Uploaded by santu02

document

advertisement
Digital Differential Protection
G. Ziegler
Differential Protection Symposium
Belo Horizonte, 7 to 9 Nov. 2005
No.: 1
Differential Protection: Discussion Subjects
Ø
Mode of operation
Ø
Measuring technique
Ø
Current transformers
Ø
Communications
Ø
Generator and motor differential protection
Ø
Transformer differential protection
Ø
Line differential protection
Ø
Busbar differential protection
Differential Protection Symposium
Belo Horizonte, 7 to 9 Nov. 2005
No.: 2
Digital Differential
Protection
Principles and Application
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 1
Contents
Pages
Mode of operation
3 - 27
Measuring technique
28 - 45
Current transformers
46 - 86
Communications
87 - 115
Generator and motor differential protection
116 - 122
Transformer differential protection
123 - 178
Line differential protection
179 - 216
Busbar differential protection
217 - 247
7UT6 product features
248 - 264
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 2
Digital Differential Protection
Mode of operation
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 3
Comparison protection - Principles
Absolute selectivity by using communications
IA
IB
B
A
Exchange of YES / NO signals
(fault forward / reverse)
protection range
reverse
forward
Relay
forward
communication
reverse
• Current comparison
| ∆I |
Relay
Sampled values
Phasors
Binary decisions
t
•Directional comparison
IA
IB
•comparison of
momentary values or phasors
B
• | ∆I | = | IA - IB | > limiting value
A
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 4
Protection Criterion “current difference“
(differential protection)
n Kirchhoff‘s law: II1 + I2 + I3 + ... InI= Idiff = 0;
Current difference indicates fault
n Security by through-current dependent restraint
|I1|+|I2|+ ... |In| = IRes
protection
object
n Characteristic:
Idiff
Trip
Ires
n Absolute zone selectivity (limits: CT locations)
No “back-up“ for external faults
n Differential protection: for generators, motors, transformers, lines and busbars
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 5
Current differential protection: Basic principle
I1
i1
I2
Protection
object
i2
∆I>
∆I=I1 + I2
=0
external fault or load
Differential Protection Symposium
I1
I2
Protection
object
i1
i2
i1
∆I>
∆I=I1 + I2
i2
internal fault
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 6
Differential protection: Connection circuit
Traditional technique
Digital technique
L1
L1
L2
L3
L2
L3
∆I
∆I
∆I
Galvanically connected circuits must only be
earthed once!
Different CT ratios need to be adapted by auxiliary
CTs!
Differential Protection Symposium
∆I
CT circuits of digital relays are
segregated and must each be earthed !
Digital relays have integrated
numerical ratio adaptation !
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 7
Generator and transformer differential protection
L1
L2
L3
L1
L2
L3
∆I
∆I
∆I
Differential Protection Symposium
Yd5
Matching
transformer
Belo Horizonte November 2005
∆I
∆I
∆I
G. Ziegler, 10/2005
page 8
Transformer differential protection
Yd5
L1
L2
L3
Matching
transformer
Differential Protection Symposium
∆I
∆I
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 9
Current transformer:
Principle, transformation ratio, polarity
i1
i2
i1
w1
u1
i2
1
Φ
u2
i1 ⋅ w1 = i2 ⋅ w2
Function principle
i1
u2
u1 u 2
=
w1 w2
2
w2
u1
Polarity marks
P1
P2
i2
i1
u1
i2
u2
S1
Equivalent electrical circuit
Differential Protection Symposium
S2
Designation of CT terminals
according to IEC 60044-1
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 10
Busbar differential protection
Digital protection 7SS52
Analog protection 7SS10/11/13
7SS600 with digital measuring relay (∆I)
∆I Central Unit
2
4
3
Optic
fibres
0
∆I
BU
BU
BU
BU
0
G
M
Grid
infeed
BU: bay unit
G
Load
Differential Protection Symposium
M
Grid
infeed
Belo Horizonte November 2005
Load
G. Ziegler, 10/2005
page 11
Line differential protection
50/60 Hz current comparison
through wire connection
I1
Phasor with digital communication
via OF, microwave or pilot wires
I1
I2
I2
∆I
DI
∆I
∆I
∆I
I1
I2
dedicated O.F.
up to about 35 km
Other
services
PCM
MUX
PCM
MUX
Other
services
O.F. or Microwave
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 12
Two wire (pilot wire) line differential protection
Voltage comparison principle
I2
I1
Grid
G
∆I
RS
U1
∆U
∆I
U2
RS
3
3
∆I
Differential Protection Symposium
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 13
False differential currents during load or external faults
I∆ / In
te
ri
st
ic
4
ac
∆IGF = total false current
re
la
y
ch
ar
3
2
∆IWF = CT false current
∆IAF = Inaccurate adaptation (CT ratios, tap
changer)
1
∆IWF = Transformer magnetising current
1
10
Differential Protection Symposium
15
ID / In
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 14
Percentage differential relay
A = I1− I2
operate
stabilise
B
S = I1+ I2
I1
Basicpick-up value (B)
I2
I1+ I2
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 15
Differential protection: analog measuring circuit
Rectifier bridge comparator with moving coil relay
I2
I1
protection
object
i1
Fault characteristic
(single side infeed)
i2
ΔI =
W2
W1
W3
k1 ⋅ I Re s
k1 ⋅ I Re s
I1 − I 2
Relay characteristic
W1
k 2 ⋅ I Op
= k1 ⋅ (I 1 − I 2 )
k1 =
I1 + I 2 > k ⋅ I1 − I 2
W4
w1
w2
Differential Protection Symposium
k=
k2 ⋅ I Op
Σ I = I1 + I 2
= k2 ⋅ (I1 + I 2 )
k2 =
w3
w4
k1
k2
with digital relays: ΣI = I1 + I 2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 16
Multi-end differential protection:
Analog measuring principle
1
n
2
Iop = I1 + I 2 + .... + I n = Σ I
Differential Protection Symposium
k ⋅ I Re s
I Op
I Res = I1 + I 2 + .... + I n = Σ I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 17
Optimised relay characteristic
G
R
2000A
Ideal fault characteristic
∆Ι
IOp =
I1 − I 2
internal
fault
300A
F
Load
RL
IOp = 2000 A
relay characteristic
IS = 2600 A
I F1
I F2
G
G
CT saturation
∆Ι
I Res = I1 + I 2
Healthy
protection object
δ
I Op = 2 ⋅ I F ⋅ cos
Differential Protection Symposium
I Re s = 2 ⋅ I F
δ
2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 18
Digital differential protection: Relay characteristic
IOp
Positive current polarity
k2
∆I
k1
Id >
IR0
I Op = ΣI = I1 + I 2
Settings:
I Res = Σ I = I1 + I 2
• slope k1
IRes
• Pick-up value Id >
• slope k2 with footing point IR0
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 19
∆I / ΣI und I1 / I2 diagram
ΔI =
I1 + I 2
I1
Internal
faults
IS0 1+ k
+
⋅B
2 2⋅k
k [% / 100 ]
slope
B
IS0
IS0 1− k
⋅B
+
2 2⋅k
Σ I = I1 + I 2
(
1
I1 + I 2 > k I1 + I 2 − I S 0
2
I1 + I 2 > B
Differential Protection Symposium
)
IS0
2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 20
I2
Polar diagram of differential protection
I1 + I 2 > k ⋅ I1 − I 2
β-Plane (remote/local current)
I
1+ 2
1+β
I1
> k or
>k
I2
1- β
1−
I1
I 
Im  2 
I1 
I
β= 2
I1
I2
Protection
object
∆Ι
I
with β = 2
I1
−
I1
1+ k
1− k
+1
-1
(k=0,5)
−
1− k
1+ k
I 
Re 2 
 I1 
Restraint area
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 21
Polar diagram of digital differential protection:
Basic pick-up value B > 0
90
I 2 jϕ
e
I1
120
I1 + I 2 > k ⋅ ( I1 + I 2 ) + B
or

I2
> k ⋅ 1 +
1+

I1

I2
I1
 B
+
 I
1

60
ϕ
150
30
180
0
5
210
10
330
300
240
270
B/I1= 0,3
a1(Φ): k=0,3
a2(Φ): k=0,6
a3(Φ): k=0,8
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 22
Mixing transformer of composed current differential protection
IL1
IL2
IL3
IL1
Composed current during
symmetrical 3-ph fault or load
IM
2
IL3
7SD503: IM = 100 mA
7SS600: IM = 100 mA
7SD502: IM = 20 mA
1
IE
3
Mixing
transformer
IM =
IL3
1
⋅ 3 ⋅ I Ph −3
w
2 ·IL1
IL3
IL1
I M = 2 ⋅ I L1 + 1 ⋅ I L3 + 3 ⋅ I E
IL3
IL2
Differential Protection Symposium
= 5 ⋅ I L1 + 3 ⋅ I L2 + 4 ⋅ I L3
⇒ composed current (vector sum)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 23
Mixing transformer:
Pickup sensitivity of standard connection (IM= 2IL1+IL3+3IE )
Fault type
Per unit composed current
related to 3-phase
symmetrical current
Composed current
L1-E
IML1-E = 5 IL1
IL2 = IL3 = 0
IML1-E / IM = 5 / √ 3 = 2.9
L2-E
IML2-E = 3 IL2
IL1 = IL3 = 0
IML2-E / IM = 3 / √3 = 1.73
L3-E
IML3-E = 4 IL3
IL1 = IL2 = 0
IML3-E / IM = 4 / √3 = 2.3
L1-L2
IML12 = 5 I L1 + 3 I L2
IL3 = 0
IML12 / IM = 2 / √3 = 1.15
L2-L3
IML23 = 3 I L2 + 4 I L3
IL1 = 0
IML23 / IM = 1 / √3 = 0.58
L1-L3
IML13 = 5 I L1 + 4 I L3
IL2 = 0
IML13 / IM = 1 / √3 = 0.58
L1-L2-L3
IML123 = 5 IL1 + 3IL2 + 4IL3
|IL1| = |I L2| = |I L3|
IML123 / IM = √3 / √3 = 1
Differential Protection Symposium
Belo Horizonte November 2005
Highest
sensitivity
G. Ziegler, 10/2005
page 24
Composed current differential protection
Behaviour during cross country fault (isolated/compensated network)
∆I
A
B
L1
L2
L3
IF
L1 internal und L3 external:
IM-A= 5⋅IF - 4⋅IF = 1⋅IF und IM-B= + 4⋅IF
∆I = |IM-A + IM-B| = 5IF und ΣI = |IM-A| + |IM-B| = 5⋅IF
∆I/ΣI = 5/5 = 1.0
Tripping
L2 internal, L3 external
IM-A= - 1⋅IF und IM-B= + 4⋅IF
∆I = |IM-A + IM-B| = 3 ⋅IF und ΣI = |IM-A| + |IM-B| = 5⋅IF
∆I/ΣI = 3/5 = 0.6
Tripping if k-setting < 0.6
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 25
Composed current differential protection
Through current stabilisation with unsymmetrical earthing conditions
2
1
3
3
2
IM2=2·IL1 + 1·IL3+ 3 ·IE
=2·IF + 1 ·IF+ 3·3IF = +12 ·IF
IM1=2·IL1 + 1·IL3 + 3 ·IE
=2 ·(–IF) + 1 ·(–IF) + 3·0= –3·IF
IOp=| IM1 + IM2 | = 9 ·IF
IRes=|IM1| +|IM2| = 15 ·IF
1
k=9/15 = 0.6
IOp
Fault L2-E
k=0.5
Faults in other phases:
Fault L1-E: IOp = (3+12) ·IF = 15 ·IF,
IRes= (3+12) ·IF = 15 ·IF,
k=1
Fault L3-E: IOp = (0+12) ·IF = 12 ·IF,
IRes= (0+12) ·IF = 12 ·IF,
k=1
Differential Protection Symposium
IRes
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 26
High impedance differential protection: Principle
Behaviour during external fault
with CT saturation
with ideal current transformers
ISC
RCT
RCT
ISC
ISC
ISC
UR
ECT −1 = (RL + RCT ) ⋅ iSC
ECT −1 = 2 ⋅ (RL + RCT ) ⋅ iSC
UR = 0
ECT −2 = (RL + RCT ) ⋅ iSC
Differential Protection Symposium
U R = (RL + RCT ) ⋅ iSC
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 27
High impedance differential protection:
Calculation example (busbar protection)
Given:
n = 8 feeders
rCT = 600/1 A
UKN = 500 V
RCT = 4 Ohm
ImR = 30 mA (at relay pick-up value)
Pick-up sensitivity:
(
600
⋅ (0.02 + 0.05 + 8 ⋅ 0.03)
1
I F − min = 186 A ⋅ (31% )
Differential Protection Symposium
RR = 10 kOhm
Ivar = 50 mA (at relay pick-up value)
Stability:
I F −min = rCT ⋅ I R − pick −up + IVar + n ⋅ I mR
I F − min =
RL= 3 Ohm (max.)
IR-pick-up.= 20 mA (fixed value)
)
I F −through − max < rCT ⋅
I F −throuh − max <
RR
⋅ I R − pick −up
RL + RSW
600 10,000
⋅
⋅ 0.02
1
3+4
I F −through − max < 17kA = 28 ⋅ I n
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 28
Digital Differential Protection
Measuring Technique
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 28
Merz and Price differential protection
Patent dated 1904
a: feeder, b: generator, c: substation, d: primary winding of CT, e: secondary winding of CT, f: earth or
return conductor, g: pilot wire, h: relay windings, i: circuit breakers, k,l: movable and fixed relay
contacts, m: circuit, n: battery, o: electromagnetic device with armature p.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 29
Electro-mechanical differential protection
based on induction relay
I2
I1
Schutzobjekt
i1
Differential Protection Symposium
∆i
i2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 30
Electro-mechanical differential protection
Rectifier bridge comparator with moving coil relay
I1
Protection
object
i1
I Re s
ΔI = I
Op
−I
i2
IOp
∆I
I Re s = k ⋅ (I 1 − I 2 )
I2
I Op = I 1 + I 2
+
Re s
Differential Protection Symposium
N
S
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 31
Differential protection
Analog static measuring circuit
I1
I2
Protection
object
i1
I Re s = k ⋅ (I 1 − I 2 )
i2
I Re s ⋅ R S
RS
V1
RS
I Op = I 1 + I 2
V3
V2
I Op ⋅ R S
URef
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 32
Digital differential protection
Measuring value acquisition and processing
0.67 ms (18 degr. el.)
MI
1.2 kHz
clock
Filter
1
IL1
IL2
IL3
IE
UL1
UL2
UL3
UE
a.s.o.
Processor system
S&H
CPU
A
D
RAM
MUX
ROM
n
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 33
Digital protection:
Measurement based on momentary values
I=
IRMS
0
I
n
∆Tsamp. corresponds to ∆ϕ ( 60Hz: 0.67 ms = 18O el.)
I=
n −1
cos (
⋅ ∆ϕ )
2
Iˆ
I RMS =
2
Iˆ =
Differential Protection Symposium
when n sampled values exceed the
pick-up limit I=
f
∆ϕ = ω ⋅ ∆Tsamp. = N ⋅ 360O
fA
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 34
Digital differential protection:
Measurement based on momentary values
4
3
∆I
5
5
6
2
4
7
3
2
8
1
∆I>
9
10
0
1
6
trip
7
8
restrain
9
0
10
18O
= 1 ms (50 Hz)
= 0.67 ms (60 Hz)
ΣI
IA
IB
∆I
∆I
Operating quantity :
∆I = I A + I B
Restraining quantity : ΣI = I A + I B
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 35
Discrete Fourier-Transformation (Principle)
sin 2π ⋅i
n
0 1 2 . .
i( k −n+i )
.
Correlate:
Multiply samples and
add for one cycle
n
Correlate IS(k)
i
k-n
I (k) = I S(k) + j ⋅ I C(k)
k
Correlate IC(k)
I (k )
j
IC(k)
cos 2π ⋅i
n
Differential Protection Symposium
Belo Horizonte November 2005
ϕ
IS(k)
G. Ziegler, 10/2005
page 36
Discrete Fourier-Transformation (calculation formulae)
i
0
i1 i2 i
3
iN
∆t
N


I = 2  ∑ sin(ω ⋅n⋅ Δt )⋅in
S N  n=1

N
i

i N-1
I = 2  O + N + ∑ cos(ω ⋅n ⋅ Δt)⋅in
C N  2 2 n=1

N-1
0 1 2 3 ....
n
0 1 2 3 ...
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 37
Orthogonal components of a current phasor
dependent on the position of the data window
Data window
Φ = ωt
IS =
Φ
1
⋅ ∫ I (ω ⋅ t ) ⋅ sin ωt ⋅ dt
2π Φ −360
IC =
Φ
1
⋅ ∫ I (ω ⋅ t ) ⋅ cos ωt ⋅ dt
2π Φ −360
I Φ = I S + j ⋅ IC
I0
= 1+ j ⋅ 0
I
O
O
O
I30
3
1
= + j⋅
I
2
2
O
I 60 1
3
= + j⋅
I
2
2
O
jIC
I
IS
ωt
t=0
I90
= 0 + j ⋅1
I
O
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 38
Transfer function of a one cycle Fourier-filter
Hrel
1,0
0,75
0,5
0,25
0
0
1
Differential Protection Symposium
2
3
4
5
6
f/fn
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 39
Digital protection
Fast current phasor estimation
N
k-N
i(t)
k
Data window
i(t) = A ⋅ sin( ωt ) +
Task:
Method:
Delta =

t

− 

B ⋅  cos( ωt) - e τ  + C ⋅ cos( ωt)






Estimation of the coefficients A, B, C on basis of
measured currents and voltages
Gauß‘s Minimization of error squares:
Delta = quality value
k
= sampling number
k
N
= length of data window
2
∑ i(n ⋅ ∆T) - f (n)
MIN
n
= variable
n=k-N
∆T
= sampling interval
sampled values
(
)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 40
Differential protection with phasors (principle)
A
∆I
B
IAC , IAS
IBC , IBS
∆I
∆I
trip
∆I>
restraint
j·IAS
ΣI
Operating quantity :
∆I = I A + I B
Restrainin g quantity : Σ I = I A + I B
IBC
IAC
j·IBS
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 41
Digital line differential protection
Synchronisation of phasors (ping-pong time alignment)
A
tA1
tA2
∆I
∆I
curre
n
phas t
o rs
α
...
tPT1
tAR
tA5
tA1
tPT2
tV
tB3 tA1
tBR
tB2
α=
tB3
nt
curre
.
.
.
rs
ph aso
Differential Protection Symposium
t B3 - t A3
⋅ 360 °
TP
tB4
Signal transmission time: t PT1 = t PT2 =
Sampling instant:
IB( tB3 )
tB1
tD
tA3
tA4
IB( tA3 )
B
1
(t A1 - t AR - t D )
2
t B3 = t A3 - t PT2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 42
Split path data transmission
Impact of unsymmetrical propagation time
I1
I2
∆I
∆I
180o
∆T[ms ]⋅
α
10ms
∆I = I ⋅ sin = I ⋅ sin
2
2
α
I2
I1
Example:
Transmit channel time 3 ms
Receive channel time 4.2 ms
→ time difference ∆ = 1.2 ms
180o
1.2ms ⋅
10ms = I ⋅ 0.19
∆I = I ⋅ sin
2
∆I
α/2
∆I = 19%!
To keep the false differential current below about 2 to 5%, the
propagation time difference should not exceed about 0.1 to 0.25 ms!
Otherwise:
→ more insensitive relay setting
→ or GPS synchronisation
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 43
Synchronisation of Differential relays via GPS
Line end 1
Line end 2
GPS-Antenna
RS232
GPS-Antenna
GPS
RS232
UH
DC
GPS-Empfänger
supply
DCF-SIM
A
B
LWL
LWL IRIG-B
24V
GPS
GPS-Empfänger Hopf DC
supply
DCF-SIM
A
B
LWL
LWL IRIG-B
24V
IRIG-B Telegram
Sec. impulse (highly accurate)
LWL
K1
LWL
BE2
K2
IRIG-B Telegram
Sec. impulse (highly accurate)
LWL
K2
K1
7XV5654 Sync-Trans.
K1 X1 K2
K2
LWL
BE2
K2
K2
7XV5654 Sync-Trans.
K1 X1 K2
K2
+ - 24V + 1 3
8 4
+ - 24V + 1 3
8 4
Y-cable 7XV5105
1 3 8 4
RUN
7SD52
SIEMENS
ERR OR
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
to max.
Differential Protection Symposium
SIEMENS
ERR OR
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
7SD52
6
V4
SIPROTEC
RUN
Max450.1A
Max450.1A
Max450.1A
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
1 3 8 4
V4
SIPROTEC
RUN
Max450.1A
Max450.1A
Max450.1A
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
1
1 3 8 4
V4
SIPROTEC
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
Y-cable 7XV5105
1 3 8 4
V4
SIEMENS
UH
SIEMENS
ERR OR
SIPROTEC
RUN
Max450.1A
Max450.1A
Max450.1A
L1 402,1A
L2 402,1A
L3 402,1A
E
00.0A
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
ERR OR
Max450.1A
Max450.1A
Max450.1A
Anr. L1
Anr. L2
Anr. L3
Anr. Erde
Automat
1
t0 max.
Belo Horizonte November 2005
6
G. Ziegler, 10/2005
page 44
Devices for GPS time synchronisation
n GPS receiver with 2 optical outputs
(7XV5664-0AA00).
Output for IRIB-B telegram
and output for second/
minute pulse
n Galvanic separation between the
receiver and the tranceiver
7XV5654
n Optic/electric signal
conversion in the tranceiver
n Distribution of the electrical
signals via Y-bus cable to
port A of the relays (telegram)
n Electronic contact for the
minute pulse in case of
synchronisation through binary
input with battery voltage
Differential Protection Symposium
Outdoor antenna
FG4490G10 for GPS
GPS receiver
7XV5664
Tranceiver
7XV5654
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 45
Additional components for SICAM SAS
GPS-System
•
•
•
•
Differential Protection Symposium
24 satellites move in a height of
20 000km on 6 different paths
Transmission frequency 1,57542GHz
For a continuous time reception min. 4
satellites is necessary
High accuracy : 1 usec
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 46
Operating characteristic of digital differential relays
I∆
=|I1+ I2|
I1
I2
b%
∆I
I∆>
a%
I∑ b
Differential Protection Symposium
I∑ = |I1|+ |I2|
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 47
Differential protection
CT saturation with internal and external faults
∆I
Protection object
I2
I1
Internal fault
External fault
I1
I2
Σ I= |I1| + |I2|
∆I=|I1 +I2|
t=0
t=10
Differential Protection Symposium
t=20 ms
t=0
t=10
t=20 ms
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 48
Saturation detector:
Locus of ∆I/ΣI for external faults without and with CT saturation
i Op( n ) = i1( n ) + i 2( n )
6'
7'
saturation
3'
re s
i 2( n )
in
tra
n
8'
External fault
5'
4' with CT
i1( n )
e
rat
e
op
i1( n ) + i 2( n )
9'
0
10
External fault
(ideal CTs)
1
2
3
4 5
9
8
7
6
i Re s ( n ) = i1(n ) + i 2( n )
Differential Protection Symposium
i1(n ) + i 2( n )
n=0
n=10
Belo Horizonte November 2005
n=20
G. Ziegler, 10/2005
page 49
Differential current caused by transient CT saturation (ext. fault)
with operating and restraint current of busbar protection 7SS5
I1
100
50
I2
0
50
IRes.= |I1| + |I2|
IOp=|I1 +I2|
Differential current appears only every second half wave!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 50
Tripping logic of digital busbar protection 7SS600/7SS5
with saturation detector (simplified)
di Re s
> k s [A / ms]
dt
i Op > iset
i Op > k ⋅ i Re s
A
N
D
A
N
D
A
N
D
3 ms
A
N
D
Transient
blocking
Differential Protection Symposium
1-out-of-1
2 150 ms
Saturation
detected
3 ms
Trip
n=2
Adaptive restraint
A
N
D
O
R
Trip
2-out-of-2
Trip
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 51
Transformer differential protection 7UT6:
Saturation detection and automatic increase stabilisation
Internal
faults
Trip
Restrain
Area of
add-on
restraint
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 52
Transient CT saturation
causes false differential currents
IF
IF
+I1
+I2
87
I1
IF
I2
+∆I
∆I
Wave shape similar to
transformer inrush current ?
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 53
Adaptive restraint against CT errors (7SD52/61)
Detection of CT saturation
(wave shape analysis)
CT Error approximation (no-saturation)
Error
%
Load range
Fault range
fL
fF
10%
ALF‘/ALFN • IN-CT
Differential Protection Symposium
ALF’ •IN-CT
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 54
Adaptive 87 restraint (7SD52/61)
considers current CT- errors
IDiff
I1
Trip Area
Trip level
With
saturation
Block-Area
IDiff>
0
0
Current summation:
Trip level
Without
saturation
I2
External
Fault
I2
I1
Max. error (ε)
without
saturation
IDiff = │I1+ I2│
Max. error (ε)
with
saturation.
IRest
Max. error summation: IRestraint = ΣIError = IDiff> + εCT1 ·I1 + fSat· εCT2 ·I2
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 55
External fault
Increase of stabilisation after detection of saturation
Begin of saturation
∆Ι
(K1:iE = -K1:iL1)
Increase of
restraint
I∆
IRestraint
ΣΙ
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 56
Fast charge comparison supplement
speeds up phasor based line differential protection (7SD52/61)
Q2
Q1
iL1/kA
20
10
0
-10
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
t/s
-0,02
-0,01
-0,00
0,01
0,02
0,03
0,04
0,05
0,06
0,07
0,08
t/s
t/s
-20
-30
-40
iL2/kA
20
10
0
-10
Q3
t/s
-20
-30
-40
iL3/kA
20
10
0
-10
-20
-30
Diff G-AUS
Q
1/4
cycle
1 cycle data windows for phasor
comparison
•Synchronized with fault inception
¼ cycle data windows of fast charge
comparison
Differential Protection Symposium
•Released by Idiff >>
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 57
Generator, Motor and Transformer protection: Adaptive algorithms to
upgrade relay stability and dependability with CT saturation (7UT6)
Measured value
processing
i1L
i2L
Side 1
Side 2
Sampled
momentary values
iRes = | i1 | + | i2 |
iOp = i1 + i2
Mean values
IRes = Mean(iRes)
Fundamental wave
IOp = RMS(iDiff)60Hz
87 algorithm
Operating characteristic
IOp
IDiff>
IRes.
Motor start
DC component
&
Trip
IOp>
Saturation detector
For security:
Harmonic Analysis:
-2nd Harmon. Blocking
-Cross Blocking
Adaptive restraint
IOp
IDiff>
>
For dependability:
Fast tripping using sampled momentary values
ensures fast operation with very high currents before
extreme CT saturation occurs!
Differential Protection Symposium
iOp
≥1
Trip
IOp>>
IDiff>>>
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 58
Current Transformers for Differential Relaying
Requirements and Dimensioning
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 46
Equivalent current transformer circuit
I2′ = I1 ⋅
I1
jX1 R1
N1
N2
Im
P1
N1
P2
jX2
N2 U2
Ideal transformer
R2
I2
S1
Zm
Zb
S2
X1 = Primary leakage reactance
R1 = Primary winding resistance
X2 = Secondary leakage reactance
Z0 = Magnetising impedance
R2 = Secondary winding resistance
Zb = Secondary load
Note:
Normally the leakage fluxes X 1 and X2 can be neglected
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 47
Current transformer:
Phase displacement (δ) and current ratio error (ε)
w1
.
I1 w
2
w1:w2 j·X2
R2
U2
I2
I1
ZB
ε
I2
δ
I‘1=
w1
·I
w2 1
Im
I2
Em
I1
Em
R2
U2
RB
Xm
Differential Protection Symposium
Im
Im
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 48
Dimensioning of CTs for differential protection
Pi = I sec .2 × R CT
CT classes to IEC 60044-1: 5P or 10P
Specification:
300/1 A
5P10, 30 VA RCT ≤ 5 Ohm
Rated burden
(nominal power) PN
Ratio In -Prim / In -Sek.
5% accuracy
at I= n x In
Actual accuracy limit factor
in operation is higher as the CT
is normally under-burdened :
Operating ALF: ALF‘
Accuracy
limit factor ALF
Dimension criterium:
P + PN
ALF ' = ALF × i
Pi + PB
I
ALF ' ≥ SC − max × KTF
In
KTF (over-dimensioning factor) considers the single sided CT over-magnetising due to the d.c.
component in short circuit current I SC.
KTF values required in practice depend on relay type and design.
Recommendations are provided by manufacturers (see Application Guide)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 49
Current transformer, Standard for steady-state performance
IEC 60044-1 specifies the following classes:
Accuracy class
Current error
at nominal
current (In)
5P
±1%
10P
± 5%
Differential Protection Symposium
Angle error δ
at rated current
In
Total error at n x In
(rated accuracy limit)
± 60 minutes
5%
10 %
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 50
Current transformers, Standard for transient performance
IEC 60044-6 specifies four classes:
Class
Error at rated current
Ratio error
TPX
(closed iron core)
TPY
with anti-remanence
air-gap
TPZ
linear core
TPS
closed iron core
Maximum error at
rated accuracy limit
Remanence
Angle error
± 0,5 %
± 30 min
εˆ ≤ 10 %
± 1,0 %
± 30 min
εˆ ≤ 10 %
± 1,0 %
± 180 ± 18 min
εˆ ≤ 10%
(a.c. current only)
Special version for high impedance protection
(Knee point voltage, internal secondary resistance)
Differential Protection Symposium
Belo Horizonte November 2005
no limit
< 10 %
negligible
No limit
G. Ziegler, 10/2005
page 51
Definition of the CT knee-point voltage (BS and IEC)
British Standard BS3938: Class X
U2
10 %
or
IEC 60044-1 Amendment 2000/07:
Class PX
UKN
50 %
Specify:
Knee point voltage
Secondary resistance RCT
Im
I
U KN ≥ K TF ⋅ (R CT + R B − connected ) ⋅ SC − max .
I n − CT
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 52
CT specification according to ANSI C57.13
w1
I‘1= w ·I1
2
I2
Im
Em
ANSI C57.13 specifies:
RCT
RB
U2
• Secondary terminal voltage U2
at 20 times rated current (20x5=100 A) and
rated burden
• Error <10%
Example:
800/5 A, C400 (RB= 4 Ω)
U2,
Em
Resulting magnetising voltage:
E al ≈ (U ANSI + 20 ⋅ 5 ⋅ R CT )
= (20 ⋅ 5 ⋅ Z B − rated + 20 ⋅ 5 ⋅ R CT )
Im
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 53
Current transformer saturation
Steady-state saturation with a.c. current
Transient saturation with offset current
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 54
CT saturation
Currents and magnetising
IP
t
φ
saturation flux
t
IS
t
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 55
Transient CT saturation due to DC component
ISC
Short circuit current
DC flux non-saturated
ΦS
Φ
Im
Differential Protection Symposium
AC flux
Magnetising current
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 56
Course of CT-flux during off-set short-circuit current
ΙP primary current
d.c. component
i p (t) =
Φ
Total flux
t
ωTp Ts - t
Φ max
Tp
K td (t) =
=
(e
- e Ts ) + 1
ˆ
Φ
Tp - Ts
a.c.
Ktd(t)
transient
d.c. flux

− cos( ωt) 


t
ωTp Ts - t
Φ
=
(e Tp - e Ts ) - sin ωt
ˆ
Φ
a.c. Tp - Ts
t
Tp
- t
2 ⋅ I p ⋅  e Tp


Φ max
ˆ
Φ
a.c.
a.c. flux
Φ̂ a.c.
Differential Protection Symposium
t
K td − max = 1 + ωTp = 1 +
Belo Horizonte November 2005
Xp
Rp
G. Ziegler, 10/2005
page 57
Theoretical CT over-dimensioning factor KTF
KTF
∞ (KTF ≈1+ωTN)
60
5000
Closed iron core
50
1000
40
TS
 T N  TS − TN
KTF = 1+ ωTS 
 TS 
TS [ms]
500
30
250
20
100
Linear core
10
TN = network time constant
(short-circuit time constant)
50
100
150
200
TN [ms]
TS = CT secondary time constant
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 58
CT with closed iron core,
Over-dimensioning factor KTF‘ for specified time to saturation (tM)
20
tM → ∞
tM
15
2.5 cycles
K‘td
2.0 cycles
10
1.5 cycles
8
1.0 cycles
 −tTM 
Ktd' = 1+ ωTp ⋅ 1− e p 




5
0.5 cycles
0
20
40
60
80
100
Tp (ms)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 59
Transient dimensioning factor K’’td for short time to saturation tM
t

− M

T
K td − Envelop = 1 + ωTp ⋅ 1 − e p


15
t

− M

'
K 'td
(Θ, t M ) = ω ⋅ Tp ⋅ cos θ ⋅ 1 − e Tp









 + sin Θ − sin (ωt M + Θ )


3
15
2.5
Ktd( 0 , tM)
10
Ktd( 80 , tM)
2
1.5
Ktd( 90 , tM)
Ktd_Envelop( tM)
5
1
0.5
0
0
0
0
20
40
60
tM
Differential Protection Symposium
80
100
100
0
0
0
1
2
3
4
Belo Horizonte November 2005
5 6
tM
7
8
9 10
10
G. Ziegler, 10/2005
page 60
CT over-dimensioning factor KTF (tM,TN)
in the case of short time to saturation (tM)
KTF
4
tM
Θ (tM,TN)
10 ms
3.5
(el. degree)
180
160
140
3
8 ms
2.5
120
100
2
6 ms
1.5
tM
10 ms
8 ms
6 ms
4 ms
2 ms
80
60
1
4 ms
0.5
40
20
2 ms
0
0
20
40
60
80
100
0
0
20
40
80
100
TN in ms
TN in ms
Differential Protection Symposium
60
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 61
Current transformer
Magnetising and de-magnetising
ΙP
B
t
B
BMax
BR
BMax
BR
Ιm
t
Differential Protection Symposium
Belo Horizonte November 2005
Ιm
G. Ziegler, 10/2005
page 62
Current transformer
Course of flux in the case of non-successful auto-reclosure
B
t F1 = duration of 1st fault
Bmax
t DT dead time
t F2 =duration of 2nd fault
t
tF1
tDT
tF2
tF1 
tDT + tF2 
tF2 
tF1
tF2

−
−
−
−
−
Bmax  ω ⋅ TN ⋅TS

 ω ⋅ TN ⋅ TS

TS
= 1 +
(e TN − e TS )  ⋅ e
(e TN − e T S ) 
+ 1 +
TN − TS
TN − T S
Bˆ ~








Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 63
Current transformer
Magnetising curve and point of remanence
I
II
III
B
up to about 80%
< 10%
negligible
H = im ⋅ w
I: closed iron core (TPX)
II: core with anti-remanence air-gaps (TPY)
III: Linearised core (TPZ)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 64
Current transformers TPX und TPY
Course of the flux with non-successful auto-reclosure
BR
BR
tF1
tDT
Differential Protection Symposium
tF2
closed iron core (TPX)
core with antiremanence air-gaps (TPY)
t
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 65
Current transformer with linear core (TPZ),
Course of the flux with non-successful auto-reclosure
ΙP
t
ΙS
B
Ιm
t
tF1
Differential Protection Symposium
tDT
tF2
Belo Horizonte November 2005
t
G. Ziegler, 10/2005
page 66
Dimensioning of CTs for protection application
Rated CT burden:
PN
Internal CT burden: Pi=Ri ⋅ I2N2
Pi + P N
Ri + RN
ALF' = ALF ⋅
= n⋅
Pi + PB
Ri + RB
Actually connected
burden :
P + PB
Ri + RB
= ALF'⋅
ALF = ALF' ⋅ i
Pi + PN
Ri + RN
I
with ALF ' ≥ K OD ⋅ SC
IN
with:
Theory:
No saturation for
the specified time tM:
K OD ≥ KTF ⋅ K Re m
K Re m = 1 +
% remanence
100
Differential Protection Symposium
RB=RL+RR= total burden resistance
RL= resistance of connecting cable
RR= relay burden resistance
No saturation during
total fault duration:
Where KOD is the total
over-dimensioning factor:
Practice:
K OD = KTF
PB= RB ⋅ I2N2
BMax
XN
= 1 + ω TN = 1 +
RN
Bˆ ~
tM
tM 

−
−
ω
⋅
T
N ⋅ TS
(e T N − e T S 
K ' 'TF = 1 +
TN − TS




K' TF =
Remanence only considered in extra high
voltage systems (EHV)
KTF-values acc. to relay manufacturers‘ guides
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 67
Practical CT dimensioning
using dimensioning factors Ktd (required minimum time to saturation)
IEC 60044-1 and 60044-6
ANSI C57.13
300/5 A, 5P20, VA (Rb= 1.0 Ω),
Rct= 0.15 Ω
300/5 A, C100 (Rb= 1 Ω)
E al ≈ (U ANSI + 20 ⋅ 5 ⋅ Rct )
= (20 ⋅ 5 ⋅ Z b − rated + 20 ⋅ 5 ⋅ Rct )
ALF' ≥ K SSC ⋅ K td
ALF' =
R ct + R b − rated
⋅ ALF
R ct + R b − connected
20 ≥ K td ⋅
I
R + R b − connected
ALF ≥ K td ⋅ F − max ⋅ ct
I pn
R ct + R b − rated
Transient dim. factor: Ktd
BS 3839 (IEC: 60044-1 addendum)
I
E al = F − max ⋅ K td ⋅ (R ct + R b − con. ) ⋅ Isn − CT
I pn
U KN ≈ (0.8...0.85) ⋅ E al
Differential Protection Symposium
I F − max R ct + R b − connected
⋅
I pn
R ct + R b − rated
No saturation:
1+X/R =1+ω·Tp
Differential relays:
1 (87BB: 0.5)
Distance relays:
2 to 4 close-in faults
5 to 10 zone end
faults
O/C relays: I>> ALF‘ > (I>>set / In)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 68
Coordination of CTs and digital relays
Summary
ü Digital relays use intelligent algorithms and are therefore highly
tolerant against CT saturation.
ü In particular differential relays allow short time to saturation
of ¼ cycle and below.
ü Determination of transient dimensioning factors for short time to saturation
must consider the real flux course after fault inception.
ü With time to saturation < 10 ms, the critical point on wave of fault inception
is not close to voltage zero-crossing (fully offset current), but
varies and is closer to voltage maximum (a.c. current).
ü CT dimensioning is normally based on relay specific Ktd factors provided by
manufacturers
ü In practice, fully offset s.c. current has been assumed while remanence has
been widely neglected for CT dimensioning.
ü A new dimensioning factor is discussed in CIGRE WG B5.02,
composed of more probable transient and remanence factors.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 69
CT dimensioning for differential protection (1)
1. Calculation of fault currents
110/20 kV
F1 40 MVA
110 kV, 3 GVA
uT=12%
F2
OH-line:
l = 8 km,
zL‘= 0,4 Ω/km
F3
Net
300/1A
7SD61
7UT61
Impedances related to 20 kV:
Impedances related to 110 kV:
Transf. :
∆ IL
∆ IL
∆ IT
Net :
200/1A
200/1A
1200/1A
F4
U N 2  kV 2 


110 2
ZN =
=
= 4.03 Ω
S SC ' ' [MVA ] 3000
Net :
U N 2  kV 2 

 uT [% ] 110 2 12 %
ZT =
⋅
=
⋅
= 36.3 Ω
PN -T [MVA ] 100
40 100
Transf. :
U N 2  kV 2 


20 2
ZN =
=
= 0.13 Ω
SSC ' ' [MVA ] 3000
U N 2  kV 2 

 uT [% ] 20 2 12 %
ZT=
⋅
=
⋅
= 1.2 Ω
PN - T [MVA ] 100
40 100
Line : Z L = l[km ] ⋅ z L ' [Ω/km ] = 8 ⋅ 0,4 = 3,2 Ω
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 70
CT dimensioning for differential protection (2)
F1
I F1 =
1.1 ⋅ U N / 3 1.1 ⋅ 110kV/ 3
=
= 17.3 kA
ZN
4.03 Ω
F2
I F2 =
1.1 ⋅ U N / 3 1,1 ⋅ 110kV/ 3
=
= 1.73 kA
Z N + ZT
4.03 Ω + 36.3 Ω
F3 I F3 =
F4
I F4 =
1.1 ⋅ U N / 3 1.1 ⋅ 20kV/ 3
=
= 9.55 kA
Z N + ZT
0.13Ω + 1.2Ω
1.1 ⋅ U N / 3
1,1 ⋅ 20kV/ 3
=
= 2.8 kA
Z N + Z T + Z L 0.13Ω + 1.2Ω + 3.2Ω
Dimensioning of the 110 kV CTs for the transformer differential protection:
Manufacturer recommends for relay 7UT61:
1) Saturation free time ≥ 4ms for internal faults
2) Over-dimensioning factor KTF ≥ 1,2
for through flowing currents (external faults)
The saturation free time of 3 ms
corresponds to KTF≥ 0,75
See diagram, page 59
Criterion 1) therefore reads:
I
17300
ALF' ≥ K TF ⋅ F1 = 0,75 ⋅
= 43
IN
300
For criterion 2) we get:
I
1730
ALF' ≥ K TF ⋅ F2 = 1,2 ⋅
=7
IN
300
The 110 kV CTs must be dimensioned according to criterion 1).
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 71
CT dimensioning for differential protection (3)
We try to use a CT type: 300/1, 10 VA, 5P?, internal burden 2 VA.
ALF ≥
Pi + Poperation
2 + 2.5
⋅ ALF ' =
⋅ 43 = 16.1 (Connected burden estimated to about 2.5 VA)
Pi + Prated
2 + 10
Chosen, with a security margin : 300 /1 A, 5P20, 10 VA, R2≤ 2 Ohm (Pi ≤ 2VA)
Specification of the CTs at the 20 kV side of the transformer:
It is good relaying practice to choose the same dimensioning as for the CTs on the 110 kV side:
1200/1, 10 VA, 5P20, R2≤ 2 Ohm (Pi ≤ 2VA)
Dimensioning of the 20 kV CTs for line protection:
For relay 7SD61, it is required:
The saturation free time of 3 ms
corresponds to KTF≥ 0.5
See diagram, page 59
Criterion 1‘) therefore reads:
I
9550
ALF' ≥ K TF ⋅ F3 = 0.5 ⋅
= 24
IN
200
1‘) Saturation free time ≥ 3ms for internal faults
2‘) Over-dimensioning factor KTF ≥ 1.2
for through flowing currents (external faults)
For criterion 2‘) we get:
I
2800
ALF' ≥ KTF ⋅ F4 = 1.2 ⋅
= 16 .8
IN
200
The 20 kV line CTs must be dimensioned according to criterion 1‘).
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 72
CT dimensioning for differential protection (4)
For the 20 kV line we have considered the CT type: 200/5 A, 5 VA, 5P?, internal burden ca. 1 VA
Pi + Poperation
1+1
⋅ ALF ' =
⋅ 24 = 8
ALF ≥
Pi + Prated
1+ 5
(Connected burden about 1 VA)
Specification of line CTs:
We choose the next higher standard accuracy limit factor ALF=10 :
Herewith, we can specify: CT Type TPX, 200/5 A, 5 VA, 5P10, R2≤ 0.04 Ohm ( Pi≤ 1 VA)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 73
Interposing CTs, Basic versions
w1
i1
separate winding connection
i2
i1
w2
wa
i2
wb
i1 -i2
Relay
i2 =
w1
⋅ i1
w2
auto-transformer connection
Relay
i2 =
wb
⋅ i1
wa + wb
No galvanic separation!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 74
Interposing CTs, Example
1A
W1=
21 turns
600/1 A
1A
600/1 A
Differential Protection Symposium
1,5 A
W2=
14 turns
1A
Wa=16
turns
0,5 A
Wb=32
turns
RB
1,5 A
RB
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 75
Interposing CTs in Y-∆-connection
Yd5
-I1c
I1a
I2a-c
I1b
I2b-a
I2c-b
I1c
w1
I2a
I1a
-I1b
I2c
I1b
I1c
w1 = w2
w2
I1 =
Differential Protection Symposium
150O
I2b
I2b
I2c
-I1a
I2a
o
1
w
⋅ I 2 ⋅ 2 ⋅ e j ⋅( n⋅30 )
w1
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 76
False operation during external fault
of transformer differential protection without zero-sequence current filter
L1
L2
L3
∆I
Differential Protection Symposium
∆
I
∆I
∆I>0 without delta winding!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 77
Zero-sequence current filter
I1a
I3a
I2a
I1b
I3b
I2b
I1c
I3c
I2c
I 1a ⋅ w1 + I 2a ⋅ ww2 + I 3a ⋅ w3 = 0
I 1b ⋅ w1 + I 2b ⋅ ww2 + I 3b ⋅ w3 = 0
I 1c ⋅ w1 + I 2c ⋅ ww2 + I 3c ⋅ w3 = 0
I 3a = I 3b = I 3c
I 2a + I 2b + I 2c = 0
Differential Protection Symposium
Relay
I
w I +I +I
I 3a = I 3b = I 3c = 1 ⋅ 1a 1b 1c = E
w3
3
3
I +I +I 
w 
I 2a = 1  I 1a − 1a 1b 1c 

w2 
3

I 1a + I 1b + I 1c 
w1 

I 2b =
I −

3
w2  1b

I +I +I 
w 
I 2c = 1  I 1c − 1a 1b 1c 

3
w2 

Belo Horizonte November 2005
G. Ziegler, 10/2005
page 78
Biasing of transformer differential protection during external earth fault
with zero-sequence current filter (closed delta winding)
L1
L2
L3
With delta winding: ∆I=0 !
Differential Protection Symposium
∆I
∆
I
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 79
Current matching with interposing CTs (1)
Calculation example
110 kV ±16%
L1
75 / 1 A
Yd5
6.3 kV
53.9A
915A
1200 / 5 A
L2
L3
0.719A
3.81A
∆I
3,81
= 2,20
3
Differential Protection Symposium
∆I
∆I
In-Relay = 5A
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 80
Current matching with interposing CTs (2)
Calculation example
Current transformation ratio:
We take through flowing rated current as reference:
:
110kV-side:
Mean current value of upper and lower tap changer position:
I1 =
10,000kVA
= 45.2A
3 ⋅ (110kV + 16%
6 kV-side:
I2 =
10,000kVA
= 62.5A
3 ⋅ (110kV − 16%
I1' =
I1− mean =
45.2 + 62.5
= 53.9A
2
10.000kVA
= 915A
3 ⋅ 6.3kV
The corresponding secondary currents are:
i1 = 53 . 9 ⋅
1
= 0 . 719 A
75
and
i 2 = 915 ⋅
5
= 3.813
1200
.
The current in the star connected winding of the interposing transformer is
The current in the delta connected winding is:
i.1
i2 / 3 .
The ratio of the interposing CT must be :
w1 i 2 / 3 3.813 / 3 2.202
=
=
=
= 3.06
w2
i1
0.719
0.719
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 81
Link selectable interposing CT 4AM5170-7AA
P1
S1
i2
A B C DE
1
0,013
2
F G H I
7
0,025 0,08
S2
P2
i1
K L
M N O P Q
16
1
2
7
16
Windings
0,75
0,013
0,025
0,08
0,75
R in Ohm
2
4
14
32
2
4
14
32
U-max. in V
5
5
5
1
5
5
5
1
Rated current in A
w1 i2 / 3 3,813 / 3 2, 202
=
=
=
= 3.06
w2
i1
0,719
0,719
chosen :
w1 16 + 16 + 2 34
=
=
= 3,09
w 2 7 + 2 + 1 + 1 11
Connection and links as shown.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 82
Designation of transformer or CT vector groups (1)
Clock-wise notation according to IEC 60076-1
11
12
0
1
0
2
10
9
3
8
4
7
6
4
8
0
6
0
6
4
1
0
4
1
0
8
2
8
2
5
9
1 (13)
5
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 83
Designation of transformer or CT vector groups (2)
Clock-wise notation according to IEC 60076-1, examples
I
II
III
12
I
II
12
III
I
I
III
II
III II
HS
I
I
II
III
NS
II
12
III
11 12
I
III II
I
III
II
I
II
III
Dyn11
12
II
III
I
5
Yny0d5
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 84
Frequently used vector groups (IEC 60076-1)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 85
Finding the vector group by using the clock principle
Proceed in the following steps:
1. Starting on the high voltage winding, the phase connection terminals are
numbered with 0, 4, 8 (always 4 x 30 O= 120O phase shift).
2. The opposite end of each winding is labelled with a number incremented
by +6 relative to the phase connection (6x 30 O =180O).
3. The secondary windings are numbered the same. In this context it is
assumed that the polarity of the windings is the same in the diagram. (If in
doubt, polarity marks may also be applied.)
4. The phase connection is labelled with the average value of the
corresponding terminal designations belonging to the winding terminals
connected to this phase terminal, e.g. (6+4)/2= 5
5. The difference between the high and low voltage side terminal numbers of
same phases corresponds each with the vector group number, being Yd5 in
this case.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 86
Checking the connections of transformer differential protection
using the clock-wise notation method
Yd5
L1
L2
L3
6
0
10 4
2
0
6
0
6
5
4
10
4
10
9
5 11
8
2
8
2
1
9
3
1
7
8
6
12
6
12 11
10
4
8
10
4 3
2
8 7
2
Yd5
Differential Protection Symposium
∆I
∆I
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 87
Current distribution in Y-∆-transformer circuits
for different external fault types
3
1
3
G
G
G
3
1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 88
Checking the connections of transformer differential protection
using the arrow method (two-phase fault)
Yd5
1
3
L1
3
L2
L3
3
3
= 3
3
∆I
∆I
Differential Protection Symposium
∆I
3
Dy5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 89
Checking the connections of transformer differential protection
using the arrow method (single-phase earth fault)
Yd5
1
L1
L2
L3
∆I
∆I
Differential Protection Symposium
∆I
3
Dy5
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 90
Digital Differential Protection
Communications
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 87
Comparison protection
Absolute selectivity by using communication
IA
A
IB
B
• Directial comparison
distance protection
Exchange of YES/NO signals
(e.g. fault forward / reverse)
• Current comparison (phasors)
differential protection
Protection
Relay
Communication
samples, phasors,
binary signals
| ∆I |
Protection
Relay
IA
IB
| ∆I | = | IA - IB | > Ipick-up
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 88
Signal transmission channels for differential relaying
Pilot wires
- AC (50/60 Hz), voice frequency and digital communication (128 - kbit/s)
- for short distances (< about 20 km)
- influenced by earth short-circuit currents!
Optical fibres
- wide-band communication (n · 64 kbit/s)
- digital signal transmission (PCM)
- up to about 150 km without repeater stations
- noise proof
Digital microwave channels 2 - 10 GHz
- wide-band communication (n · 64 kbit/s)
- digital signal transmission (PCM)
- up to about 50 km (sight connection)
- dependent on weather conditions (fading)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 89
Analog pilot wire differential relaying
3
3
87L
87L
• Pilot wires are normally operated insulated form earth
• Voltage limiters (glow dischargers) connected to earth ,
as used with telephone lines, are not allowed!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 90
Relay-to-Relay pilot wires communication
New technology on existing (copper-) pilots
Traditional:
Composed current
measurement
Comparison of analogue values
Modern:
E
O
O
E
Phase
segregated
measurement
Digital data transmission
64 kbps bi-directional
4 value digital code (2B1Q)
Amplitude and phase modulation
Spectrum mid frequency: 80 kHz
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 91
Wire pilot cables
Longitudinal voltage induced by earth currents
Relay B
Relay A
G
IF
Φ
E
F1
E/2
F2
Differential Protection Symposium
A) Symmetrical
coupling along
the pilot cable
E/2
F2
F1
E
Belo Horizonte November 2005
B) Unsymmetrical
Coupling along
the pilot cable
G. Ziegler, 10/2005 page 92
Disturbance voltage caused by rise in station potential
RG STP
STP
E Ω = I SC − G ⋅ R G
PGA
RGP
Legend:
RG
STP
PGA
RGP
E
station grounding resistance
station potential
potential gradient area
remote ground potential
station potential rise against remote ground (ohmic coupled disturbance voltage )
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 93
HV insulated protection pilot cable (example)
core diameter
pilot
resistance
Core Loop
pilot
capacitance
mm
Ω/km
Ω/km
nF/km
1,4
0,8
11,9
---
--73,2
--60
test voltage (r.m.s. value)
triple pair pair to
core- coretriple
to
core
core shield
core
pair
to
triple
core
kV
kV
kV
kV
kV
2,5
8
8
8
2
2
2
Symmetry: better 10–3 (60 db) at 800/1000 Hz
better 10–4 (80 db) at 50/60 Hz
(Uq <10–4·Ul)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 94
American practice
Neutralising reactor to compensate potential rise at the station
Gas tube
Relay
neutralising
reactor
Relay
potential
gradient
potential at insulating
transformer and relay
Voltage profile at the
neutralising reactor
Differential Protection Symposium
potential of the
pilot wires
Belo Horizonte November 2005
potential of the
remote earth
G. Ziegler, 10/2005 page 95
Optic fibre (OF) Cable
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 96
Optic fibers and connectors
Multi-mode fiber (IEC 793-2)
Type 62.5 / 125 µm
for 850 and 1300 nm
Cladding
Mono-mode fiber (IEC 793-2)
Type 10/125 µm
for 1300 and 1550 nm
ST connector
Core
Coating
62,5 µm
125 µm
250 µm
Refractive index
LC connector
Differential Protection Symposium
10 µm
125 µm
250 µm
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 97
Optic fibres: Principle of light wave propagation
r
n2
n1
rL
n
A) Graded index
fibre
AA
AE
γA
t
EingangsInput
impulse
Output
impulse
impuls
Refractive index profile
r
B) Mono-mode
fibre
Geometric design
Wave propagation
n2
n1 r
L
AE
AA
n
t
t
EingangsInput impulse
impuls
Differential Protection Symposium
Belo Horizonte November 2005
Output
impulse
G. Ziegler, 10/2005 page 98
Optic attenuation of a mono-mode fibre
10,0
5,0
Attenuation
(dB/km)
Infrared
absorption
1,0
Rayleigh
dispersion
0,85
0,1
0,8
1,3
1,0
1,2
1,55
1,4
1,6
1,8
Wave length (µm)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 99
Optic fibre connections:
Coarse planning rules
Optic component:
Attenuation:
Mono-mode fibre at 1300 nm
αOFC = 0.45 dB/km
at 1550 nm
αOFC = 0.30 dB/km
at 850 nm
αOFC = 2,5 to 3,5 dB/km
at 1300 nm
αOFC = 0.7 to 1.0 dB/km
Gradient fibre
αSPL = 0.1 dB
Per splice
Per connector
Reserve
FSMA
αCON = 1.0 dB
FC
αCON = 0.5 dB
αRES = 0.1 to 0.4 dB/km
Total attenuation of the OF cable system:
αTOT = l ⋅ αOFC + n ⋅ αSPL + 2 ⋅ αCON + l ⋅ αRES
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 100
Optic Fibre signal transmission system:
Calculation example
Task:
Optic fibre signal transmission device 7VR500
Estimation of maximum reach
Given:
Device data:
Seached:
Maximum distance that can be bridged
Solution:
The cable length is: l=x⋅2 km
The number of splices is: n=x-1
The admissible system attenuation: −14− (−46)=32 dB
Therefore:
dB
dB
32dB = x ⋅ 2km ⋅ 0,45
+ ( x − 1) ⋅ 0,1dB + 2 ⋅ 0,5dB + x ⋅ 2km ⋅ 0,2
km
km
Sending power of laser diode: αS= –14 dB
Minimum reception power: αE= -46 dB
Optic wave length: 1300 nm
The optic fibre cable is shipped in sections of each 2 km.
For reserve, 0.2 dB/km have been chosen.
we get:
x=22 and l=44 km
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 101
Radio (Micro-wave) Signalling
repeater
station
terminal
station
radiolink
terminal
station
• Line-of-sight path (up to about 50 km without repeater)
• 150 MHz to 20 GHz, n times 4 kHz channels analog and n times 64 (56) kbit/s digital (PCM)
• Advantage: Independent of line short-circuit and switching disturbances
• Disadvantage: Fading and reflections during bad weather conditions
Additional pilot links necessary to sending/receiver stations
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 102
Digital communication
u Wide-band communication via optic fibre or digital microwave
u n times 64 (56) kbit/s channels
u pulse code modulation (PCM)
u transmission via dedicated channels or communication network
u access through time division multiplexers
u interface standard for synchronous data transmission:
CCITT G.703 or X.21 (wired connection)
u interface standard for asynchronous data transmission:
V.24/V.28 to CCITT or RS485 to EIA (wired connection)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 103
Function sequence of message transmission
Sending side
Message
Digital coding
Segmentation into
information blocks
wide band
transmission
Error control
Parallel-to-serial
conversion
modulation
block
synchronisation
Differential Protection Symposium
coding
base band
transmission
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 104
Structure of a remote control telegram
Start
Control
Start sign
Kind of telegram
Block limit
Transmission
cause
Identification
Information
Error check
Address
User data
Checking
Origin
Measuring
values
Check bits
Destination
Telegram length
Status
etc.
Commands
End
End sign
etc.
Information field
Block length
Transmitted frame
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 105
Digital communication
Synchronous transmission mode
• all bits follow a fixed time frame
• synchronism between sending and receiving station. (separate
clocking line or signal codes with clock regain)
• block (frame) synchronising by opening and closing flags
• suitable for high data rates
• used protocol: HDLC (high-level data link control)
• cyclic redundancy check (CRC) or frame check sequence (FCS) by
16 or 32 added check-bits (probability of non-detected telegram block
errors: 10–5 (CRC-16) or 10–10 (CRC-32))
• used for high speed teleprotection
HDLC telegram frame
format
to ISO 3309:
Opening
Flag
Address
Field
Control
Field
01111110
8 or more bits
8 or 16 bits
Differential Protection Symposium
Information Field
any length
Belo Horizonte November 2005
Frame Check
FCS
Closing
Flag
16 or 32 bits
01111110
G. Ziegler, 10/2005 page 106
Multiplexing
Frequency Multiplexing
f1
f2
Coded voice tones
300 to 4000 Hz
FC +f1+f2
M
U
X
Carrier frequency,
FC e.g. 100 kHz with PLC
M
U
X
f1
f2
FC
Time Divison Multiplexing (TDM)
125 µs
M
U
X
64 kbit/s channels
Clock
M
U
X
> 2 Mbit/s
Differential Protection Symposium
Clock
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 107
Communication through transmission networks
M
U
X
A
User /
Source
Modem
Network node
circuit / packet switching
trunk
Modem
Station
user terminal point
M
U
X
line
Transmission path
B
loop
Differential Protection Symposium
User /
Destination
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 108
Structure of a modern data communication network
622 Gbit/s
ØNetworks are plesiochronous (PDH),
synchronous (SDH) or asynchronous (ATM)
ØData terminal devices (e.g. relays) are
synchronised through the network
ØRings guarantee redundance.
ØData of different services (e.g. telephone and
protection are commonly transmitted
(time multiplexed)
ØProtection relays must be adapted to the given
network conditions (e.g. changing propagation
time due to path witching.
622 Gbit/s
POTS: Plain Old Telephone Services
ISDN: Integrated Services Digital Network
STM-n: Synchronous Transport Module level n
SMA: Synchronous Module Access
ATM: Asynchronous Transmission Mode
ISP: Internet Service Provider
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 109
Comparison of Switching Methods
Circuit Switching
Packet switching
The physically assigned channel is
established before and disconnected after
communication
Data stream is segmented to packets
POT (Plain old telephony), ISDN
Digital networks on basis of PCM with
plesiochronous digital hierarchy (PDH)
Reliable and fast transmission possible
when connection is established.
Circuit establishment requires a free
channel from A to B
Connection occupies channel also when no
data is exchanged
Deterministic data transmission (fixed data
transmission time per channel)
Differential Protection Symposium
Transmission runs connection-oriented or
connection-less
Synchronous digital hierarchy (SDH), ATM
Backbone
Cannel not occupied during whole connection
time
Channels can be used quasi-simultaneously
Data transmission by principle time is random.
SDH and ATM can provide virtual circuitswitched channels. However, split path signal
routing may however result in unsymmetrical
signal transmission times.
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 110
SDH network: Split path routing
Node
F
Node
E
Node
D
Standby
path
Node
A
tP2‘
Node
B
Relay
End 1
Differential Protection Symposium
tP1
Node
C
tP1‘
tP2
Healthy
path
Relay
End 2
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 111
Digital Transport Systems: Bundling of channels
PCM 7680
PDH Hierarchy
PCM 1920
Plesiochronous (almost synchronous)
PCM 480
PCM 120
PCM 30
M
U
X
M
U
X
M
U
X
M
U
X
M
U
X
565 Mbit/s
140 Mbit/s
32 Mbit/s
8 Mbit/s
2 Mbit/s
64 kbit/s
SDH Hierarchy
Synchronous
SMT-1
155 Mbit/s
SMT-4
622 Mbit/s
1
SMT-16
2.5 Gbit/s
1
2
1
2
2
3
3
3
4
Differential Protection Symposium
SMT-64
10 Gbit/s
1
4
4
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 112
PDH (Plesiochronous Digital Hierarchy)
Multiplexing structure:
ØBase rate 64 kbit/s (digital equivalent of analogue telephone channel)
ØEquipments may generate slightly different bit rates due to independent internal clocks
ØBit stuffing is used to bring individual signals up to the same rate prior to multiplexing
(Dummy bits are inserted at the sending side and removed at the receiving side)
ØIntermediate inserting and extracting of individual channels is not possible, but the full
multiplexing range has always to be run through.
Hierarchical level
0
1
2
3
4
Europe
64 kbit/s
2‘048 Mbit/s
8‘448 Mbit/s
34‘368 Mbit/s
139‘264 Mbit/s
Differential Protection Symposium
USA
56 kbit/s
1‘544 Mbit/s
6‘312 Mbit/s
44‘736 Mbit/s
139‘264 Mbit/s
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 113
SDH (Synchronous Digital Hierarchy)
Multiplexing structure
Ø SONET (Synchronous Optical Network) first appeared in USA (1985)
Ø ITU-T (formerly CCITT) issued B-ISDN as world wide standard (1988)
Ø All multiplexing functions operate synchronously using clocks derived from a
common source
Ø Designed to carry also future ATM
SDH
STM level
STM-1
STM-4
SZM-16
STM-64
Aggregate Rate
155,520 Mbit/s
622,080 Mbit/s
2‘488,320 Mbit/s
9‘953,280 Mbit/s
Differential Protection Symposium
SONET
OC level
STS level
Aggregate Rate
OC-1
OC-3
OC-12
OC-48
OC-192
STS-1
STS-3
STS-12
STS-48
STS-192
51,840 Mbit/s
155,520 Mbit/s
622,080 Mbit/s
2‘488,320 Mbit/s
9‘953,280 Mbit/s
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 114
ATM (Asynchronous Transfer Mode) and Broadband B-ISDN
Features of ATM:
Ø Synchronisation individually per packet
Voice Audio
Fax
Data
Video
Ø Packets carry each complete address of
destination so that each can be separately
delivered (Datagrams, here called Cells)
Ø Information stream is segmented into cells
that are 53 octets long
Ø ATM sets up a virtual switched connection
and sends data along a switched path from
source to destination
ISDN
Ø Requirements on bandwidth, bounded delay
and delay variation can be set by the user
ØSingle cells can be inserted or removed at the
nodes, as required
Ø The predominant use is for net backbones
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 115
TDM over optical fiber
Hicom
FO
MUX
>2 Mbit/s
L1-L2
21,3 KA
73,6 kW
I
O
Optic fibres in the
core of earth wires
x 64 kbit/s
V
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 116
Bit error rate (of data channels)
Bit error rate:
p=
number of faulty bits
total number of sent bits
Typical bit error rates of public services:
Telephone circuits
ca. 10 -5
Digital data networks (Germany)
ca. 10 -6 to 10-7
Coaxial cables (LAN)
ca. 10 -9
Fiber optic communication
ca. 10 -12
Utility conditions (CIGRE SC34 Report 2001):
Fiber optic communication
ca. 10 -6
Data networks (PDH, SDH, ATM) ca. 10-6
Microwave
ca. 10 -3
Requirements acc. to CIGRE report:
Protection and control
in general:
< 10-6
Function guaranteed up to
< 10 -3 however downgraded (reduced operating speed)
Line differential protection
< 10 -6 and < 10-5 during power system faults
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 117
Error detection methods: Cyclic redundancy check
01111110
Flag
01111110
Address
Control
I(x)
Data field
Check field
Flag
I(x) + R(x)
Receiver
Sender
Division
by G(x)
R(x) = CRC
error free
data block
CRC 16: G(x) = X16 + X15 + X2 + 1
binary: 1 1000 0000 0000 0101
Reduction of the block failure rate by the factor > 10 -5 against the
bit failure rate!
(CRC 32: > 10-10)
Differential Protection Symposium
Division
by G(x)
R(x) = 0
faulty
data block
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 118
Data integrity (line differential protection 7SD52/61)
Received data
Block failure rate
P = 10-5
Error detection
e.g. CRC = 32
Residual data
Block failure rate
R = 10-15
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 119
Residual error rate
Residual error rate:
R=
number of not detected faulty telegrams (data blocks)
total number of sent telegrams (data blocks)
Practical range of protection and control systems:
Time between 2 not detected errors:
T=
R < 10 -10 to 10-15
n
v⋅R
n= length of telegram (data block)
v= transmission speed in bit/s
Example:
Telegrams of n =200 bit are continuously transmitted at 64 kbit/s.
R
T
10-7
20 hours
10-10
2.3 years
10-15
230000 years
typical application
cyclic transmission (metering)
remote control and protection
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 120
Protection of a short line lines
Differential relay using direct digital relay-to-relay communication
A
B
D
7SA6
D
7SA6
Communication via direct relay-relay connection
Fibre type
optical wave
length
maximum
attenuation
permissible
distance
Multi-mode
62.5/125 µm
820 nm
16 dB
ca. 3.5 km
Monomode
9/ 125 µm
1300 nm
29 dB
ca. 60 km
9/ 125 µm
1500 nm
29 dB
ca. 100 km
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 121
Line differential relaying using digital communication
A
B
D
7SD52
D
7SD52
D
7SD52
Chain topology or
redundant ring topology
typical <1.5 km
multimode fibre
62.5/ 9/ 125 µm
C
O
Communication
network
E
X21 or
G703.1
Differential Protection Symposium
O
E
Communication
converter
X21 or
G703.1
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 122
Differential protection
with communication through data net
l Microsecond exact time keeping in the relays
Each relay has its individual time keeping
n Sent and received telegrams get microsecond accurate time stamps
n
l Special relay properties for network communication
Measurement of propagation times and automatic correction 0 - 30 ms
Detection of channel switching in the network
Unique address for each relay (1 - 65525)
to detect signal misdirection (channel cross-over of loop-back)
Measurement of channel quality (availability, error rate)
l Change of the network path -> Adaptive add-on stabilisation
Settable time difference to consider given data transmission asymmetry
l Adaptive topology recognition
Automatic recognition of connections and remote end devices
Automatic re-routing from ring to chain topology if one data connection fails
In case of multi-terminal protection, remaining relay system continues operation
if one line end is switched off and the relay is logged out for maintenance
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 123
Individual time references by synchro-phasors
Definition of a synchrosynchro-phasor:
phasor:
SynchroSynchro-phasors,
phasors, are phasors,
phasors, which are measured at different network locations by
independent devices and referred to a common time basis
Time reference
iB
iA
Ort : A
Ort : B
IM
IA
relay A
RE
IB
relay B
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 124
Phasor synchronisation between line ends
A
tA1
tA2
∆I
∆I
curre
n
phas t
o rs
tAR
tA5
B
α
...
tA1
tPT1
tB2
tBR
α=
tB3
tPT2
...
tV
tB3 tA1
nt
curre
rs
ph aso
Signal transmission time:
Sampling instant:
Differential Protection Symposium
IB( tB3 )
tB1
tD
tA3
tA4
IB( tA3 )
t B3 - t A3
⋅ 360 °
TP
tB4
t PT1 = t PT2 =
1
(t A1 - t AR - t D )
2
t B3 = t AR - tTP2
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 125
Specification of data channel for line differential protection
based on Cigre Report: Protection using Telecommunication *)
Data rate
64 kbit/s (min.)
Channel delay time:
< 5 ms
Channel delay time unsymmetry:
< 0.2 ms
Bit error rate normal:
< 10 -6
during power system fault
Availability:
< 10-5 *)
> 99.99 %
*) Report of WG34/35.11, Brochure REF. 192, Cigre Central Office, Paris, 2001,
*) It is suggested that for a BER of less than 10-6 the dependability shall not suffer a noticeable deterioration . For a
BER of 10-6 to 10-3 the teleprotection may still able to perform its function although a loss in dependability is to be
expected.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005 page 126
Digital Protection
of
Generators and Motors
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 116
Generator differential protection
a
a
c
S
S
S
A
IA/In
3
2
S
S
A
1
S
A
Connection circuit
Differential Protection Symposium
1
2
3
4
5
6
IS/In
Operating characteristic
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 117
Generator HI differential protection
a
b
c
A
Differential Protection Symposium
A
A
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 118
Transverse differential protection
a
b
c
S
S
S
S
S
A
Differential Protection Symposium
A
S
A
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 119
HI earth current differential protection
L1
L2
L3
∆IE>
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 120
Earth current differential protection for generators
L1
L2
L3
U0>
∆IE>
Tripping
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 121
Motor starting current
20
IRush /IN
TRush
15
Tst
10
Ist/IN
5
0
5
0
50
100
150
200
250
300
tst (ms)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
Seite 122
Transformer
Differential Protection
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 123
Transformer: Function principle and equivalent circuits
I1
w1
w2
I2
U1
Xσ1
R1
Φ
U2
Φ σ1
Φ σ2
U1
I1
I ⋅ w + I ⋅ w = I µ ⋅ w1
1 1 2 2
I µ << I 1, 2 '
Differential Protection Symposium
Xµ
R2 '
I2'
U 2'
Equivalent electric circuit
Equivalent electromagnetic circuit
At load and short-circuit:
Iµ
X σ 2'
RTK
U1
X TK
I1 = I 2 '
I1 ⋅ w1 = I 2 ⋅ w 2
U 2'
Belo Horizonte November 2005
X TK = X σ 1 + X σ 2 '
RTK = R1 + R 2 '
G. Ziegler, 10/2005
page 124
Typical Transformer data
kV/kV
Short-circuit
voltage
% UN
No-load magnetizing
current
% In
850
850/21
17
0.2
600
400/230
18.5
0.25
300
400/120
19
0.1
300
230/120
24
0.1
40
110/11
17
0.1
16
30/10.5
8.0
0.2
6.3
30/10.5
7.5
0.2
0.63
10/0.4
4.0
0.15
Rated power
Ratio
MVA
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 125
Transformer Inrush current
IRush
Flux
φ
φ
φRem
Im
Inrush-current of a single
phase transformer
U
t
Source: Sonnemann, et al.: Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 126
Inrush currents of a Y-∆-transformer
Neutral of Y-winding earthed
ΦC
IA
ΦB
ΦA
IB
I mC
ID
IC
I mA
Oscillogram:
IA
5
1
I A = ⋅ I mA − ⋅ I mC
6
6
IA
IB
1
1
I B = − ⋅ I mA − ⋅ I mC
6
6
IB
IC
5
1
IC = ⋅ I mC − ⋅ I mA
6
6
IC
Source: Sonnemann et al. : Magnetizing Inrush phenomena in transformer banks, AIEE Trans., 77, P. III, 1958, pp. 884-892
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 127
Inrush current : Content of 2nd und 3rd harmonic
I m (ν )
I m (1)
%
100
B
80
B
360O
60
I m (2)
40
I m (1)
I m (3)
20
I m (1)
90O
17,5%
180O
270O
360O Width of base B
240O
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 128
Inrush currents of a three-phase transformer
recorded with relay 7UT51
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 129
Transformer Inrush current:
Amplitude and time constant
Î Rush
Î N
12
Rated power
in MVA
time constant
in seconds
8
0,5....1,0
0,16....0,2
6
1,0
0,2 .....1,2
10
10
>10
4
1,2 ....720
2
5
10
50
100
500
Rated transformer power in MVA
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 130
Sympathetic Inrush
Wave form:
Transient currents:
I1
I
I1
I2
I2
IT
IT
I1
IT
T1
G
resistance
I2
Current circulating
between transformers
Transformer
being closed
G
RS
IT
Transformer
already closed
T2
Differential Protection Symposium
t
XS
Belo Horizonte November 2005
I1
I2
T1
T2
G. Ziegler, 10/2005
page 131
Transformer overfluxing
Deduction of wave form
Harmonic content
Im
B
1,5
× 10 4 Gauß
U
1,0
%
100
80
I150/I50
60
I250/I50
40
I350/I50
I50/InTr
20
0
0,5
5
10
15 A
Im
0
Differential Protection Symposium
10
100
120
20 ms
% 160
140
U/Un
t
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 132
Vector group adaptation with matching CTs
Current distribution with external ph-ph fault
IR
I1
R
Ir
r
1
3
IS
I2
IT
I3
S
T
Is
It
s
G
t
3 /1
87T
Differential Protection Symposium
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 133
Vector group adaptation and I0-elimination with matching CTs
Current distribution with external ph-E fault
A
B
Yd1
IA
Ia
r
IB
Ib
s
IC
Ic
t
C
G
cp
Ic
= 3
IT=3
cn
3 /1
87T
87T
87T
Ia
= 3
Cn
Cp
A0 B0 C0
30O
cp
cn
bp
Bp
Ap
An
Bn
Differential Protection Symposium
ap
ap
an
30O
bn
an
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 134
Traditional I0-elimination with matching CTs
Current distribution in case of an external earth fault
a
A
b
B
c
C
87T
Differential Protection Symposium
G
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 135
Traditional I0-elimination with matching CTs
Current distribution in case of an internal earth fault
a
A
b
B
G
c
C
!
87T
Differential Protection Symposium
87T
87T
Ø Sensitivity only 2/3 I F!
Ø Non-selective fault
indication!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 136
Traditional I0-correction with matching CTs
Current distribution with external ph-E fault
a
A
b
B
G
c
C
3/1
87T
Differential Protection Symposium
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 137
Traditional I0-correction with matching CTs
Current distribution with internal ph-E fault
a
A
b
B
G
c
C
3/1
87T
Differential Protection Symposium
87T
87T
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 138
Transformer differential protection, connection
L1
IA1
IB1
UA
L2
IA2
IB2
UB
(110 kV)
L3
IA3
IB3
(20 kV)
Digital protection
contains:
Adaptation to
7UT6
∆I
∆I
∆I
• Ratio UA / UB
• Vector group
Software replica of matching transformers
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 139
Digital transformer protection
Adaptation of currents for comparison (1)
CT 1
JR-sec
JS-sec
JT-sec
W2
W1
JR-prim
Jr-prim
JS-prim
Js-prim
JT-prim
Jt-prim
N
o
r
m
I N − Transf − W1 =
IR
IS
IT
IR*
I0elim. IS*
IT*
Comparison
∆I
SN
J R −sec
I N − Prim − CT 1
IS =
⋅ J S −sec = kCT −1 ⋅
I N − Transf - W1
IT
JT −sec
Differential Protection Symposium
It**
Vector
group
adapt.
Ir*
Is*
It*
I0elim.
Ir
Is
It
N
o
r
m
I N − Transf − W2 =
3 ⋅ U N -1
IR
Ir**
Is**
J R −sec
J S −sec
JT −sec
CT 2
Jr-sec
Js-sec
Jt-sec
SN
3 ⋅ U N -2
Ir
J r − sec
I N − Prim − CT 2
Is =
⋅ J s − sec = k CT − 2 ⋅
I N − Transf -W2
It
J t − sec
Belo Horizonte November 2005
J r − sec
J s − sec
J t − sec
G. Ziegler, 10/2005
page 140
Digital transformer protection
Adaptation of currents for comparison (2)
CT 1
JR-sec
JS-sec
JT-sec
1
⋅ (I R + I S + I T )
3
IR * = IR − I0
W2
W1
JR-prim
Jr-prim
JS-prim
Js-prim
JT-prim
Jt-prim
N
o
r
m
IR
IS
IT
IR*
I0elim. IS*
IT*
Com_
parison
∆I
I0 =
Ir**
Is**
It**
Vector
group
adapt.
Ir*
Is*
It*
I0elim.
Ir
Is
It
N
o
r
m
IS * = IS − I0
IT * = IT − I0
I ∆ −T
IT *
Differential Protection Symposium
It **
Ir **
−1 0
1
1
Is ** =
1 −1 0 ⋅
3
0
1 −1
It * *
Belo Horizonte November 2005
Jr-sec
Js-sec
Jt-sec
I0 =
Example Yd5:
I∆−R
IR *
Ir **
I∆−S = IS * + Is **
CT 2
Ir *
Is *
It *
1
⋅ (I r + I s + I t )
3
Ir * = Ir − I0
I s * = Is − I 0
I t * = I t − I0
G. Ziegler, 10/2005
page 141
Adaptation of currents for comparison
Relay input data
Input data:
•n times 30O
vector group number
(only for 2nd and 3rd winding,
1st winding is reference)
Winding 1 (reference) is normally:
•High voltage side
•UN (kV)
Rated winding voltage
•SN (MVA)
rated winding power
•INW (A)
Primary rated CT current
At windings with tap
changer:
•Line or BB
direction of CT neutral
UN = 2⋅
•Elimination /
Correction /
without
I0-treatment
•Side XX
Assignment input for REF
•INW S (A)
Primary rated current of neutral CT
•Neutral CT
Earth side connection to relay: Q7 or Q8?
Differential Protection Symposium
U max ⋅ U min
U max + U min
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 142
Digital transformer protection
Current adaptation, Example (1)
SN = 100 MVA
UN1= 20 kV
W2
3000/5 A
UN2= 110 kV
Yd5
W1
600/1 A
2.400 A
7621 A
1A
5A
Differential Protection Symposium
∆I
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 143
Digital transformer protection
Current adaptation, Example (2)
110-kV-side
20-kV-side
I N − Trafo − W2 =
100MVA
= 2887A
3 ⋅ 20kV
I N − Trafo − W1 =
1
3 = 4,4 3 A
⋅ 13200
3000
3000
3A
I Norm =
⋅ 4,4 3 = 4,57
2887
J r,s, t - sek =
J R, S, T -sek =
I Norm =
4,57
I A − S = I S * + I s * * = − 2 ⋅ 4,57
I A −T = IT * + I t * * =
Differential Protection Symposium
1
⋅ 2400 = 4,0 A
600
600
⋅ 4 = 4,57A
525
Vector group adaptation: Yd5
Ir *
2 −1 −1
0
4 ,57 3
1
I s * = ⋅ − 1 2 − 1 ⋅ − 4,57 = − 2 ⋅ 4 ,57 3
3
It *
−1 −1 2
0
4 ,57 3
I0-elimination:
Ir **
−1 0
1
4,57 3
− 4,57 / 3
1
Is ** =
1 − 1 0 ⋅ − 4,57 3 = 2 ⋅ 4,57 / 3
3
It **
0
1 −1
0
− 4,57 / 3
IA −R = IR * + I r * * =
100MVA
= 525A
3 ⋅ 110kV
4,57
3 − 4,57
3
3 + 2 ⋅ 4,57
3 − 4,57
=0
3=0
3
=0
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 144
Current adaptation (1)
Practical example for the need of matching CTs
*)
Matching CTs recommended, if
k_Wan_n > 4 or k_Wan_n < 1/4: *)
To keep the specified measuring accuracy of 7UT51. For protectio n only
necessary if 8 <k_Wan_n <1/8
345 kV, 1050 MVA
1500/5 A
2000/5 A
500 kV,
1050 MVA
1213 A
(1050
MVA)
1000/1 A
43.930 A
(1050 MVA)
4,04 A
43,43 A
13,8 kV,
30 MVA
1/0.2A
8,786
7UT513 (5A Relay)
Differential Protection Symposium
k CT _ 3* =
8,786
= 1,76 < 4!
5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 145
Current adaptation (2)
Practical example for the need of matching CTs
I n −Tr −W 1 =
I
1050 ⋅103
3 ⋅ 500
n −Tr −W 1−sec =
1213A
= 4,04 A
1500 / 5
4.04
kCT −1 =
= 0,809
5
I n −Tr −W 2 =
I
1050 ⋅ 103
3 ⋅ 345
n −Tr −W 2− sek =
kCT − 2 =
40·In= 15 Bit +sign
= 215 = 32.768
32.768
15
40·In
1
0,122%In
32.36
351,44
= 1757 A
1757 A
= 4,39 A
2000 / 5
1050 ⋅103
3 ⋅13,8
n −Tr −W 3 _ sek =
kCT −3 =
Transformer
winding 3
4,39
= 0,878
5
I n −Tr −W 3 =
I
Transformer
winding 1
Relay
= 1213A
= 43.930 A
43.930 A
= 43,93 A
1000 / 1
43,93
= 8,786 > 4!
5
Differential Protection Symposium
0,099%
Belo Horizonte November 2005
1,072%
G. Ziegler, 10/2005
page 146
7UT6
Operating characteristic
5
I
ST
F =
IF
7UT6
7
6
I DIFF >>
AB
8
ID
IDiff/ In
I2
I1
9
IDIFF = |I1+ I2|
Tripping area
IStab = |I1| + |I2|
4
2
e
op
Sl
3
Stable operation
2
Slope
1
I DIFF >
0
0
1
2
Additional stabilisation
for high Is.c.
1
3
Differential Protection Symposium
4
5
6
7
8
9
10
Belo Horizonte November 2005
11
Istab / In
G. Ziegler, 10/2005
page 147
I0-elimination / correction: Summary
è I0- elimination necessary at all windings with earthed neutral or
with grounding transformer in the protection range
Earth fault sensitivity reduced to 2/3 !
Incorrect fault type indication!
è I0- correction provides full earth current sensitivity and correct
phase selective fault type indication, however requires CT in the
neutral-to-earth connection of the transformer.
è As an alternative, earth differential protection can be used to
enhance earth fault sensitivity.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 148
Transformer winding to earth fault
Solid earthed neutral
IF
per unit
10
8
UR
h⋅UR
IF
6
Infeed side
4
IF
IK
2
IK
0
20
40
60
80
100
Short-circuited winding part h in %
Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 149
Transformer winding to earth fault
Resistance or reactance earthed neutral
UR
%
100
h⋅UR
I
Infeed side
50
IF
IK
IK
RE
0
20
40
100
60
80
Short-circuited winding part h in %
h ⋅U R
RE
U 2n
h ⋅ w2
=
⋅ IF = h ⋅
⋅ IF
w1
U 1n ⋅ 3
IF =
IK
IF
I Max
1 U 2n U R
I K = h2 ⋅
⋅
⋅
3 U 1n R E
Source: P.M. Anderson: Power System Protection, McGraw-Hill and IEEE Press (Book)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 150
Transformer winding short-circuit
100
IK
10
IF , I K
x In 80
8
60
6
IP
x In
IF
4
40
IK
20
2
IF
0
5
10
15
20
25
Short-circuited winding part h in %
Source: Protective Relays, Application Guide, GEC Alstom T&D, 1995
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 151
Restricted earth fault protection of relay 7UT6
IR
IS
IT
K0= 4
K0= 2
100
80
2
120
60
1.2
I0 *
⋅ e ϕ (I 0 * /I 0 * *)
I 0 * *40
0.8
20
1.6
K0= 1.4
140
160
0.4
K0= 1
180
Blocking
0
ϕ
+
1
Tripping
200
I>
IN
∆ IE
0
I0*
I0**
340
220
320
240
300
260
280
Polarised earth current
differential protection
3.14
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 152
Restricted earth fault protection 87N (7UT6)
Application aspects
n Increased sensitivity with earth faults near winding neutral
Preferably used in case of resistance or reactance neutral earthing
n Sensitive to turns short-circuit
n I0 / IN amplitude and angle comparison
n 2nd harmonic stabilised
n Can protect a separate shunt reactor or neutral earthing transformer in
addition to the two winding transformer differential protection
n Not applicable with autotransformers! (as only one stabilising input at transformer
terminal side, -- high impedance principle to be used in this case.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 153
Transformer HI-earth fault protection
IR
Ir
IS
Is
IT
It
ZE
∆IE>
Differential Protection Symposium
IN
∆IE>
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 154
HI differential protection of an autotransformer
Ir
IR
Is
IS
It
IT
87
Differential Protection Symposium
87
87
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 155
HI earth fault protection of an autotransformer
Ir
IR
Is
IS
It
IT
IN
∆I>
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 156
Transformer tank protection 64T: Principle
IE>
Insulated
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 157
Transformer protection, Relay design
7UT6 differential protection
for
•Transformers
•Generators
• Motors
•Busbars
7UT612:
7UT613:
7UT633:
7UT635:
for protection objects with 2 ends
for protection objects with 3 ends
for protection objects with 3 ends
for protection objects with 5 ends
Differential Protection Symposium
(1/3 x 19’’ case 7XP20)
(1/2 x 19’’ case 7XP20)
(1/1 x 19’’ case 7XP20)
(1/1 x 19’’ case 7XP20)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 158
7UT6
Integrated protection functions
Function
ANSI No.
Function
ANSI No.
Differential
87T
Overfluxing V/Hz
24
Earth differential
87 N
Breaker failure
50BF
Phase overcurrent,
50/51
Temperature monitoring
38
Neutral overcurrent IN>, t
50N/51N
Ground overcurrent (IE, t)
50G/51G
Hand reset trip
86
Unbalanced current I2>, t
46
Trip circuit supervision
74TC
Thermal overload IEC 60255-8
49
Therm. OL IEC 60354 (hot spot)
49
Differential Protection Symposium
Binary inputs for tripping commands
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 159
Application range (7UT6)
∆
∆I
∆I
Shunt Reactor
G
Three winding
transformer
Two winding
transformer
∆I
Generator / Motor
Differential Protection Symposium
∆I
∆I
Transformer bank
(1-1/2-LS)
∆I
∆I
Busbars
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 160
Digital transformer protection relay 7UT613:
Current inputs and integrated protective functions
YN
yn0
d5
R
S
T
ϑ>
(2)
ϑ>
(1)
Differential Protection Symposium
I>>,
I>t
∆ITE
∆IT
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 161
Operating characteristic (7UT6)
Idiff >>
I
7
Locus of
internal faults
45°
6
Op
5
In
pe
o
l
S
operate
2
restrain
4
3
2
Idiff >
1
S lo p
0 0
2
supplementary
restraint
e1
4
6
8
10
12
14
16
IRes
In
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 162
7SA6: Temperature monitoring
RS485 Interface
7XV5662-(x)AD10
7XV5662-(x)AD10
Two thermo-devices can be connected to the serial service interface (RS485)
Monitoring of up to 12 measuring points (6 per thermo-device)
- each with two pick-up levels
Display of the measured temperatures
- directly at the thermo-device (which can also be used stand alone)
- at the relay
One input is reserved for hot spot monitoring (measurement of oil temperature)
Thermistors: Pt100, Ni100 or Ni120
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 163
7UT6: Temperature monitoring with hot spot calculation (1)
Example: Natural cooling
Θ h = Θ O + H gr ⋅ k Y
Θh= hot spot temperature
ΘO= oil temperature
Hgr=hot-spot-to-oil temperature gradient
k= load factor I/In
Y= winding exponent
Aging rate:
Oil Temp.
HV
LV
V=
Aging at Θh
= 2(Θ h −98)/6
Aging at 98°C
98O is reference for
the aging of
Cellulose insulation
Mean value of aging during a fixed time interval:
T
2
1
L=
⋅ ∫ V ⋅ dt
T2 − T1 T1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 164
7UT6: Temperature monitoring with hot spot calculation (2)
Θ h = Θ o + H gr ⋅ k Y ≈ 73 + 23 ⋅1.151.6 = 102°C
(L)
V = 2(Θ h −98)/6 = 2(102−98)/6 ≈ 1.6
108°C
k,
V,
L
98°C
102°C
73°C
Θh Hot spot
temp.
Θo oil temp.
(from thermodevice)
[°C]
Θh
Θo
1.6
k (I/In)
V (relative
aging)
L (mean
value of V)
1.15
t
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 165
7UT6: Commissioning und service tool (1)
WEB-Technology
Access to WEB Browser
Help system in the
INTRANET / INTERNET
http://www.siprotec.com
1. Serial connection
Directy or with modem
to standard DIAL-UP
network
2. HTM L page view
at IP-address of the relay
http://141.141.255.160
Differential Protection Symposium
Relay homepage address of :
http://141.141.255.160
IP-address can be set with
program DIGSI 4 at the front or
service interface of the relay
WEB server
in relay firmware
Server sends HTML pages and
JAVA code to WEB Browser via
DIAL-UP connection
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 166
7UT6: Commissioning and service tool (2)
Display of current phasors of all terminals
Transformer YNd11d11, 110/11/11kV, 38.1MVA,
IL2S2à wrong polarity
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 167
7UT6: Commissioning and service tool (3)
Display of operating/restraint state
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2à wrong polarity
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 168
Application examples
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 169
Protection of a two winding transformer
7SJ600
7UT512
50
51
W1
52
87T
Bu
W1 (OS)
49
W2 (US)
W2
52
Differential Protection Symposium
52
51
52
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 170
Protection of a three winding transformer
7SJ600
50
51
52
7UT513
W1 49-1
Bu
87T
W1
W2
W2 49-2
W3
W3
51
52
Load
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 171
Restricted earth fault protection
for a two winding transformer
7SJ600
7UT513
50
51
W1 49-1
52
Bu
W1 (OS)
87T
W2 (US)
ZE
51
87TE
52
Differential Protection Symposium
52
W2
52
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 172
Protection of an autotransformer
52
7SJ600
51BF
51N
50
51
7UT513
87
TL
Load
52
87
TH
7VH600
49
52
3Y
51
59
7RW600
50
BF
Bu
50
51
50
BF
7SJ600
7SJ600
51
N
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 173
Protection of a large transformer bank
52
52
7SA6
49
21
7UT513
87
TL
50
BF
87
TH
7VH6 (3)
49
3
Load
52
52
51
59N
7RW6
50
BF
7SJ6
Differential Protection Symposium
7SA6
21
51N
49
51
BF
7SJ6
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 174
Protection of a phase regulating transformers
Phase regulator
Bu
50/50N
50/50N
51/51N
Exciting
transformer
Bu
51/51N
87
TS
87
TP
51N
50N
Differential Protection Symposium
51N
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 175
Protection of a compensation reactor
No phase CTs at neutral side
3
52
49-1
50
51
87N
7UT613
1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 176
Protection of a compensation reactor
with phase CTs at neutral side
7SJ600
50
3
52
51
7UT613
49
87
87N
3
1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 177
Differential protection of generation units (1)
a)
c)
d)
e)
52
52
52
52
∆IT
∆IT
∆IT
∆IT
G
G
G
∆IG
52
∆IG
G
Differential Protection Symposium
Belo Horizonte November 2005
∆IG
G. Ziegler, 10/2005
page 178
Differential protection of generation units (2)
52
∆IT
52
*)
∆IT
G
∆IG
*) same ratio as generator CTs
52
Differential Protection Symposium
Auxiliaries
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 179
Dimensioning of CTs at the station service transformer
250 MVA
220 /10 kV
T1
∆IT
Fault F1:
High fault currents in relation to the rated current
of the station-service transformer T2 (>100xIN)
and long DC time constants (>100 ms) require
considerable over-dimensioning of CT cores Œ
and • .
IK-T
250 MVA
10 kV
IK-G
Œ
•
G
F1
25 MVA
10,5 / 5 kV
∆IT
T2
Ž
F2
Differential Protection Symposium
EB
7UT61
Fault F2:
uncritical as current is limited by short-circuit
impedance of station-service transformer T2.
CT Ž can have normal dimensions
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 180
Digital Transformer Differential
Protection
I0-correction
+ vector group adaptation
Differential Protection Course
PTD Service
Power Training Center
Nürnberg 2005
G. Ziegler, 5/2005
page 1
Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
Transformer differential protection with I0-correction
External fault
L3
L1
L2
L2
L3
L1
Yd5
3
3
3
L1
L2
L3
1
3
1:3
Vector group adaptation
3
1
I0-correction
Differential Protection Course
1
2
3
2
∆
∆
∆
PTD Service
Power Training Center
3
Nürnberg 2005
G. Ziegler, 5/2005
page 2
Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
Transformer differential protection with I0-correction
Internal fault
L3
L1
L2
L2
L3
L1
Yd5
3
3
3
L1
L2
L3
1
3
1:3
1
I0-correction
Differential Protection Course
Vector group adaptation
1
1
3
2
∆
∆
∆
PTD Service
Power Training Center
3
Nürnberg 2005
G. Ziegler, 5/2005
page 3
Copyright © SIEMENS AG PTD SE 2002. All rights reserved.
Digital Line Differential Protection
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 179
Line differential protection, Versions
Line differential protection with wire connection
I1
Three-wire
(control cables)
up to
about 15 km
current comparison
∆Ι
∆I
I2
I1
voltage comparison
I2
∆U
∆I
∆I
I2
Two-wire
(telefon pilots)
up to about 25 km
∆I
U2
U1
I1
7SD503
7SD502/
7SD600
Line differential protection with digital communication
I
7SD61
Other
services
I2
1
I
2
I1
∆I
∆I
∆I
Up to ca. 200 km
line length
∆I
PCM
MUX
Data net
PCM
MUX
PCM
MUX
dedicated optic
fibres up to ca. 35 km
OF or microwave
PCM
MUX
Differential Protection Symposium
Belo Horizonte November 2005
7SD61
G. Ziegler, 10/2005
page 180
Digital pilot wire relay 7SD600
Combines
ØTraditional pilot wire protection principle
with
ØModern digital relay technology
Novel features:
§ Self-monitoring and pilot wire supervision
§ Saturation detector
§ Measurement of pilot loop resistance
§ Add-on functions
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 181
Relay to Relay pilot wires communication
New technology on existing (copper-) pilots
Traditional:
Composed current
measurement
Comparison of analogue values
Modern:
E
O
O
E
Phase
segregated
measurement
Digital data transmission
64 kbps bi-directional
4 value digital code (2B1Q)
Amplitude and phase modulation
Spectrum mid frequency: 80 kHz
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 182
Digital Relay to Relay Communication (Overview)
Dedicated Optic Fiber
or
E
O
O
Data Comms net
E
87L
87L
E
or
ISDN
O
E
O
E
or
O
O
E
Pilot wires
Communication according to given possibilities
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 183
Converter for digital communication via pilot wire
7SD52/61
7XV5662-0AC00
5 kV
insulated
7XR9516
OF-cable
mutli-mode fibre
max. 1,5 km
Differential Protection Symposium
Barrier
transformer
20 kV (optional)
Belo Horizonte November 2005
Wire
connection
up to ca. 8 km
G. Ziegler, 10/2005
page 184
Line differential protection
with converter for digital communication
7SD52/61
7XV56
Digital
data
network
OF
Multi-mode fibre
max. 1.5 km
Differential Protection Symposium
Interface to data network:
X.21 or G.703.1
(wired connection)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 185
Relay to Relay Communication:
Two terminal configuration with hot standby connection
Commsconverter
FO 820 nm
O
FO 820 nm
X21 or
G703.1
Main
connection
interrupted
Hot standby
connection
Permanent
supervision.
Commsconverter
E
I2
Direct FOconnection.
Main
connection
512 kBit/s
for the 87L
function
Loss of main
connection
Data
Comms
network
E
X21 or
G703.1
(64 kBit/s)
I2
Hot standby
connection
active
Switchover
takes 20 ms
I1
O
Data
Comms
network
I1
O
E
O
Main connection
re-established
E
Closed ring
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 186
Relay to Relay Communication:
Ring- and Chain topology, loss of one data connection tolerated
Closed ring
Chain
side 2
side 2
I2
side 3
I3
side 3
I2
I3+ I1
I3
I2
I1+ I2
I1
I3+ I1
I3
I1
I1+ I2
side 1
side 1
Partial current sums
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 187
Line differential relay with digital communication (7SD52)
Application to 3-terminal line
C
5P20
1600:1
Cable tab 110 kV
8 km, 0.25 µF/km
IC=40 A
A
OH-line A-B
110 kV, 60 km
8 nF/km, IC=10 A
10P10
400:1
O
E
OF: 820 nm
PCM
5P20
1600:1
Digital
communication
network
PCM
B
O
E
Wired interface:
X.21 or G701.1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 188
Line differential relay with digital communication (7SD52)
Application to tapped line
87L
7SA52
7SA52
87L
Net
Net
7SA52
87L
7SA52
87L
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 189
Line differential relay with digital communication (7SD61)
Transformer-line protection
10P10, 10 VA, 200:1
20 MVA, 110 kV / 20 kV,
Yd5
10P10, 10 VA, 600:5
8 km
50/51
LWL
7SD61
87T
50/51
50 BF
Differential Protection Symposium
87T
50/51
50 BF
7SD61
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 190
7SD52/61: Bias for CT errors
I1
Error
%
i1
10%
fL
fF
Load range
Fault range
I1
ALF‘/ALFN • IN-CT
f
: relay setting parameters
Differential Protection Symposium
ALF’ •IN-CT
Example: 10P10, fL < 3%, fF = 10% at ALF‘•IN-CT
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 191
Relays 7SD52/61: Operating characteristic
IDiff
I2
Tripping
area
Restraint
area
IDiff>
Operation
I3
I1
I3
I1
External
fault
I2
fCT
IStab
IDiff = I1 + I2 + I3
(Calculated differential current)
IStab = IDiff> + Σ Sync.error + |I1| •fCT1 +|I2| • fCT2 + |I3| • fCT3
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 192
7SD52/61: Impact of line charging current
I1
E1
U1
I2
IC
U2
E2
IDiff = I1 + I2 + IC (currents I1 and I2 counted positive in line direction!)
Without charge current compensation:
Pick-up value:
IDiff> > 2,5.. 4 • I C
è Senstive setting only for short cables or lines
With charge current compensation:
Pick-up value:
IDiff> > 0,2 • IN
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 193
7SD52/61: High resistance fault sensitivity
230 kV
A
IL= 1000 A
1000/1 A
1000/1 A
B
Infeed
7SD52
IF
Load
RF
7SD52
lline = 120 km
Ic = 72 A
Channel unsymmetry: 0.2 ms = 4.32 O ≈ 5O (60 Hz)
5P type CT, i.e. 1% error in the load area, set: f CD= 2%
Relay pick-up setting about 4xIC: IDiff> = 30% In = 300 A
I Op = I A + I B = 1000 A + I F − 1000 A = I F
I Re s = I Diff > + Fsync + f CTA ⋅ I A + f CTB ⋅ I B = I Diff > + ( I L + I F ) ⋅ sin
∆ϕ
∆ϕ
+ I L ⋅ sin
+ f CTA ⋅ ( I L + I F ) + f CTB ⋅ I L
2
2
I Diff > + (2 ⋅ sin (∆ϕ / 2 ) + f CTA + f CTB ) ⋅ I L 300 A + (2 ⋅ sin 5o / 2) + 0.02 + 0.02) ⋅1000 A
IF >
=
= 457 A
o
1 − (sin (∆ϕ / 2 ) + f CTA )
1 − (sin(5 / 2) + 0.02)
R F− max . =
230 kV
230 kV
=
= 290 Ohm
3 ⋅ I F− min .
3 ⋅ 457A
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 194
7SD52/7SD61: Charge comparison protection supplement
Q2
Q1
Q
Q3
1/4 cycle
n+4
n+3
n+2
n+1
n
n-1
speed
64 kbit/s
128 kbit/s
512 kbit/s (FO)
Calculation of the charge
n+5
t +T 4
Q=
∫
i
i
I(t) ⋅ dt ≈ ( n + n + 5 +
2
2
t
n+4
∑ In ) ⋅ ΔT
QDiff =
│Q1+Q2+Q3│
n +1
with ∆T= 1 ms (18O el.)
2 relays
21 ms
16 ms
14 ms
3 relays
21 ms
16 ms
14 ms
Differential Protection Symposium
6 relays
41 ms
24 ms
17 ms
Trip
Area
Restrain
Area
QDiff>>
Settable pick-up value
0
Belo Horizonte November 2005
0
Qrest= Σ Q errors
G. Ziegler, 10/2005
page 195
Development of IED processing and communication power
Year
Memory
1986
192 kB
0.5 MIPS
16 bit
19.2 kbps
1992
768 kB
1.0 MIPS
16 bit
115.2 kbps
1998
8.5 MB
35 MIPS
32 bit
1.5 Mbps (LAN)
2004
28 MB
80 MIPS
32 bit
100 Mbps (LAN)
Processing
power
Differential Protection Symposium
Bus width
Communication
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 196
21 & 87 Relay
United full scheme distance and differential protection
21
87
Copy of well proven
features
21, 21N
85 - 21
67N
85 - 67N
68, 68T
27 WI
79
25
59
27
49
81
51/51N
50 BF
21 & 87
2 in 1
87
∆I
IRest
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 197
Universal line protection relay
87 Differential
21 Distance
line protection
67 DEF
For all kind of lines
Short to long lines
For all kind of communication:
Parallel lines
Traditional : PLC, Pilot wires, Microwave
Multi-terminal lines
Dedicated OF
Tapped lines
Digital microwave
Transformer lines
Comms networks
For all kind of operation
Single and/or three-pole ARC
Series comp. lines
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 198
Line with larger transformer taps
Release of 87 by 21 distance overreaching zone
87
87
21
21
Net
Net
87
&
21
Permissive
tripping
Differential Protection Symposium
Allows low setting of 87 pick-up!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 199
Line differential relay with digital communication (7SD61)
Application to tapped line, Example
400/1 A
∆I
∆I
400/1 A
Net
Net
110 kV
SSC1‘‘=2000 MVA
ZS1 = 6.05 Ω
l1= 8 km
XL1=
3.2 Ω
l2= 10 km
XL2=
4.0 Ω
20 MVA
uT=12 %
XSC-T= 73 Ω
1.1 ⋅ U N / 3 1.1 ⋅ 110/ 3 kV
ISC ≈
=
= 957 A
X SC − T
73 Ω
l3= 5 km
XL3 =
2.0 Ω
5 MVA
uK=8 %
XSC-T= 194 Ω
l4= 4 km
XL4=
1.6 Ω
110 kV
SSC2‘‘=1000 MVA
ZS2= 12.1 Ω
10 MVA
uK=10 %
XSC-T= 121 Ω
S N −T
∑
ΣI Rush ≈ 5 ⋅
= 5⋅
3 ⋅U N
35 MVA
3 ⋅110 kV
= 918 A
u Setting pick-up value ∆I > 1.3·957 A
u or blocking ∆I via remote signalling when tap protection operates
u or release of ∆I by an overreaching distance zone
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 200
Fully redundant line protection
using dissimilar protection and comms principles
87
MUX
comms net
MUX
87
21
21
87
87
PLC
PLC
21
21
Fully redundant 87 and 21 teleprotection remains in operation
in each combination of relay and communication failure!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 201
Phase segregated 87 differential and 21 distance pilot protection:
Enhanced selectivity with multiple faults
87 differential
and
21 pilot protection
Ph a - E
Ph b - E
Phase selective fault clearance and auto-reclosing also with multiple-faults
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 202
Phase segregated 87 differential and 21 distance pilot protection:
Enhanced selectivity with multiple faults
87 differential
and
21 pilot protection
Ph a - E
Ph b - E
Phase selective fault clearance and auto-reclosing also with multiple-faults
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 203
Two-sided fault locator using 87&21 relay
communication
I1
I2
Grid 1
Grid 2
U1
U2
Digital comms
XL•I1
XL•I2
U2
U1
(I1+I2)•RF
Distance
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 204
Conclusions
ü Combined distance and differential protection relays , together with
modern comms, allow to enhance line protection in a cost saving way.
üThe dissimilar protection principles complement each other perfectly.
üDistance and differential protection can both be configured as phase
segregated teleprotection schemes allowing absolute phase selective fault
clearance and autoreclosure even with complex cross county and intercircuit faults.
üDigital relay to relay comms allows to exchange data for upgraded two
sided fault locating.
üUsing a single relay type for distance and/or differential protection also
saves on cost in investment and operation.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 205
7SD51: Phase comparison,
Dynamic supplement based on delta-quantities
I1
I2
PCP
PCP
7SD512
7SD512
i2(t)
i1(t)
∆ i1(t) = i1(t) -i1(t -2T)
−
Differential Protection Symposium
−
+
+
−
−
+
Sign.{ ∆i2 }
Belo Horizonte November 2005
+
Sign.{ ∆i1 }
∆ i1(t) = i1(t) -i1(t -2T)
G. Ziegler, 10/2005
page 206
7SD51: Phase comparison
I1
I2
PVS
PVS
PVS
PVS
7SD512
7SD512
7SD512
7SD512
i1(t)
I1
i1(t)
i2(t)
−
−
+
+
−
+
−
no coincidence
+
+
−
−
−
+
+
+
I2
−
no coincidence
i2(t)
+
−
+
+
−
+
+
−
−
Full coincidence
−
Differential Protection Symposium
−
+
+
−
−
Full coincidence
Tripping
External fault
+
Tripping
Internal fault,
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 207
7SD51: Phase comparison: Impact of charging current
I1=IL+IC
-I2= IL
IL
IC
E1
I1
E2
ϕKO
IC
I1
-I2
Differential Protection Symposium
-I2
undefined
range
ϕ
Phase shift ϕ caused by
charging current IC
ϕ
I2
Tripping
range
undefined range due to
discrete sampling :
±1/2∆T = ± 1,66/2 ms= ± 15O
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 208
Phase comparison protection 7SD51:
Sampling of the rectangular sign wave and data transmission telegram
i(t)
Sampling interval (1,66 ms)
01
Sign.{ i(t) }
00
11
−+++
START
1 1
···
1 0 1
CHECK
END
Telegram acc. to IEC 60870-5
Hamming distance d= 4
4 directional signs per phase = 12 binary digits
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 209
Measurement based on delta quantities, Principle
∆I1, ∆I2: DELTA-quantities
Total situation after fault inception:
ZV1
E1
I2
I1
∼
ZV2
RF
∼
E2
∼
E2
Load before fault inception:
ZV1
E1
Pure fault part :
I1L
I2L
∼
ZV2
UFL
ZV1
∆I1=I1F
∆I2=I2F
RF
Differential Protection Symposium
∼
ZV2
UFL
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 210
Digital Busbar Protection
Gerhard Ziegler
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 217
Busbar differential protection, Principle
(Analog technique)
Busbar
1
n
2
Iop
k ⋅ I Res
IOp
Measuring
circuit
Tripping
area
Operating
characteristic
k%
Iop>
IRes
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 218
Part-digital Busbar protection 7SS6
4AM
3
3
2
1
ΣI
100mA∼ /IN
3
n
7SD601
=
7TM70
Differential Protection Symposium
ΣI
=
1,9 mA= /IN
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 219
7SS6: Operating characteristic
IA
Internal faults (k=1)
Relay characteristic
k= 0.25 to 0.8
Id >
IS
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 220
Isolator replica, Principle, (stabilising circuit not shown)
BB 1
+
1
_
+
2
+
k
_
_
BB 2
+
_
_
_
+
+
∆I1
∆I2
_
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 221
Decentralised BB-protection 7SS52, Structure
Optic fibre-communication
- HDLC protocol
- 1,2 MBaud
Wired
connections
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 222
7SS50/52: Maximum configuration
1
2
3
4
5
6
7
Transfer bus
7SS50
centralised
Bays
7SS52
decentralised
32
48
BB-zones
8
12
couplings
4
16
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 223
7SS50/52: Acquisition and supervision of isolator positions
Connection to
central unit
OF
+
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 224
Operating characteristic of BB protection 7SS52
Internal faults (k=1)
IOp
Relay characteristic
(k =0.1 - 0.8)
k
Optional extension
for networks with limited earth
current (impedance earthing)
(release by U0>)
∆I >
∆IE >
IRes<
Differential Protection Symposium
IRes
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 225
BB-Protection 7SS52
Performance in networks with earth current limitation
110 /10 kV
40 MVA
IL =
35MVA
10kV ⋅ 3
= 2 kA
I F = I E = 10/ 3kV/6Ω ≈ 1 kA
RE= 6 Ohm (IE = 1 kA)
Restraint current:
I Res = Σ I = (2 + 1) + 2 kA
Operating current:
I Op = ΣI = I E = 1 kA
k=
35 MW
k
IOp
I Op
I Re s
=
1
= 0.2
5
Relay operating characteristic
(k =0.1 - 0.8)
Additional, for earth faults
(release by U0>)
∆I>
Iop-E= IE = 1kA
∆IE>= 500 A
IRes-L= 4kA
IRes
Ihres-E= 1kA
IRes<= 7kA
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 226
Check zone of busbar protection
∆ISS1
∆ISS2
∆ICheck
Check zone:
Ø in the past used with HI protection on EHV level (needs separate CT cores)
Ø in general not used with traditional low impedance busbar protection (too expensive)
Ø However, now integrated as software function in full scheme versions 7SS51 and 7SS52
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 227
7SS52: special restraint algorithm avoids over-stabilisation
Check zone
I1
I2
IOp
I4
I3
I3 + I4
IOp
I1 +I2
I1 +I2
2·(|I3| +|I4| )
I1 +I2
IRes
Normal restraint:
Sum of all current magnitudes
|I3 + I4|
Special restraint algorithm:
Positive and negative currents are added separately.
Σ I p = I1 + I 2 + I 3 + I 4
I Res = Σ I = I1 + I2 + I3 + I 4 + I3 + I4
IRes
Σ I n = I3 + I 4
Smaller value is then taken:
I Res = Σ I n = I3 + I 4
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 228
7SS52: Special treatment of dead zone faults (1)
BB-A
BB-B
Differential Protection Symposium
Bus coupler CB aux. contacts not connected:
• 87-A trips bus coupler
• Current inverted in 87-B after T-BF.
Subsequently 87-B trips BB-B
Coupler CB auxiliary contacts connected:
• 87-B trips immediately after opening of bus
coupler CB because coupler current is
removed from bus protection.
→ time reduction (T-BF saved)
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 229
7SS52: Special treatment of dead zone faults (2)
BB-A
A) Bus coupler CB aux. contacts not connected:
• 87-A overfunctions and trips unnecessarily.
• 87-B „sees“ an external fault and only trips finally
through BF function (delay T-BF!)
B) Bus coupler CB aux. contacts connected:
• 87-A remains stable („sees“ no fault current)
• 87-B trips immediately
BB-B
Coupler CB auxiliary contacts connected to 7SS52:
Coupler current is removed from 87-A and 87-B current
comparison with open coupler CB.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 230
7SS52: Special treatment of dead zone faults (3)
Two CTs in coupling bay, overlapping protection zones
BB-A
Coupler CB auxiliary contacts
connected:
• 87-A „sees“ external fault and
remains stable
• 67-B correctly trips BB-B
BB-B
87 A
87 B
Coupler CB auxiliary contacts connected to 7SS52:
Coupler currents are removed from 87-A and 87-B current
comparison with open coupler CB.
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 231
7SS52: Treatment of switch onto a faulted (earthed) bus
BB-A
BB-B
Differential Protection Symposium
Coupler CB close command is detected by
bus protection (change of biary input
signal):
• Coupler current is immediately reincluded in the 87 current comparison
before CB contacts close.
• Selective tripping of BB-B by 87-B.
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 232
7SS52 : Integral breaker fail protection
Busbar
protection7
SS52
Bay
protection
&
Fault
detection
Trip
&
T-BF
Current
reversal
∆I
87
Trip
With line fault and CB failure:
• Trip command of bay protection hangs on at BB protection
• Forced current reversal of the current of concerned bay after T-BF
• Zone selective tripping only of the concerned busbar
• Advantage: Reset time (overtravel time) of bay protection does not matter
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 233
External bay dedicated BF protection
Zone selective tripping via isolator replica of 7SS52 busbar protection
Bay (feeder) protection
trip
7SS52
T-BF
&
I>
&
Isolator
replica
Selective
bus
trip
Fault
detection
•
•
•
BF trip command to busbar protection binary input
(for security: fault detection signal as second criterion)
Distribution of trip commands via isolator replica to breakers of concerned
busbar
èzone selective tripping of concerned busbar
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 234
Fail safe design: 3-out-of-3 decision per bay
∆I of check zone
calculated
from all samples
∆I of discriminative
zones, calculated from
even samples
∆I of discriminative
zones, calculated from
odd samples
Trip- relay
(per bay)
L+
L–
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 235
Adaptive measurement (Booster circuit) (7SS5)
Odd
Samples
Even
Samples
dI S
dt
dI S
dt
1 ms
Differential Protection Symposium
dI S
dt
Check zone
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 236
Digital busbar protection 7SS5, Measuring technique
External fault, symmetrical fault current
I1
I2
1
1
IOp= |I1+I2|
I1
0
10
20
0
1
I2
2
1.5
1
0.5
0.5
1
1.5
10
20
t
20
0
10
20
0
10
20
0
1.5
0
10
20
k·IRes = k·(|I1|+|I2|)
1
0.5
1.5
IRes=|I1|+|I2|
1
1
∆I = IOp - IRes
0.5
0
10
Differential Protection Symposium
20
1
0.5
0.5
1
1.5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 237
Digital busbar protection 7SS5, Measuring technique
Internal fault, symmetrical fault current
I1
I2
2
1
1
I1
0
10
20
IOp= |I1+I2|
1
I2
)
1.5
1
0.5
0.5
1
1.5
0
10
20
0
10
20
0
10
20
1.5
0
10
20
k·IRes =k·(|I1|+|I2|)
1
0.5
2
1
1
1
0.5
)
0.5
1
1.5
∆I=IOp - IRes
IRes=|I1|+|I2|
0
10
20
Differential Protection Symposium
Belo Horizonte November 2005
Tripping!
G. Ziegler, 10/2005
page 238
7SS5/6: Admissible over-burdening - Necessary dimensioning of
CTs with regard to symmetrical fault currents
Ri
I1
IM
∫
∫
Φ = e2(t ) =(Ri + RB ) i 2(t )
RB
I2
E2
φ
5
1
2
φmax
180O
54O
90O
Im
Φ max ≅
180O
180O
180O
0
o
o
∫ ALF'⋅u 2N (t) ⋅dt = (Ri + R B ) ∫ ALF'⋅i2N (t) ⋅ dt = (R i + R B )⋅ ALF'⋅Î2 ⋅ ∫ sinx ⋅ dt = (Ri + R B )⋅ ALF'⋅Î2N ⋅ 2
x
∫
Î 2F sinx ⋅ dt = ALF'⋅Î 2N ⋅
o
O
180
∫ sinx ⋅ dt = ALF'⋅Î2N ⋅ 2
o
Differential Protection Symposium
I 2F
2
= ALF'⋅
x
I 2N
sinx
∫
I
I
2
k OB = 2F 2N =
x
ALF'
sinx
o
Belo Horizonte November 2005
∫
o
G. Ziegler, 10/2005
page 239
Required restraining factor k dependent on over-burdening
factor KOB (over-dimensioning factor KTF)
1.5
1
1
IRes= |I1|+|I2|
0.5
0
10
IOp < k·IRes
Condition for stability:
1‘
sinx >
0
0
I F < k ⋅ 2 ⋅ I F ⋅ sin x
1
2⋅k
I
I
2
2
ü = 2K 2N =
=
x
n'
1 − cosx
sinx
(from previous transparency)
2
20
2 ⋅ I F ⋅ sin x
x
∫
o
IOp= |I1+I2|
IK
k>
K OB
4 ⋅ K OB − 1
10
20
t
20
1
or
k>
1
4 ⋅ K TF − K 2 TF
KOB= CT over-burdening factor
KTF= 1/KOB = CT over-dimensioning factor
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 240
Digital busbar protection 7SS5, Measuring technique
External fault, fault current with DC offset
I1
I2
2
2
I1
IOp= |I1+I2|
0
20
40
1
60
0
20
0
20
40
60
40
60
40
60
2
I2
0
20
40
60
k·IRes =k·(|I1|+|I2|)
1
2
t
2
IRes=|I1|+|I2|
1
∆I=IOp - IRes
1
0
20
1
0
20
40
Differential Protection Symposium
60
2
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 241
Digital busbar protection 7SS5, Measuring technique
Internal fault, fault current with DC offset
I1
I2
3
2
1
2
IOp= |I1+I2|
I1
0
20
40
60
40
60
1
0
I2
20
40
2
t
2
k·IRes =k·(|I1|+|I2|)
0
20
t
2
3
60
40
1
0
60
20
1
t
2
2
2
∆I=IOp - IRes
IRes=|I1|+|I2|
0
20
40
60
0.75
0.5 0
40
60
1.75
3
Differential Protection Symposium
20
Tripping!
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 242
CT dimensioning for busbar protection 7SS5, Example (1)
25 ⋅ 106
I N −T =
= 1440A
10 ⋅103 ⋅ 3
110kV
SSC‘‘= 4 GVA
110/10 kV
25 MVA
uT= 14%
TT= 60 ms
G
1500/1
2MW
600/1
300/1
150/1
5MW
10 kV
10 MVA
Xd‘‘= 15%
TG= 100 ms
300/1
300/1
ISt= 6·IN
Xd‘‘= 17%
TM= 35 ms
M
M
5MW
5MW
Differential Protection Symposium
I N −G =
10 ⋅10 6
= 577A
3
10 ⋅ 10 ⋅ 3
5 ⋅10 6
ΣI N − M -HV = 2 ⋅
= 577A
3
10 ⋅ 10 ⋅ 3
IF−T =
1.1 ⋅ 1440
= 11.3 kA
0.14
IF−G =
1.1 ⋅ 577
= 4.2 kA
0.15
ΣI F − M =
Belo Horizonte November 2005
1.1 ⋅ 577
= 3.7 kA
0.17
G. Ziegler, 10/2005
page 243
CT dimensioning for busbar protection 7SS5 and 7SS6, Example (2)
As worst case, the CT 150/1 A in bay 1 is considered.
Total fault current with a fault at the transformer HV terminals:
ΣI F = I F − T + I F − G + ΣI F − M = 11,3 + 4,2 + 3,7 = 19,2 kA
Equivalent time constant:
I
⋅ T + I F − G ⋅ TG + ΣI F − M ⋅ TM 11.3 ⋅ 60 + 4.2 ⋅ 100 + 3.7 ⋅ 35
TEquiv. = F − T T
=
= 64 ms
I F − T + I F − G + ΣI F − M
11.3 + 4.2 + 3.7
We consider a CT type 5P?, 30 VA, internal burden Pi= 15% (4.5 VA):
Connected burden Pa= 1 VA
CT over-dimensioning factor for 3ms saturation free time: KTF ca. 0.45
Corresponding to an overburdening factor of kOB= 1/KTF = 2.2
Checking of the k-setting
(Stability with symmetrical fault currents):
ALF ' =
ΣI F
I N − CT
⋅ K TF =
19 .200
⋅ 0 . 45 = 58
150
k>
k OB
4 ⋅ kOB − 1
ALF =
=
2,2
= 0 .5 (chosen: k=0.6)
4 ⋅ (2 .2 − 1)
Pa + Pi
1 + 4.5
⋅ ALF ' =
⋅ 58 = 9.3
PN + Pi
30 + 4.5
We finally choose: CT 5P10, 150/1, 30 VA, R2≤ 4.5 Ohm
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 244
Transient performance of iron closed CT cores (type TPX)
Over-dimensioning factor KTF for short time to saturation
1.5
1.5
KTF
1.4
TM
1.3
KTF
1.4
1.2
1.2
5 ms
1.1
1.1
1
1
0.9
0.9
0.8
4 ms
0.7
0.5
0.5
3 ms
0.3
0.2
0.2
0.1
0.1
10 20 30 40 50 60 70 80 90 100
3 ms
0.4
0.3
0
4 ms
0.7
0.6
0.4
5 ms
0.8
0.6
0
TM
1.3
0
0
1
2
3
4
6
7
8
9
10
TN
TN
Differential Protection Symposium
5
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 245
High impedance busbar protection
RCT
RCT
RCT
RCT
RCT: Resistance of CT secondary
winding
RL
RL
RL
RL
RL: Connection cable resistance
RRV: Relay series resistance
RRS: Relay shunt resistance
RRS
Varistor
IV
IS
RRV
∆I
Differential Protection Symposium
IR
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 246
HI busbar protection, calculation example
RL= 3 Ohm (max.)
IR=20 mA (fixed value)
RRV = 10 kOhm
RRS = 250 Ohm
Iv = 50 mA (at relay pick-up voltage)
Given: :n = 8 feeders
rCT = 600/1 A
UKN = 500 V
RCT = 4 Ohm
ImR = 30 mA (at relay pick-up voltage)
Primary pick-up current:
I F − min = rCT ⋅ (I R + IS + I V + n ⋅ I mR
I F − min =
Stability with external faults:
)
I F − through − max < rCT ⋅
600
⋅ (0.02 + 0.89 + 0.05 + 8 ⋅ 0.03 )
1
I F − min = 666A ⋅ (111%I N − CT )
Differential Protection Symposium
I F − through − max <
RR
⋅ IR
R L + R CT
600 10.000
⋅
⋅ 0.02
1
3+ 4
I F − through − max < 17 kA = 28 ⋅ I n
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 247
Busbar protection, Composite current type (7SS600):
Performance under unfavourable system earthing conditions
Busbar
2
1
3
3
2
IM=2·IL1 + 1·IL3+ 3 ·IE
=2·IF + 1 ·IF+ 3·3IF = +12 ·IF
IM=2·IL1 + 1·IL3 + 3 ·IE
=2 ·(–IF) + 1 ·(–IF) + 3·0= –3·IF
IOp=| IM1 + IM2 | = 9 ·IF
IRes=|IM1| +|IM2| = 15 ·IF
1
k=9/15 = 0.6
IOp
Fault L2-E
k=0.5
Faults in other phases:
Fault L1-E: IOp = (3+12) ·IF = 15 ·IF,
IRes= (3+12) ·IF = 15 ·IF,
k=1
Fault L3-E: IOp = (0+12) ·IF = 12 ·IF,
IRes= (0+12) ·IF = 12 ·IF,
k=1
Differential Protection Symposium
IRes
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 248
Busbar protection, Composite current type (7SS600):
Performance in networks with earth current limitation
IL =
110/10 kV
40 MVA
35MVA
10kV ⋅ 3
= 2 kA
I F = I E = 10/ 3 kV/6Ω ≈ 1 kA
RE= 6 Ohm (IE = 1 kA)
Worst case: Fault in phase L2
Restraint current:
Operating current:
Ph-E
I Res = 3 ⋅ 3 kA
I Op = 3 ⋅ I KE = 3 kA
k=
35 MW
I Op
I Re s
IL1
IL3
IE
2·IL1
IM-L
IL2
Differential Protection Symposium
3
3⋅ 3
= 0,57
Fault L2-E
IOp
IL3
=
k=0.5
|IM-L|
IRes
Load
Belo Horizonte November 2005
IRes
G. Ziegler, 10/2005
page 249
Differential Protection 7UT6
Remarkable Features
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 248
The 7UT6 Family
7UT6 differential protection
for
•Transformers
•Generators
• Motors
•Busbars
7UT612:
7UT613:
7UT633:
7UT635:
for protection objects with 2 ends
for protection objects with 3 ends
for protection objects with 3 ends
for protection objects with 5 ends
Differential Protection Symposium
(1/3 x 19’’ case 7XP20)
(1/2 x 19’’ case 7XP20)
(1/1 x 19’’ case 7XP20)
(1/1 x 19’’ case 7XP20)
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 249
7UT6: Hardware options
Relay version
current inputs
(normal)
(sensitive)
voltage inputs (Uph / UE)
Binary inputs
Output contacts
Life contact
LC Display
7UT612
7UT613
7UT633
7UT635
7 (7)1)
1
--3
4
1
4 rows3)
11 (6) 1)
1 2)
3/1
5
8
1
4 rows3)
11 (6) 1)
1 2)
3/1
21
24
1
Graphic
14 (12 1)
2 2)
--29
24
1
Graphic
1)
1A, 5A, (1A, 5A, 0.1A)
2)
link selectable normal/sensitive
3)
alpha-numeric
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 250
7UT6: Scope of functions
Function
ANSI No.
Function
Differential
87T/G/M/L
Overfluxing V/Hz
24
Earth differential
87 N
Breaker failure
50BF
Phase overcurrent,
50/51
Temperature monitoring
38
Neutral overcurrent IN>, t
50N/51N
Ground overcurrent (IE, t)
50G/51G
Hand reset trip
86
Unbalanced current I2>, t
46
Trip circuit supervision
74TC
Thermal overload IEC 60255-8
49
Therm. OL IEC 60354 (hot spot)
49
Differential Protection Symposium
ANSI No.
Binary inputs for tripping commands
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 251
7UT6: Application
(1)
∆
∆I
∆I
Shunt Reactor
G
Three winding
transformer
Two winding
transformer
∆I
Generator / Motor
Differential Protection Symposium
∆I
∆I
Transformer bank
(1-1/2-LS)
∆I
∆I
Busbars
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 252
7UT6: Application
Generation Unit
protection
(overall differential)
Y
∆
(2)
HI restricted earth fault protection
7UT6xx
7UT635
G
3~
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 253
7UT6:
selectable: I0-correction or restricted earth fault protection
YN
yn0
d5
R
S
T
49
(1)
49
(2)
50
51
∆ITE
∆IT
7UT613
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 254
7UT6: operating characteristic
Idiff >>
7
Locus of
internal faults
6
I Op
In
45°
5
S
operate
e2
p
lo
restrain
4
*)
3
2
Idiff >
1
e1
p
o
l
S
0 0
2
supplementary
restraint
4
6
8
10
12
14
16
IRes
*) Slope of add on characteristic:
In
7UT6 à as slope 1 (7UT5 à ½ of slope 1)
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 255
7UT6: Effect of supplementary restraint in case of CT saturation
Restrain
45°
Trip
Area of
add-on
restraint
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 256
Differential protection functions IDiff> and IDiff>>
Sampled
momentary values
Measuring value
processing
i1L
iRes = |i1|+ |i2|
Side 1
i2L
iOp = i1 + i2
Side 2
Average value
IStab = iRest
Fundamental wave:
IDiff = Eff(iDiff)50Hz
Operating characteristic,
Saturation detector
IDiff
IDiff>
IStab
&
Trip
IDiff>
≥1
Trip
IDiff>>
Motor start,
DCcomonent
Harmonic Analysis:
-2nd Harmon. Blocking
-Cross Blocking
iRes IRes
IDiff
IDiff
IDiff>>
I / InO
I / InO
iDiff
ms
iDiff
2·IDiff>>
ms
Fast tripping using sampled momentary values
ensures dependable operation in case of extreme CT saturation!
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 257
7SA6: Temperature monitoring
RS485 Interface
7XV5662-(x)AD10
7XV5662-(x)AD10
Two thermo-devices can be connected to the serial service interface (RS485)
Monitoring of up to 12 measuring points (6 per thermo-device)
- each with two pick-up levels
Display of the measured temperatures
- directly at the thermo-device (which can also be used stand alone)
- at the relay
One input is reserved for hot spot monitoring (measurement of oil temperature)
Thermistors: Pt100, Ni100 or Ni120
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 258
7UT6: Temperature monitoring with hot spot calculation (1)
Example: Natural cooling
Θ h = Θ O + H gr ⋅ k Y
Θh= hot spot temperature
Θh= oil temperature
Hgr=hot-spot-to-oil temperature gradient
k= load factor I/In
Y= winding exponent
Aging rate:
Oil Temp.
HV
LV
Aging at Θh
V=
= 2(Θ h −98)/6
Aging at 98°C
98O is reference for
the aging of
Cellulose insulation
Mean value of aging during a fixed time interval:
T
2
1
L=
⋅ ∫ V ⋅ dt
T2 − T1 T1
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 259
7UT6: Temperature monitoring with hot spot calculation (1)
Example: Natural cooling
Θ h = Θ o + H gr ⋅ k Y ≈ 73 + 23 ⋅1.151.6 = 102°C
(L)
V = 2(Θ h −98)/6 = 2(102−98)/6 ≈ 1.6
108°C
k,
V,
L
98°C
102°C
73°C
Θh Hot spot
temp.
Θo oil temp.
(from thermodevice)
[°C]
Θh
Θo
1.6
k (I/In)
V (relative
aging)
L (mean
value of V)
1.15
t
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 260
7UT6: Commissioning und service tool
(1)
WEB-Technology
Access to WEB Browser
Help system in the
INTRANET / INTERNET
http://www.siprotec.com
Relay homepage address of :
http://141.141.255.160
IP-address can be set with
program DIGSI 4 at the front or
service interface of the relay
1. Serial connection
Directy or with modem
to standard DIAL-UP
network
2. HTM L page view
at IP-address of the relay
http://141.141.255.160
Differential Protection Symposium
WEB server
in relay firmware
Server sends HTML pages and
JAVA code to WEB Browser via
DIAL-UP connection
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 261
7UT6: Commissioning and service tool
(2)
Current phasors of all terminals can be displayed
Transformer YNd11d11, 110/11/11kV, 38.1MVA,
IL2S2à wrong polarity
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 262
7UT6: Commissioning and service tool (3)
Operating/restraint position can be displayed
Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2à wrong Polarität
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 5/2005
page 263
Power Transmission and Distribution
Differential Protection (7UT)
Determination of the Transformer Vector Group
Transformer with Vector Group Yy0
7UT612
80 MVA
Yy0
2500A/1A
20 kV
110 kV
500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 2
Method of Vector Group Determination (ExampleYy0)
IL1,S2
Side 2:
Side 1:
2L1
1L1
IL1,S1
2L2
1L2
2L3
1L3
IL1,S2 = IL1
UL1,S1
UL1,S2
IL1,S1
UL3,S2
UL2,S2
UL3,S1
UL2,S1
0°
Vector group is
Yy0
PTD PA13 N. M Tests 7UT 05/03 No. 3
Transformer Protection
7UT612
80 MVA
Yd11
2500A/1A
20 kV
110 kV
500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 4
Method of Vector Group Determination (ExampleYd11)
IL1,S2
Side 2:
Side 1:
2L1
IL1,S1
2L2
1L1
1L2
2L3
1L3
IL1,S2 = IL1 - IL2
IL1,S1
UL1,S1
UL1,S2
UL2,S2
UL3,S1
UL2,S1
UL3,S2
Vector group is
Y d 11
330°
(n * 30°)
PTD PA13 N. M Tests 7UT 05/03 No. 5
Definitions in SIPROTEC 4 Relays
Vector definition to a node is positive
The shown vectors or phase angles are transformed in
this positive definition
The phase angle is displayed mathematics positive.
The reference phase is always phase L1 on side 1
How to see the vector group Yd11?
Original
Siprotec 4 (Browser)
Phase angles
Side 1: 0°
(reference phase)
Side 2: 210°
Please subtract 180°,
than you get 30°
(360° - 30° = 330°)
PTD PA13 N. M Tests 7UT 05/03 No. 6
Web Tool (Browser) Vector group YNd11
PTD PA13 N. M Tests 7UT 05/03 No. 7
Vector Group Determination via Fault Record
IL1;Side 2 lags 150° or leads 210°
Star point is towards the protected object
IL1;Side 1
Way 1:
IL1 Side: 150° + 180° = 330°
Way 2:
IL1 Side: 210° - 180° = 30°
leads 30° or lags 330°
Phase shift is according the vector group definition 330° → 11 * 30°
PTD PA13 N. M Tests 7UT 05/03 No. 8
Digital Transformer Differential
Protection
I0-correction
+ vector group adaptation
Differential Protection Symposium
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 1
Transformer differential protection with I0-correction
External fault
L3
L1
L2
L2
L3
L1
Yd5
3
3
3
L1
L2
L3
1
3
1:3
Vector group adaptation
3
1
I0-correction
Differential Protection Symposium
1
2
3
2
∆
∆
∆
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 2
Transformer differential protection with I0-correction
Internal fault
L3
L1
L2
L2
L3
L1
Yd5
3
3
3
L1
L2
L3
1
3
1:3
1
I0-correction
Differential Protection Symposium
Vector group adaptation
1
1
3
2
∆
∆
∆
3
Belo Horizonte November 2005
G. Ziegler, 10/2005
page 3
Power Transmission and Distribution
Differential Protection (7UT)
Determination of the Transformer Vector Group
Transformer with Vector Group Yy0
7UT612
80 MVA
Yy0
2500A/1A
20 kV
110 kV
500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 2
Method of Vector Group Determination (ExampleYy0)
IL1,S2
Side 2:
Side 1:
2L1
1L1
IL1,S1
2L2
1L2
2L3
1L3
IL1,S2 = IL1
UL1,S1
UL1,S2
IL1,S1
UL3,S2
UL2,S2
UL3,S1
UL2,S1
0°
Vector group is
Yy0
PTD PA13 N. M Tests 7UT 05/03 No. 3
Transformer Protection
7UT612
80 MVA
Yd11
2500A/1A
20 kV
110 kV
500A/1A
PTD PA13 N. M Tests 7UT 05/03 No. 4
Method of Vector Group Determination (ExampleYd11)
IL1,S2
Side 2:
Side 1:
2L1
IL1,S1
2L2
1L1
1L2
2L3
1L3
IL1,S2 = IL1 - IL2
IL1,S1
UL1,S1
UL1,S2
UL2,S2
UL3,S1
UL2,S1
UL3,S2
Vector group is
Y d 11
330°
(n * 30°)
PTD PA13 N. M Tests 7UT 05/03 No. 5
Definitions in SIPROTEC 4 Relays
Vector definition to a node is positive
The shown vectors or phase angles are transformed in
this positive definition
The phase angle is displayed mathematics positive.
The reference phase is always phase L1 on side 1
How to see the vector group Yd11?
Original
Siprotec 4 (Browser)
Phase angles
Side 1: 0°
(reference phase)
Side 2: 210°
Please subtract 180°,
than you get 30°
(360° - 30° = 330°)
PTD PA13 N. M Tests 7UT 05/03 No. 6
Web Tool (Browser) Vector group YNd11
PTD PA13 N. M Tests 7UT 05/03 No. 7
Vector Group Determination via Fault Record
IL1;Side 2 lags 150° or leads 210°
Star point is towards the protected object
IL1;Side 1
Way 1:
IL1 Side: 150° + 180° = 330°
Way 2:
IL1 Side: 210° - 180° = 30°
leads 30° or lags 330°
Phase shift is according the vector group definition 330° → 11 * 30°
PTD PA13 N. M Tests 7UT 05/03 No. 8
Download