Dear Prakash, According to pre-commissioning report for multiple well CP system New Coated Oil Well HRDH-355, Existing Bare Oil Wells HRDH-240 & HRDH-207 are protected as per SAES-X700. As Per Pre-commissioning Report: TR Rating Operating Output Operating Resistance Max. Allowable Circuit Resistance (90% of TR Rating). Total Number of Anode (TA-4) 50V/50A 17.13V/37.50A 0.456 Ohms 0.90 Ohms 12TA-4 ( New AGB-003), 10TA-4 ( Existing AGB1) & 6TA-4 ( Existing AGB-2) Current measurement at well casing: Negative Cable F/L Casing Minimum Design Current Require As Per SAES-X-700 (Amps) New Well HRDH355 (Coated Oil) 3.83 (+)1.83 5.66 1-3 Protected Ex. Well HRDH207 ( Bare Oil) 13.34 (+)0.50 13.84 12-15 Protected Ex. Well HRDH240 ( Bare Oil) 20.18 (-)6.78 13.40 12-15 Current (Amps) Well / FL No. Status Protected Recommendation: . All wells are protected and anode ground beds having enough anodes to deliver TR rated current. Hence precommission report is accepted. Regards Mohamed Mahfouz Engineering Manager (NACE-CP4) Abdulla Fouad Impalloy Ltd. Co. Office: (+966) 13 810 1945