Manual No. '14 • KX-DB-203
updated December 03, 2014
DATA BOOK
VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS
KXZ Outdoor units
Hi-COP series
Single use (Used also for combination)
FDC224KXZXE1, 280KXZXE1, 335KXZXE1
Combination use
FDC450KXZXE1, 500KXZXE1, 560KXZXE1, 615KXZXE1, 670KXZXE1, 735KXZXE1, 800KXZXE1,
850KXZXE1, 900KXZXE1, 950KXZXE1, 1000KXZXE1
•
Note:
(1) Regarding the indoor unit series, refer to the No.’14 • KX-DB-206.
'14 •• KX-DB-203
KX-DB-203
'14
PREFACE
PREFACE
Combination table for KX4, KX6 and KXZXE1 series
Connectable
remote control
3-wire type
Category
Outdoor unit
Indoor unit
Same or
Same series Same series Mixed series Mixed series Mixed series Mixed series Mixed series Same series
RC-E1
3-wire type
RC-E1R
2-wire type
RC-E3
RC-E4
RC-E5
RC-EX1A
KXE4
KXE4(A)
KXE4A
KXE4A
KXE4A
KXE4R
KXE4BR
KXE5R
KXE4R
KXE4BR
KXE5R
KXE4A
KXE4R
KXE4BR
KXE5R
KXE4R
KXE4BR
KXE5R
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
FDCA-HKXE4
5HP
YES[D]
YES[D]
NO
NO
NO
NO
NO
NO
FDCA-HKXE4
8-48HP
NO
YES[D]
NO
NO
NO
NO
NO
NO
FDCA-HKXE4A
FDCA-HKXE4R
5HP
5,6HP
NO
YES[D]
YES[D] 1
NO
NO
YES[D]
NO
NO
8-48HP
8-48HP
8-48HP
8-48HP
NO
YES[D]
YES[D]
YES[D]
YES[D]
YES[D]
YES[D]
FDC-KXE6
4,5,6HP
NO
NO
NO
NO
NO
NO
NO
YES[B] 6
FDC-KXE6
8-48HP
NO
NO
NO
NO
NO
YES[C]
YES[C]
YES[B]
FDC-KXZXE1
8-36HP
NO
NO
NO
NO
NO
NO
NO
YES[A]
FDCA-HKXE4A
Heat pump FDCA-HKXE4R
(2-pipe)
FDCA-HKXE4BR
systems
FDCA-HKXE4D
1
YES[D]
1 Except FDKA71KXE5R
Note (1) YES: Connectable (See following table in detail), NO: Not connectable
Connected indoor unit
Outdoor unit
Dip switch
setting of
Same series Mixed series outdoor unit
KXZE1/KXE6
Superlink
protocol
Limitation
YES[A] 2
KXZXE1
KXE6
Ⅱ(New)
New (for
New (for
KXZXE1/KXE6) KXZXE1/KXE6)
YES[B] 2
KXE6
KXE6
Ⅱ(New)
New (for
New (for
KXZXE1/KXE6) KXZXE1/KXE6)
YES[C]
KXE6
KXE4 series
YES[D]
KXE4 series
KXE4 series KXE4 series
KXE6 & KXE4
Ⅰ(Previous)
series
Previous
(for KXE4)
Previous
(for KXE4)
Previous
(for KXE4)
Previous
(for KXE4)
2 If outdoor unit system (YES [A] or YES [B]) is connected to other outdoor unit systems (YES [C] and/or YES [D]) in one
Superlink network, the dip switch of outdoor unit KXZXE1 (YES [A]) or KXE6 of (YES [B]) should be set from (New) to (Previous).
In this case the Superlink protocol and limitation of outdoor unit system (YES [A] or YES [B]) are switched to Previous (for KX4).
(2) Combination with new Central control, PC windows central control and BMS interface unit
YES[A]
&
YES[B]
YES[C]
&
YES[D]
Connectable
I/U
Superlink
protocol
Connectable
network
Connectable
I/U
Superlink 5
protocol
Connectable
network
Central control, PC windows central control and BMS interface unit
SC-SL1N-E SC-SL2NA-E SC-SL4-AE/BE SC-WGWNB-A/B SC-LGWNA-A SC-BGWNA-A/B
128
128
96
128
16
64
(128x1)
(64x2) 3
(48x2)
(64x2) 3
New
New
New
New
New
1
1
1
2
2
96 4
(48x2)
96 4
(48x2)
New
2
16
48
144
(48x3)
96 4
(48x2)
Previous
Previous
Previous
Previous
Previous
Previous
1
1
3
2
2
2
3 Maximum number of AC Cell is limited up to 96.
In case the number of connected indoor units are more than 96, some AC Cells should hold 2 or more indoor units.
4 In case of other Central control like SC-SLxN-E is connected in the same network, the connectable indoor unit is limited up to 64(32x2).
5 In case of previous Superlink protocol, the Superlink mode of new central control should be set "Previous".
6 In case of (YES[A] or YES[B]), previous central control is available to use. But the limitation of connectable indoor unit and so on is
complied with the rule of previous Superlink.
ht,9%#
'14 • KX-DB-203
CONTENTS
1. GENERAL INFORMATION ............................................................................... 1
1.1 Specific features............................................................................................ 1
1.2 How to read the model name ........................................................................ 1
1.3 Table of models ............................................................................................. 2
1.4 Outdoor units combination table ................................................................... 3
2. OUTDOOR UNIT ................................................................................................ 4
2.1 Specifications ................................................................................................ 4
2.2 Exterior dimensions....................................................................................... 6
2.3 Electrical wiring ............................................................................................. 8
2.4 Noise level................................................................................................... 10
3. RANGE OF USAGE & LIMITATIONS .............................................................. 11
4. PIPING SYSTEM ............................................................................................. 18
5. SELECTION CHART........................................................................................ 20
6. WARNINGS ON REFRIGERANT LEAKAGE ................................................ 35
'14 • KX-DB-203
1. GENERAL INFORMATION
1.1 Specific features
Connectable indoor capacity
Capacity from 80% to 200% or 160% is possible.
Item
Number of connectable units
Model
1
1
1
2
2
2
2
2
3
3
3
3
3
3
FDC224KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC450KXZXE1
FDC500KXZXE1
FDC560KXZXE1
FDC615KXZXE1
FDC670KXZXE1
FDC735KXZXE1
FDC800KXZXE1
FDC850KXZXE1
FDC900KXZXE1
FDC950KXZXE1
FDC1000KXZXE1
to
to
to
to
to
to
to
to
to
to
to
to
to
to
29
37
44
60
53
59
65
71
78
80
80
80
80
80
Connectable capacity
180
224
268
360
400
448
492
536
588
640
680
720
760
800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
448
560
670
900
800
896
984
1072
1176
1280
1360
1440
1520
1600
Note
For outdoor unit, EN61000-3-2 and EN61000-3-12 are not applicable as consent by the utility company or notification to the utility company is given before usage.
1.2
How to read the model name
(1) Outdoor unit
Example:
FDC 735 KXZX E
1
Series No.
Application power source...See the specifications
Multi KXZX series
Nominal capacity (nominal cooling capacity : 73.5kW)
Model name (Outdoor unit)
(2) Indoor unit
Example: FDT 28 KX
E
6F
Series No.
Application power source...See the specifications
Multi KX series
Nominal capacity (nominal cooling capacity : 2.8 kW)
Model name Indoor unit : FDT, FDTC, FDTW, FDTS,
FDTQ, FDU, FDUM, FDUT, FDK, FDE, FDFL, FDFU, FDFW, FDUH,
FDU-F
-
-
'14 • KX-DB-203
1.3 Table of models
Capacity
Model
Ceiling cassette-4 way type
(FDT)
Ceiling cassette-4 way compact type
(FDTC)
Ceiling cassette-2 way type
(FDTW)
Ceiling cassette-1 way type
(FDTS)
Ceiling cassette-1 way compact type
(FDTQ)
Duct connected-High static pressure type
(FDU)
Duct connected-Low/Middle static pressure type
(FDUM)
Duct connected (thin)-Low static pressure type
(FDUT)
Wall mounted type
(FDK)
Ceiling suspended type
(FDE)
Floor standing (with casing) type
(FDFL)
Floor standing (without casing) type
(FDFU)
Floor standing-2 way type
(FDFW)
Duct connected-compact and Flexible type
(FDUH)
Outdoor air processing unit
(FDU-F)
Outdoor units to be combined
(FDC)
15
○
22
○
28
36
45
56
71
90
112
140
160
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
224
280
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
(500)
○
(850)
○
(1300)
○
(1800)
FDC224KXZXE1-FDC1000KXZXE1
Note (1) Reference No. of data book : ’14·KX-DB-206
-
2-
#
'14 • KX-DB-203
1.4 Outdoor units combination table
Item Combination outdoor unit models
Indoor unit
Number of
connectable units
2 to 60 units
-
Connectable
capacity
360 _ 900
400 _ 800
-
448
896
2 to 59 units
1
1
492
984
2 to 65 units
-
-
2
536
FDC735KXZXE1
2
1
-
588
FDC800KXZXE1
1
2
-
640
FDC850KXZXE1
-
3
-
680
FDC900KXZXE1
-
2
1
720
FDC950KXZXE1
-
1
2
760
FDC1000KXZXE1
-
-
3
800
FDC450KXZXE1
FDC224
KXZXE1
2
FDC280
KXZXE1
-
FDC335
KXZXE1
-
FDC500KXZXE1
1
1
FDC560KXZXE1
-
2
FDC615KXZXE1
-
FDC670KXZXE1
Models
(a)
_
_
_ 1072
_ 1176
_ 1280
_ 1360
_ 1440
_ 1520
_ 1600
2 to 53 units
2 to 71 units
3 to 78 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
Outdoor unit side branch pipe set (Option)
Outdoor unit
Branch pipe set
For two units (for FDC450KXZXE1-670KXZXE1)
DOS-2A-3
For three units (for FDC730KXZXE1-1000KXZXE1)
DOS-3A-3
Note (1) Be sure to use this when combining units.
(b)
Branch pipe set (Option)
Total capacity downstream
(c)
Branching pipe set
Less than 180
DIS-22-1G
180 or more but less than 371
DIS-180-1G
371 or more but less than 540
DIS-371-1G
540 or more
DIS-540-3
Header pipe set (Option)
Total capacity downstream
Header set model type
Number of branches
Less than 180
HEAD4-22-1G
4 branches at the most
180 or more but less than 371
HEAD6-180-1G
6 branches at the most
371 or more but less than 540
HEAD8-371-2
8 branches at the most
540 or more
HEAD8-540-3
8 branches at the most
-
-
Power factor
-
Sound pressure level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Motor
Starting method
Crankcase heater
Refrigerant equipment
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Static pressure
Shock & vibration absorber
FDC335KXZXE1
28.0
31.5
3 Phase 380-415V 50Hz / 380V 60Hz
6.95
6.83
11.7 / 10.7
11.7 / 10.7
90 / 90
89 / 89
56 / 56
33.5
37.5
dB(A)
4.98
5.56
8.7 / 8.0
9.6 / 8.8
87 / 87
88 / 88
56 / 57
mm
1690×1350×720
kg
280
kW
A
%
325
3.23×1
W
33×1
-
M fin & inner grooved tubing
kg
l
11.0
2.25(M-MA32R)
Electronic expansion valve
R410A
Microcomputer controlled De-Icer
11.5
2.9(M-MA32R)
Propeller fan × 2
W
m3/min
Pa
220 / 200
mm(in)
Gas line:φ19.05(3/4")
MPa
PCB003Z858
PCB003Z860
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling*1
Heating*2
5.72×1
40×1
Indoor air temperature
DB
WB
19 ˚C
27 ˚C
20 ˚C
-
Outdoor air temperature
DB
WB
35 ˚C
24 ˚C
7 ˚C
6 ˚C
Standards
386×2
Direct start
220 / 200
280 / 200
Max.50
Rubber mount (for compressor)
Compressor overheat protection / Overcurrent protection
Power transistor overheating / Protection / Abnormal high pressure protection
Liquid line:φ12.7(1/2")
Liquid line:φ9.52(3/8")
Gas line:φ25.4(1")
Gas line:φ22.22(7/8")
(φ22.22(7/8"))
Gas line:Brazing / Liquid line:Flare
High 4.15 Low 2.21
Hole for drain (φ20 × 10pcs , φ45 × 3pcs)
Necessary (both Liquid & Gas lines)
PCB003Z859
PCB003Z859
PCB003Z861
PCB003Z861
Adapted to RoHS directive
ISO-T1
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) Refrigerant piping size applicable to European installations are shown in parentheses.
'14 • KX-DB-203
PCB003Z839
Connecting method
MAX. Pressure
Drain
Insulation for piping
Accessories
Exterior dimensions
Electrical wiring
GUC5185ND47V×1
4.60×1
Direct line starting
Safety equipment
Installation data
Refrigerant piping size
2048×1350×720
GTC5150NC47LF×1
kW
8.68
8.39
14.7 / 13.4
14.3 / 13.1
90 / 90
89 / 89
62 / 57
2. OUTDOOR UNIT
Running current
Cooling
Heating
Cooling
Heating
Cooling
Heating
FDC280KXZXE1
22.4
25.0
2.1 Specifications
Power consumption
kW
FDC224KXZXE1
• Single use (Used also for combination)
Models
Nominal cooling capacity *1
Nominal heating capacity *2
Power source
Combination unit
Power source
Nominal cooling capacity *1
Nominal heating capacity *2
Power consumption
Running current
Power factor
Net weight
kW
Cooling
Heating
Cooling
Heating
Cooling
Heating
Liquid line
Refrigerant piping size Gas line
Oil equalization
kW
A
%
kg
-
5-
Combination unit
Power consumption
Running current
Power factor
Net weight
kW
Cooling
Heating
Cooling
Heating
Cooling
Heating
Liquid line
Refrigerant piping size Gas line
Oil equalization
FDC500KXZXE1
FDC560KXZXE1
FDC615KXZXE1
FDC670KXZXE1
FDC224KXZXE1
FDC224KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC224KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC335KXZXE1
kW
A
%
kg
50.0
56.0
11.8
12.3
20.0 / 18.5
21.2 / 19.4
89 / 89
88 / 88
605
FDC735KXZXE1
FDC800KXZXE1
FDC850KXZXE1
FDC900KXZXE1
FDC950KXZXE1
FDC1000KXZXE1
FDC224KXZXE1
FDC224KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC224KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC335KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC335KXZXE1
FDC335KXZXE1
95.0
106.0
24.3
23.5
41.0 / 37.6
40.1 / 36.7
90 / 90
89 / 89
975
100.0
112.0
25.9
25.1
43.7 / 40.0
42.8 / 39.2
90 / 90
89 / 89
975
73.5
82.5
17.1
18.2
29.4 / 27.0
31.4 / 28.7
88 / 88
88 / 88
885
80.0
90.0
19.3
19.7
32.9 / 30.1
33.5 / 30.7
89 / 89
89 / 89
930
mm
Notes (1) The data are measured at the following conditions.
Indoor air temperature
DB
WB
19 ˚C
27 ˚C
20 ˚C
-
Outdoor air temperature
DB
WB
35 ˚C
24 ˚C
7 ˚C
6 ˚C
Standards
67.0
75.0
17.4
16.8
29.3 / 26.8
28.6 / 26.2
90 / 90
89 / 89
650
3 Phase 380-415V 50Hz / 380V 60Hz
85.0
90.0
95.0
100.0
21.1
22.7
20.6
21.9
35.6 / 32.6
38.4 / 35.1
35.2 / 32.2
37.4 / 34.3
90 / 90
90 / 90
89 / 89
89 / 89
975
975
φ15.88
φ31.75(φ34.92)
φ9.52
φ38.1
Adapted to RoHS directive
ISO-T1
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) Refrigerant piping size applicable to European installations are shown in parentheses.
'14 • KX-DB-203
PCB003Z839
Item
Operation
Cooling*1
Heating*2
3 Phase 380-415V 50Hz / 380V 60Hz
56.0
61.5
63.0
69.0
13.9
15.6
13.7
15.2
23.5 / 21.5
26.4 / 24.1
23.3 / 24.4
26.0 / 23.8
90 / 90
90 / 90
89 / 89
89 / 89
650
650
φ12.7
φ28.58
φ9.52
45.0
50.0
10.0
11.1
17.5 / 16.0
19.2 / 17.6
87 / 87
88 / 88
560
mm
Models
Power source
Nominal cooling capacity*1
Nominal heating capacity*2
FDC450KXZXE1
• Combination use
Models
#
2.2 Exterior dimensions
Models FDC224KXZXE1
19.05
-
-
'14 • KX-DB-203
PCB003Z858
Models FDC280KXZXE1, 335KXZXE1
280: 22.22
335: 25.4
280: 9.52
335: 12.7
-
-
'14 • KX-DB-203
PCB003Z859
PWB3-1
CNN2 GN
CNN9 BK
CNN6 PK
CNQ1 WH
BK
BK
CNN1 RD
BK
BL
BK
CNM1 GY
BL
CNR1 WH
SV1
BL
CNW RD
GN
SV11
CNN8 PK
CNL2 WH
RD
WH
BK PSL
CNL1 BL
RD
WH
BK PSH
L1o L2o L3o No
BK
WH
RD
RD
WH
BL
Circuit
breaker
Earth leakage
breaker
(Impulse
withstanding type)
CNZ1 RD
CT1
CNH BL
52X1-2
52X1-1
Power source
3 Phase
380-415V 50Hz
/380V 60Hz
E
SV6
20S
BL
Noise filter
BK
CH1
L1i L2i L3i Ni
BR
RD
L3
RD
WH
BL
BK
YE/GN
63H1-1
52X1-2
SW1
7SEG1
CNY WH
7SEG2
CNG1 BL
52X1-4
52X1-3
RD
RD
SW2
LED1
SW3
RD
WH
BL
ON
OFF
AC1 AC2 AC3
SW4
1 2 3 4 5 6 7 8
CONTROL
PWB1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CNS1 GN
+
C1-2
CNV
SW8
J11
SW7
J12
J13
J14
J15
CNS2 RD
PC
(RS232C)
J16
WH
Silent mode
input
WH
External
input
WH
Demand
input
R1-4
RD
BL
GY
GY
1 2 3 4 5 6 7 8
CNG2 WH
SW6
WH
Cooling/Heating
forced input
WH
RD
R1-3
52X1-4
SW5
LED3
SW9
+
C1-1
52X1-3
LED2
+
BL
YE L1-2 WH
BL
-
WH
DM1
YE L1-1
R1-2
RD
R1-1
RD
Reserve
output
Operation
output
Trouble
output
2.3 Electrical wiring
FMC1
52X1-1
Models FDC224KXZXE1
TB1
L1
L2
L3
N
Signal line
WH
WH
BL
BK
WH
CNSL1,2
BK
NETWORK CONNECTOR
BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN
OUTDOOR UNITS ON THE SAME REFRIGERANT LINE.
BETWEEN OUTDOOR UNITS ON THE DIFFERENT
REFRIGERANT LINES.
Defrost recover temp
Defrost start temp
Spare
Inspection(Red)
Normal(Yellow)-Flashing
Normal(Green)
Service(green for service)
D.C.reactor
D.C.reactor
Mark
PSH
PSL
PWB1-3
R1-1-1-4
SV1
SV6
SV11
SW1
SW2
SW3-1
SW3-2 ON
OFF
SW3-3
SW3-4 ON
OFF
SW3-5 ON
OFF
SW3-6
SW3-7 ON
OFF
SW3-8
t°
BK
BK
BK
t°
t°
Tho-C1
t°
CNU1
BL
Tho-P1
t°
BK
BK
BK
BK
YE
BK
t°
CNP1
YE
V(White)
W(Blue)
A1 B1
Compressor
Terminal block
A2 B2
Parts name
High pressure sensor
Low pressure sensor
Printed wiring board(PCB)
Rush current suppression resistor
Solenoid valve(CM1:bypass)
Solenoid valve(oil separator CM1)
Solenoid valve(gas bypass)
Address setting SW outdoor unit No.(2 digits)
Address setting SW outdoor unit No.(1 digit)
inspection LED reset
Auto backup operation
Regular operation
Spare
Refrigerant quantity check
Regular operation
Check operation
Regular operation
Spare
Forced cooling/heating
Regular operation
Spare
BK
U(Red)
t°
CNF2
GN
Tho-H
EEVH2
t°
CNF1
WH
Tho-SC
EEVSC
t°
CNB4
RD
Tho-R4
EEVH1
t°
Tho-R3
M
Tho-R2
M
CNB3
BK
Mark
SW4-1-4
SW4-5
SW4-6
SW4-7
SW4-8
SW5-1 ON
OFF
SW5-2 ON
OFF
SW5-3 ON
OFF
SW5-4
SW5-5 ON
OFF
SW5-6-8
SW6-1-3
SW6-4 ON
OFF
SW7
SW8
SW9
Parts name
Model setting
Spare
Spare
Address setting switch(master・slave)
Address setting switch(master・slave)
Trial operation
Regular operation
Trial operation mode/cooling
Trial operation mode/heating
Pump down operation
Regular operation
Spare
Super Link communication
Super Link communication
Spare
Spare
High Head
Standard
Data clear/insert
7-segment indicate(unit's place)
7-segment indicate(ten's place)
Mark
TB1,2
Tho-A
Tho-C1
Tho-D1
Tho-H
Tho-P1
Tho-R1
Tho-R2
Tho-R3
Tho-R4
Tho-S
Tho-SC
20S
52X1-1-1-4
63H1-1
7SEG1
7SEG2
Parts name
Terminal block
External air thermistor
Under-dome thermistor
Discharge pipe thermistor
Sub-cooling coil thermistor 2
Power transistor thermistor
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(inlet)
Heat exchanger thermistor(inlet)
Suction pipe thermistor
Sub-cooling coil thermistor 1
4way valve
Solenoid for CM
High pressure switch(for protection)
7-segment L.E.D.(function indication)
7-segment L.E.D.(data indication)
Color mark
Mark
BK
BL
BR
GN
GY
OR
RD
WH
YE
PK
Color
Black
Blue
Brown
Green
Gray
Orange
Red
White
Yellow
Pink
Yellow
YE/GN
/Green
'14 • KX-DB-203
PCB003Z860
Parts name
Crankcase heater
Compressor motor
Connector
Current sensor
Electrolytic capacitor
Diode module
Expansion valve for heating
Expansion valve for SC
Fuse
Fan for IPM
Blower motor
Intelligent power module
Set up model(volt)
External input select level/pulse
BK
BL
OR
YE
WH
M
Tho-A
W
M
Tho-S
FMo2
Tho-D1
M
CNB2
RD
CNTH WH
CNEEV3 WH
RD
CNEEV2 BL
BL
OR
YE
WH
CNEEV1 RD
Tho-R1
FMo1
RD F(4A)
MS
3〜
CNA3 CNA1
WH WH
t°
CNI3 BK
V
CNFAN2 RD
RD
CNFAN1 WH
BL
OR
YE
WH
CNX1
YE
BK
Meaning of marks
Mark
CH1
CM1
CNA-Z
CT1
C1-1,2
DM1
EEVH1,2
EEVSC
F
FMC1
FMo1,2
IPM
J11,12
J13
J14
J15
J16
LED1
LED1(INV)
LED2
LED3
L1-1,2
L3
LED1
(INV)
RD F(4A)
U
CM1
TB2
A1
B1
A2
B2
CNI1
WH
WH
OR
YE
BL
GN
PK
WH
OR
YE
BL
GN
PK
BK
RD
BK
RD
RD
P
IPM1
U V W
BL
-
CNI2 WH
CNA WH
N
RD
WH
-
CNR WH
Inverter
PWB2-1
FMC1
52X1-1
BK
CNN2 GN
CNN6 PK
CNN7 GN
CNQ1 WH
BK
BK
WH
RD
RD
CNN8 PK
BK
SW1
7SEG1
1 2 3 4 5 6 7 8
52X1-4
LED2
SW5
1 2 3 4 5 6 7 8
LED3
CNG2 WH
SW6
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CNS1 GN
CNV
SW9
SW8
L1-1
YE L1-2 WH
WH
BL
YE
RD
WH
BK PSH
CNG1 BL
SW4
CONTROL
PWB1
+
YE L1-3 WH
BL
CNL1 BL
CNY WH
7SEG2
52X1-2
SW2
SW3
ON
OFF
RD
WH
BL
-
RD
WH
BK PSL
CNH BL
AC1 AC2 AC3
DM1
CNL2 WH
CNZ1 RD
LED1
52X1-3
BK
BL
CNN1 RD
BK
BL
CNM1 GY
20UF
BL
BK
BR
CNR1 WH
CT1
RD
RD
RD
R1-1
R1-2
RD
R1-5
RD
CNW RD
GN
SV1
L1o L2o L3o No
RD
WH
BL
52X1-1
Power source
3 Phase
380-415V 50Hz
/380V 60Hz
BK
RD
WH
BL
Circuit
breaker
Earth leakage
breaker
(Impulse
withstanding type)
L1i L2i L3i Ni
GN E Noise filter
PWB3-2 CN1
SV6
20S
BL
GN
BK
CH1
L1o L2o L3o No
RD
RD
WH
BL
BK
L1i L2i L3i Ni
GN E Noise filter
PWB3-1 CN1
L3
RD
WH
BL
BK
YE/GN
63H1-1
52X1-2
J11
SW7
J12
J13
J14
J15
CNS2 RD
PC
(RS232C)
J16
Reserve
output
Operation
output
Trouble
output
WH
Cooling/Heating
forced input
WH
Silent mode
input
WH
External
input
WH
Demand
input
Models FDC280KXZXE1, 335KXZXE1
TB1
L1
L2
L3
N
R1-3
52X1-4
+
C1-2
WH
RD
+
C1-1
52X1-3
RD
BL
GY
Signal line
TB2
A1
B1
A2
B2
WH
WH
BL
BK
WH
CNSL1,2
BK
NETWORK CONNECTOR
EEVH2
BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN
OUTDOOR UNITS ON THE SAME REFRIGERANT LINE.
BETWEEN OUTDOOR UNITS ON THE DIFFERENT
REFRIGERANT LINES.
Inspection(Red)
Normal(Yellow)-Flashing
Normal(Green)
Service(green for service)
D.C.reactor
D.C.reactor
t°
t°
t°
t°
BK
BK
t°
BK
BK
BK
BK
BK
BK
YE
t°
t°
V(White)
W(Blue)
A1 B1
Compressor
Terminal block
A2 B2
Parts name
High pressure sensor
Low pressure sensor
Printed wiring board(PCB)
Rush current suppression resistor
Solenoid valve(CM1:bypass)
Solenoid valve(oil separator CM1)
Address setting SW outdoor unit No.(2 digits)
Address setting SW outdoor unit No.(1 digit)
inspection LED reset
Auto backup operation
Regular operation
Spare
Refrigerant quantity check
Regular operation
Check operation
Regular operation
Spare
Forced cooling/heating
Regular operation
Spare
Mark
SW4-1-4
SW4-5
SW4-6
SW4-7
SW4-8
SW5-1 ON
OFF
SW5-2 ON
OFF
SW5-3 ON
OFF
SW5-4
SW5-5 ON
OFF
SW5-6-8
SW6-1-3
SW6-4 ON
OFF
SW7
SW8
SW9
Parts name
Model setting
Spare
Spare
Address setting switch(master・slave)
Address setting switch(master・slave)
Trial operation
Regular operation
Trial operation mode/cooling
Trial operation mode/heating
Pump down operation
Regular operation
Spare
Super Link communication
Super Link communication
Spare
Spare
High Head
Standard
Data clear/insert
7-segment indicate(unit's place)
7-segment indicate(ten's place)
Mark
TB1,2
Tho-A
Tho-C1
Tho-D1
Tho-H
Tho-P1
Tho-R1
Tho-R2
Tho-R3
Tho-R4
Tho-S
Tho-SC
20S
20UF
52X1-1-1-4
63H1-1
7SEG1
7SEG2
Parts name
Terminal block
External air thermistor
Under-dome thermistor
Discharge pipe thermistor
Sub-cooling coil thermistor 2
Power transistor thermistor
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(inlet)
Heat exchanger thermistor(inlet)
Suction pipe thermistor
Sub-cooling coil thermistor 1
4way valve
Capacity control
Solenoid for CM1
High pressure switch(for protection)
7-segment L.E.D.(function indication)
7-segment L.E.D.(data indication)
Color mark
Mark
BK
BL
BR
GN
GY
OR
RD
WH
YE
PK
Color
Black
Blue
Brown
Green
Gray
Orange
Red
White
Yellow
Pink
Yellow
YE/GN
/Green
'14 • KX-DB-203
PCB003Z861
Defrost recover temp
Defrost start temp
Spare
Mark
PSH
PSL
PWB1-3
R1-1-1-5
SV1
SV6
SW1
SW2
SW3-1
SW3-2 ON
OFF
SW3-3
SW3-4 ON
OFF
SW3-5 ON
OFF
SW3-6
SW3-7 ON
OFF
SW3-8
BK
U(Red)
t°
CNU1
BL
Tho-C1
EEVSC
t°
CNP1
YE
Tho-P1
EEVH1
t°
CNF2
GN
Tho-H
M
CNF1
WH
Tho-SC
M
CNB4
RD
Tho-R4
M
CNB3
BK
Tho-R3
M
Tho-R2
FMo2
Tho-A
M
Tho-S
FMo1
W
Parts name
Crankcase heater
Compressor motor
Connector
Current sensor
Electrolytic capacitor
Diode module
Expansion valve for heating
Expansion valve for SC
Fuse
Fan for IPM
Blower motor
Intelligent power module
Set up model(volt)
External input select level/pulse
BK
BL
OR
YE
WH
t°
CNI3 BK
CNB2
RD
CNTH WH
CNEEV3 WH
RD
CNEEV2 BL
RD
LED1
(INV)
BL
OR
YE
WH
CNEEV1 RD
BL
OR
YE
WH
CNA3 CNA1
WH WH
Tho-D1
MS
3〜
CNFAN2 RD
BK
Meaning of marks
Mark
CH1
CM1
CNA-Z
CT1
C1-1,2
DM1
EEVH1,2
EEVSC
F
FMC1
FMo1,2
IPM
J11,12
J13
J14
J15
J16
LED1
LED1(INV)
LED2
LED3
L1-1-3
L3
V
CNFAN1 WH
Tho-R1
U
CM1
CNX1
YE
RD F(4A)
P
IPM1
U V W
RD
WH
BL
-
CNI2 WH
CNI1
WH
CNA WH
N
RD F(4A)
-
CNR WH
Inverter
PWB2-1
WH
OR
YE
BL
GN
PK
WH
OR
YE
BL
GN
PK
BK
RD
BK
RD
RD
GY
R1-4
'14 • KX-DB-203
2.4 Noise level
Measured based on JIS B 8616
Mike position as highest noise level in position as below
Distance from front side 1m
Height
1m
Model FDC280KXZXE1
Cooling
Souud Pressure Level (dB)
(standard 2×10-5Pa)
80
Heating
N80
70
N70
60
N60
50
N50
30
80
70
60
50
40
40
N40
N30
63
125
250
500
1000
2000
Model FDC355KXZXE1
Noise level 56 dB (A) at cooling
56 dB (A) at heating
4000
30
8000
Mid Octave Band Frequency (Hz)
Cooling
80
Souud Pressure Level (dB)
(standard 2×10-5Pa)
Noise level 56 dB (A) at cooling
57 dB (A) at heating
Noise level 62 dB (A) at cooling
57 dB (A) at heating
Heating
N80
70
N70
60
N60
50
N50
70
60
50
40
40
30
80
N40
N30
63
125
250
500
1000
2000
4000
30
8000
Mid Octave Band Frequency (Hz)
- 10 -
Cooling
80
Souud Pressure Level (dB)
(standard 2×10-5Pa)
Model FDC224KXZXE1
Heating
N80
70
N70
60
N60
50
N50
70
60
50
40
40
30
80
N40
N30
63
125
250
500
1000
2000
4000
30
8000
Mid Octave Band Frequency (Hz)
'14 • KX-DB-203
3. RANGE OF USAGE & LIMITATIONS
• Single use (also for combination use)
System
Item
Indoor air temperature
(Upper, lower limits)
FDC224KXZXE1
FDC280KXZXE1
Refer to page 15
Outdoor air temperature
(Upper, lower limits)
Indoor units
that can be
used in
combination
Number of connected units
Connectable capacity (1)
Total piping length
FDC335KXZXE1
1 to 29 units
1 to 37 units
1 to 44 units
180 - 448
224 - 560
268 - 670
(2)
1000m or less
Main pipe length
130m or less
Single direction piping length
Actual length : 160m or less, Equivalent length : 185m or less
Allowable pipe length from the first branching
90m or less (However, difference between the longest and shortest piping : 40m or less(6))
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
50m or less (Max. 70m or less) (5)
Outdoor unit is higher
40m or less
Outdoor unit is lower
18m or less
Difference in the elevation of indoor units in a system
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
stop/start
frequency
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
1 cycle time
3 min or more
Stop time
Power source
voltage
(3)
Voltage fluctuation
Within 10% of rated voltage
Voltage drop during start
Within 15% of rated voltage
Phase unbalance
Within 3%
First branch
MAX. 90m
Outdoor unit
MAX. 18m
MAX. 18m
MAX. 130m
MAX. 18m
50m
(Outdoor unit is lower : 40m)
Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW series, limit the connectable capacity not higher than 130%.
(2) When the pipe extension length exceeds 510 m, additional refrigerant oil must be charged (1,000 cc).
(3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10 .
(4) I f Superlink I (previous Superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity
and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See
technical manual
’07·KX·KXR-T-114).
In addition to above limitations,
all of new functions for KX6 and KXZ such as automatic address
Outdoor
unit
Indoor unit
denotes
setting function for multiple refrigerant systems and etc. will be
cancelled.
(5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to
page 16.
MAX. 90m
(6)When it is required to install in the difference between the longest and shortest piping
moreunit)
than 40m, refer to page 17.
(Highest indoor
(Lowest indoor unit)
Indoor unit
First branch
(Lowest indoor unit)
MAX. 90m
-
11 -
MAX. 18m
MAX. 18m
(Header)
MAX. 18m
MAX. 130m
50m
(Outdoor unit is lower : 40m)
(Highest indoor unit)
'14 • KX-DB-201
'14 • KX-DB-203
Allowable length of refrigerant piping, height difference between indoor and outdoor unit
(1) Branch pipe system (Bran ch piping used)
Outdoor unit
Indoor unit
MAX.
denotes
90m (2)
MAX. 40m (3)
Ⅳ
First branch
Ⅴ
Ⅵ
MAX. 90m (2)
(Lowest indoor unit)
(2) Header system (Header used)
Outdoor unit
MAX. 18m
Ⅲ
MAX. 18m
Ⅱ
MAX. 130m
MAX. 18m
(Outdoor unit is lower : 40m)
50m (Max.70m)
(Highest indoor unit)
Ⅰ
Indoor unit
MAX. 40m (3)
Ⅲ
First branch
Ⅳ (Lowest indoor unit)
MAX. 18m
Ⅱ
(Header)
MAX. 18m
MAX. 130m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Ⅰ
MAX. 18m
(Highest indoor unit)
MAX. 90m (2)
(3) Mixed system (Bran ch piping and header used)
Outdoor unit
Indoor unit
MAX.90m(2)
Ⅱ
Ⅲ
First branch
(Header)
Ⅴ
MAX.90m(2)
Ⅳ
MAX.18m
MAX.18m
Ⅰ
MAX.130m
MAX.18m
50m (Max.70m)
(Outdoor unit is lower: 40m)
(Highest indoor unit)
(3)
MAX.40m
Ⅵ
(Lowest indoor unit)
Note (1) A branch piping system cannot be connected after a header system.
(2) 90m or less (However, difference between the longest and shortest piping : 40m or less (3))
(3) When it is required to install the difference between the longest and shortest piping more than 40m, refer to page 17.
Important
When the Additional refrigerant quantity (S+P+I) is over the following table, please separate the refrigerant line.
Outdoor unit
224-670
735-1000
S+P+I (kg)
45
90
S: Standard additional refrigerant quantity (kg)
P: Additional refrigerant quantity for piping (kg)
I : Additional refrigerant quantity for indoor units (kg)
-
12 -
'14 • KX-DB-203
• Combination use
System
Item
Indoor air temperature
(Upper, lower limits)
FDC450KXZXE1
FDC500KXZXE1
Number of connected units
Connectable capacity
(1)
2 to 60 units
2 to 53 units
360 - 900
400 - 800
Total piping length (2)
2 to 59 units
2 to 65 units
2 to 71 units
448 - 896
492 - 984
536 - 1072
1000m or less
Single direction piping length
Actual length : 160m or less, Equivalent length : 185m or less
130m or less
Main pipe length
Allowable pipe length from the first branching
90m or less (However, difference between the longest and shortest piping : 40m or less (6) )
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
FDC670KXZXE1
Refer to page 15
Outdoor air temperature
(Upper, lower limits)
Indoor units
that can be
used in
combination
FDC615KXZXE1
FDC560KXZXE1
Outdoor unit is higher
50m or less (Max.70m or less) (5)
Outdoor unit is lower
40m or less (3)
Difference in the elevation of indoor units in a system
18m or less
Difference in height between outdoor units
(Same system)
MAX. 0.4m
Difference between an outdoor unit and
on outdoor unit side branch pipe
MAX. 5m
Length of oil equalization piping
MAX. 10m
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
1 cycle time
stop/start
Stop time
frequency
Power source
voltage
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
3 min or more
Voltage fluctuation
Within
Voltage drop during start
Within
System
FDC735KXZXE1
Item
Indoor air temperature (Upper, lower limits)
FDC800KXZXE1
FDC850KXZXE1
Connectable capacity
3 to 78 units
588 - 1176
FDC1000KXZXE1
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
640 - 1280
680 - 1360
720 - 1440
760 - 1520
800 - 1600
1000m or less
Single direction piping length
Main pipe length
Allowable pipe length from the first branching
Actual length : 160m or less, Equivalent length : 185m or less
130m or less
90m or less (However, difference between the longest and shortest piping : 40m or less (6) )
18m or less
Elevation difference between the first branching point and the indoor unit
Outdoor unit is higher
50m or less (Max.70m or less) (5)
Outdoor unit is lower
40m or less (3)
Difference in the elevation of indoor units in a system
18m or less
Difference in height between outdoor units
(Same system)
MAX. 0.4m
Difference between an outdoor unit and
on outdoor unit side branch pipe
MAX. 5m
Length of oil equalization piping
MAX. 10m
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
1 cycle time
stop/start
Stop time
frequency
Power source
voltage
FDC950KXZXE1
3 to 80 units
Total piping length (2)
Difference in
height between
indoor and outdoor
units
FDC900KXZXE1
Refer to page 15
Outdoor air temperature (Upper, lower limits)
Number of connected units
15% of rated voltage
Within 3%
Phase unbalance
Indoor units
that can be
used in
combination
10% of rated voltage
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
3 min or more
Voltage fluctuation
Within
Voltage drop during start
Within
10% of rated voltage
15% of rated voltage
Within 3%
Phase unbalance
Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW series, limit the connectable capacity not higher than 130%.
(2) When the pipe extension length exceeds 510 m, additional refrigerant oil must be charged (1,000 cc).
(3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10 .
(4) I f Superlink I (previous Superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity
and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See
technical manual ’07·KX·KXR-T-114). In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address
setting function for multiple refrigerant systems and etc. will be cancelled.
(5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to
page16.
(6)When it is required to install in the difference between the longest and shortest piping more than 40m, refer to page 17.
-
13 -
'14
'14••KX-DB-203
KX-DB-201
Allowable length of refrigerant piping, height difference between indoor and outdoor unit
(1) Branch pipe system (Bran ch piping used)
Outdoor unit
Indoor unit
denotes
MAX. 90m (2)
MAX. 130m
MAX. 5m
MAX. 40m (3)
(Highest indoor unit)
MAX. 18m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Outdoor
unit 2
MAX. 10m
Outdoor unit
side branch
(DOS-2A-3)
MAX. 18m
MAX. 0.4m
MAX. 5m
First branch
MAX. 90m (2)
(Lowest indoor unit)
(2) Header system (Header used)
Outdoor unit
Oil equalization
piping
Outdoor
unit 1
Indoor unit
MAX. 40m (3)
MAX. 130m
MAX. 5m
(Highest indoor unit)
MAX. 18m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Outdoor
unit 2
MAX. 10m
First branch
MAX. 18m
MAX. 0.4m
MAX. 5m
Outdoor unit
side branch
(DOS-2A-3)
MAX. 18m
Outdoor
unit 1
(Header)
MAX. 18m
Oil equalization
piping
(Lowest indoor unit)
MAX. 90m (2)
(3) Mixed system (Bran ch piping and header used)
Outdoor unit
Indoor unit
MAX. 130m
MAX. 5m
MAX.90m(2)
(Highest indoor unit)
MAX.40m(3)
MAX.18m
Ⅰ
Ⅱ
MAX. 10m
Outdoor unit
side branch
(DOS-2A-3)
Ⅲ
First branch
(Header)
Ⅴ
MAX.90m(2)
Ⅳ
MAX.18m
Outdoor
unit 2
MAX. 5m
MAX.18m
Outdoor
unit 1
MAX. 0.4m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Oil equalization
piping
Ⅵ
(Lowest indoor unit)
(4) Pipe system for combination of 3 outdoor units (Displaying only outdoor units)
Oil equalization
piping
Outdoor
unit 3
MAX. 130m
L1 ≦ 5m
L2 + L4 ≦ 5m
L3 + L4 ≦ 5m
MAX. 0.4m
L3
Outdoor
unit 2
L2
Lc
L4
La + Lb ≦ 10m
Lb + Lc ≦ 10m
Lc + La ≦ 10m
Outdoor
unit 1
L1
Lb
La
Outdoor unit
side branch
(DOS-3A-3)
First branch
Note (1) A branch piping system cannot be connected after a header system.
(2) 90m or less (However, difference between the longest and shortest piping : 40m or less (3))
(3) When it is required to install the difference between the longest and shortest piping more than 40m, refer to page 17.
Important
When the Additional refrigerant quantity (S+P+I) is over the following table, please separate the refrigerant line.
Outdoor unit
224-670
735-1000
S+P+I (kg)
45
90
S: Standard additional refrigerant quantity (kg)
P: Additional refrigerant quantity for piping (kg)
I : Additional refrigerant quantity for indoor units (kg)
- 14
18 -
'14 • KX-DB-203
Operating temperature range
50
Outdoor air D.B.
temperature
°CDB
Cooling operation
46℃DB
43℃DB
40
30
20
10
0
-10
-20
10
-15℃DB
12
14
16
18
20
22
24
26
Indoor air W.B. temperature °CWB
*In case it is the promised installation location that the outdoor unit is used on conditions with
the ambient temperature of 43℃ or more, refer to page 6 (2.2 Exterior dimensions).
35
Indoor air D.B.
temperature
°CDB
Heating operation
30
27℃DB
25
20
15
10
5
-20
-15
-10
-5
0
5
10
15
20
25
Outdoor air W.B. temperature °CWB
“CAUTION” Cooling operation under low outdoor air temperature conditions
KXZ models can be operated in cooling mode at low outdoor air temperature condition within above temperature range. However in
case of severely low temperature conditions if the following precaution is not observed, it may not be operated in spite of operable
temperature range mentioned above and cooling capacity may not be established under certain conditions.
[Precaution]
In case of severely low temperature condition
1) Install the outdoor unit at the place where strong wind cannot blow directly into the outdoor unit.
2) If there is no installation place where can prevent strong wind from directly blowing into the outdoor unit, prepare a windbreak
fence or something like that locally in order to divert the strong wind from the outdoor unit.
[Reason]
Under the low outdoor air temperature conditions of -5˚C or lower, if strong wind directly blow into the outdoor unit, the outdoor
heat exchanger temperature will drop, even though the outdoor fan is stopped by outdoor fan control. This makes high and low pressures to drop as well. This low pressure drop makes the indoor heat exchanger temperature to drop and will activate anti-frost control
at indoor heat exchanger at frequent intervals, that cooling operation may not be established for any given time.
-
15 -
'14 • KX-DB-203
Specification for installation with large head difference (Applicable to: FDC224 - 1000KXZXE1)
In case when the outdoor unit is installed at a higher place and the difference in the elevation between the indoor and the outdoor
units is larger than 50 m and smaller than 70 m, the limitation on application differs partially from ordinary applications and, instead,
the following specification applies. The pipe size, refrigerant amount and way of switch setting become also different.
In the range of use, the outdoor air temperature (lower limit), indoor units allowed to combine, total piping length and difference in
the elevation between indoor units in the same system are different from ordinary applications.
Table 1 Range of use
Item
FDC224-1000KXZXE1
Indoor air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor units that can be
used in combination
Total piping length
Refer to Table 2
Number of connected units
Connectable capacity
Refer to Table 3
510m or less
130m or less
Actual length:160m or less, Equivalent length:185m or less
90m or less
(However, difference between the longest and shortest piping:40m or less)
Main pipe length
Single direction piping length
Allowable pipe length from the first branching
Elevation difference between
the first branching point and
Allowable difference in the the indoor unit
Outdoor unit is higher
elevation
Outdoor unit is lower
Difference in the elevation of
indoor units in a system
18m or less
50m or more-70m or less
40m or less
15m or less
0.4m or less
Difference in the elevation
Elevation from outdoor unit to
Limitation on piping from
branching pipe at outdoor unit side
outdoor unit to branching
Oil equalizing pipe length
pipe at outdoor unit side
Length between outdoor branching
pipes for a combination of 3 units
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models
FDT,FDTC,FDTW,FDTQ,FDTS,FDU,FDUM,FDUH,FDUT
Compressor stop/start
frequency
Power source voltage
5m or less
10m or less
5m or less
。
Dew point temperature 28 C or less, relative humidity 80% or less
。
(FDT,FDK,FDFL,FDFU,FDFW:Dew point temperature 28 C or less, relative humidity
80% or less)
5 min or less (from stop to stop or from start to start)
3 min or more
Within ±10% of rated voltage
Within –15% of rated voltage
Within 3%
1 cycle time
Stop time
Voltage fluctuation
Voltage drop during start
Phase unbalance
Table 3 Number of connectable indoor units and capacity range
Table 2 Indoor air temperature/Out door air t e mpe rat ure
Outdoor air D.B.
temperature
°CDB
Cooling operation
Model/Item
50
43℃DB
40
30
20
10
0
-5℃DB
-10
-20
10
12
14
16
18
20
22
24
Indoor air W.B. temperature °CWB
Indoor air D.B.
temperature
°CDB
Heating operation
35
30
27℃DB
25
20
15
10
5
-10
-5
0
5
10
15
20
25
Outdoor air W.B. temperature °CWB
-
16 -
26
FDC224KXZXE1
FDC280KXZXE1
FDC335KXZXE1
FDC450KXZXE1
FDC500KXZXE1
FDC560KXZXE1
FDC615KXZXE1
FDC670KXZXE1
FDC735KXZXE1
FDC800KXZXE1
FDC850KXZXE1
FDC900KXZXE1
FDC950KXZXE1
FDC1000KXZXE1
Number of
connectable
units
1 to 1 4
1 to 1 8
1 to 2 2
2 to 3 0
2 to 3 3
2 to 3 7
2 to 4 1
2 to 4 4
3 to 4 9
3 to 5 3
3 to 5 6
3 to 6 0
3 to 6 3
3 to 6 6
Connectable
capacity
180 - 224
224 - 280
268 - 335
360 - 450
400 - 500
448 - 560
492 - 615
536 - 670
588 - 735
640 - 800
680 - 850
720 - 900
760 - 950
800 - 1000
'14 • KX-DB-203
<Pipe size selection>
In the figure for pipe selection, sizes of main pipe and the pipe between the branch at the indoor side and the indoor unit are selected
on the basis different from normal practice.
(1) Main pipe (branch of the outdoor unit – first branch at the indoor side)
Size of liquid pipe is different. Change the size of main pipe according to Table 4.
When the maximum length (from the outdoor unit to the furthest indoor unit) is larger than 90 m (actual length), change the size
of main pipe according to Table 4.
Table 4 Main pipe size
Main pipe size (normal)
Gas pipe
Liquid pipe
φ19.05 × t 1.0
φ12.7 × t 0.8
φ22.22 × t 1.0
φ25.4 (φ22.22) × t 1.0
Outdoor unit
224
280
335
450
500
560
615
670
735
800
850
900
950
φ15.88 × t 1.0
φ28.58 × t 1.0
φ31.8 × t 1.1
(φ34.92 × t 1.2)
φ19.05 × t 1.0
Pipe size for an actual length of 90m or longer
Gas pipe
Liquid pipe
φ22.22 × t 1.0
φ12.7 × t 0.8
φ25.4 (φ22.22) × t 1.0
φ15.88 × t 1.0
φ31.8 × t 1.1
(φ28.58 × t 1.0)
φ38.1 × t 1.35
(φ34.92 × t 1.2)
φ19.05 × t 1.0
φ38.1 × t 1.35
(φ34.92 × t 1.2)
1000
(2) Between branch at the indoor side and indoor unit
Size of gas pipe for indoor unit with capacity larger than 112 is different. Change the size of pipe
connected to indoor unit according to Table 5.
Table 5 Indoor unit connecting pipe size
Capacity
Indoor unit
Gas pipe
15,22,28
36,45,56
71,90
112,140,160
224
280
Liquid pipe
φ 9.52 × t0.8
φ 12.7 × t0.8
φ15.88 × t1.0
φ19.05 × t1.0
φ22.22 × t1.0
φ 25.4 × t1.0
φ 6.35 × t0.8
φ 9.52 × t0.8
(3) Refrigerant quantity
In addition to normal charge quantity for refrigerant pipes, charge quantity for the difference in capacity between the indoor and
the outdoor units, and standard additional refrigerant quantity, measure and charge the additional refrigerant quantity for the
installation with the difference in the elevation being over 50 m and less than 70 m.
Table 6 Additional refrigerant quantity for the installation with the difference in the elevation being over 50 m and less than 70 m
Outdoor unit
224
280
335
450
500
560
615
(kg)
0.2
0.3
0.5
0.7
0.8
0.9
0.8
Outdoor unit
670
735
800
850
900
950
1000
(kg)
1.0
1.1
1.2
1.3
1.4
1.6
1.6
(4) Microcomputer control
Setting of microcomputer control needs to be changed when the outdoor unit is installed upwards and the difference in elevation is larger
than 50 m and less than 70 m. Make sure to set SW6-4 at ON position on both the master and slave units, before turning the power on.
When the difference between the longest and shortest piping is longer
than 40 m, adjust the difference in the elevation of indoor units in a
system such that it will fall in the OK range on the following graph.
When the difference in the elevation between the indoor and the outdoor
units is 50 m – 70 m, the difference between the longest and shortest
piping cannot exceed 40 m. Reduce it to less than 40 m.
If the refrigerant quantity over occurs when the difference between the
ongest and shortest piping is longer than 40 m, there is a risk that the
heating capacity becomes insufficient. Take sufficient care to adjust
the additional refrigerant quantity at correct value.
Difference between the longest
and shortest piping (m)
Specification for installation with the difference between the longest and shortest piping more than 40m
85
80
75
70
NO
65
60
55
OK
50
45
40
0
2
4
6
8
10
12
14
16
18
Difference in the elevation of indoor units in a system (m)
-
17 -
Oil
separator
Capillary tube
Capillary tube
For outdoor
unit 2
18 -
Service valve
(Oil equalization line)
Strainer
Electronic
expansion valve
Strainer
Liquid line
Service valve
To next indoor units
(Tho-R1)
(Thermistor,Exit・Front)
(Tho-R2)
(Thermistor,Exit・Back)
Sub-cooling
coil
Sub-cooling
coil
Accumlator
Strainer
Strainer
Strainer
Strainer Sub-cooling coil
Thermistor
(Tho-SC)
Sub-cooling coil
Electronic
Strainer
expansion valve
(EEVSC)
Strainer
Strainer
Receiver
Thi-R1, R2 : Heating operation : Indoor fan control.
Cooling operation : Frost prevention control.
Super heat control.
Thi-R3 :
For super heat control of cooling operation.
Tho-D :
For control of discharge pipe temperature.
Tho-C :
For control of temperature under the dome.
Tho-S :
For control of suction pipe temperature.
Tho-R1, R2 : For control of defrosting.
Tho-A :
For control of defrosting.
Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation
Tho-SC :
Electronic expansion valve (EEVSC) control of cooling operation.
Tho-H :
For super heat control of sub-cooling coil.
'14 • KX-DB-203
PCB003Z862
Notes (1) Preset point of protective devices
63H1-1 : Open 4.15MPa, Close 3.15MPa
(For protection)
(2) Function of thermistor
PSH :
For compressor control
3.70 ON (MPa)
PSL :
ON 0.18MPa, OFF 0.20MPa
(For compressor control)
ON 0.134MPa, OFF 0.18MPa
(For protection)
Heat
exchanger
Electronic
expansion valve
(EEVH2)
-
Thermistor(Entrance)
(Thi-R2)
Compressor 1
Thermistor
(Tho-C1)
Indoor unit
Thermistor
(Thi-A)
CM1
Electronic
expansion valve
(EEVH1)
Heat
exchanger
Thermistor(Bend)
(Thi-R1)
Heat
exchanger
Strainer
Capillary tube
Thermistor(Exit)
(Thi-R3)
Thermistor
(Tho-S)
Thermistor
(Tho-D1)
Strainer
Solenoid
valve(SV6)
Electronic
expansion valve
Low pressure
sensor(PSL)
Muffler
High pressure
switch(63H1-1)
Sub-cooling coil
Thermistor
(Tho-H)
Strainer
Check joint
(Tho-R4)
(Thermistor,Entrance・Back)
Check valve
Strainer
Solenoid
valve
(SV11)
(Tho-R3)
(Thermistor,Entrance・Front)
Indoor unit
Thermistor
(Thi-A)
Thermistor(Entrance)
(Thi-R2)
Check joint
High pressure
sensor(PSH)
Capillary tube
Heat
exchanger
4way valve
Thermistor(Bend)
(Thi-R1)
Solenoid
valve
(SV1)
Thermistor(Exit)
(Thi-R3)
Thermistor
(Tho-A)
Models FDC224KXZXE1
Service valve
Gas line
4. PIPING SYSTEM
Outdoor unit
Service valve
Gas line
19 -
Electronic
expansion valve
Strainer
Liquid line
Service valve
To next indoor units
Strainer
Strainer Sub-cooling coil
Thermistor
(Tho-SC)
Sub-cooling coil
Electronic
Strainer
expansion valve
(EEVSC)
Strainer
(Tho-R2)
(Thermistor,Exit・Back)
Heat exchanger
(Tho-R1)
(Thermistor,Exit・Front)
(Tho-R4)
(Thermistor,Entrance・Back)
Strainer
Sub-cooling
coil
Strainer
Strainer
Receiver
Thi-R1, R2 : Heating operation : Indoor fan control.
Cooling operation : Frost prevention control.
Super heat control.
Thi-R3 :
For super heat control of cooling operation.
Tho-D :
For control of discharge pipe temperature.
Tho-C :
For control of temperature under the dome.
Tho-S :
For control of suction pipe temperature.
Tho-R1, R2 : For control of defrosting.
Tho-A :
For control of defrosting.
Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation
Tho-SC :
Electronic expansion valve (EEVSC) control of cooling operation.
Tho-H :
For super heat control of sub-cooling coil.
'14 • KX-DB-203
PCB003Z863
Notes (1) Preset point of protective devices
63H1-1 : Open 4.15MPa, Close 3.15MPa
(For protection)
(2) Function of thermistor
PSH :
For compressor control
3.70 ON (MPa)
PSL :
ON 0.18MPa, OFF 0.20MPa
(For compressor control)
ON 0.134MPa, OFF 0.18MPa
(For protection)
Capillary tube
Electronic
expansion valve
(EEVH1)
-
Service valve
(Oil equalization line)
Accumlator
Sub-cooling
coil
Electronic
expansion valve
(EEVH2)
Compressor 1
For outdoor
unit 2
Strainer
Capillary tube
CM1
Thermistor
(Tho-C1)
Indoor unit
Thermistor
(Thi-A)
Thermistor(Entrance)
(Thi-R2)
Thermistor(Bend)
(Thi-R1)
Capillary tube
Solenoid
valve(SV6)
Heat
exchanger
Capillary tube
Thermistor(Exit)
(Thi-R3)
Thermistor
(Tho-S)
Strainer
Heat exchanger
Thermistor
(Tho-D1)
Strainer
(Tho-R3)
(Thermistor,Entrance・Front)
Oil
separator
Electronic
expansion valve
Low pressure
sensor(PSL)
Muffler
High pressure
switch(63H1-1)
Check valve
Strainer
Check joint
Sub-cooling coil
Thermistor
(Tho-H)
Indoor unit
Thermistor
(Thi-A)
Thermistor(Entrance)
(Thi-R2)
Check joint
High pressure
sensor(PSH)
Solenoid
valve
(SV1)
Heat
exchanger
4way valve
Thermistor(Bend)
(Thi-R1)
Solenoid
valve(20UF)
Thermistor(Exit)
(Thi-R3)
Thermistor
(Tho-A)
Models FDC280KXZXE1, 335KXZXE1
Outdoor unit
'14 • KX-DB-203
5. SELECTION CHART
(1)
Equipment selection flow
Calculate the load for each room separately, then determine the indoor load.
Select an indoor unit that matches the indoor load (tentative).
Calculate the temperature compensation,
then calculate the indoor unit capacity.
(See item (2) (a) for the calculation method.)
Indoor unit
capacity (tentative)
Indoor load
Change the indoor unit.
Select the outdoor unit (tentative).
NO
Calculate temperature compensation and piping
compensation, etc., then calculate the outdoor unit
capacity. (See item (2) (b) for the calculation method.)
YES
Calculate the total indoor unit capacity.
Calculate the system capacity
(See item (2) (c) for the calculation method.)
NO
Total indoor unit
capacity System capacity
Change the outdoor unit.
YES
Calculate the indoor unit capacity.
(See item (2) (d) for the calculation method.)
Indoor unit
capacity Indoor load
YES
Equipment selection complete.
-
20 -
NO
'14 • KX-DB-203
(2) Capacity calculation method
(a) Calculating the indoor unit capacity compensation
Indoor unit capacity (cooling, heating) = Indoor unit total rated capacity
× Capacity compensation coefficient according to temperature conditions
See item (3) (a) concerning the capacity compensation coefficient according to temperature conditions.
(b) Calculating the outdoor unit capacity compensation
Outdoor Unit Capacity (cooling, heating) = Outdoor unit rated capacity (rated capacity when 100% connected)
× Capacity compensation coefficient according to temperature conditions
× Capacity compensation coefficient according to piping length
× Capacity compensation coefficient according to height difference
× Correction of heating capacity in relation to the frost on the outdoor unit
heat exchanger
× Capacity compensation coefficient according to indoor unit connection
capacity
See item (3) (a) concerning the capacity compensation coefficient according to temperature conditions.
See item (3) (b) concerning the capacity compensation coefficient according to piping length.
See item (3) (c) concerning the capacity compensation coefficient according to height difference. This compensation
should be carried out only in cases where the outdoor unit is lower during cooling and higher during heating.
See item (3) (d) correction of heating capacity in relation to the frost on the outdoor unit heat exchanger. This compensation should be carried out only when calculating the heating capacity.
See item (3) (e) concerning the capacity compensation coefficient according to indoor unit connected capacity. This
compensation should be carried out only in cases where the indoor unit total capacity is 100% or higher.
(c) Calculating system capacity
Compare the capacities determined in items (a) and (b) above and let the smaller value be the system capacity (cooling,
heating).
In cases where indoor unit total capacity (cooling, heating) > outdoor unit capacity (cooling, heating)
System capacity (cooling, heating) = Outdoor unit capacity (cooling, heating)
In cases where indoor unit total capacity (cooling, heating) < outdoor unit capacity (cooling, heating)
System capacity (cooling, heating) = Indoor unit capacity (cooling, heating)
(d) Calculating indoor unit capacity [item (c) 1 only]
Indoor unit capacity (cooling, heating) = System capacity (cooling, heating)
× [(Indoor unit capacity) / (Indoor unit total capacity)]
Capacity calculation examples
Example 1
Cooling (when the indoor unit connected total capacity is less than 100%)
• Outdoor unit FDC450KXZXE1................................................... FDC224KXZXE1 × 2 units
• Indoor unit FDT56KXE6F........................................................... 7 units
• Piping length ............................................................................... 60 m (Equivalent length)
• Indoor, outdoor unit height difference......................................... 15 m (Outdoor unit is lower)
• Temperature conditions ............................................................... Outdoor temperature: 33˚C DB
• Temperature conditions................................................................ Indoor temperature: 19˚C WB
<Indoor unit total cooling capacity>: Item (2) (a) calculation.
• Indoor unit rated cooling capacity: 5.6 kW
• Capacity compensation coefficient according to temperature conditions:
1.02 (Calculated according to Indoor 19˚C WB / Outdoor 33˚C DB); (See page 23)
.
Indoor unit cooling capacity: 5.6 kW × 1.02 =. 5.7 kW
• Indoor unit total cooling capacity calculation;
indoor unit total cooling capacity: 5.7 kW × 7 units = 39.9 kW
<Outdoor unit maximum cooling capacity> : Item (2) (b) calculation
• Outdoor unit rated cooling capacity: 45.0 kW
• Capacity compensation coefficient according to temperature conditions:
1.02 (Calculated according to Indoor 19˚C WB / Outdoor 33˚C DB); (See page 23)
.
Outdoor unit cooling capacity: 45.0 kW × 1.02 =. 45.9 kW
• Capacity compensation coefficient according to piping length: 0.94 (calculated according to 60 m length); (See page 25)
.
45.9 kW × 0.94 =. 43.1 kW
-
21 -
'14 • KX-DB-203
• Capacity compensation coefficient according to height difference: 0.97 (calculated according to 15 m difference); (See page 27)
.
43.1 kW × 0.97 =. 41.8 kW
• Capacity compensation coefficient according to indoor unit connected total capacity: 1.0 , (56 × 7) / 450 < 100%)
No compensation
<System cooling capacity>: Item (2) (c) calculation
Compare the indoor unit total cooling capacity and the outdoor unit maximum cooling capacity. The smaller value is the actual
system cooling capacity.
• Indoor unit total cooling capacity: 39.9 kW
e System cooling capacity: 39.9 kW
• Outdoor unit maximum cooling capacity: 41.8 kW
<Indoor unit capacity compensation> No compensation (5.7 kW)
Example 2
Cooling (when the indoor unit connected total capacity is 100% or higher)
• Outdoor unit FDC450KXZXE1................................................... FDC224KXZXE1 × 2 units
• Indoor unit FDT56KXE6F........................................................... 10 units
• Piping length ............................................................................... 60 m (Equivalent length)
• Indoor, outdoor unit height difference......................................... 15 m (Outdoor unit is higher)
• Temperature conditions ............................................................... Outdoor temperature: 35˚C DB
• Temperature conditions................................................................ Indoor temperature: 18˚C WB
<Indoor unit total cooling capacity>: Item (2) (a) calculation.
• Indoor unit rated cooling capacity: 5.6 kW
• Capacity compensation coefficient according to temperature conditions:
0.95 (Calculated according to Indoor 18˚C WB / Outdoor 35˚C DB); (See page 23)
.
Indoor unit cooling capacity: 5.6 kW × 0.95 =. 5.3 kW
• Indoor unit total cooling capacity calculation;
indoor unit total cooling capacity: 5.3 kW × 10 units .=. 53.0 kW
<Outdoor unit maximum cooling capacity> : Item (2) (b) calculation
• Outdoor unit rated cooling capacity: 45.0 kW
• Capacity compensation coefficient according to temperature conditions:
0.95 (Calculated according to Indoor 18˚C WB / Outdoor 35˚C DB); (See page 23)
.
Outdoor unit cooling capacity: 45.0 kW × 0.95 =. 42.8 kW
• Capacity compensation coefficient according to piping length: 0.94 (calculated according to 60 m length); (See page 25)
.
42.8 kW × 0.94 =. 40.2 kW
• Capacity compensation coefficient according to height difference: 1.0 (the outdoor unit is higher during cooling)
No compensation
.
• Capacity compensation coefficient according to indoor unit connected total capacity: 1.05 , (56 × 10) / 450 =. 124%) (See page 29)
..
40.2 kW × 1.05 = 42.2 kW
<System cooling capacity>: Item (2) (c) calculation
Compare the indoor unit total cooling capacity and the outdoor unit maximum cooling capacity. The smaller value is the actual
system cooling capacity.
• Indoor unit total cooling capacity
: 53.0 kW e System cooling capacity: 42.2 kW
• Outdoor unit maximum cooling capacity : 42.2 kW
<Indoor unit cooling capacity Compensation>: Item (2) (d) calculation.
42.2 kW × 5.3 kW .
=. 4.2 kW
53.0 kW
Example 3
Heating (when the indoor unit connected total capacity is 100% or higher)
• Outdoor unit FDC450KXZXE1................................................... FDC224KXZXE1 × 2 units
• Indoor unit FDT56KXE6F........................................................... 10 units
• Piping length ............................................................................... 60 m (Equivalent length)
• Indoor, outdoor unit height difference......................................... 20 m (Outdoor unit is higher)
• Temperature conditions ............................................................... Outdoor temperature: 6˚C WB
• Temperature conditions................................................................ Indoor temperature: 19˚C DB
<Indoor unit total heating capacity>: Item (2) (a) calculation.
• Indoor unit rated heating capacity:6.3 kW
• Capacity compensation coefficient according to temprature conditions:
1.04 (Calculated according to Outdoor 6˚C WB / Indoor 19˚C DB); (See page 24)
Indoor unit heating capacity: 6.3 kW × 1.04 .=. 6.6 kW
• Indoor unit total heating capacity calculation;
.
indoor unit total heating capacity: 6.6 kW × 10 units =. 66.0 kW
-
22 -
'14 • KX-DB-203
<Outdoor unit maximum heating capacity> : Item (2) (b) calculation
• Outdoor unit rated heating capacity: 50.0 kW
• Capacity compensation coefficient according to temperature conditions:
1.04 (Calculated according to Outdoor 6˚C WB / Indoor 19˚C DB); (See page 24)
Outdoor unit heating capacity: 50.0 kW x 1.04 = 52.0 kW
• Capacity compensation coefficient according to piping length: 0.982 (calculated according to 60 m length); (See page 27)
.
52.0 kW x 0.982 =. 51.0 kW
• Capacity compensation coefficient according to height difference: 0.96 (calculated according to 20 m difference); (See page 27)
.
51.0 kW x 0.96 =. 49.0 kW
• Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger:
1.0 (calculated according to 6˚C WB); (See page 27)
.
49.0 kW x 1.0 =. 49.0 kW.
.
• Capacity compensation coefficient according to indoor unit connected total capacity: 1.01 ← (56 x 10) / 450 =. 124%) (See page 29)
.
49.0 kW x 1.01 =. 49.5 kW.
<System heating capacity> : Item (2) (c) calculation
Compare the indoor unit total heating capacity and the outdoor unit maximum heating capacity. The smaller value is the actual
system heating capacity.
• Indoor unit total heating capacity
: 66.0 kW ⇨ System heating capacity: 49.5 kW
• Outdoor unit maximum heating capacity : 49.5 kW
<Indoor unit heating capacity compensation> : Item (2) (d) calculation
49.5 kW x 6.6 kW .
=. 5.0 kW
66.0 kW
(3) Capacity compensation coefficient
(a) Capacity compensation coefficient and power consumption compensation coefficient according to indoor and outdoor temperature conditions.
1) Capacity compensation coefficient
1.40
◆ Cooling
Indoor air W.B. temperature 24˚CWB
1.35
Indoor air W.B. temperature 26˚CWB
Capacity compensation coefficient
1.30
1.25
Indoor air W.B. temperature 22˚CWB
1.20
Indoor air W.B. temperature 21˚CWB
1.15
1.10
Indoor air W.B. temperature 20˚CWB
1.05
Indoor air W.B. temperature 19˚CWB
1.00
0.95
Indoor air W.B. temperature 18˚CWB
0.90
Indoor air W.B. temperature 17˚CWB
0.85
0.80
Indoor air W.B. temperature 16˚CWB
Indoor air W.B. temperature 15˚CWB
0.75
0.70
Indoor air W.B. temperature 14˚CWB
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Outdoor air D.B. temperature (˚CDB)
32
34
36
38
40
42
44
46
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
(2) When performing the cooling operation with the outdoor air temperature being -5°C or under, a windbreak fence must be
installed.
--140 23 -
'14 • KX-DB-203
◆ Heating
1.20
1.15
Outdoor air W.B. temperature 18˚CWB
Capacity compensation coefficient
1.10
Outdoor air W.B. temperature 10˚CWB
1.05
Outdoor air W.B. temperature 14˚CWB
1.00
Outdoor air W.B. temperature 6˚CWB
0.95
Outdoor air W.B. temperature 2˚CWB
0.90
Outdoor air W.B. temperature -2˚CWB
0.85
Outdoor air W.B. temperature -6˚CWB
0.80
0.75
Outdoor air W.B. temperature -10˚CWB
0.70
0.65
Outdoor air W.B. temperature -15˚CWB
0.60
0.55
17
16
18
Outdoor air W.B. temperature -20˚CWB
19
20
21
22
23
24
Indoor air D.B. temperature(˚CDB)
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
2) Power consumption correction factor
1.30
◆ Cooling
Power consumption compensation coefficient
1.25
1.20
1.15
Indoor air W.B. temperature 26˚CWB
1.10
Indoor air W.B. temperature 24˚CWB
1.05
1.00
Indoor air W.B. temperature 22˚CWB
0.95
Indoor air W.B. temperature 21˚CWB
0.90
0.85
Indoor air W.B. temperature 20˚CWB
0.80
Indoor air W.B. temperature 19˚CWB
0.75
Indoor air W.B. temperature 18˚CWB
0.70
0.65
Indoor air W.B. temperature 17˚CWB
0.60
Indoor air W.B. temperature 16˚CWB
0.55
0.50
Indoor air W.B. temperature 15˚CWB
0
2
4
6
8
Indoor air W.B. temperature 14˚CWB
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor air D.B. temperature(˚CDB)
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
--141
24 --
'14 • KX-DB-203
1.25
◆ Heating
Power consumption compensation coefficient
Outdoor air W.B. temperature 6˚CWB
1.20
Outdoor air W.B. temperature -2˚CWB
Outdoor air W.B. temperature 2˚CWB
Outdoor air W.B. temperature -6˚CWB
1.15
1.10
Outdoor air W.B.
temperature 10˚CWB
1.05
1.00
0.95
Outdoor air W.B.
temperature -15˚CWB
0.90
0.85
Outdoor air W.B. temperature -10˚CWB
0.80
Outdoor air W.B. temperature -20˚CWB
Outdoor air W.B. temperature 14˚CWB
0.75
Outdoorair W.B. temperature 18˚CWB
0.70
16
17
18
19
20
21
22
23
24
Indoor air D.B. temperature(˚CDB)
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
(b)
Correction of cooling and heating capacity in relation to one way length of refrigerant piping.
(Note) This table is for reference only. If the refrigerant piping one way equivalent after the first branch is extended longer than 40 m, it could
drop further by about 10% in the worst case.
1) Cooling
Model FDC224KXZXE1
Model FDC280KXZXE1
1.00
Gas pipe: ø22.22
0.95
0.90
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Gas pipe: ø19.05
0.85
0.80
0
20
40
60
0.85
0
20
40
60
80
100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Refrigerant piping one way equivalent length (m)
Model FDC335KXZXE1
Model FDC450KXZXE1
(FDC224KXZXE1 + FDC224KXZXE1)
1.00
Capacity compensation
coefficient
Capacity compensation
coefficient
Gas pipe: ø22.22
0.90
0.80
80 90100 120 140 160 180
1.00
0.95
Gas pipe: ø25.4
0.90
0.85
Gas pipe: ø22.22*
0.80
Gas pipe: ø25.4
0.95
0
20
40
60
80
100
120
140
160
Gas pipe: ø28.58
0.90
0.85
0.80
180
0
20
40
60
80 90 100
120
140
160
180
Refrigerant piping one way equivalent length (m)
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
-
Gas pipe: ø31.8
0.95
25
30 -
'14 •• KX-DB-203
KX-DB-203
'14
0.95
Gas pipe: ø28.58
0.90
0.85
0.80
0
20
40
60
0.85
40
60
Capacity compensation
coefficient
Capacity compensation
coefficient
Gas pipe: ø28.58
0.90
20
0.85
Gas pipe: ø34.92*
0.85
0.80
0
20
40
60
0.85
0.85
0.80
Gas pipe: ø34.92*
0
20
40
60
80 90 100
120
140
160
60
80 90100 120 140 160 180
Model FDC800KXZXE1
(FDC224KXZXE1+FDC280KXZXE1+FDC280KXZXE1)
0.95
Gas pipe: ø31.8
0.90
Gas pipe: ø34.92*
0.85
1.00
Capacity compensation
coefficient
Capacity compensation
coefficient
Gas pipe: ø31.8
0.90
40
0
20
40
60
80 90100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Model FDC850KXZXE1
(FDC280KXZXE1+FDC280KXZXE1+FDC280KXZXE1)
Gas pipe: ø38.1
20
Gas pipe: ø38.1
0.80
80 90 100 120 140 160 180
0.95
Gas pipe: ø28.58
0.90
Refrigerant piping one way equivalent length (m)
1.00
80 90100 120 140 160 180
Gas pipe: ø31.8
1.00
Capacity compensation
coefficient
Capacity compensation
coefficient
Gas pipe: ø31.8
0.90
60
Refrigerant piping one way equivalent length (m)
Model FDC735KXZXE1
(FDC224KXZXE1+FDC224KXZXE1+FDC280KXZXE1)
0.95
40
Model FDC670KXZXE1
(FDC335KXZXE1 + FDC335KXZXE1)
0.80
0
80 90100 120 140 160 180
Gas pipe: ø38.1
20
0.95
Refrigerant piping one way equivalent length (m)
1.00
0
1.00
0.95
0
Gas pipe: ø28.58
0.90
Refrigerant piping one way equivalent length (m)
Model FDC615KXZXE1
(FDC280KXZXE1 + FDC335KXZXE1)
Gas pipe: ø31.8
0.80
Gas pipe: ø31.8
0.95
0.80
80 90100 120 140 160 180
Refrigerant piping one way equivalent length (m)
1.00
Model FDC560KXZXE1
(FDC280KXZXE1 + FDC280KXZXE1)
1.00
Gas pipe: ø31.8
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Model FDC500KXZXE1
(FDC224KXZXE1 + FDC280KXZXE1)
180
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
- 26 31 -
Model FDC900KXZXE1
(FDC280KXZXE1+FDC280KXZXE1+FDC335KXZXE1)
Gas pipe: ø38.1
0.95
0.90
Gas pipe: ø31.8
0.85
0.80
Gas pipe: ø34.92*
0
20
40
60
80 90 100 120 140 160 180
Refrigerant piping one way equivalent length (m)
'14
'14• •KX-DB-203
KX-DB-203
Gas pipe: ø38.1
*
Gas pipe: ø34.92
0.95
Gas pipe: ø31.8
0.90
0.85
0.80
0
20
40
60
80 90 100
120
140
160
1.00
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Model FDC950KXZXE1
(FDC280KXZXE1+FDC335KXZXE1+FDC335KXZXE1)
Model FDC1000KXZXE1
(FDC335KXZXE1+FDC335KXZXE1+FDC335KXZXE1)
0.95
Gas pipe: ø38.1
0.90
*
Gas pipe: ø34.92
0.85
0.80
0
180
Refrigerant piping one way equivalent length (m)
20
40
60
80 90100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
2) Heating
Capacity compensation
coefficient
1.00
0.98
0.96
0.94
0.92
0.90
0
20
40
60
80
100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Note (1) Equivalent piping length can be obtained by calculating as follows.
Equivalent piping length = Real gas piping length + Number of bends in gas piping × Equivalent piping length of bends.
Unit : m/one part
Equivalent length of each joint
Gas piping size
Joint (90˚ elbow)
φ15.88
0.25
φ19.05
0.30
φ22.22
0.35
φ25.4
0.40
φ28.58
0.45
φ31.8
0.55
φ34.92
0.60
φ38.1
0.65
(c) When the outdoor unit is located at alower height than the indoor unit in cooling operation and when the
outdoor unit is located at a higher height than the indoor unit in heating operation, the following values
should be subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
5m
10 m
15 m
20 m
25 m
30 m
35 m
0.99
0.98
0.97
0.96
0.95
0.94
0.93
40 m
45 m
50 m
55 m
60 m
65 m
70 m
0.92
0.91
0.90
0.89
0.88
0.87
0.86
(d) Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
-20
-15
-13
-11
-9
-7
-5
-3
-1
1
3
5 or more
0.96
0.96
0.96
0.95
0.94
0.93
0.91
0.88
0.86
0.87
0.92
1
The correction factors will change drastically according to weather conditions. So necessary adjustment should be
made empirically according to the weather data of the particular area.
--32
27--
'14 • KX-DB-203
(e) The capacity compensation coefficient and power consumption compensation coefficient vary according to
the total capacity of concurrently operating indoor units, as shown below.
(Note) This table shows typical values.
Model FDC224KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC280KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
28 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
Model FDC335KXZXE1
‫ ی‬Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
Capability compensation
coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC450KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
29 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
Model FDC500KXZXE1
‫ ی‬Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
Capability compensation
coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC560KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
30 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
Model FDC615KXZXE1
‫ ی‬Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
Capability compensation
coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC670KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
31 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
Model FDC735KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC800KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
32 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
Model FDC850KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC900KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
33 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
Model FDC950KXZXE1
‫ ی‬Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
Capability compensation
coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.6
0.4
0.2
1.2
0.8
0.6
0.4
0.2
0
0.8
0
0
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
1.0
20
40
60
80
100
Heating
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC1000KXZXE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
‫ ی‬Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
‫ ی‬Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0.6
0.4
0.2
0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
34 -
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0.8
Total capacity of concurrently operating indoor unit (%)
-
0
1.0
120
-
Heating
'14 • KX-DB-203
6.
ON REFRIGERANT
LEAKAGE
WARNINGS
ON REFRIGERANT
LEAKAGE
6. WARNINGS
Check of concentration limit
Important
The room in which the air conditioner is to be installed requires
a design that in the event of refrigerant gas leaking out, its
concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is
safe,without the toxicity or combustibility of ammonia, and is
not restricted by laws to be imposed which protect the ozone
layer. However, since it contains more than air, it poses the risk
of suffocation if its concentration should rise excessively.
Suffocation from leakage of R410A is almost nonexistent. With
the recent increase in the number of high concentration buildings,
however, the installation of multi air conditioner systems is on
the increase because of the need for effective use of floor space,
individual control, energy conservation by curtailing heat and
carrying power etc.
Most importantly, the multi air conditioner system is able to
replenish a large amount of refrigerant compared with conventional
individual air conditioners. If a single unit of the multi conditioner
system is to be installed in a small room, select a suitable model
and installation procedure so that if the refrigerant accidentally
leaks out, its concentration dose not reach the limit (and in the
event of an emergency, measures can be made before injury
can occur).
In a room where the concentration may exceed the limit, create
an opening with adjacent rooms, or install mechanical ventilation
combined with a gas leak detection device.
The concentration is as given below.
Note(2) The standards for minimum room volume are as
follows.
① No partition (shaded portion)
② When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening
without a door,or an opening 0.15% or larger than
the respective floor spaces at the top or bottom of
the door).
Outdoor unit
Refrigerant piping
Indoor unit
③ If an indoor unit is installed in each partitioned room and
the refrigerant tubing is interconnected, the smallest
of course becomes the object.
But when a mechanical ventilation is installed interlocked
with a gas leakage detector in the smallest room where
the density limit is exceeded, the volume of the next
smallest room becomes the object.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
Refrigerant piping
≤ Concentration limit (kg/m3)
Outdoor unit
The concentration limit of R410A which is used in multi air
conditioners is 0.42kg/m3. (ISO5149)
Note(1) If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
Small
room
Room C
Room D
Room E
Min. indoor floor area (m2)
40
Room B
Large room
Note(3) The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When
the ceiling is 2.7m high)
e.g.,
Charged amount (15kg)
Indoor unit
Room A
Medium
room
Mechanical ventilation device - Gas leak detector
Outdoor unit
e.g., Charged
amount (10kg)
Indoor unit
Very
small
room
Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms
A, B and C is 10kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15kg.
35
30
Range below the
density limit of
0.42kg/m3
(countermeasures
not needed)
25
20
15
Range above
the density limit
of 0.42kg/m3
(countermeasures
needed)
10
5
0
10
20
30
Total amount of refrigerant (kg)
-
35 -
VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS
Air-Conditioning & Refrigeration Division
16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japan
http://www.mhi.co.jp
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
c Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.