Uploaded by root

ROCB Lighting Panel

advertisement
A-Series
Lighting Control
Panel
with Remotely Operated
Circuit Breakers (ROCB)
1
ROCB Panel
A-Series Lighting Control Panel
with Remote Operated Circuit Breakers
Factors Driving Use
Continued Rise in Energy Costs
Market Adopting Energy Efficient Codes
Integration of Systems within Facilities
Lighting is 30% of energy cost for Commercial
Benefits
• Reduced Energy Cost
•Reduced Lighting Cost (Extend lamp life, lower maintenance cost)
• Short Circuit Protection and Remote Control
• Maximizes Lighting Effectiveness and Property Security At Min. Cost.
2
ROCB Panel
Remote Operated Circuit Breaker Overview
+
=
3
ROCB Panel
Remote Operated Circuit Breaker Overview
Remotely Operated Circuit Breaker:
Amps: 15, 20, 30A
Volts: 120/240, 208Y/120, 277/480VAC
Status Indicator
Green – open
White - closed
Poles: 1 and 2 Pole
UL:
489 Certified
20 Year Life reliability
50,000 operations under full load
Bolt On
Line strap
Unidirectional
Motor
Floating Control Pin for
Electrical Connection
Snap on Clip
Aux Switch for Contact Status,
linked to Contact Arm
4
ROCB Panel
A-Series Lighting Control Panel Overview
TEYRC:
Remote Operated
Circuit Breaker
Backplane: PC Boards
Houses Breaker Input/Output
Connections and Controller
Plug-In Interface
Cable:
DB 25 straight thru
Cable connection
Integral Controller:
Schedules and
Controls Breakers
Class 2 Transformer:
Fed Off Main Bus To
Power Controller
5
ROCB Panel
A-Series Lighting Control Panel Overview
Panel Highlights
• TEYRC and TEY branch breakers
• THQBGF / THQBGFEP available @ 120/208V
• Maximum branch ampacity = 150A
Capability to mount
standard TEY breakers
• Main bus ratings up to 400A UL
• Subfeed Breaker Combinations:
• (1) SF @ 225A and (1) TED @ 150A
Capability to mount
240V Ground Fault
6
ROCB Panel
Controller Overview
Controller: (Internal Firmware)
• Open Protocol; Native BacNet & Modbus
• 16 Time of Day, On/Off Scheduling
•Day of week repeating schedule
• 16 Lighting Zones/groups of control
• Real Time & Astronomical Clock
• Holidays Control Override
• Leap Year & Day Light Savings Time
Controller: (Internal Hardware)
• 16 Digital Inputs, 2 or 3 wire
• 3 Analog Inputs
• Auto Flip
• Off Warning (flick)
• Self Diagnostics, Breaker contact status
• Burn Hour Tracking, Load Priority Management
• Event alarm and recovery
• Battery back-up
•Daylight Optimization Module
7
ROCB Panel
Controller
16 Digital Inputs
Auto
Flip
Battery
Backup
Addressable
Dip Switch
Analog Inputs
Hand-held
Programmer Port
Alarm
Output
Local
Overrides
8
ROCB Panel
Controller Comm
RS232
Programming
port
Ethernet port
(Optional – highly
recommend on at
least 1 ROCB per
system)
RS485
Net 1
For
multiple
ROCB
RS485
Net2 for
Daylight
& Sw
Modules
9
ROCB Panel
A-Series
Lighting
Control
Panelboard
Section 9
BuyLog
10
ROCB Panel
Lighting Control Panel: How to Review
Standard TEY
Breaker
Int Control
w/Ethernet
RC = ROCB
Breaker
Approval Drawing
11
ROCB Panel
Controller Set-up and Configuration
Hand Held Programmer
Software Programming
12
ROCB Panel
13
ROCB Panel
14
ROCB Panel
15
ROCB Panel
16
ROCB Panel
ROCB PANEL WORKSHEET
Notes:
1)
2)
3)
4)
RJC
FEB,06
This is a worksheet for basic functions, see instruction book for details and
more complex functions.
Decide which circuits will be controlled at the same time, put these in group.
Max 16 groups per panel, groups can be inside groups.
Decide how a group will be controlled: hard wire input, time of day schedule,
Astrological time for location, or photo cell.
Fill out schedule with on periods of lights, max 8 per day. Max 16 schedules/panel.
Lighting Group No (ZN01 to ZN16) ___________LTG Grp
(Can be breakers in this panel or other panel; or other groups.)
I/O Definition
Lighting Outputs
(Select which breakers will be in a group of control)
Breaker No
Panel No Circuit description
Configuration
Flick Warning Enable___ Minutes before off ____(Will blink lights before shutting them off.)
Input_____Time_____(ex Switch to turn lgts on if working late)
Override
(Can control on, off or both)
Schedule No /
______
On_____ Off_____ (See Schedule below.)
or Input No
On_____ On offset______min Off______ Off offset____min
Astro
Astro clock based on location (ex Cleveland, OH), can control on, off or both
Input_____On_____ Off_____ (Can control on, off or both)
Photo Cell
Schedule No (SchA to SchP) ___________
Daily Schedule
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Holiday CAL 1
Holiday CAL 2
On_____
On_____
On_____
On_____
On_____
On_____
On_____
Y/N_____
Y/N_____
(Set on/off times for each day of week, max 8 on/off per day)
Off_____ On_____ Off_____ On_____ Off_____ On_____
Off_____ On_____ Off_____ On_____ Off_____ On_____
Off_____ On_____ Off_____ On_____ Off_____ On_____
Off_____ On_____ Off_____ On_____ Off_____ On_____
Off_____ On_____ Off_____ On_____ Off_____ On_____
Off_____ On_____ Off_____ On_____ Off_____ On_____
Off_____ On_____ Off_____ On_____ Off_____ On_____
(Sub Schedule to control lights on a holiday)
(Sub Schedule to control lights on a holiday)
Off_____
Off_____
Off_____
Off_____
Off_____
Off_____
Off_____
17
ROCB Panel
ROCB PANEL WORKSHEET
Panel 200 (LP4-P2)
Notes:
1)
2)
ROCB
Panel
Address
3)
4)
RJC
This is a worksheet for basic functions, see instruction book for details and
more complex functions.
Decide which circuits will be controlled at the same time, put these in group.
Max 16 groups per panel, groups can be inside groups.
Decide how a group will be controlled: hard wire input, time of day schedule,
Astrological time for location, or photo cell.
Fill out schedule with on periods of lights, max 8 per day. Max 16 schedules/panel.
Lighting Group No (ZN01 to ZN16) ___ZN02____LTG Grp
2 Pole
Breakers
In Group
Used Astro
Clock
I/O Definition
Lighting Outputs
Breaker No
Panel No
7,9
200
11,13
200
15,17
200
8,10
200
12,14
200
(Can be breakers in this panel or other panel; or other groups.)
(Select which breakers will be in a group of control)
Circuit description
Site Poles
Site Poles
Site Poles
Site Poles
Site Poles
Configuration
Flick Warning Enable___ No Can't use with Metal Halide fixtures
Input_____Time_____Not used
Override
Not used
Schedule No /
______
On_____ Off_____ Not used
or Input No
Astro
HID – No flick
warning
ON YES On offset 60 min Off YES Off offset 60 min
Astro clock based on location Erie, PA
Photo Cell
Input_____On_____ Off_____ Not used
Schedule No (SchA to SchP) Not Used
18
ROCB Panel
PROGRAMMABLE PANEL WORKSHEET
02/21/2006
Lighting Group # ZN01
Breaker No
2,4
6,8
10,12
16,18
20,22
24,26
28,30
32,34
36,38
Panel No
A
A
A
A
A
A
A
A
A
Added
14
A
Circuit description
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
SITE LIGHTING POLES
Sign@ Whipple Ave
Configuration
Flick Warning
Override
Schedule No /
or Input No
Astro
NO - not capable with metal halide fixtures
NO
SEE PHOTOCELL INPUT BELOW
Photo Cell
Lights will be on from dusk-to-dawn and also on gloomy days, based on the photocell.
NO
Used input 101, wired as maintained 2 wire input.
Photo Cell
Connected to
1 of 16 Inputs
19
ROCB Panel
School Lighting Control System
With 4 ROCB’s
Address Set w/
Dip Switch
ROCB
PANEL
100
ROCB
PANEL
200
Line
Circuit
Breaker
Building
Automation
System
Line
Load
Circuit
Breaker
ON
OFF
Status
Controller
Controller
ROCB
PANEL
400
Line
Load
Circuit
Breaker
ON
OFF
Status
Panel
Ethernet
ROCB
PANEL
300
Line
Load
Circuit
Breaker
ON
OFF
Status
Controller
Panel
ON
OFF
Status
Controller
Panel
Ethernet
Or Net 1
Ethernet
Or Net 1
RS485
RS485
Load
Panel
Ethernet
Or Net 1
RS485
20
ROCB Panel
A-Series Lighting Control Panel
with Remote Operated Circuit Breakers
Specifying Tips
Use internal controller (If space allows) with Ethernet
Spec panel with TVSS (To protect electronic ballast)
Spec Software (Provides backup file) or Hand Held Programmer to configure panel.
Spec Factory Programming (Provide control scheme desired or must be quoted
at a latter time.)
Spec On-site System commissioning (Particularly for larger jobs or BAS interface.)
Analysis and Benefits
• Compare Installed Cost – ROCB vs. Lighting Panel w/Relay Panel
w/Interconnection
• Lighting Control w/ communication, lamp burn info, flexible, expandable.
• Install ROCB to meet energy code, configure and define as building use grows.
21
ROCB Panel