Offer Nº Order Nº Page Nº Low Voltage Cables Product identification and Features Cable code Cable type Standard Standard Standard Nominal voltage Nº of cores x C.S.A. Construction and Dimensions Conductor material Shape Class / Standard Max. wires diameter Nominal diameter Mica glass tape Insulation material Nominal radial thickness Diameter over insulation Outer sheath material Nominal radial thickness / Minimum at any point Nominal overall diameter Nominal total weight Maximum pulling load Minimum bending radius (after installation) Electrical Data Maximum conductor DC resistance, at 20 ºC Star reactance per phase, at 50 Hz Maximum permanent current rating (*) Maximum conductor temperature in service / in short-circuit Maximum adiabatic short-circuit current rating (0.1/0.5/1.0 s) (*) In air, at 40 ºC / Buried, at 25 ºC - 1,5 ºK·m/W - 0,7 m (see more details in ANNEX) N/A = Not Applicable Units 1 Item1 Item2 Item3 19921J3 RZ1-K Specif. CERN 3818 IEC 60502-1 IEC 60332-3-23 0,6/1 kV 1 x16 mm² 19921G9 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x25 mm² 19921H0 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x35 mm² mm mm kgs/km N mm Copper Circular 5 / IEC 60228 0,41 4,95 NO XLPE 0,7 6,4 LSF-OH 1,4 / -9,2 200 800 37 Copper Circular 5 / IEC 60228 0,41 6,20 NO XLPE 0,9 8,0 LSF-OH 1,4 / -10,8 290 1250 44 Copper Circular 5 / IEC 60228 0,41 7,30 NO XLPE 0,9 9,1 LSF-OH 1,4 / -11,9 380 1750 48 Ohm/km Ohm/km A ºC kA 1,21 0,098 91 (7) / 83 (6) 90 / 250 7,23 / 3,23 / 2,29 0,78 0,095 122 (5) / 106 (6) 90 / 250 11,3 / 5,05 / 3,57 0,554 0,090 153 (5) / 128 (6) 90 / 250 15,8 / 7,07 / 5 mm mm mm mm Signed by : F. Soldevila Date : 22/11/2016 Nominal values subject to the usual manufacturer tolerances General Cable reserves the right to change or modify the specifications and materials depending on future improvements. Based on this, data listed above could be modified due to these changes Offer Nº Order Nº Page Nº Low Voltage Cables Product identification and Features Cable code Cable type Standard Standard Standard Nominal voltage Nº of cores x C.S.A. Construction and Dimensions Conductor material Shape Class / Standard Max. wires diameter Nominal diameter Mica glass tape Insulation material Nominal radial thickness Diameter over insulation Outer sheath material Nominal radial thickness / Minimum at any point Nominal overall diameter Nominal total weight Maximum pulling load Minimum bending radius (after installation) Electrical Data Maximum conductor DC resistance, at 20 ºC Star reactance per phase, at 50 Hz Maximum permanent current rating (*) Maximum conductor temperature in service / in short-circuit Maximum adiabatic short-circuit current rating (0.1/0.5/1.0 s) (*) In air, at 40 ºC / Buried, at 25 ºC - 1,5 ºK·m/W - 0,7 m (see more details in ANNEX) N/A = Not Applicable Units 2 Item4 Item5 Item6 19921G6 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x50 mm² 19921H3 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x70 mm² 19921G8 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x95 mm² mm mm kgs/km N mm Copper Circular 5 / IEC 60228 0,41 8,70 NO XLPE 1,0 10,7 LSF-OH 1,4 / -13,5 525 2500 54 Copper Circular 5 / IEC 60228 0,51 10,60 NO XLPE 1,1 12,8 LSF-OH 1,4 / -15,6 715 3500 63 Copper Circular 5 / IEC 60228 0,51 12,15 NO XLPE 1,1 14,4 LSF-OH 1,5 / -17,4 925 4750 70 Ohm/km Ohm/km A ºC kA 0,386 0,087 188 (5) / 152 (6) 90 / 250 22,6 / 10,1 / 7,14 0,272 0,084 243 (5) / 187 (6) 90 / 250 31,6 / 14,1 / 10 0,206 0,082 298 (5) / 222 (6) 90 / 250 42,9 / 19,2 / 13,6 mm mm mm mm Signed by : F. Soldevila Date : 22/11/2016 Nominal values subject to the usual manufacturer tolerances General Cable reserves the right to change or modify the specifications and materials depending on future improvements. Based on this, data listed above could be modified due to these changes Offer Nº Order Nº Page Nº Low Voltage Cables Product identification and Features Cable code Cable type Standard Standard Standard Nominal voltage Nº of cores x C.S.A. Construction and Dimensions Conductor material Shape Class / Standard Max. wires diameter Nominal diameter Mica glass tape Insulation material Nominal radial thickness Diameter over insulation Outer sheath material Nominal radial thickness / Minimum at any point Nominal overall diameter Nominal total weight Maximum pulling load Minimum bending radius (after installation) Electrical Data Maximum conductor DC resistance, at 20 ºC Star reactance per phase, at 50 Hz Maximum permanent current rating (*) Maximum conductor temperature in service / in short-circuit Maximum adiabatic short-circuit current rating (0.1/0.5/1.0 s) (*) In air, at 40 ºC / Buried, at 25 ºC - 1,5 ºK·m/W - 0,7 m (see more details in ANNEX) N/A = Not Applicable Units 3 Item7 Item8 Item9 19921H2 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x120 mm² 19921H1 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x150 mm² 19921G4 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x240 mm² mm mm kgs/km N mm Copper Circular 5 / IEC 60228 0,51 14,00 NO XLPE 1,2 16,4 LSF-OH 1,5 / -19,4 1165 6000 78 Copper Circular 5 / IEC 60228 0,51 15,40 NO XLPE 1,4 18,2 LSF-OH 1,6 / -21,4 1450 7500 86 Copper Circular 5 / IEC 60228 0,51 19,60 NO XLPE 1,7 23,0 LSF-OH 1,7 / -26,4 2290 12000 135 Ohm/km Ohm/km A ºC kA 0,161 0,080 348 (5) / 253 (6) 90 / 250 54,2 / 24,2 / 17,1 0,129 0,080 404 (5) / 286 (6) 90 / 250 67,8 / 30,3 / 21,4 0,0801 0,078 552 (5) / 370 (6) 90 / 250 108 / 48,5 / 34,3 mm mm mm mm Signed by : F. Soldevila Date : 22/11/2016 Nominal values subject to the usual manufacturer tolerances General Cable reserves the right to change or modify the specifications and materials depending on future improvements. Based on this, data listed above could be modified due to these changes Offer Nº Order Nº Page Nº Low Voltage Cables Product identification and Features Cable code Cable type Standard Standard Standard Nominal voltage Nº of cores x C.S.A. Construction and Dimensions Conductor material Shape Class / Standard Max. wires diameter Nominal diameter Mica glass tape Insulation material Nominal radial thickness Diameter over insulation Outer sheath material Nominal radial thickness / Minimum at any point Nominal overall diameter Nominal total weight Maximum pulling load Minimum bending radius (after installation) Electrical Data Maximum conductor DC resistance, at 20 ºC Star reactance per phase, at 50 Hz Maximum permanent current rating (*) Maximum conductor temperature in service / in short-circuit Maximum adiabatic short-circuit current rating (0.1/0.5/1.0 s) (*) In air, at 40 ºC / Buried, at 25 ºC - 1,5 ºK·m/W - 0,7 m (see more details in ANNEX) N/A = Not Applicable Units 4 Item10 Item11 19921J8 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x300 mm² 19921G5 RZ1-K Specif. CERN 361 IEC 60502-1 IEC 60332-3-24 0,6/1 kV 1 x400 mm² mm mm kgs/km N mm Copper Circular 5 / IEC 60228 0,51 23,00 NO XLPE 1,8 26,6 LSF-OH 1,8 / -30,2 2855 15000 155 Copper Circular 5 / IEC 60228 0,51 27,00 NO XLPE 2,0 31,0 LSF-OH 1,9 / -34,8 3815 20000 175 Ohm/km Ohm/km A ºC kA 0,0641 0,077 639 (5) / 418 (6) 90 / 250 136 / 60,6 / 42,9 0,0486 0,076 748 (5) / 486 (8) 90 / 250 181 / 80,8 / 57,1 mm mm mm mm Signed by : F. Soldevila Date : 22/11/2016 Nominal values subject to the usual manufacturer tolerances General Cable reserves the right to change or modify the specifications and materials depending on future improvements. Based on this, data listed above could be modified due to these changes METHODS DESCRIPTION AND INSTALLATION CONDITIONS (1) 3 single-core cables, in trefoil touching formation, with effective air renovation. In free air at 40ºC, solar radiation protected, in accordance with UNE 211435 (2) 3 single-core cables, in trefoil touching formation, buried direct in the ground. Direct buried at 25ºC - 1,5ºK·m/W - 0,7m, in accordance with UNE 211435 3 single-core cables, in trefoil touching formation, with effective air renovation. (3) In free air at 40ºC, solar radiation protected, calculation criteria in accordance with IEC 60287 (4) 3 single-core cables, in trefoil touching formation, buried direct in the ground. Direct buried at 25ºC - 1,5ºK·m/W - 0,7m, calculation criteria in accordance with IEC 60287 (5) F Single-core cables, in trefoil touching formation in free air. Clearance to wall not less than one cable diameter. In air at 40ºC, solar radiation protected, in accordance with IEC 60364-5-52, Method F (3 loaded conductors) (6) D Single-core cables, in cable ducting in the ground. Buried at 25ºC - 1,5ºK·m/W - 0,7m, in accordance with IEC 60364-5-52, Method D (3 loaded conductors) (7) Single-core cables, in trefoil touching formation in free air. Clearance to wall not less than one cable diameter. In air at 40ºC, solar radiation protected, calculation criteria in accordance with IEC 60287 (3 loaded conductors) (8) Single-core cables, in cable ducting in the ground. Buried at 25ºC - 1,5ºK·m/W - 0,7m, calculation criteria in accordance with IEC 60287 (3 loaded conductors) (9) Aerial Bundled Cables In free air at 40ºC, solar radiation exposed, in accordance with UNE 211435 (10) Aerial Bundled Cables In free air at 40ºC, solar radiation exposed, calculation criteria in accordance with IEC 60287 Insulated conductors in conduit in a thermally insulated wall. In air at 40ºC, in accordance with IEC 60364-5-52, Method A1 (3 loaded conductors) Insulated conductors in conduit in a thermally insulated wall. In air at 40ºC, calculation criteria in accordance with IEC 60287 (3 loaded conductors) (11) A1 (12) (13) E Multi-core cable in free air. Clearance to wall not less than 0.3 times cable diameter. In air at 40ºC, solar radiation protected, in accordance with IEC 60364-5-52, Method E (2 loaded conductors for 2-core cables and 3 loaded conductors for 3-core, 4-core and 5-core cables) (14) D Multi-core cable in cable ducting in the ground. Buried at 25ºC - 1,5ºK·m/W - 0,7m, in accordance with IEC 60364-5-52, Method D (2 loaded conductors for 2-core cables and 3 loaded conductors for 3-core, 4-core and 5-core cables) (15) Multi-core cable in free air. Clearance to wall not less than 0.3 times cable diameter. In air at 40ºC, solar radiation protected, calculation criteria in accordance with IEC 60287 (2 loaded conductors for 2-core cables and 3 loaded conductors for 3-core, 4-core and 5-core cables) (16) Multi-core cable in cable ducting in the ground. Buried at 25ºC - 1,5ºK·m/W - 0,7m, calculation criteria in accordance with IEC 60287 (2 loaded conductors for 2-core cables and 3 loaded conductors for 3-core, 4-core and 5-core cables) Single-core or multicore cable on a wooden wall. In air at 40ºC, solar radiation protected, in accordance with IEC 60364-5-52, Method C Single-core or multicore cable on an horizontal surface. In air at 40ºC, solar radiation protected, in accordance with Cenelec HD 516 S2 Table 7 (17) (18) C Derating Factors for different installation conditions : Please contact our Technical Department