ST266F Intelligent General Protection and measurement device Operation Instruction Wenzhou Boerstn Electric Co., Ltd Preface Please read this chapter carefully before using this product! This chapter introduces the safety precautions before using this product. Please make sure the content of this chapter is fully read and understood before installation and usage. Our company will not undertake any responsibilities for any damage or injury caused by improper operations because of ignoring relevant warnings in this operation instruction. Before operating this device, relevant professional personnel shall read this instruction carefully and well understand the content. Operation instructions and warnings: The following standard definitions will be adopted in this operation instruction.。 Danger! Ignoring of safety precautions may cause personal death, serious personal injury or serious equipment damage. Warning! Ignoring of safety precautions may cause personal death, serious personal injury or serious equipment damage. Caution! Ignoring of safety precautions may cause a slight personal injury or equipment damage, especially the damage of device or the equipment protected by the device. Danger! When the primary system is live working, secondary open circuit for the current transformer connected to the device is absolutely forbidden, and the open of this circuit may cause extremely dangerous high voltage. Warning! Some parts of the device may have high voltage when the electrical device is running. Improper operation may cause serious personal injury or equipment damage.。 Only qualified professional personnel are allowed to operate the device or work nearby the device. The operators shall well understand the precautions, working flows and safety regulations mentioned in this instruction. Special attention: General working regulations for high voltage live equipment shall be abided; otherwise it may cause serious personal injury and equipment damage. Caution! Grounding terminals of the device shall be firmly grounded. The device is only permitted to run in atmospheric environment that specified in the technical specifications, and abnormal vibrations shall be avoided in its running environment. When connect the AC voltage current circuit or power circuit, please make sure they conform to the rated parameters of the device. When the output terminals of the device are connected to external circuit, please check carefully the voltage of external power to prevent overheating of the circuit. Carefully check the cable connected to the device, preventing applying too much external force on it. Content 1.Introduction of the Device .................................................................................................. 1 1.1 Application scope ································································································1 1.2 Function feature。 ·······························································································1 2. Technical Performance Indexes......................................................................................... 3 2.1 Conditions of Working Environment ··········································································3 2.2 Electrical technical parameters ·················································································3 2.3 Insulation property ·······························································································5 2.4 Electromagnetism immunity property ·········································································7 2.5 Mechanical property ·····························································································7 2.6 Protection grade ··································································································7 3. Model Selection instuction ................................................................................................. 8 4. Function configuration....................................................................................................... 9 4.1 The surge current blocking function ···········································································9 4.2 Three –steps inter-phase overcurrent protection ·····························································9 4.3 Two-section zero-sequence(grounding) current protection ················································11 4.4 over-voltage protection ·························································································11 4.5 Low voltage protection ·························································································11 4.6 Multipule reclosing ·····························································································11 4.7 Post-acceleration later ··························································································12 4.8 Over –load protection ···························································································12 4.9 PT wire-breakage alarm ························································································12 4.10 The intellegence switching input ············································································13 4.11 Signal inditactor ································································································14 4.12 Event record ····································································································14 5. Structure Installation and Connection............................................................................ 15 5.1 Structure and Installation ·······················································································15 5.2 Connection ·······································································································18 6. Setting of parameters ....................................................................................................... 19 6.1 System Parameters ······························································································19 6.2 Fixed value parameters ·························································································20 7. Operation of Man-machine Interface ............................................................................. 25 Operation instruction of ST266F Intelligent general protection and measurement control Device 1.Introduction of the Device 1.1 Application scope ST266Fintelligent general protection device is developed for application of ring power grid. It contains function such as three-section inter-phase over current protection、 inverse time limited over current protection with several curve action characteristics、 two-section zero-sequence over current (earth grounding) protection 、many times reclosing、over voltage、low voltage protection and intelligent switching input, and monitoring function includes electric-quantity measurement、remote control、remote signals and so on. 1.2 Function feature。 ST266F intellectual protect device adopts high integrating micro processor with bus in the chip to process the signals both from the voltage and current transformers, and output these signals through digital logical operation control. The device sdopts seal case, maintenance-free design, sound anti-interference performance, and it specially suits for ring power grid running in worse environment and with limited installation position. Low power consumption design technology is adopted for the whole machine, to ensure the protection functions can start quickly reliably at any conditions. The structure of the device is simple and smart, easy and flexible to install, suiting for the compact installation conditions of ring network system. The functions of this device includs:three-section inter-phase over current protection,two-section zero-sequence (earth grounding )current protection, a variety inverse curve options of IEC standard,and votage protection. With surge current blocking function, to prevent incorrect tripping due to transformer no-load switching. Instantaneous trip protection uses a fast algorithm of Short Data Window, to ensure rapid removal of short-circuit fault to avoid override trip. Protection configuration is flexible and compelete , all protection functions can freely switch on or switch off through control figure. The device has perfect measuring and controlling functions , and may measure electrical parameters such as voltage、current、active power、reactive power、 apparent power、power factor and so on; provides special remote control relays to 1 Operation instruction of ST266F Intelligent general protection and measurement control Device realize remote control function; owns seven switching input circuit with customized pre-define function. Chinese LED display interface and multi-layer menu display is adopted,there are chinese menu or english menu optional, time alarming window design,with frendly human-machine interface. With automatic-dynamic-gain current measurement circuit design, the device has an extremely wide measuring range, so as to meet the transformers of secondary rated1A or 5A current. 50Hz, 60Hz system is customizable by the user; the mode of zero-sequence collection is optional (external connection or internal algorithms). With a very wide operating temperature range and waterproof and dustproof design, it ensures reliable operations under extreme conditions. The device can record at least 60 times of historical events record, and no data will lose even the power is off,it is convenient to accidents recall. The device provides RS-485 communication bus interface and provides open communication protocols to clients, so as to realize SCADA function. 2 Operation instruction of ST266F Intelligent general protection and measurement control Device 1.3 Series Device List ST266F intelligent general protection and measurement control device is one model among our ST26x RMU special protection device series. The Series Device List is shown as table below. Device Model ST260E ST260M ST268N ST266B ST266F Device Name Device Function Device Features Intelligent Three-sect inter-phase overcurrent (self-powered) protection, two-sect zero-sequence LCD graphic display interface passive overcurrent protection, gas (temperature) protection device protection Intelligent Three-sect inter-phase overcurrent (self-powered) protection, one-sect zero-sequence Rotate the coding switch to set passive overcurrent protection, gas (temperature) the value; very wide range of protection device protection temperature adaptation Intelligent Two-sect inter-phase overcurrent Rotate the coding switch to set (self-powered) protection, one-sect zero-sequence the value; very wide range of passive overcurrent protection, gas (temperature) temperature adaptation; slim protection device protection modular structure Spare power automatic switching, Spare power automatic Intelligent spare three-sect inter-phase overcurrent, two-sect switching protection device; power automatic zero sequence overcurrent, voltage monitoring and control switching protection, gas (temperature) protection, function with lead-in protection device monitoring and control functions, etc. line protection; LCD graphic display interface Intelligent Three-sect inter-phase overcurrent, Active protection device; integrated two-sect zero-sequence overcurrent, multifunctional protection and protection multiple reclosing, voltage protection, control functions; LCD monitoring and intelligent switch input, monitoring and graphic display interface control device control functions 2. Technical Performance Indexes 2.1 Conditions of Working Environment 2.1.1 Environment temperature: Working temperature -20°C - 60°C Reservation temperature -40°C 2.1.2 Relative humidity: 5% 2.1.3 Atmospheric pressure: 70 KPa 2.1.4 Altitude: - 85°C - 95% - 110KPa Less than or equal to 4000 m 2.2 Electrical technical parameters 2.2.1Rated data: AC voltage:100V or 220V (indicate the order) AC current:5A / 1A(General) Frequency: 50Hz/60Hz(General) DC220(110)V,±20% 3 Operation instruction of ST266F Intelligent general protection and measurement control Device DC48V,±20% DC24V,±20% Power: AC220(110)V,±20% DC220(110)V,±20% DC48V,±20% DC24V,±20% 2.2.2Overload ability: voltage circuit: long-time running-------1.5Un current circuit: long-time running-------10A 10s-----------------50A 1s------------------100A 2.2.3Power consumption: The source power shall not be greater than 5W. Each of AC input circuit power shall not be greater than0.5VA. 2.2.4Measuring scope: Voltage 0.01Un -- 2Un Phase Current: 0.05A Zero sequence current: 0.005A - 5A 2.2.5 Measuring precision:Voltage - 50A <1% or no larger than 0.01A Phase current : <1% or no larger than 0.01A Zero sequence current :<1% or no larger than 0.01A 2.2.6 Scope of protection:The range of protection current: 0.1A —50A 2.2.7 Operate time of protection: The national actuation time of quick-break protection under 2 times fixed value is not larger than 20ms. The national actuation time of all protection under 1.5 times fixed value is not larger than 35ms. 2.2.8Input circuit: External power supply, type of voltage is customized ; current consumption is 2mA 2.2.9Output circuit: DC220V, 5A current can pass the contact point continuously. 2.2.10Communication interface: panel communication intrface, special debugging interface The terminal interface --RS-485interface 4 Operation instruction of ST266F Intelligent general protection and measurement control Device 2.3 Insulation property 2.3.1 Insulation resistance No. Test Position 1 Test requirements Remark AC current to the ground Between the AC circuit and 2 Measure with 3 power circuit Insulation Power circuit to the ground resistance>100mego Switching value input 4 distant-reading hm manometer circuit to the ground 5 1000V Output circuit to the ground Between switching value 6 2.3.2 input and output circuit Dielectric strength Test No. Test position Test condition requirements 1 Power circuit to the ground Under normal Communication circuit to test atmospheric 2 the ground conditions, carry out Non-breakdo 3 AC circuit to the ground 1 minute power Between AC circuit and frequency wn flashover and damage status of 4 anti-voltage test power circuit components under specific Switching value input 5 voltage, wherein 2 circuit to the ground 6 tests are under Output circuit to the ground 5 Operation instruction of ST266F Intelligent general protection and measurement control Device 1000V,others are under 2000V), the other circuits shall connect each other Between switching value 7 to the ground with input and output circuit equal electric potential,when applying voltage to the tested voltage. 2.3.3 Impulse voltage Test No. Test Test position conditions 1 AC circuit to the ground Under normal test Between AC circuit and atmosphere requirements 2 conditions, the power circuit 3 Power circuit to the ground device undertakes Non-breakdo Switching value input 1.2/50us standard wn flashover, lightning short insulation damage time impulse and component voltage test, damage 4 circuit to the ground 5 Output circuit to the ground switching value Between switching value 6 output test voltage input and output circuit is 5KV. 2.3.4Anti-humidity and anti-heat property The device shall be able to bear the permanent humidity and heat test specified in GB/T 2423.9. Test temperature: +40℃±2℃; relative humidity: (93±3)%; test period: 48h. 6 Operation instruction of ST266F Intelligent general protection and measurement control Device According to the requirements in 2.3.1, 2 hours before the termination of the test, the insulation between each circuit shall be measured and the resistance shall not be less than 1.5 MΩ;the anti-voltage strength of the dielectric shall not be lower than 75% of the dielectric strength test voltage amplitude specified in 2.3.2. 2.4 Electromagnetism immunity property 2.4.1 Electrostatic discharge immunity Pass the standard of GB/T 17626.2-1998 and the test for electrostatic discharge immunity Grade 4. 2.4.2 Radiated radio frequency electromagnetic field immunity Pass the standard of GB/T 17626.3-1998 and the test for radiated radio frequency electromagnetic field immunity Grade 4. 2.4.3 Electrical fast transient/burst (EFT/B) immunity Pass the standard of GB/T 17626.4-1998 and the test for electrical fast transient/burst (EFT/B) immunity Grade 4. 2.4.4 Surge immunity Pass the standard of GB/T 17626.5-1998 and the test for surge immunity Grade 4. 2.5 Mechanical property 2.5.1 Vibration Pass the Grade I vibration response test specified in Section 16.2 of GB/T 7261. 2.5.2 Impulse Pass the Grade I impulse response test specified in Section 17.4 of GB/T 7261. 2.5.3 Impact Pass the Grade I impact response test specified in Chapter 18 of GB/T 7261. 2.6 Protection grade IP54 7 Operation instruction of ST266F Intelligent general protection and measurement control Device 3. Model Selection instuction ST 266F XX xx X X S ele cti on of Selection of installation direction: L —vertical installation H —horizontal installation Selection of terminal mode: B —The back extraction cT External input contact power selection: A1 — External power, AC220V A2 — External power, AC110V D1 — External power, DC220V D2 — External power, DC110V D3 — External power, DC48V D4 — External power, DC24V The device power selection: A1 — External power, AC220V A2 — External power, AC110V D1 — External power, DC220V D2 — External power, DC110V D3 — External power, DC48V D4 — External power, DC24V Products series code Company code 8 Operation instruction of ST266F Intelligent general protection and measurement control Device 4. Function configuration 4.1 The surge current blocking function If the function is put into use, the line is running detected by device, When the secondary harmonic content of the line exceeds 15% current of the fundamental, it will lock the protection trip output. If the lines without transformer load, the function will sends no action. 4.2 Three –steps inter-phase overcurrent protection The functions of three- section inter-phase overcurrent protection for devices are respectively quick-break protection、time-limited quick-break protection、overcurrent protection. Both the quick-break protection and time limited quick-break protection are defined time limited characteristics; The over current protection can provides four types of curves as: Definite curve、Normally Inverse Curve, Very Inverse Curve, and Extremely Inverse Curve. The time-current formulas for the last three curves are as following: Normally Inverse Curve: Very Inverse Curve: Extremely Inverse Curve Wherein: t - Tripping time tI〉 - Times I - Fault current Is - Current setting 9 Operation instruction of ST266F Intelligent general protection and measurement control Device Please see Fig. 4.2, Fig.4.3 and Fig. 4.4 for these three types of inverse time action curves. Fig. 4.1 Operating characteristics of definite time-lag Fig. 4.3 Operating characteristics of very inverse curve Fig. 4.2 Operating characteristics of normally inverse time-lag Fig. 4.4 Operating characteristics of extremely inverse curve 10 Operation instruction of ST266F Intelligent general protection and measurement control Device 4.3 Three-section zero-sequence(grounding) current protection The device set three-section definite time limited zro-sequence protection detecting the earth grounding current.,and it is mainly used for the neutrol point insulation or compensation system.The first is definite time limited characteristic ,the second and the third includes four types performance curve:Definite Curve、Normally Inverse Curve、 Very Inverse Curve、Very Inverse Curve. The mode of zero-sequence collection can be selected to access to pecial zero-sequence CT or internal calculation of device.(“zero-sequence mode” can be choosen in system menu) Because the zero sequence current in the indirect grounding system is relatively small, the relatively higher detection precision is necessory for the zero-sequence collected by device, generally,the connection way is advised to adopt instaling special zero-sequence CT. 4.4 over-voltage protection The device check Uab、Ubc、Uca , when anyone of the three linevoltage is larger than set value,after the set delaying,it output tripping order, turn on the tripping signal indicate. Protection can select switch on or switch off respectively, also,current and time value can be set respectively. 4.5 Low voltage protection The device check Uab、Ubc、Uca , when the three line-voltage are eighty percentage greater rated line-voltage and after keeping two seconds,the device is judged running normal; at the moment ,if the three line-voltage are lower than set voltage, after .set time value delaying , the device output corresponding order. This protection can select trip directly or only alam no tripping. 4.6 Multipule reclosing The device has reclosing function up to four times. When Over voltage protection、 low-voltage protection、zero-sequence protection trip, the device can block reclosing function. The motion logic of reclosing simulate to the way of traditional capacitor charging and discharging. The reclosing charging conditions as followings: 11 Operation instruction of ST266F Intelligent general protection and measurement control Device 1、Switching on the soft link of reclosing; 2、No external contact blocking reclosing; 3、Circuit- breaker closing position. The above conditions have realized for 15seconds, the reclosing finishes charging. The device will discharge immediately if any of the conditions is not met or device receives remote order. After power charging of function reclose is finished, when the position of Circuit Breaker changed from closed to opening, the device immediately start function of reclosing ,then the device output tripping order with time delaying. There are two methods to start the function of reclosing in the software of device, protection starting mode (which is described above) is default in device, if it is necessary, the non-corresponding way which is other method ,can be set via connect to after-sale officer to modify the hidden menu. 4.7 Post-acceleration later When the post-acceleration protection switched on, the device should judge whether the fault of line is disappeared after reclosing, if the fault meet three- section phase current protection tripping, and the acceleration time less than three-section phase protection motion time, the device will start the set time delay of acceleration in two seconds. 4.8 Over –load protection The three-phase current collected by devices,comparad to the set value of over-load current, when the current is larger than the set value ,the device will send out alarm signal. 4.9 PT wire-breakage alarm The collection voltage of the device is line-voltage. The device judges whether voltage circuit wired-breakage or not automatically, the criterion is as following: i. No action signal of inter-phase over current protection ; ii. Each of phase current is larger than 0.2A, each of line-voltage is less than 2V; As soon as both above conditions are met that the PT is wired-breakage, if it is true, the device will sent alarm signal after 5 seconds time delay. 12 Operation instruction of ST266F Intelligent general protection and measurement control Device 4.10 The intellegence switching input The device is designed seven switching input loops supplied by external power, the power source voltage shown in order can be customized h by users. Generally, without any special instruction, the power is similar to the device power voltage. The device take measurement enough to remove jitter in both the hardware and software, without special requirement the device can distinguish 10ms width impulse, with resolution accuracy of 1ms. The intelligence characteristics of switching input are include two sides : 1 、The name of each the switching input can be defined by user-self,the user can input the names in the “system” menu in order to keep the displaying names are similar to the real collecting contact name, the types of input signal are as followings: the normal switching input signal the circuit- breaker closing position signal the circuit-breaker open position signal the isolation switch closing position signal the isolation switch open position signal the grounding switch closing position signal the grounding switch open position signal the carrier work position signal the carrier test position signal the spring stored signal the spring un stored signal the transformer door open signal the heavy gas signal the light gas signal the over-temperature signal the high-temperature signal the pressure release signal blocking reclosing signal 13 Operation instruction of ST266F Intelligent general protection and measurement control Device blocking back-up switching signal remote control signal 2、loops are pre-defined, the protection device software will automatically scan the position of each input status signal, which will involve in the analysis of relevant protection logic based on the definition e.g. reclose, backup power auto input, which renders the secondary design of protection device more flexible and meets the need for contingent adjustment of wiring out of certain cause on site. 3、According to the set parameters above,the device detects whether alarming signal input, if the device detect signal input such as “heavy gas”、“over-temperature” or “pressure release” ,then the device will output tripping order and alarm information automatically. 4.11 Signal inditactor There are two signal indicators on the device panel, i.e. "RUN" (green) and "TRIP" (red). The indicator "RUN" (green) has three flicker frequencies: 5 rapid flashings per second (5Hz) indicate that a internal fault needs to be repaired; 2 normal speed flashings per second (2Hz) indicate that the device is running properly; 2 slow flashings per second (0.5Hz) indicate that the protection function is under the exit status. Indicator "TRIP" (red) lighting up indicates that trip output will appear. 4.12 Event record The device can record a total of 100 historical events. Records include overcurrent protection actions, switch quantity input displacement, equipment failures and other types of events, Event records are stored by the order of occurrence time. When there are more than 60 events, the latest records will automatically overwrite the oldest records sequentially. 14 Operation instruction of ST266F Intelligent general protection and measurement control Device 5. Structure Installation and Connection 5.1 Structure and Installation 5.1.1 Panel Layout Fig. 5.1 Diagram of the panel 5.1.2. External dimension and installation ST266F protection device has a structure with uniform dimention,it has one terminal outlet way(back outlet way(B- type))and two intallation directions(vertical (L-type)、 horizontal(H-type).The horizoncal(H-type) installation direction is 90°counter clock wise to vertical direction. All diagrams in the chapter are shown vertical (L-type) installation dimensional diagram of device. The following gives introductions respectively according to the different terminal outlet methods. All the dimensions units are in millimeter (mm). 15 Operation instruction of ST266F Intelligent general protection and measurement control Device 5.1.2.1Back terminal outlet (B-type) method 2.5 6.5 74 110 22 142 137 Figure5.3 right-side view diagram(B-type) Figure 5.2 front view diagram(B-type) 68 70 136 138 Figure5.4Back view diagram (B-type) Figure 5.5 opening dimension chart of L-type embedded switch cabinet(B-type) 16 Operation instruction of ST266F Intelligent general protection and measurement control Device M4 installation screw hole M4 安装螺孔 32 图 5.6 底面视图(B 型) 77 Figure 5.6 button view diagram (B-type) Allow screwing depth no longer than 6mm 允许拧入深度≤6mm 33 Figure 5.7 Installation method suggested diagram (B-type) 17 Operation instruction of ST266F Intelligent general protection and measurement control Device 5.2 Connection Fig 5.8 Terminal wiring diagram 18 Operation instruction of ST266F Intelligent general protection and measurement control Device 6. Setting of parameters Three types of parameters of the device shall be set, namely system parameters; fixed value parameters and channel parameters. The three types of parameters shall be respectively set correspongding to the System, Fixed Value and Calibration menus. For the setting of channel parameters is the compensation to the AC channel of the hardware, it is finished setting before shipped with no introduction here. The following introduct respectively setting of system parameters and fixed value parameters. 6.1 System Parameters Before formally put into operation, the system parameters shall be correctly input to ensure the normal operating of the device. The system parameters chart as following: No. Parameter name Parameter introduction Setting score 1 Equipment language The language of the Human-machine is set in Chinese/English device. 2 Rated frequency The rated frequency of device AC quantity is set 50Hz/60Hz in device. 3 Open time To set the time of breaker. 4 The rated value of To set the secondary rated value of PT PT secondary side 0~9999V 5 The rated value of To set the primary rated value of PT PT primary side 0~99.99KV 6 Ratio of CT Setting the ratio of current in device. 0~9999 7 Zero-sequence mode Zero-sequence current collection mode. External input/internal arithmetic 8 Ratio of Setting the ratio of zero-sequence CT in device zero-sequence CT 9 Data display mode 10 DI filtering 0~9999 Setting the data display mode of human-machine Secondary value/original value “RUN” menu in device. To set the time of Binary filtering in device. 0~9999ms 11 Communication protocol To set the communication protocol of RS485 in Modbus/IEC101/IEC103/IEC104 device. 12 Communication address Rs485 communication bus address 0~254 13 Communication baud rate Rs485 communication bus baud rate 1200/2400/4800/9600/14400/19200bps The check mode of RS485communication None/odd/even 14 Check mode 15 Display contrast To set contrast value of the human-machine interface LCD screen, for the contrast will 0~9 change as the environment changed, through 19 Operation instruction of ST266F Intelligent general protection and measurement control Device adjusting this value to gain the best result. 16 Operation word pass When the authorization menu is entered from the human-machine interface in device, password 0000~9999 must be input. 17 S1 define To define the type of switch S1 input. 18 S2 define To define the type of switch S2 input. 19 S3 define To define the type of switch S3 input. 20 S4 define To define the type of switch S4 input. 21 S5 define To define the type of switch S5 input. 22 S6 define To define the type of switch S6 input. 23 S7 define To define the type of switch S7 input. 24 Equipment date To set the data of system clock in device. 25 Equipment time To set the time of system clock in device 26 Software Version To set the software version of the device To see section 4.9 V1.0021 Note: 1、Both the “phase CT ratio” and “zero-sequence CT ratio” are value of the ratio, for example,for the CT ratio 500A/5A,set value is 500/5=100; 2、”The mode of data display” is only valuable to “run” men, under the other menus (includes “value”、“record”、“calibration”) of the device, the data appear in secondary value. 3、Switch inherent action time: The time scope is from tripping coil of Circuit breaker energized by the power until the Circuit breaker tripping contact is trigged to close. The real action time of protection device is that the value of set time reduces the inherent time of circuit breaker. The default value of circuit breaker inherent time is 50ms. 6.2 Fixed value parameters Fixed value parameters include all controlling parameters of protection function, please set correctly according to the introduction in Section 4 20 Operation instruction of ST266F Intelligent general protection and measurement control Device Name of Fixed No. Protection Explanation to setting Value 1 2 3 Surge current blocking on/off Short for(Inrush) Value of Surge current blocking Short for(Value) Inter-Phase current quick-break on/off Short for(I>) function Fixed value of soft strap, options:“Switch On” and “Switch Off”. Fixed value of current, setting scope: 0~50A Fixed value of soft strap, options:“On and “Off”. 4 Inter-Phase current quick-break current Short for(Current) 5 Inter-Phase current quick-break time Short for(Delay) 6 Inter-Phase current time-limited quick break on/off Short for(I>>) 7 Inter-Phase current time-limited quick break current Short for(Current) Fixed value of current, setting scope: 0~50A 8 Inter-Phase current time-limited quick break time Short for(Delay) Fixed value of time, setting scope: 0s~600s 9 Curve options of Inter-Phase over current Short for(I>>>) 10 Inter-Phase over-current current Short for(Current) 11 Inter-Phase over-current time Short for(Delay) Surge current blocking Fixed value of current, setting scope: 0~50A Fixed value of time, setting scope: 0s~600s Inter-phase quick-break Fixed value of soft strap, options:“On” and “Off”. Curve set value selection, optional:, “definite curve” 、 “Normal inverse curve”, “Very inverse curve”, “Extremely inverse curve” , “Cut Off”. Fixed value of current, setting scope: 0~50A Fixed value of time, setting scope: 0s~600s 21 Inter-Phase current time-limited quick break Inter-Phase over-current protection Operation instruction of ST266F Intelligent general protection and measurement control Device 12 Inter-phase over-current protection time multiple Short for(Timemul) Time multiple set value, setting scope: 0.05~20 13 Zero sequence over-current 1 section current switch on/switch off Short for(I0>) Fixed value of soft strap, options:“On” and “Off”. 14 Zero-sequence current control Short for(Outstyle) 15 Zero sequence over-current 1 section current Short for(Current) 16 Zero sequence over-current 1 section time Short for(Delay) 17 Zero-sequence over-current 2 section curve option Short for(I0>>) To select set value Curve, options:, “definite curve” 、 “Normal inverse curve”, “Very inverse curve”, “Extremely inverse curve” ,“Cut Off”. 18 Zero-sequence current control Short for(Outstyle) Fixed value of control,options:”alarm” 、 “trip”. 19 Zero sequence over-current 2 section current Short for(Current) Fixed value of current, setting scope: 0~5A 20 Zero sequence over-current 2 section time Short for(Delay) 21 Zero-sequence over-current 3 section curve option Short for(I0>>>) To select set value Curve, options:, “definite curve” 、 “Normal inverse curve”, “Very inverse curve”, “Extremely inverse curve” ,“Cut Off”. 22 Zero-sequence current control Short for(Outstyle) Fixed value of control , options:”alarm” 、 “trip”. Fixed value of control,options:“alarm” 、 “trip”. Zero-sequence over-current 1section Fixed value of current, setting scope: 0~5A Fixed value of time, setting scope: 0s~600s. Zero-sequence over-current 2 section Fixed value of time, setting scope: 0s~600s. 22 Zero-sequence over-current 3 section Operation instruction of ST266F Intelligent general protection and measurement control Device 23 Zero sequence over-current 3 section current Short for(Current) 24 Zero sequence over-current 3 section time Short for(Delay) 25 Inter-phase over-current protection time multiple Short for(Timemul) Time multiple set value, setting scope: 0.05~20 26 Over-voltage protection switch on /switch off Short for(Over vol) Fixed value of soft strap,options: “On” and “Off”. 27 Over-voltage protection voltage Short for(Voltage) Fixed value of voltage, setting scope: 0~20xUn. 28 Over-voltage protection time Short for(Delay) 29 low-voltage protection switch on /switch off Short for(Under vol) Fixed value of current, setting scope: 0~5A Fixed value of time, setting scope: 0s~600s. Over-voltag e protection Fixed value of time, setting scope: 0s~600s. Fixed value of soft strap,options: “On” and “Off”. 30 Low-voltage protection control Short for(Outstyle) 31 Low-voltage protection voltage Short for(Voltage) 32 Low-voltage protection time Short for(Delay) 33 Time multiple of reclose Short for(Reclose times) Setting score: 0~4, 0 stands for function reclose switch off. 34 The fist time of reclose Short for(delay1st) Fixed value of time, setting scope: 0s~600s. 35 The second time of reclose Short for(delay2nd) Fixed value of control , options:”alarm” 、 “trip”. Low-voltag e protection Fixed value of voltage, setting scope: 0~20xUn. Fixed value of time, setting scope: 0s~600s. Fixed value of time, setting scope: 0s~600s. 23 Reclose protection Operation instruction of ST266F Intelligent general protection and measurement control Device 36 The third time of reclose Short for(delay3rd) Fixed value of time, setting scope: 0s~600s. 37 The forth time of reclose Short for(delay4th) Fixed value of time, setting scope: 0s~600s. 38 Post-acceleration protection switch on /switch off Short for(Accafter) Fixed value of soft strap,options: “On” and “Off”. 39 Post-acceleration protection time Short for(delay) 40 Over-load protection switch on /switch off Short for(Overload) Fixed value of soft strap,options: “On” and “Off”. 41 Over-load protection current Short for(current) Fixed value of current, setting scope: 0~50A. 42 Over-load protection time Short for(delay) Fixed value of time, setting scope: 0s~600s. 43 PT wired-breakage switch on /switch off Short for(PT line) Fixed value of soft strap,options: “On” and “Off”. Post-accele ration protection Fixed value of time, setting scope: 0s~600s 24 Over-load protection PT wire-breakage Operation instruction of ST266F Intelligent general protection and measurement control Device 7. Operation of Man-machine Interface The device owns two operation modes for man-machine interface: one is operation from the device, composed of signal indicators, small touch button board, large LCD screen Chinese; the other operation mode is to realize man-machine operation through background debugging assistant software. Man-machine operation from the device is introduced in this section. A 2*2 small touch button board is provided on the bottom of the panel, which has four buttons, namely “ENT” (Confirmation, Exit), “↑/+” (move the cursor upward /plus one), “↓/-” (move the cursor downward /minus one), “→” (move the cursor rightward). “ENT” is used for entering the submenu or returning to the main menu; “↑/+” is used for moving the cursor one step upward or plus one during modification of the parameter; “↓/-” is used to move the cursor one step downward or minus one when modifying the parameters; “→” is used to move the cursor rightward. On the button of left panel, there is a round key that pressed to start the device debugging state, using high energy battery self-carried by the device, user can do these operation as checking , setting and so on. If the key do not press in 20 seconds, the device will cut off the power. The LCD screen cabinets adopt for the displaying mode with layering menus including five main menus: MONITOR、SYSTEM、VALUE、EVENT、CALIBRITION. The following are respectively introduction of different menus. 7.1 Monitor menu When the device is normally connected to the power, the LCD screen will enter the run menu automatically. Both the real-time Ia 301.5A Ib monitoring AC quantities and switching input quantities of device are displayed on the sixth row in front of the screen. If one of the switch define is switch position or energy stored state signal in system menu, the corresponding signal icon will show in the first row of LCD screen. As shown in fig.7.1, the display data refresh every one second automatically in the LCD screen. This screen has two pages of screen 25 284.3A Ic: 321.8A : Figure 7.1 monitor menu Operation instruction of ST266F Intelligent general protection and measurement control Device to display, and every 10 seconds, screen will turn automatically from one to another page, also, can turn over manually with “↑/+” and “↓/-” keys. 7..2 Main menu Pressing the “ENT” key can enter main menu from run menu. Main menu The main menu picture is shown as Fig 7.1. The main menu contain five parts as: run, system, value, calibration, and event. Via “↑/+”、“↓/-”keys to choose the menu need Monitor system value event calibration to enter, black color cursor position color is anti-black. Pressing the “ENT key can enter sub menu of cursor position. output Figure 7.2Main menu 7.3 System menu After entering the system menu from the main menu “Brose”, “Modification” are displayed on the LED screen, in case“browse” is selected, the system parameters will be displayed directly, but the Brose Modify parameter can not be modified or set; in case “Modify is selected”, the parameters can be set, However, correct operation password should be input before modifying the system parameters. Figure 7.3 Brose/modify menu Switching selections with “↑/+” and “↓/-” buttons in “Browse” and “Modification” interface, then press “ENT” button to confirm the selection. In the operating password input interface,entering the Password: 0208 modification status with “→”button, and then select the digit of digitals to be input, then input the numbers with “↑/+” and “↓/-” buttons, then confirm the operating password with “ENT” button. In case the password is wrong, the device will return to the main menu Figure 7.4 operation password input automatically. Under the interface of system parameter modification, select the parameters to be modified with “↑/+” and “↓/-” buttons, and then enter modification status and select the digit of inputting Password 0000 CT ratio 500/5A Address 0003 modification status and select the digit of inputting digitals with “→” Figure 7.5 system menu 26 2/7 Operation instruction of ST266F Intelligent general protection and measurement control Device buttons, and then input numbers with “↑/+” and “↓/-” buttons. After input the numbers, move to the cursor parameter selection status with “→” button and select the next parameter. Finally, press “ENT” button to confirm all modifications and save the parameters and exit the system menu. 7.4 Fixed value menu The operation procedure of the fixed value menu is basically the same with the system menu, fisrtly, select “Browse” and Current Time limited quick-break “Modification”, then input the operating password, and then entering Turn On/Off On the fixed value display screen。 The current value 21.05A The top status colum indicates the protection type of the fixed 09/21 value. The bottom line of status colum indicates the order/total number Figure 7.6 value menu of the current fixed value All the voltage、current value are descriped by secondary value. 7.5 Event record menu Entering the event record menu, shown as Fig.7.7 The device record and show the fresh 100 recoed,each one contains timemark accurated to millisecond,and two pages screen for 10-10-28 08:24:35 235ms Definite quick-break data shown.the first is shown types of event,timemark of event happening;the secomd is shown all AC volumn value when events start 002/200 happening. Check the records with “↑/+” and “↓/-” buttons, and then switch among screens of one record with “→” button. Figure 7.7event menu The voltage and the current in the event record menu are shown with secondary value. Ia: 1.543 3.001A 7.6Calibration menu Ib: 1.534 3.002A In order to eliminate the difference caused of different hardware Ic: 1.527 among AC volumn imput, the calibritation menu is set especially to 2.999A 3/5 09/21 Figure 7.8 calibration menu 27 Operation instruction of ST266F Intelligent general protection and measurement control Device adjust the channel balance through software. Operation course of calibration menu is basically similar to the system menu. For all channel parameters are input correctly before device for ship, it is not necessary to change these parameters when the device normal operation. Do not enter the modification state freely to avoid bad operation and error modification of parameters. If you enter this menu wronged, please press ENT key to turn back to main menu. 7.7 Output menu The output menu is used for relays testing in device. Before operation, you should take attention to the consequence to primary equipment. The right password must be input to enter output menu. Relay1 Relay2 Relay3 Relay4 As shown figure 7.9.entering the menu, you can choose the relay need to be driving by “↑/+”、 “↓/-” keys, press the key “→” to drive relay, the relay will be return after 0.5seconds. 2/4 Figure 7.9 output menu Note: 1. In order to prevent the protection device from malfunctioning in the process of modifying various parameters, when the man-machine interface entering the interface of modifying various parameters (including system parameter, setting parameter, channel parameter), the device will automatically exit all protection functions. Therefore, after modifying the parameters, one should timely return to the main menu or running menu to ensure the timely switching on of protection functioning. 28 Operation instruction of ST266F Intelligent general protection and measurement control Device 2. High energy stand-by battery is provided with the power self-supply device. The stand-by battery can provide power for the device when there is not external power. In case the power line can not provide enough power to the device, the device will enter the status of low power consumption stand-by status, then the device can be activate through low power consumption. The stand-by battery is a high performance maintain free lithium cell and can work for over 15 years in normal conditions. 29