FSO OKHA 1 P1231 HEATING SYSTEM FOR HAWSEPIPE Heat Calculation Hawse pipe Hawse pipe particulars: Affected Length Inside Diameter Wall Thickness Outside Diameter L Di Tp Do = 12000mm (12meters) = 717.6 mm = 22.2 mm = 762 mm Consider the inside wall of the pipe as a plate of dimension: L x W x Tp : 12000 x π Di x 22.2 Area of This wall: π Di L = 27.04 m2 → 290.95 ft2 ≈ 291 ft2 12000 mm Tp = 22.2 T2 T1 + 5° C 2253mm -20° C 22.2 Heat flow across wall as: T1 = -20° C or -4°F T2 = +5 ° C or 41°F ∆T = T2 - T1 = 25ºC or 45°F Heat Transmission across Wall Section of Pipe: Q = U x A x ∆T Q is Rate of heat transfer of Steel at 22.2 TBC U = 33.75 Btu/hr/ft2/R in still Air U is U value of wall(steel) = 33.75 A is Area = 27.04 m2 = 290.95 ft2 ∆T is 25° C or 45°F Q = 33.75 x 290.95 x 45 → 441,880 Btu Take 10% safety factor in above, The heat load → 441,880 x 1.1 → 486068 Btu/Hr → 142 KW heating GB MARINE PTE LTD SINGAPORE FSO OKHA 2 P1231 Calculate heating Agent Flow from Calorifier through the I - tubes wrapped around: As per ASHRAE: Flow of heating agent = total heat load / (500 x ∆T) Where ∆T is temperature different between inlet and outlet of heating media via Tube & Heaters. We assume: inlet Temp → 200°F Outlet Temp → 175°F So ∆T → 25°F But this is not the same as the Korean said, which is not practical at all >: Flow of liquid / Agent Heating agent flow rate = Heat load / (500 x 25) = 486068/ (500 x 25) = 38.88 gpm = 8.83 m3/Hr. --- (ASHRAE) Check Velocity at 8.83 m3/Hr → 12.20 m/sec → 2400 ft/ min→ Linear Flow Tank Volume = 1.2 x 0.8 x 1.2H = 1.152 m3 = 1152 litres Now we calculate the total surface area of heating coil required to transfer heat of required amount through the 16 mm OD copper tube: Surface Area = Total Heating Load / Loading Total Heating Load = 486068 Loading (as per ASHRAE) = 550 As = 486068 / 550 = 883.76 ≈ 884 ft2 / Pipe Diameter = 16 mm = 0.0525 ft Surface Area = π D Lp Where Lp → surface area(As) / π D = 884 / π D = 5362 ft = 1635 m Add 10% safety factor on pipe → 1798 m → say 1800 m GB MARINE PTE LTD SINGAPORE FSO OKHA P1231 3 Check if this pipe can be wrapped around the Hose of 12m, Figure 12000mm 12000 ÷ 16 mm pitch → 750 Turns → each turn at 2.5 m around hose pipe. So, 750 x 2.5 → 1875 m of pipe is possible → OK Observation Amount of Glycol remain over 1800m tube at all time → 350 ~ 360 litres heated at all time. Observation/ Consideration 1) 2) 3) 4) Temperature Gradient → 25°C or 45°F Calorifier inlet/ outlet → 200°F / 175°F ∆T → 25°F Not as suggested 70°C ??? Insulation must be improved to minimise loss due to any leak on tubes by rockwool of Blanket type. Exposed pipe/ tube from Calorifier to be insulated. GB MARINE PTE LTD SINGAPORE FSO OKHA 4 P1231 Schematic of Piping 22.2 mm x 762 mm HOSE PIPE Ckt 1 Ckt 2 Ckt 3 Ckt 4 Ckt 5 Supply Header Return Header 200°F From Calorifier Total Tube length 175°F To Calorifier 1800 meters on the body of the hose pipe GB MARINE PTE LTD SINGAPORE FSO OKHA P1231 5 COMMENTS (1) Glass wool thickness and density are not mentioned in the contractor quotation. We recommend mineral glass wool blanket at about 4'' (100mm) thickness at minimum 80 Kg/ m3 density. (2) All pipes, valves and fittings are to be suitably insulated. (3) It appears that there is a gap of 16mm between every turn of tubes. We do not agree to this, as this will not be sufficient to cater for heat load. In other word, length of copper tube as suggested by the contractor of 1,017m approximately to be substantially low. We would recommend that there is no gap between the copper tube (length would be approximately 1800m to 2000m). (4) In the calorifier specification, we note that temperature of Heating agent are inlet: -20°C and outlet: + 50°C. This seems to be not a reasonable figure as the temperature is extremely high to cause any damage to calorifier internals. It is only reasonable in calculation is to have ∆T about 20-25°F Taking outlet → 200°F (93°C) of calorifier (inlet of supply Header) and Inlet of calorifier as 175°F (79°C) which is outlet of return Header (See our schematic). (5) Outlet from Calorifier to the hawsepipe should be installed from bottom to upwards. (6) Calorifier dimensions shown appear to be rectangular where as in description "type" as vertical cylinder. (7) No comments are expressed on electrical heater and control parts for calorifier. (8) We assume that necessary pressure and temperature safety valve(s) will be arranged by contractor. (9) We have not reviewed on overall pipes, fittings and valves etc., as we do not have any layout, detailed drawings from vendor. GB MARINE PTE LTD SINGAPORE