace Quantities of Water-Soluble Chloride, Fluoride, Silicate, Sodium Ions and pH. ISO 3575 Continuous Hot-dip Zinc-coated Carbon Steel Sheet of Commercial, Lockforming and Drawing Qualities. ISO 5000 Continuous Hot-dip Aluminium-silicon Coated Cold-reduced Carbon Steel Sheet of Commercial and Drawing Qualities. ISO 9001 Quality Management Systems – Requirements. ISO 9364 Continuous Hot-dip Aluminium/zinc Coated Steel Sheet of Commercial, Lock-forming and Structural Qualities. ISO 12241 Thermal Insulation for Building Equipment and Industrial Installations – Calculation Rules. ISO 129445:2007 Paints and Varnishes - Corrosion Protection of Steel Structures by Protective Paint Systems – Part 5: Protective Paint Systems. ISO 14015 Specification for the Design and Manufacture of Site Built, Vertical, Cylindrical, Flat-Bottomed, Above Ground, Welded, Steel Tanks for the Storage of Liquids at Ambient Temperature and Above. Acoustic Insulation for Pipes, Valves and Flanges. ISO 15665 NORSOK M501:2012 NACE SP0108 3.2. Revision: 01A Surface Preparation and Protective Coating. Corrosion Control of Offshore Structures by Protective Coatings. RESPONSIBILITIES The party whoever performs (directly/indirectly) the insulation activity those are responsible for complying with this specification requirements. 3.3. ORDER OF PRECEDENCE VENDOR shall notify CONTRACTOR and COMPANY of any conflict between this specification, the related datasheets, Material Requisition, the Codes, Standards and any other Specifications 7 BGC Insulation Specification Revision: 01A referenced herein. Resolution and / or interpretation of precedence shall be obtained from CONTRACTOR and COMPANY in writing before proceeding with the design or Manufacture. The order of precedence shall be: • Iraq Statutory laws and regulations, • Project specific datasheet(s) (for the component(s) being welded), • This specification, • NORSOK M-501:2012; • ISO 12944-5:2007; Other codes and standards listed in section 3.1 of this specification. In case of conflict between above documents, the most stringent requirement shall apply. In such cases, VENDOR shall provide its interpretation in writing of the most stringent requirement for COMPANY / CONTRACTOR’s approval. In all such cases of conflict, COMPANY / CONTRACTOR decision shall be final. 4. QUALITY ASSURANCE AND QUALITY CONTROL CONTRACTOR shall operate a quality system, covering the scope of supply, to ensure that the requirements of this specification are met. Unless otherwise stated in the PO, CONTRACTOR's quality system shall be in accordance with ISO 9001 or approved equivalent. The effectiveness of the quality system and CONTRACTOR’s compliance with it will be subject to continuous monitoring by COMPANY, and in addition, may be audited. All testing and inspection activities shall be indicated in the Inspection & Test Plans (ITP). COMPANY shall have the right to undertake inspection or testing of the pipe during any stage of manufacture and to undertake inspection or testing of raw materials. CONTRACTOR shall ensure that all documents relating to this specification and the PO are collated, indexed and retained for subsequent presentation to COMPANY in the form of a Manufacturing Record Book (MRB). 5. 5.1. TECHNICAL REQUIREMENTS GENERAL All carbon steel and stainless steel under insulation shall be suitably protected with a coating system as per BGC External Painting Specification1000-BGC-G000-ISGP-G00000-RA-7754-00001. All piping and equipment which require only personnel protection shall be coated suitably as same as un-insulated according to project painting specification. Insulation installation work shall not commence until surface preparation and coating of the surface to be insulated has been completed and the coating system has fully cured. All surfaces which are to be insulated shall be cleaned of dirt, grease, foreign material primed and dried before insulation is applied. All insulation shall be protected from moisture and weather before 8 BGC Insulation Specification Revision: 01A and during installation. If applied insulation should get wet before it is jacketed, it shall be thoroughly dried by heating or other suitable means before it is sealed with weatherproofing. The Insulation Contractor/Applicator shall be responsible for dry cleaning of surfaces to be insulated prior to application of insulation. Insulation shall not be applied over wet surfaces. Sub-contractor's proposals shall detail the proposed design and define the fabrication methods, including the extent of field assembly required. All materials shall be new and previously used materials shall not be used. Sealants, mastics and adhesives shall be supplied in factory sealed containers. Materials selected for jacketing, cementing, sealing and coating shall be compatible with the insulation material, temperature conditions, atmospheric conditions and intended functions of the insulation system. At all flanged joints, the pipe insulation shall be cut back or beveled at such an angle as to permit removal of the studs from either side of the flange without damage to the adjacent insulation. The recommended Bolt clearance from the flange to the insulation jacketing shall be at least the bolt length plus an additional 30 mm. If hydraulic bolt tension or torque equipment is used, a greater bolt clearance may be required. All materials shall be installed in accordance with this standard and the manufacturers recommended methods. Insulation materials will be protected against the elements at all times from delivery to finish weather coating. Any insulation damaged as a result of improper protection from weather will not be accepted and shall be replaced by the insulation subcontractor at the subcontractor’s expense. Thermal insulation types are listed in Table 5 .1 for external surfaces of piping and equipment. Insulation type is based on the intended application (and type shall be confirmed as per Process requirement) and is specified on the piping isometric drawings, P&ID, and on the equipment, drawings issued by the COMPANY. 9 BGC Insulation Specification 5.2. Table 5-1: INSULATION CODE CATEGORY TAG 1 Cycling or Dual Process temperature between -20 and 320°C (or lower) 2 Process Temperature between 50 °C and 120°C 3 Process Temperature between -5 °C and 49°C 4 Process Temperature between 121 °C and 175°C 5 All process Temperatures > 175°C 6 All process Temperatures < -5°C N No Insulation required for Process temperature reasons REQUIREMENT TAG E T PROCESS TEMPERATURE DESCRIPTION REQUIREMENT Thermal Conservation (Hot and Cold) of Equipment and Piping Temperature Control of processes or Products e.g. To avoid Condensation, Solidification, or Too high a viscosity. (Heat Traced) Personnel protection i.e. On surfaces operating temperature above 70°C within 2100 mm (7 ft.) above grade or platforms and 900 mm (3 ft.) horizontally from the periphery of platforms, walkways, or ladders Preventing or Reducing damage to Equipment and piping from exposure to freezing conditions. P F N Not Required A Acoustic CONTACT OR NON-CONTACT TYPE OF INSULATION C N 5.3. Revision: 01A DESCRIPTION Contact type Insulation Non-Contact type Insulation is an insulation system in which there is limited contact between bare surface of Pipe/Equipment and the insulation material. GUIDELINES FOR THE SELECTION OF INSULATION MATERIAL • For operating temperatures between 20 C and 600 C mineral wool product (as listed in the Table 5.2) should be used. • For operating temperatures between 600 C and 750 C, calcium silicate products may be considered, if economically justified. • For operating temperatures above 750 C, calcium silicate products should be used. • Process control, e.g. to avoid condensation, solidification, or too high viscosity, rapid temperature variations. 10 Revision: 01A BGC Insulation Specification • Personnel protection, for piping and equipment having an operating temperature of > 60 C or < -10 C if the location presents a danger to personnel. • Noise reduction of piping and equipment where ever applicable. Table 5-2: INSULATION MATERIAL SELECTION REQUIREMENT TAG Cat E Temperature range a 1 g Cycling or Duel o process temp -20 and r 320°C y 2 T From 50 °C to 120°C A 3 G from -5°C to below 50°C T (heat tracing) P F A N/A N/A N/A N/A N/A Mineral wool Mineral wool N/A N/A PIR/PUF with vapor barrier Mineral wool N/A N/A N/A Mineral wool N/A N/A N/A N/A N/A N/A N/A N/A 4 from 121 °C to 175°C Mineral wool PIR/PUF, Unsealed & No vapor barrier Mineral wool 5 > 175°C Mineral wool Mineral wool 6 < -5°C PIR/PUF with vapor barrier N/A Mineral wool N/A N No insulation N/A N/A N/A Insulation and finish requirements for piping and equipment shall be as specified herein. In general, Thermal conservation (Mineral wool) and Personal Protection insulation (Mineral wool) of thickness greater than 3’’ (75 mm) shall be installed with double layers. For Cold insulation (PUF), number of insulation layer shall be as per Table 13-8. If any conflicts between the requirements defined herein and those indicated in the piping/equipment drawings shall be brought to the attention of COMPANY for resolution prior to application of the insulation system. The term "equipment" includes vessels (towers, drums, reboilers, and exchangers), machinery (pumps, compressors, turbines) and tanks (vertical, cylindrical storage tanks). 5.4. UNINSULATED SURFACES Following surfaces shall be left uninsulated • Pumps; • Name Plates; • Air-Cooled Equipment; • Compressors • Steam Traps • Name Plates 11 Revision: 01A BGC Insulation Specification 5.5. • Expansion Joints; • Rotating Joints; • Code inspection Plates; • Stampings EXTENT OF INSULATION FOR PIPING AND EQUIPMENT Table 5.3: EXTENT OF INSULATION FOR PIPING AND EQUIPMENT INSULATION TYPE Thermal Personnel Application Description Heat ConservationProtection Trace Hot Insulation YES As YES (Note-1) (Note-1) Straight or Bent Pipe, applicable For steam service piping (Note-1) Flange manual valves, Flange control valves YES NA NA and flange instruments For ET (Electrical traced) piping Flange manual valves, Flange control valves and flange instruments NO NO NO For Piping other than steam Flange manual valves, Flange control valves and flange instruments Manway cover on Vessels NO NO NO As applicable NO (Note-1) NO NO NO NO YES As applicable NA YES As applicable YES Pump Casings NO NO NO Compressors [Note 2] [Note 2] NO Relief Valves Heat Exchanger Shell and Fixed Rear Bonnet Surfaces Heat Exchanger Channel, Channel Cover, Channel Bonnet and Channel/Body Flange Joints NOTES TO TABLE 5-3: 1. 2. 3. 6. 6.1. Insulation shall be done up to neck in tapered shape so as to permit removal of studs without damaging the adjacent insulation. Insulation shall be furnished in accordance with the equipment supplier's recommendations. For Cold insulation, all pipe fittings, flanged joints and valves shall be completely insulated as described in section 12 of this document. INSULATION REQUIREMENTS A MINERAL WOOL PIPE, SLAB AND MATTRESS INSULATION Mineral wool is the considered material for heat conservation, Personal protection, and Electric traced (ET), when the process temperature is 50°C and above. Mineral wool insulation for pipe sectional insulation, slab and mattress shall satisfy the following requirements: 12 BGC Insulation Specification PROPERTY Revision: 01A REQUIREMENT 3 Density 128 kg/m , water repellent pH 6 – 10.5 (when wet) Leachable total chloride content 10 ppm (10 mg/kg) max when measured in accordance with ASTM C871 Thermal conductivity Tested in accordance with ASTM C177 Shot content 20% max. (ASTM C1335) Thermal insulation products shall be qualified for use on austenitic stainless steel in accordance with ASTM C795. The material manufacturer shall demonstrate that the material that will be furnished for this project has passed the pre-production corrosion test in accordance with ASTM C692. The material manufacturer shall also furnish a chemical analysis in accordance with ASTM C871 The Material shall be suitable to use at specified minimum/maximum operating temperature of piping/Vessels and others. Mineral wool molded pipe segments shall conform to ASTM C547, Type II, except non-fibrous (shot) content is limited to 20% max. Mineral wool mattress of same thermal performance as sections shall only be used on irregular equipment and vessel Heads or other complex shapes as approved by COMPANY. Mineral wool wire mesh faced mattress shall have one side stitched with galvanized wire and 25 mm hexagonal pattern. On stainless steel piping and equipment, stainless steel wire mesh shall be applied using stainless steel wire. 13 BGC Insulation Specification 6.2. Revision: 01A PREFORMED FOAM FOR COLD INSULATION Preformed Polyurethane (PUF), Polyisocyanurate (PIR) foam (Closed cell, CFC free) of minimum density 45 Kg/m3 is the considered material for Cold insulation. COLD INSULATION MATERIAL PROPERTIES Temperature Range Insulation Material pH Range Min (°C) Max (°C) Minimum Density (kg/m3) Cellular Glass 6 - 10 -260 430 125 (±10%) 0.048 Polyurethane Foam (PUF) 6 - 10 -200 120 40 0.024 6-9 -200 120 40 0.024 Polyisocyanurate (PIR) 6.3. Maximum Conductivity at (200°C ) (W/mK) PROTECTIVE COVERING / CLADDING / JACKETING Aluminium. The weather barrier shall be made from Aluminium, with the following characteristics: • • • Thickness: 0.6 mm for piping up to and including DN 300 (12”) Thickness: 0.8 mm for piping over DN 300 (12”) Thickness: 0.8 mm for equipment (i.e. vessels, exchangers, tanks etc.) The sheet shall be fastened to the supports underneath by means of stainless steel self-tapping screws with reinforced neoprene washers. Aluminium jacket on vertical vessels over 36’’ diameter shall have a 1-1/4’’ (32mm) corrugation. Aluminium jacketing shall not be used in combination with passive fire protection All cut-outs are to be suitably sealed with caulking. Aluminium protective covering installation shall be as chapter 7.7 Aluminized steel jacketing Aluminized steel jacketing shall have Coating Type T2-300 in accordance with ASTM A463/A463M. The aluminized steel jacketing mechanical properties, chemical composition and corrosion resistance shall be in accordance with ASTM A463/A463M. Additional requirements for aluminized steel jacketing shall be as follows: • the copper, nickel and manganese content of the coating bath less than 0.040 % wt; • all cut edges of the aluminized steel Type T1 coated to ensure corrosion protection. The aluminum coating shall not crack, flake or peel during the required mechanical processing. Aluminized steel jacketing shall not be used in climates where salt-containing condensation can evaporate due to high daytime temperatures. 14 BGC Insulation Specification Revision: 01A Aluminized steel jacketing shall be at least 0.8 mm (0.03 in) thick and sections at least 500 mm width (20 in). Stainless-steel jacketing Stainless-steel Type 304 or Type 316 in accordance with ASTM A240 shall be used for stainless-steel jacketing. Mechanical and chemical properties and corrosion resistance for stainless-steel jacketing shall be in accordance with ASTM A240. The thickness of the stainless-steel jacketing shall be as per Table 6.1. Table 6.1 Thickness of stainless-steel jacketing Outside diameter insulation in mm Minimum thickness of the SS sheeting in mm < 140 0.5 140 – 300 0.6 >300 0.8 Removable covers (such as for flanges, valves) shall be made of 0.8 mm (0.03 in) sheets. Refer to CINI 3.1.5. UV curable Glass Reinforced Plastic (GRP) Weather resistant, UV curable, GRP jacketing shall be a laminate based on glass fiber reinforced polyester resins, which cures by UV-radiation. The surface to be finished with UV curable GRP shall be even, clean and dry. Joints in the finishing material have an overlap of minimum 30 mm (1¼ in). The finishing layer shall be of even thickness across the surface. UV curable GRP material requirements shall be as per Table 6.2 Table 6.2 UV curable GRP material properties Data Acceptable level Temperature range 0-90 °C (32-194°F) Weight 2 kg/m2 Bending strength 130 MPa (18850 psi) Tensile strength 50 MPa (7250 psi) Elongation at break 1% Compressive strength 125 MPa (18130 psi) Impact resistance 57 kJ/m2 Temper 45 Barcol Layer thickness 1.5 mm Applicable standard 15 BGC Insulation Specification Data Acceptable level Applicable standard Water vapour permeability 0.001 g/(m2.h.mmHg) ASTM E96/E96M proc. E Flame spread index 20 ASTM E84 Class I BS 476-7 32 °C (90 °F) ASTM D93 Flash point Revision: 01A In cold services, UV curable GRP shall be applied over a multiplex foil vapour barrier. Packaging shall be such that the material is fully protected against light. Packaging shall protect against damage during transport and storage. For curing, natural UV light or UV lamps shall be used. Vapour barriers For vapour barriers, the following materials may be used: • multiplex foil; • butyl rubber tape with aluminium backing; • vapour barrier mastic, latex, polymer, bitumen or elastomer based. Multiplex foil shall have a thickness as follows: • 25 μm (1 mil) polyester film; • 50 μm (2 mil) aluminium foil; • 25 μm (1 mil) polyester film; • total thickness 100 μm (4 mil). Water vapour permeability shall be in accordance with ASTM E96/E96M, procedure E, maximum 10*10-6 g/m2.h.mm.Hg. Flexible tapes and foils Aluminium foil provided with an adhesive layer and covered with a reinforced protective foil may be use as flexible jacketing material in a temperature range of -30 °C – 120 °C (-20 °F – 250 °F). Aluminium foil provided with an adhesive layer and covered with a reinforced protective foil shall comply with all of the following: • tensile strength 20 N/mm (150 lbf/in) or higher in accordance with ASTM D882; • elongation at break 8% or higher than in accordance with ASTM D882; • puncture resistance at least 350 N (78 lbf) in accordance with ASTM D1000; • water vapour permeability 0 in accordance with ASTM E96/E96M. 16 BGC Insulation Specification 6.4. Revision: 01A FASTENERS AND MISCELLANEOUS INSULATION ACCESSORIES All metallic accessory materials (bands, seals, screws, etc.) shall be austenitic stainless steel, Type 316, unless noted otherwise. Self-tapping screws shall be in accordance with the jacketing material 4.8 x 13 mm (ISO 1481 type C).All banding shall be furnished deburred. Tie wire shall be 1.0 mm minimum diameter, stainless steel 316. Sheet metal screws for fastening sheet to structure or sub-girt shall be austenitic stainless steel with hex drive head and integral EPDM washer or Pan Head with EPDM washer. For cold insulation, Tape for fastening insulation shall be 200gr/25 mm wide pressure sensitive glass filament reinforced tape. Weather barrier mastic shall be capable of being applied by trowel, glove or brush. It shall be a non-corrosive, heat resistant, fire retardant plastic suitable for continuous exposure to 82°C minimum. Mastic shall be furnished in Aluminium grey (Foster 90-66 or similar), unless otherwise specified. Nonmetallic jacketing sealants, synthetic tape and contact adhesives should be selected and installed to the Jacketing Manufacturer/Supplier’s recommendations. For temperature < 300 °C (572 °F), a one component polysiloxane based permanent flexible sealer shall be used. For temperatures > 300 °C (572 °F), a sodium silicate-based sealer shall be used. 6.5. FABRICATION ADHESIVES, MASTICS AND METAL SEALANTS All adhesives, mastics for cold insulation and metal sealants shall be suitable to temperature conditions, atmospheric conditions and intended functions of the insulation system. 6.6. REMOVABLE INSULATION COVERS If insulation specified for Flanges, valves, man ways and other item where insulation would interfere with normal operation, removable insulation covers should be provided. Insulation applicator can adopt his own good engineering design in providing the removable insulation covers, but it should be in two halves with locks/pins wherever applicable. The design shall be reviewed and approved by the COMPANY. 6.7. PREFORMED HD PIR/PUR FOAM FOR PIPE SUPPORTS IN COLD INSULATION SYSTEM: The insulation thickness at the supports shall be the same as the pipe insulation. The material of the insulation sections at the supports shall match with the adjacent insulation system. In doing so, a similar material with a higher compressive strength may be applied. The dimensions of the pipe support shall be calculated in detail with the following governing factors: a. the maximum design load of the support, based on two span lengths; b. compressive strength of the insulation material; c. safety factor 5:1 for the compressive strength at minimum operating temperatures; 17 BGC Insulation Specification d. e. f. g. pipe; h. i. Revision: 01A load transfer based on 60° load spread; load spread underneath the brackets / steel support cradles during fixing of the bolt; clamping forces on the pipe, such that the support moves with the pipe; length of the base plates of the support based on maximum contraction/expansion of the the support shall not move across the insulation system (cladding); the pipe shall not move inside the insulation system. The HD PIR/PUR foam at the bottom part of the support shall have a minimum density of the following: a. 160 kg/m3 (10 lbm/ft3) for pipe diameters up to 200 mm (8 in); b. 224 kg/m3 (14 lbm/ft3) for pipe diameters between 200 mm (8 in) and 600 mm (24 in); c. 320 kg/m3 (20 lbm/ft3) for pipe diameters above 600 mm (24 in). The HD PIR/PUR foam at the top part of the support shall have a minimum density of 160 kg/m3 (10 lb/ft3). Pipe support design and application in cold insulation systems shall be subject to approval by the Principal. For pipe supports in cold service, reference is made to CINI 5.1.09, 5.1.10 and 5.1.11. For pipe supports in cryogenic service, reference is made to CINI 10.5.01 and 10.5.02. 7. 7.1. INSTALLATION, HOT INSULATION (Heat conservation, Personnel Protection & Electric traced) GENERAL The installation of high temperature insulation systems shall be in accordance with the requirements of this standard. Functionally equivalent application practices, which are technically acceptable alternates to the requirements herein, may only be used when identified in the bidder's proposal and approved by the COMPANY. Application temperature for sealants and adhesives shall be within the acceptable temperature range recommended by the manufacturer and shall be in strict accordance with the manufacturer's current data sheets. The use of broken or otherwise defective insulation shall not be permitted. All insulation shall be smooth and free from cracks, voids, gaps. Care shall be exercised in the handling and application of materials so as not to splatter concrete foundations, paving, structural steel, equipment items, gage glasses, instruments, machined surfaces, valve stems and packing. Insulation Contractor shall be responsible for all overspray or splatter problems, and liabilities associated with corresponding corrective actions. Extent of insulation shall be as indicated in Table 13-2 7.2. PIPING INSULATION When a thickness of insulation of 100 mm or more is required, the material shall be applied in several layers. Each layer shall have a minimum thickness of 50 mm and shall be of approximately the same thickness as the other layers. 18 BGC Insulation Specification Revision: 01A The insulating material shall be outermost wrapped dry around the piping, without underlay, leaving the wire mesh. Each layer of double layer insulation shall be held in place separately. The insulation shall be performed and of the correct size. Voids shall be filled with pieces of the same material or with suitable insulating cement. Insulation shall be fastened to the piping with 1.6 mm diameter 316L stainless steel wire or 12 x 0.6 mm 316L. Stainless steel straps every 300 mm maximum. The ends of each piece of wire shall be twisted together and embedded in the insulation; and the edges of the wire mesh shall be subsequently sewn together with 1.6 mm 316L stainless steel wire. Joints shall be staggered and the union of the end surfaces of the pipe covers or boards shall leave no gaps. Insulation adjacent to flanges in piping shall be terminated to allow removal of bolts without damage to insulation. Minimum free space from the flange to the nearest part of the insulation shall be equal to the bolt length +25mm. The termination of the weather protection shall be waterproof. Valves, flanges and other fittings, when insulation is required, may have removable insulation, which is achieved either by using removable boxes filled with insulation material, kept in place by stainless steel wire-mesh, or by a semi-fixed insulation, the gaps of which are filled with wellpacked loose insulation, and with boards wound round the whole, in order to obtain a cylindrical outside surface for the flanges and a bi-cylindrical outside surface for the valves. On vertical lines or lines inclined at more than 45º from horizontal with straight runs of more than 3 meters, an insulation support shall be provided at the bottom and every 3 meters after. Supports shall be designed and located to allow removal of bolts at flanged joints. Support designs shall be submitted to COMPANY for approval. 7.3. EQUIPMENT INSULATION Insulation shall be applied in one or two layers to the thicknesses specified. All joints shall be carefully fitted. Circumferential joints shall be staggered for horizontal equipment and longitudinal joints shall be staggered for vertical equipment. In double layer applications, all joints in the outer layer shall be staggered with respect to inner layer joints. The insulation installation shall be as specified in chapter 13 Unless otherwise specified, vertical equipment support legs and lugs and saddle supports for horizontal equipment shall not be insulated. Insulation on skirt supported vertical vessels shall be extended past the bottom tangent line, down the exterior surface of the skirt to the bottom insulation support ring. Vessels having skirt inside diameters exceeding 1200 mm shall have the corresponding inside skirt surface insulated. Equipment nozzles connected to bare piping shall have the equipment insulation system terminated on the nozzle and finished with a metallic cover. The insulation shall be applied to the nozzle prior the application of insulation to the shell of the vessel. In case of double layer application, the installation of the insulation on the nozzle shall be applied first for each consecutive layer in order to form a staggered joint at the nozzle/shell juncture. 19 BGC Insulation Specification Revision: 01A For insulation of vessel shells, rigid pipe sections or rigid curved radius segments shall be utilized up to the maximum commercially available size. Beveled block insulation for vessel shells shall be used only when shell diameters exceed the commercially available size of curved radius segments. Edge beveling of block shall be in accordance with ASTM C450 Adjunct ADJC0450. Bevels may be applied to either one or both block edges. Small voids around nozzles and other projections through the insulation on the shell and heads shall be packed with suitable material. Heat exchangers shall be insulated in a manner similar to horizontal vessels. Heads on exchangers that are removable shall be insulated to allow access to the bolts with minimum damage to the insulation. Flanged ends shall be insulated with a flat cover that is removable. Code or other nameplates shall not be covered by insulation. 7.3.1. Shell Cylindrical equipment of up to and including 600 mm (24”) diameter shall be insulated as for piping. For cylindrical equipment exceeding 600 mm (24”) diameter (vessels, exchangers, tanks, etc.), a metal support shall be fixed in place before applying the insulation which shall serve as a support for the insulation itself and also for fastening the metal jacketing. The insulation boards or blanket shall be applied to the surfaces to be covered using the same methods as for the piping but shall be held in place by stainless steel straps of 12 x 0.6 mm, spaced every 250 mm, mechanically tightened and either fixed with buckles or riveted. When the straps are in place there shall be no bruises, cracks ore open joints in the insulation. The maximum length of the aforesaid straps shall not exceed 6 m. Longer straps shall be formed of several sections locked together. Expansion / contraction joints shall be provided as required. Gaps caused by cutting the boards to avoid the projecting parts of the equipment, e.g. supports, nozzles, instrument tapings, shall be filled up with insulation material. Pumps shall not be insulated. 7.3.2. Bottom The boards shall be suitably shaped and fastened to the bottoms by stainless steel, hooked in to appropriate supports. The points between boards shall be closely aligned and the wire mesh shall be sewn together using 1.2 mm stainless steel wire. 7.3.3. Heads The insulation for heads shall be segmental in shape and held together with binding wire. The segments shall be fixed at one end to support straps of stainless steel around the shell and the other end to a floating ring of 10mm 316 stainless steel bar. The joints between insulation sheets shall be closely aligned and the edges of the wire mesh sewn together with 1.2 mm stainless steel wire. 20 BGC Insulation Specification 7.3.4. Revision: 01A Miscellaneous (Special Items, Manholes, Nozzles, etc All valves (except relief valves), manholes, flanges, expansion joints and other items on insulated pipelines shall be insulated. Items with removable insulation shall be insulated to the same thickness as the adjacent vessel or pipe. Where a special item is insulated, it shall be insulated in such a way that the insulation may be easily removed without damaging the insulation close to the item and so as to allow any bolts to be extracted if applicable. In the event that frequent inspection of special items is required, insulation shall be carried out using removable insulated metal boxes, held in place by metal straps and self-tightening devices. The box shall be adequately sealed (including vapour barrier if required) with special attention paid to valve stems and other protrusions. The voids around irregular shapes shall be filled with loose insulation material. 7.4. MACHINERY INSULATION No insulation is required for pumps and other rotating equipment. Compressor insulation shall be as per Compressor vendor recommendations and no further insulation is recommended as per this specification. Unless specified otherwise on individual equipment data sheets or in an equipment insulation summary, insulation shall not be applied to other machinery items. 7.5. INSTRUMENT INSULATION Instrument signal tubing, instrument analyzer tubing and equipment instrument bridles up to instrument connections shall be insulated if heat traced and for personnel protection if operating 0 temperature is above 70 C. Instrument tubing on steam piping shall not be insulated. Heat traced bridles shall be insulated in accordance with the insulation requirements specified for piping. 7.6. VAPOUR BARRIER If the op rating temperature of the pipe or equipment is below ambient or is likely to drop below ambient (during blowdown etc.), a vapour barrier shall be applied over the insulation. Vapour barrier shall be a heavy-duty multiplex foil, adhered to the insulation using a coat of mastic sealant. 7.7. INSULATION FINISH JACKETING All insulation terminations on piping and equipment shall be metal finished and weather tight. Jacketing shall be fitted carefully around vessel and piping attachments which pass through it. Metal sealant shall be applied to the extent necessary to prevent the entrance of water around penetrations through the jacketing. Jacketing shall be installed to shed water. Piping Sheet jacketing shall be erected in such a way as to cover perfectly the insulation beneath. The terminations of cladding shall be water / vapour tight (see Figure 7.1). 21 BGC Insulation Specification Revision: 01A The longitudinal joints of the jacketing shall have a 50 mm minimum overlap, with the free edge beaded for reinforcement, and shall be fixed with self-threading stainless-steel screws every 150 mm. Joints shall be positioned on the side of horizontal piping with the lap orientation to shed rain / water. Peripheral joints shall have a 50 mm minimum overlap with male-female type beading on the edges. They shall not be fixed with screws, in order to give free play to the thermal expansion. Peripheral joints on vertical piping shall be installed with the upper section overlapping the lower. The finishing of elbows shall be executed in geometrically traced segments. Figure 7.1 Jacketing for Piping ITE DESCRIPTION 1 Performed Insulation Pipe Section 2 3 Sheet Metal Cladding Chloride Barrier (where applicable) 4 Adhesive Tape 5 Butyl or Silicone Mastic Tape 6 316 Stainless Steel Tie Wire 7 316 Stainless Steel Banding 8 Stainless Steel Slotted Pan-head Self Tapping crew C/W Reinforced Neoprene Washer 22 BGC Insulation Specification Revision: 01A Equipment Shaped or curved elements shall be fixed to each other and to the support by means of selfthreading screws every 150 mm (see Figure 7.2 - Figure 7.5). Longitudinal and peripheral joints shall be overlapped, not less than 50 mm and the overlap edges shall be beaded. For large flat surfaces, the metal sheet shall be shaped in "diamond point" form or otherwise as reinforcement against flexure. For convex, conical, or truncated conical surfaces, the jacketing shall be executed in geometrically traced segments, the radial joints of which shall overlap for at least 50 mm and be fixed by selfthreading stainless-steel screws. Spaces in the elements due to sundry interruptions (stub-pipes, nozzles, nameplates, etc.) shall be protected by ribbed dummies or fixed with self-threading stainless-steel screws, or else riveted. Particular care shall be taken with all sheet joints, dummies and head jackets, which shall be waterproofed by sealing with bituminous mastic. Equipment requiring inspection and checks, for which a demountable insulating protection is necessary, shall be protected using the same criteria as for valves or flanges covering boxes. The marks and identification tags of equipment shall remain clearly visible after the insulation is applied. The openings made in the insulation for this purpose shall be carefully sealed to avoid the infiltration of water. Exchanger flanges and connecting flanges between the various parts of the equipment in general, valve bodies, angles for fixing gangways or ladders, and supports in general, shall not be insulated. Manholes and nozzles shall not be insulated unless otherwise indicated. Breaks in the insulation due to flanges and manholes shall be executed so as to allow the bolts to be removed without damaging the covering. 23 BGC Insulation Specification Revision: 01A Figure 7.2 Jacketing for Equipment ITEM DESCRIPTION 1 Sealing Cap or Disc 2 “Orange Peel” Metallic Cladding 3 Vapour Barrier (Cold Insulation Only) 4 Butyl or Silicone Mastic Strip 5 Self-tapping Screw c/neoprene Washers 6 Insulation Retaining Bands 7 Staggered Insulation Blocks 8 Insulation Retaining Head Bands 9 Floating Ring 10 Head Band Ties 11 Cladding Securing Bands 12 Sheet Metal Cladding 24 BGC Insulation Specification Revision: 01A Figure 7.3 Jacketing for Equipment 25 BGC Insulation Specification Revision: 01A Figure 7.4 Jacketing for Equipment u Figure 7.5 Jacketing for Equipment M ITEM DESCRIPTION 1 Valve Box Landing Collar 2 Insulating Retaining Clip (detail “a”) 3 SS Quick Release Toggles 4 5 Butyl or Silicone Mastic Strip Valve Box End cover Lock Formed all Sizes 26 BGC Insulation Specification 7.8. Revision: 01A REQUIREMENTS FOR PERSONNEL PROTECTION INSULATION Personnel protection shall be provided if normal temperature of a surface exceeds 70ºC and if the surface is in an area that is accessible to personnel. Accessible area is defined as an area in which personnel regularly perform duties, including maintenance, during plant operation. Personnel protection shall be provided to 2100 mm (7 ft.) above grade or platforms and 900 mm (3 ft.) horizontally from the periphery of platforms, walkways, or ladders. Open Wire-Mesh guards (see Figure 6.1) as used for personnel protection shall be provided by secured & bolted metal mesh guards a d shall be offset from the hazardous surface a minimum of 50 mm. Mesh shall be 316L stainless steel with mesh size such that fingers cannot pass through. The guards shall not create a fire hazard. Guards shall be easily removed and reinstalled on pipes and equipment that require regular maintenance. Figure 7.6 Mesh Guard 7.9. ADDITIONAL REQUIREMENTS FOR ELECTRICAL TRACED INSULATION Jacketing for insulation type ET (electrical traced) piping shall be installed with bands only. Screws and rivets may damage the electrical tracing and are not acceptable fasteners for any jacketing installed to finish insulation on electrically traced piping. 8. INSTALLATION, COLD INSULATION 8.1. PIPING INSULATION Sectional and segmental insulation shall be applied in one or two layers, as required by insulation type and operating temperature, to the thickness specified. Reinforced tape may be used 27 BGC Insulation Specification Revision: 01A in place of metal bands. Single-layer insulation shall be applied with joints staggered, all edges completely coated with joint sealer and tightly butted. Multi-layer insulation shall be applied with side and end joints staggered over the joint of the preceding layer. The joints of all layers shall be sealed and tightly butted. All pipe fittings and flanges shall be completely insulated. All valves shall be insulated up to but not including the packing gland or nut except for control valves with extended bonnets, these shall be insulated to the bonnet flange. All sharp corners and edges of insulation should be rounded. Large voids other than contraction joints or inside boxed areas shall not be filled with joint sealer but eliminated by refitting or replacing insulation. A vapor barrier shall be installed over the insulation. The mastic type vapor barrier shall have a first coat of mastic with a fabric membrane embedded and a final coat of mastic. Aluminum jacketing shall be installed over the vapor barrier as specified in Cini guidelines. 8.2. EQUIPMENT INSULATION The insulation shall be performed and of the correct size. All voids must be filled with pieces of the insulating material and sealed with waterproofing mastic. All joints shall be tightly butted together, sealed with joint sealer. The insulation shall be held in place with ¾’ filament tape or with ½’’ stainless steel bands (max 300 mm centers). A vapor barrier shall be installed over the insulation. The mastic type vapor barrier shall have a first coat of mastic with a fabric membrane embedded and a final coat of mastic. Aluminum jacketing shall be installed over the vapor barrier as specified in Cini guidelines. Openings in the jacket at nozzles, brackets and related items shall be cut as close as possible to provide a snug fit and shall be sealed with joint sealer to prevent moisture from penetrating the jacket. Equipment saddles on horizontal vessels are to be insulated with 1’’ thick Aramaflex (or equal) for a distance below the insulation that is equal to four (4) times the thickness of the vessel insulation. Heat exchangers shall be insulated in a manner similar to horizontal vessels. Heads on exchangers that are removable shall be insulated such to allow access to the bolts with minimum damage to the insulation. Flanged ends shall be insulated with a flat cover that is removable. 9. STORAGE AND HANDLING OF INSULATION MATERIALS Insulating materials shall be handled and stored in accordance with the MANUFACTURER’s recommendations and such that they are maintained in factory dry condition until permanent and final weather protection is fitted. Insulation shall be protected, and containers shall be fully sealed to prevent contamination by water and salts before and during application. 28 BGC Insulation Specification Revision: 01A Products employed shall be properly packaged and identified by MANUFACTURER, type, batch number and date of manufacture. Packaging for insulation shall consist of wrapped or pre-shrunk polythene, or weather-proof cartons or containers. If removed from its original packaging (e.g. partially used cartons), insulation shall be placed in sealed polythene bags (or other material impermeable to moisture) with identifying labels. Materials shall be stored under cover until required for use. Materials which become wet or contaminated with dirt or other extraneous matter shall not be used. Material that becomes wet before or during installation shall be replaced without charge. Insulating materials shall remain in their packaging until immediately before use, and a minimum of handling shall be employed during application. The interval between application of the insulation and weatherproofing should be kept as short as possible. If immediate application of the weatherproofing is impractical, the insulation shall receive adequate temporary weather protection. Irrespective of whether a temporary enclosure is being employed, the insulation shall be protected against ingress of water at all times. 10. INSPECTION SUPPLIER shall submit material datasheets for COMPANY approval, together with applicable laboratory test certificates. Should the material be delivered in multiple batches, a compliance certificate shall be submitted certifying the materials are in accordance with the technical specifications of the first batch. Installation and application of insulation shall be inspected at every stage to ensure quality of workmanship in accordance with COMPANY’s approved inspection and test plan. An Inspection and Test Plan (ITP) and method statement shall be developed. The extent and frequency of inspection shall be defined in the ITP. All inspection activities shall be performed in accordance with the following points: 10.1. CONTROL PRIOR TO THE APPLICATION • Completion of hydro testing; • Completion of welding and NDE; • Completing of structural supports; • Completion of surface treatment according to the Coating and Painting; • Schedule. 10.2. • • • • CONTROL DURING APPLICATION Application according to the applicable standard or MANUFACTURER’s recommendation. Aluminium / metal jackets overlapping and fixing requirements. Proper handling of insulation material. At the end of each daily work shift, verify the adequacy of the protection required by the principle for installed insulation before insulation is covered with jacketing / sheeting. Check sealing between sheets. 29 BGC Insulation Specification • • Revision: 01A The Supervisor shall systematically check ambient conditions and is responsible for halting insulation activities should the conditions be unsuitable, such as rain and temperature below dew point of the surfaces to be insulated. The Supervisor shall comply with the conditions (temperature, humidity, absence of rain, etc.) for applying adhesive and sealing materials in accordance with the MANUFACTURER’s instructions. 10.3. INSPECTION CRITICAL Insulation / jacketing shall be judged as defective and shall be removed and replaced under any of the following criteria / reasons: • If there are any cracks extending through the insulation; • If there are any cracks that could cause the insulation to break upon sawing or gently flexing; • If the ends are broken or damaged; • If more than 10% of the surface area of the insulation is composed of large voids; • If any large void has a depth greater than 10% of the insulation thickness. 10.4. FINAL CONTROL Final inspection shall include the following: • Metal jacket sealing • Fixing of bands • Completion of full scope of work to all the required standards and specifications. 10.5. IN SERVICE INSPECTION In service inspection shall include the following: • Special inspection at dead legs of piping / insulation • Inspection near vibrating lines which can disturb seals • Inspect near reciprocating compressors • Inspection extent and frequency to be detailed in the quality plan. 11. WARRANTY AND PERFORMANCE GUARANTEE Unless otherwise agreed, all work shall be guaranteed as follows: • All work shall perform satisfactory under the specified operating conditions and shall be fit for the intended purpose. • All materials supplied shall be guaranteed free from defects. • All workmanship shall be guaranteed free from defects and in accordance with the best industrial standards and practices. • SUPPLIER shall guarantee the mechanical and structural integrity, workmanship and the materials of construction used. • Under the warranty, the Seller shall replace all work that is found to be faulty due to defective design, workmanship, or materials during the warranty period at no cost to the principle. SUPPLIER shall, if required by COMPANY, supply the services of an experienced technician to supervise the necessary repairs and replacements. 12. DOCUMENTATION All drawings, technical documents, instruction manuals and legend plates, equipment and operating panels, shall be in English. Documentation requirements and submittal times are itemized in SUPPLIER’s Data Requirements List provided in the request for tender submission 30 Revision: 01A BGC Insulation Specification 13. INSULATION ATTACHMENT METHODS, INSULATION FINISH REQUIREMENT AND INSULATION THICKNESS TABLE 13.1. Table 13-1: INSULATION ATTACHMENT METHODS AND MATERIALS (Mineral wool) )INSULATION Form Material EQUIPMENT Type Size (Note 1) METHOD OF ATTACHMENT Type (Note 2& 5) Segments, Block and Lags Mineral Wool Pipe and equipment shells Slab Mineral wool Equipment shells Over 1800 mm Band "B" Mineral wool Equipment heads, Irregular equipment surfaces All Band "B" Mattress Over 750 mm Band "B" Spacing (Note 4) 300 mm on centers for single/ outer layers and 450 mm on centers for all inner layers 225 mm on centers for single/ outer layers and 450 mm on centers for all inner layers 300mm maximum space at knuckle radius- minimum 1 per block (Note-3) NOTES TO TABLE 9.1: 1 2 Size is the nominal pipe size or vessel outside diameter. Materials are as follows: Band "A": 13 mm by 0.50 mm, Stainless steel 316. Band "B": 19 mm by 0.50 mm, Stainless steel 316. Wire: 1.0 mm diameter Stainless steel 316 wire. 3 Attachment of high temperature insulation over irregular surfaces may be with wire if the use of bands is impractical. 4 Band or wire spacing specified as "300 mm maximum all layers" or "450 mm maximum all layers" applies to 900 mm long insulation segments. Shorter lengths, such as 600 mm long V grooved mineral wool slab requires two (2) bands or wires per section on all layers. 5 Unless noted otherwise, equipment insulated with fibrous type insulation does not require insulation springs for bands securing insulation to the shell of equipment. For equipment insulated with rigid block insulation, 100 mm long, flat springs are required for each band. 31 BGC Insulation Specification 13.2. Revision: 01A Table 13-2: INSULATION FINISH REQUIREMENTS EQUIPMENT OR PIPING OUTSIDE DIAMETER INSULATION FINISH END LAP (Note 2) (Note 7) Shells Vertical Vessels 915 mm (36’’) or less Flat metallic sheet Over 915 mm (36’’) 32 mm corrugated metallic sheet All Gored flat metallic sheet, same thickness as shell Gores require a -75 mm lap at shell junction All Flat metallic sheet 75 mm - longitudinal and circumferential All Gored flat metallic sheet Gores require a 75 mm lap at shell junction Flat metallic sheet 50 mm - longitudinal and circumferential Flat metallic sheet (Note 4) 75 mm - longitudinal and circumferential All Gored cover fabricated from flat metallic sheet - same thickness as pipe End laps same as above for straight pipe - lap individual gores 50 mm along inside radius End laps as above for straight pipe, etc. All Gored cover fabricated from flat metallic sheet - same thickness as pipe Removable and reusable insulation covers 50 mm - all directions Exposed Heads Concealed Heads Shells and Horizontal Vessels and Channels Heat Heads Exchangers Straight Pipe, NPS 24 or less Tees and Piping Branch Over NPS 24 Connections Bent Pipe Piping Elbows Valves, Flanges (only when insulation is required) NPS 24 or less Over NPS 24 75 mm - longitudinal and circumferential 2 corrugations longitudinal 75 mm - circumferential 75 mm - all directions 32 Revision: 01A BGC Insulation Specification 13.3. Table 13-3: INSULATION FINISH REQUIREMENTS (continued) ITEM METHOD OF ATTACHMENT LOCATION OF FINISH OUTSIDE DIAMETER SECUREMENT TYPE (Note 2) (Note 7) (Note 1) Less than 1200 mm Shells 1200 mm and larger Band "B" (Note 8) 300 mm maximum centers supported radially with belt loops on 4.5 m centers minimum 2 per band (Notes 3, 4 5) Screws (Notes 5 & 150 mm centers along gore laps Vertical Vessels Exposed Heads All 6) Concealed Heads Horizontal Vessels and Heat Exchangers Piping Shells All Heads and Channels Straight Pipe, Tees and branch connections NPS 24 and less Over NPS 24 Piping Fittings, Valves Band "B" 225 mm maximum centers (Note 3) Screws (Notes 5 & 6) 150 mm centers along gore laps Band "A" Band "B" Band "A", Elbows, Bent Pipe Screws All And Flanges Valves, Flanges (Only when Insulation is required) SPACING 300 mm maximum centers (Notes 3, 4, 5) Band "A", Screws For insulation dia Less than or equal to 150 mm (6’’) : 225 mm maximum centers; For insulation dia greater than 150 mm (6’’) : 300 mm maximum centers; (Note 3) Band fasten die-formed and gored elbow covers at each circumferential end lap over (or under) the adjacent weather jacket. Fasten longitudinal heel and throat laps on die-formed covers with screws on 100 to 125 mm centers - minimum 1 screw for the throat lap and 3 screws for the heel lap. Fasten both longitudinal and circumferential laps in the throat area of each gored segment using a single screw. Fasten all gored segment circumferential laps with 1 screw per lap along the outside radius or heel of the gored cover. (Note 9) 300 mm maximum centers, minimum 2 per cylindrical section - screws on 100 mm maximum centers along seams. NOTES TO TABLE 9.2 & 9.3: 1. Band material shall be as follows: 33 BGC Insulation Specification Revision: 01A Band "A" - 13 mm x 0.5 mm, Stainless steel 316 Band "B" - 19 mm x 0.5 mm, Stainless steel 316 Belt loops shall be fabricated from the same material as the bands and shall be riveted to high points of corrugations on 450 mm maximum centers. 2. 3. 4. Laps shall be oriented to shed water. 5. Longitudinal laps in jacketing on vertical vessels shall be screw fastened on 150 mm centers. Circumferential laps on all vessels shall not be screw fastened except at the head gore/shell finish lap which requires circumferentially placed screws on staggered 150 mm nominal centers and at the bottom of the shell jacketing which requires circumferentially placed screws on 150 mm nominal centers. 6. Convex equipment heads that have been insulated with a flat disc shall have the lapping surfaces of the blind cover coated with silicone sealant prior to installation of the cover. Covers on horizontal equipment shall have the lapped seam oriented to shed water. 7. 8. Outside diameter refers to nominal pipe or equipment diameter. All circumferential laps shall be banded. Vertical sheathing support shall be provided on all vertical vessels and vertical piping having insulation outside diameters of 450 mm or more with the application of 13 mm by 0.5 mm austenitic stainless steel "S-clips" installed on 450 mm maximum centers (minimum 2 clips per sheet regardless of diameter). Screws are not allowed for cold Insulation. Band shall be used with a minimum of one band per gored segment. However, if band not at all possible to use, screws may be used (Subject to approval). 34 Revision: 01A BGC Insulation Specification 13.4. Table 13-4: INSULATION THICKNESSES (mm) FOR PIPING AND EQUIPMENT HEAT CONSERVATION - Mineral wool - MODERATE CLIMATE Operating temperature in ⁰C (°F) PIPE DIAMETERS Inches/DN/mm 50 (120) 100 (210) 150 (300) 200 (390) 250 (480) 300 (570) 350 (660) 400 (750) 450 (840) 500 (930) Insulation thickness [mm (in) ] 1"/25/33.40 25 (1) 40 (1.5) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 1½"/40/48.26 25 (1) 40 (1.5) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 50 (2) 2"/50/60.33 30 (1.2) 50 (2) 50 (2) 60 (2.4) 60 (2.4) 70 (2.6) 70 (2.6) 80 (3) 80 (3) 80 (3) 3"/80/88.90 30 (1.2) 50 (2) 50 (2) 60 (2.4) 60 (2.4) 80 (3) 80 (3) 80 (3) 80 (3) 80 (3) 4"/100/114.3 40 (1.5) 50 (2) 60 (2.4) 60 (2.4) 60 (2.4) 70 (2.6) 80 (3) 80 (3) 80 (3) 80 (3) 6"/150/168.3 40 (1.5) 60 (2.4) 60 (2.4) 60 (2.4) 70 (2.6) 80 (3) 80 (3) 80 (3) 80 (3) 100 (4) 8"/200/219.1 50 (2) 80 (3) 80 (3) 90 (3.5) 90 (3.5) 100 (4) 100 (4) 100 (4) 100 (4) 100 (4) 10"/250/273.1 60 (2.4) 80 (3) 80 (3) 90 (3.5) 90 (3.5) 100 (4) 120 (4.7) 120 (4.7) 120 (4.7) 120 (4.7) 12"/300/323.9 60 (2.4) 80 (3) 80 (3) 90 (3.5) 100 (4) 120 (4.7) 120 (4.7) 120 (4.7) 120 (4.7) 140 (5.5) 14"/350/355.6 50 (2) 90 (3.5) 90 (3.5) 100 (4) 100 (4) 120 (4.7) 120 (4.7) 140 (5.5) 140 (5.5) 140 (5.5) 16"/400/406.4 60 (2.4) 90 (3.5) 90 (3.5) 100 (4) 120 (4.7) 120 (4.7) 140 (5.5) 140 (5.5) 160 (6.3) 160 (6.3) 18"/450/457.2 60 (2.4) 90 (3.5) 90 (3.5) 100 (4) 120 (4.7) 120 (4.7) 140 (5.5) 160 (6.3) 160 (6.3) 160 (6.3) 20"/500/508.0 60 (2.4) 70 (2.6) 80 (3) 100 (4) 120 (4.7) 140 (5.5) 140 (5.5) 160 (6.3) 160 (6.3) 160 (6.3) 24"/600/609.6 60 (2.4) 90 (3.5) 100 (4) 100 (4) 120 (4.7) 140 (5.5) 160 (6.3) 160 (6.3) 160 (6.3) 160 (6.3) Flat Equipment 70 (2.6) 120 (4.7) 120 (4.7) 120 (4.7) 120 (4.7) 140 (5.5) 160 (6.3) 160 (6.3) 160 (6.3) 160 (6.3) Insulation system: Mineral wool with aluminized steel jacketing Ambient temperature: 15 °C (60 °F) Wind speed: 5 m/s (11 mph). Service life: 25 yr Process temperatures: between 50 °C and 500 °C (120 °F to 930 °F) 35 Revision: 01A BGC Insulation Specification 13.5. Table 13-5: INSULATION THICKNESSES (mm) FOR PIPING AND EQUIPMENT PERSONNEL PROTECTION - Mineral wool For process temperatures from 60 C to 250 C (140 °F – 480 °F) barrier protections should be applied, without insulation (3.1.3) For process temperatures > 250C (480°F), rock wool with metal cladding should be used. Normal operating temperature [°C (°F)] 60 to 250 > 250 350 400 450 500 600 Nominal pipe diameter (DN) Nominal pipe diameter (NPS) Distance from sheet/ guard to bare surface [mm (in)] < 25 <1 50 (2) 25 (1) 30 (1.2) 40 (1.5) 40 (1.5) 50 (2) 60 (2.4) 25 1 50 (2) 25 (1) 30 (1.2) 40 (1.5) 40 (1.5) 50 (2) 60 (2.4) 40 1½ 50 (2) 25 (1) 30 (1.2) 40 (1.5) 50 (2) 60 (2.4) 70 (2.6) 50 2 50 (2) 25 (1) 40 (1.5) 40 (1.5) 50 (2) 60 (2.4) 70 (2.6) 80 3 50 (2) 30 (1.2) 40 (1.5) 40 (1.5) 50 (2) 60 (2.4) 80 (3) 100 4 50 (2) 30 (1.2) 40 (1.5) 50 (2) 50 (2) 70 (2.6) 80 (3) 150 6 50 (2) 30 (1.2) 40 (1.5) 50 (2) 60 (2.4) 70 (2.6) 80 (3) 200 8 50 (2) 30 (1.2) 40 (1.5) 50 (2) 60 (2.4) 80 (3) 80 (3) 250 10 50 (2) 30 (1.2) 40 (1.5) 50 (2) 60 (2.4) 80 (3) 100 (4) 300 12 100 (4) 30 (1.2) 40 (1.5) 50 (2) 60 (2.4) 80 (3) 100 (4) 350 14 100 (4) 30 (1.2) 40 (1.5) 50 (2) 70 (2.6) 80 (3) 100 (4) 400 16 100 (4) 30 (1.2) 40 (1.5) 50 (2) 70 (2.6) 80 (3) 100 (4) 450 18 100 (4) 30 (1.2) 40 (1.5) 50 (2) 70 (2.6) 80 (3) 100 (4) 500 20 100 (4) 40 (1.5) 40 (1.5) 50 (2) 70 (2.6) 80 (3) 100 (4) 40 (1.5) 40 (1.5) 50 (2) 70 (2.6) 80 (3) 100 (4) Equipment Channels/Flat Surfaces Insulation thickness [mm (in)] The table is based on: • Ambient temperature of 25C (77°F). • Wind velocity of 1 m/s (2.2 mph). • Surface temperature protection max. 60C (140°F) Criteria could be different for other locations and applicable values should be determined per location. 36 Revision: 01A BGC Insulation Specification 13.6. Table 13-6: INSULATION THICKNESSES (mm) ELECTRICAL HEAT TRACING (ET)Mineral wool NOMINAL PIPE SIZE 0.50 0.75 NORMAL/MAXIMUM OPERATING TEMPERATURE, C 38-100 101-150 151-200 201-250 30.0 30.0 30.0 40.0 30.0 30.0 40.0 40.0 1 1.5 30.0 30.0 40.0 40.0 30.0 30.0 40.0 40.0 2 30.0 30.0 40.0 40.0 2.5 30.0 30.0 40.0 40.0 3 30.0 30.0 40.0 50.0 4 30.0 30.0 40.0 50.0 5 30.0 30.0 40.0 50.0 6 30.0 30.0 40.0 50.0 8 10 30.0 30.0 40.0 50.0 30.0 30.0 40.0 50.0 12 30.0 30.0 40.0 50.0 14 30.0 30.0 40.0 50.0 16 30.0 30.0 40.0 65.0 18 30.0 30.0 40.0 65.0 20 30.0 30.0 40.0 65.0 24 30.0 30.0 40.0 65.0 30 36 30.0 30.0 40.0 65.0 30.0 30.0 50.0 65.0 42 30.0 30.0 50.0 65.0 48 54 30.0 30.0 50.0 65.0 30.0 30.0 50.0 65.0 60 30.0 30.0 50.0 80.0 72 30.0 40.0 50.0 80.0 84 96 30.0 40.0 50.0 80.0 30.0 40.0 50.0 80.0 108 30.0 40.0 50.0 80.0 120 30.0 40.0 50.0 80.0 *144 30.0 40.0 50.0 80.0 Notes: 1. Pipe sections used for the insulation of electrically traced piping shall have a diameter equal to the pipe diameter. In the case of spiralwound tracing >2 mm, oversized pipe sections (commercial size) shall be used. 2. For steam tracing, the next largest pipe size insulation (commercial size) shall be used to accommodate both parent pipe and tracing pipe. 37 Revision: 01A BGC Insulation Specification 13.7. Table 13-7: INSULATION THICKNESSES (mm) FOR PIPING AND EQUIPMENT COLD INSULATION- MODERATE CLIMATE Operating temperature in ⁰C (°F) PIPE DIAMETERS -5 (23) -10 (14) -20 (-4) -40 (-40) Inches/DN/mm -60 (-76) -80 (-110) -100 (-150) -120 (-185) -140 (-220) -160 (-255) -180 (-290) Insulation thickness [ mm (in) ] 1"/25/33.40 15 (0.6) 20 (0.8) 25 (1) 35 (1.4) 40 (1.5) 50 (2) 60 (2.4) 65 (2.6) 75 (3) 80 (3.2) 85 (3.4) 1½"/40/48.26 15 (0.6) 20 (0.8) 25 (1) 35 (1.4) 45 (1.8) 55 (2.2) 65 (2.6) 70 (2.8) 80 (3.2) 85 (3.4) 95 (3.7) 2"/50/60.33 15 (0.6) 20 (0.8) 25 (1) 35 (1.4) 45 (1.8) 55 (2.2) 65 (2.6) 75 (3) 85 (3.4) 90 (3.5) 100 (4) 3"/80/88.90 20 (0.8) 20 (0.8) 25 (1) 40 (1.5) 50 (2) 60 (2.4) 70 (2.8) 80 (3.2) 90 (3.5) 100 (4) 110 (4.3) 4"/100/114.3 20 (0.8) 20 (0.8) 30 (1.2) 40 (1.5) 50 (2) 65 (2.6) 75 (3) 85 (3.4) 95 (3.7) 105 (4.1 115 (4.5) 6"/150/168.3 20 (0.8) 20 (0.8) 30 (1.2) 40 (1.5) 55 (2.2) 70 (2.8) 80 (3.2) 90 (3.5) 105 (4.1 115 (4.5) 125 (5) 8"/200/219.1 20 (0.8) 20 (0.8) 30 (1.2) 45 (1.8) 55 (2.2) 70 (2.8) 85 (3.4) 95 (3.7) 110 (4.3) 120 (4.7) 130 (5.1) 10"/250/273.1 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 60 (2.4) 70 (2.8) 85 (3.4) 100 (4) 110 (4.3) 125 (5) 135 (5.3) 12"/300/323.9 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 60 (2.4) 75 (3) 90 (3.5) 100 (4) 115 (4.5) 125 (5) 140 (5.5) 14"/350/355.6 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 60 (2.4) 75 (3) 90 (3.5) 105 (4.1 115 (4.5) 130 (5.1) 140 (5.5) 16"/400/406.4 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 60 (2.4) 75 (3) 90 (3.5) 105 (4.1 120 (4.7) 130 (5.1) 145 (5.7) 18"/450/457.2 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 60 (2.4) 75 (3) 90 (3.5) 105 (4.1 120 (4.7) 135 (5.3) 145 (5.7) 20"/500/508.0 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 60 (2.4) 75 (3) 90 (3.5) 105 (4.1 120 (4.7) 135 (5.3) 150 (6) 24"/600/609.6 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 65 (2.6) 80 (3.2) 95 (3.7) 110 (4.3) 125 (5) 140 (5.5) 150 (6) 30"/750/762.0 20 (0.8) 25 (1) 30 (1.2) 45 (1.8) 65 (2.6) 80 (3.2) 95 (3.7) 110 (4.3) 125 (5) 140 (5.5) 155 (6.1) 40"/1000/1016.0 20 (0.8) 20 (0.8) 30 (1.2) 45 (1.8) 65 (2.6) 80 (3.2) 95 (3.7) 115 (4.5) 130 (5.1) 145 (5.7) 160 (6.3) 80"/2000/2032.0 15 (0.6) 20 (0.8) 30 (1.2) 45 (1.8) 65 (2.6) 80 (3.2) 100 (4) 115 (4.5) 135 (5.3) 150 (6) 165 (6.5) Flat Equipment 15 (0.6) 20 (0.8) 30 (1.2) 50 (2) 65 (2.6) 85 (3.4) 105 (4.1 125 (5) 140 (5.5) 165 (6.5) 180 (7) Insulation system: PIR with GRP cladding or specified by BGC BGC Insulation Specification Ambient temperature: 15 °C (60 °F) Wind speed: 5 m/s (11 mph). Relative humidity: 80% Maximum heat gain: 25 W/m2 (8 Btu/hr/ft2) Revision: 01A Note: For Electrical traced lines when operating temperature is between -5C to below 50C, Polyurethane insulation joints shall not be sealed, and no vapor barrier shall be applied. BGC Insulation Specification 13.8. Table 13-8: REFERENCE TABLE FOR THE LAYERING OF COLD INSULATION Total insulation [ mm (in) ] Pre-formed PIR [ mm (in) ] Cellular Glass [ mm (in) ] 30 (1.2) 30 (1.2) 30 (1.2) 40(1.5) 40(1.5) 40(1.5) 50(2) 50(2) 50(2) 60(2.4) 30/30(1.2/1.2) 60(2.4) 70(2.8) 30/40(1.2/1.5) 70(2.8) 80(3.2) 40/40(1.5/1.5) 40/40(1.5/1.5) 90(3.5) 40/50(1.5/2) 40/50(1.5/2) 100(4) 50/50(2/2) 50/50(2/2) 110(4.3) 50/60(2/2.4) 50/60(2/2.4) 120(4.7) 30/40/50(1.2/1.5/2) 60/60(2.4/2.4) 130(5.1) 30/50/50(1.2/2/2) 60/70(2.4/2.8) 140(5.5) 40/50/50(1.5/2/2) 70/70(2.8/2.8) 150(6) 50/50/50(2/2/2) 70/80(2.8/3/2) 160(6.3) 50/60/50(2/2.4/2) 80/80(3.2/3.2) 170(6.7) 50/70/50(2/2.8/2) 80/90(3.2/3.5) 180(7) 50/80/50(2/3.2/2) 90/90(3.5/3.5) 190(7.5) 50/90/50(2/3.5/2) 90/100(3.5/4) 200(8) 50/100/50(2/4/2) 100/100(4/4) 210(8.3) 50/50/60/50(2/2/2.4/2) 70/70/70(2.8/2.8/2.8) 220(8.7) 50/50/70/50(2/2/2.8/2) 70/70/80(2.8/2.8/3.2) 230(9) 50/50/80/50(2/2/3.2/2) 70/80/80(2.8/3.2/3.2) 240(9.5) 50/50/90/50(2/2/3.5/2) 80/80/80(3.2/3.2/3.2) 250(10) 50/50/100/50(2/2/4/2) 80/80/90(3.2/3.2/3.5) Revision: 01A