Uploaded by dilankahewage1

Three Phase Circuits

advertisement
EE1302 Introduction to Electrical Engineering
EE1302 Introduction to Electrical Engineering
Unit 8: Three Phase Circuits
Dr.R.P.S. Chandrasena
1
EE1302 Introduction to Electrical Engineering
Generation of three phase voltages
𝑉𝑝 = RMS phase voltage
2
EE1302 Introduction to Electrical Engineering
3
Balanced three phase voltages
In a balanced three phase supply, the phase voltages are equal in magnitude and are out of phase by 1200
with each other.
𝑣𝐴𝑁
𝑣𝐡𝑁
𝑣𝐢𝑁
EE1302 Introduction to Electrical Engineering
4
abc or positive sequence
The phase sequence is the time order in which the voltages pass through their respective maximum values.
Hence, the phase sequence of the three phase voltages shown below is abc or positive sequence.
𝑣𝐴𝑁
𝑣𝐡𝑁
𝑣𝐢𝑁
EE1302 Introduction to Electrical Engineering
acb or negative sequence
The phase sequence of the three phase voltages shown below is acb or negative sequence.
𝑣𝐴𝑁
𝑣𝐢𝑁
𝑣𝐡𝑁
𝑣𝐴𝑁 = 2𝑉𝑝 π‘π‘œπ‘ πœ”π‘‘
𝑣𝐢𝑁 = 2𝑉𝑝 π‘π‘œπ‘  πœ”π‘‘ − 1200
𝑣𝐡𝑁 = 2𝑉𝑝 π‘π‘œπ‘  πœ”π‘‘ + 1200
5
EE1302 Introduction to Electrical Engineering
6
Phase sequence: Example
Determine the phase sequence of the set of voltages given as
𝑣𝐴𝑁 = 200 π‘π‘œπ‘  πœ”π‘‘ + 100
𝑣𝐢𝑁 = 200π‘π‘œπ‘  πœ”π‘‘ − 2300
𝑣𝐡𝑁 = 200π‘π‘œπ‘  πœ”π‘‘ − 1100 .
EE1302 Introduction to Electrical Engineering
Star (Y) connected three phase source
Phase voltages:
Line voltages:
π‘‰π‘Žπ‘ is
7
3 times π‘‰π‘Žπ‘› and leads by 300.
EE1302 Introduction to Electrical Engineering
8
Delta (βˆ†) connected three phase source
Line voltages = Phase voltages
EE1302 Introduction to Electrical Engineering
Three Phase Loads
Star connected load
Delta connected load
A balanced load is one in which the phase impedances are equal in magnitude and in phase. Star – Delta
transformation can be applied to transform a delta-connected load to an equivalent star-connected load
and vise versa.
For balanced three
phase load
9
EE1302 Introduction to Electrical Engineering
Star - Connected Three Phase Loads
For a star-connected load, phase currents and line currents are the same,
The line voltage is 3 times the phase voltage with 300 phase shift.
10
EE1302 Introduction to Electrical Engineering
Delta - Connected Three Phase Loads
For a delta-connected load, phase voltages and the line to line (line) voltages are the same. Line currents are 3
times the phase currents with -300 phase shift.
11
Phase currents
πΌπ‘Žπ‘ = 𝐼𝑝 ∠πœƒ
Line currents
πΌπ‘Ž = 3𝐼𝑝 ∠ πœƒ − 300
𝐼𝑏𝑐 = 𝐼𝑝 ∠ πœƒ − 1200
𝐼𝑏 = 3𝐼𝑝 ∠ πœƒ − 1500
πΌπ‘π‘Ž = 𝐼𝑝 ∠ πœƒ − 2400
𝐼𝑐 = 3𝐼𝑝 ∠ πœƒ + 900
EE1302 Introduction to Electrical Engineering
12
Delta - Connected Three Phase Loads: Example
EE1302 Introduction to Electrical Engineering
Delta - Connected Three Phase Loads
Taking IAB as the reference.
For a delta-connected load, phase voltages and the line to line (line) voltages are the same. Line currents are 3
times the phase currents with -300 phase shift.
13
Phase currents
πΌπ‘Žπ‘ = 𝐼𝑝 ∠πœƒ
Line currents
πΌπ‘Ž = 3𝐼𝑝 ∠ πœƒ − 300
𝐼𝑏𝑐 = 𝐼𝑝 ∠ πœƒ − 1200
𝐼𝑏 = 3𝐼𝑝 ∠ πœƒ − 1500
πΌπ‘π‘Ž = 𝐼𝑝 ∠ πœƒ − 2400
𝐼𝑐 = 3𝐼𝑝 ∠ πœƒ + 900
EE1302 Introduction to Electrical Engineering
14
Source – Loads connection
Since both three phase source and three phase load can be either star or delta connected, there are four
possible source to load connections.
• Y - Y connection
• Y -  connection
•  -  connection and
•  - Y connection.
EE1302 Introduction to Electrical Engineering
Balanced Y – Y connection
Circuit for phase A (Per phase equivalent circuit)
When solving balanced three phase circuits, it is convenient to analyze the per phase circuit and then
derive the parameters in other phases using the results obtained through per phase analysis.
For a balanced Y – Y connected system, the per phase equivalent circuit can be obtained simply by
considering one phase.
15
EE1302 Introduction to Electrical Engineering
16
Balanced Y – Y connection: Example
For the given figure, 𝑬𝐴𝑁 = 120V∠00 .
a) Solve for line currents.
b) Solve for the phase voltages at the load.
c) Solve for the line voltages at the load.
EE1302 Introduction to Electrical Engineering
17
Balanced Y – Y connection: Example
For the given figure, 𝑬𝐴𝑁 = 120V∠00 .
a) Solve for line currents.
b) Solve for the phase voltages at the load.
c) Solve for the line voltages at the load.
EE1302 Introduction to Electrical Engineering
18
Balanced Y –  or  - Y connection
Transform the  connected source/load to equivalent Y connected source/load to transform the circuit to
Y – Y connected system. Then apply the per phase analysis, considering one phase and used the voltage
and current relationships for  connected system to obtain the required parameters of the original circuit.
EE1302 Introduction to Electrical Engineering
19
Balanced Y –  or  - Y connection
A balanced abc – sequence Y-connected source with π•π‘Žπ‘› = 100∠100 V is connected to a -connected
balanced load 8 + 𝑗4 Ω per phase. Calculate the phase and line currents.
EE1302 Introduction to Electrical Engineering
20
Balanced Y –  or  - Y connection
A balanced -connected load having an impedance 20 – j15 Ω is connected to a -connected, positivesequence generator having π•π‘Žπ‘ = 330∠00 V. Calculate the phase currents of the load and the line
currents.
EE1302 Introduction to Electrical Engineering
21
Balanced Y –  or  - Y connection
A balanced Y-connected load with a phase impedance of 40 + j25 Ω is supplied by a balanced, positive
sequence -connected source with a line voltage of 210 V. Calculate the phase currents. Use π•π‘Žπ‘ as a
reference.
EE1302 Introduction to Electrical Engineering
22
Balanced Y –  or  - Y connection
The line voltage of the generator is 207.8 V.
I.
Find the line voltage π‘‰π‘Žπ‘ at the load.
II.
Find the  currents.
EE1302 Introduction to Electrical Engineering
23
Power in a Balanced Three Phase System
For a Y-connected three phase load with a per phase impedance 𝑍∠πœƒ ,
𝑉𝑝 and 𝐼𝑝 are rms voltage and rms current.
Thus the total instantaneous power,
EE1302 Introduction to Electrical Engineering
24
Power in a Balanced Three Phase System
Thus the total instantaneous power,
Using the trigonometric identity
EE1302 Introduction to Electrical Engineering
Power in a Balanced Three Phase System
Thus the total instantaneous power,
𝑝 = 3𝑉𝑝 𝐼𝑝 π‘π‘œπ‘ πœƒ
Thus the total instantaneous power in a balanced three-phase system is constant.
Hence, average total active and reactive power
𝑃𝑇 = 3𝑉𝑝 𝐼𝑝 π‘π‘œπ‘ πœƒ
𝑄𝑇 = 3𝑉𝑝 𝐼𝑝 π‘ π‘–π‘›πœƒ
where  is the power factor angle.
The average per phase active and reactive power become
𝑃𝑝 = 𝑉𝑝 𝐼𝑝 π‘π‘œπ‘ πœƒ
𝑄𝑝 = 𝑉𝑝 𝐼𝑝 π‘ π‘–π‘›πœƒ
The total real and reactive power,
These expressions are valid for both Y and  connected loads.
25
EE1302 Introduction to Electrical Engineering
26
Power in a Balanced Three Phase System
The total complex power
𝑺𝑻 = 3𝑉𝑝 𝐼𝑝 π‘π‘œπ‘ πœƒ + 𝑗3𝑉𝑝 𝐼𝑝 π‘ π‘–π‘›πœƒ
𝑺 𝑇 = 𝑃𝑇 + 𝑗𝑄𝑇
𝑺 𝑇 = 3𝑽𝑝 𝑰𝑝 ∗
𝑺 𝑇 = 3 𝑉𝐿 𝐼𝐿 ∠πœƒ
𝑆𝑇 = 3 𝑉𝐿 𝐼𝐿
27
EE1302 Introduction to Electrical Engineering
Power in a Balanced Three Phase System
28
EE1302 Introduction to Electrical Engineering
Power in a Balanced Three Phase System
29
EE1302 Introduction to Electrical Engineering
Power in a Balanced Three Phase System
EE1302 Introduction to Electrical Engineering
30
Power Factor Correction in Three Phase System
In three phase systems, three capacitors are needed and hence Qcap represent the reactive power
supplied by all three capacitors. Also note that the voltage applied across the capacitor vary based on
the type of connection of the capacitors.
EE1302 Introduction to Electrical Engineering
31
Power Factor Correction in Three Phase System
Two balanced loads are connected to a 240 kV rms, 60 Hz line, as shown in the figure below. Load 1
draws 30 kW at a power factor of 0.6 lagging, while load 2 draws 45 kVAR at a power factor of 0.8
lagging. Assuming the abc sequence, determine
(a) The complex, real, and reactive power absorbed by the combined load
(b) The line currents
(c) The kVAR rating of the three capacitors βˆ† connected in parallel with the load that will raise the
power factor to 0.9 lagging and
(d) The capacitance of each capacitor.
Download