SAMPLES OF PROBLEMS THAT WE ARE FACING DURING SYSTEM CHECK(DONE BY ETC) FROM 7TH TO 2ND FLOOR
DEVICE
PROBLEM
SYSTEM FAULT
RESPONSIBLE
7F-P5-L23-CM109
CONTROL MODULE RELAY OF OUTPUT DAMAGE
FIRE
SBM
7F-P5-L23-CM109
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
7F-P5-L23-CM58 ACCESS CONTROL
DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET
‫اﻟﺼﺎﻧﻊ‬
7F-P5-L24-CM103
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
7F-P5-L23-CM18
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
SMOKE DETECTOR HAVE DELY IN ZONE 3 FOR PRESSURIZATION FAN
FIRE
CSC
SMS DAMPER TRIGERED FROM SMOKE DETECTORS ONLY ZONE 3
FIRE
CSC
SMS FANS TRIGGRED FROM BREAK GLASS ONLY ZONE 3
CSC
FIRE
NO ZONING FOR ELEVATORS
CSC
FIRE
WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1
ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE
FIRE
CSC & SBM
FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY
THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT
ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2
CSC
6F-P5-L21-CM103
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
6F-P5-L22-CM105
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
6F-P5-L22-CM55 ACCESS CONTROL
DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET
‫اﻟﺼﺎﻧﻊ‬
ZONING MISTACKE BETWEEN ZONE 1 AND ZONE 2 (TREGERED IN SAME TIME IN D1 TIME)
CSC
FIRE
SMS FANS TRIGGRED FROM SMOKE DETECTOR IN D03
FIRE
CSC
SMS FANS TRIGGERED FROM D2 ONLY FROM BREAK GLASS ZON3
FIRE
CSC
WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1
ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE
FIRE
CSC & SBM
FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY
THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT
ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2
CSC
FIRE
5F-P4-L20-CM105
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
5F-P4-L20-CM56 ACCESS CONTROL
DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET
‫اﻟﺼﺎﻧﻊ‬
NO EVACUATION ALSO NO ALERTING (PUBLIC ADDRESS)IN THE FLOOR
PUBLIC ADDRESS
CSC
ZONING MISTACKE BETWEEN ZONE 1 AND ZONE 2 (TREGERED IN SAME TIME IN D1 TIME)
FIRE
CSC
SMS FANS TRIGGRED FROM SMOKE DETECTOR IN D03
CSC
FIRE
SMS FANS TRIGGERED FROM D2 ONLY FROM BREAK GLASS ZON3
FIRE
CSC
WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1
ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE
CSC
FIRE
FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS
ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2
FIRE
CSC
4F-P4-L18-CM103 ACCESS CONTROL
DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET
‫اﻟﺼﺎﻧﻊ‬
4F-P4-L18-CM44 ACCESS CONTROL
DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET
‫اﻟﺼﺎﻧﻊ‬
4F-P4-L18-CM171 ACCESS CONTROL
DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET
‫اﻟﺼﺎﻧﻊ‬
4F-P4-L17-CM175
INTERFACE MODULE WRONG TERMINATION
FIRE
SBM
4F-P4-L18-CM67 PUBLIC ADDRESS
VOLUME CONTROL WRONG TERMINATION FOR FIRE CASE
SBM
4F-P4-L18-CM37
MODULE WAS NOT TERMINATED TO ACCESS CONTROL PANEL
FIRE
SBM
SMS FANS TRIGGRED FROM SMOKE DETECTOR IN D03
CSC
SMS FANS TRIGGERED FROM D2 ONLY FROM BREAK GLASS ZON3
CSC
WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1
ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE
CSC&SBM
FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY
THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT
ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2
CSC
3F-P3-L14-CM133
USING WRONG MODULE (FIXING S434410 AS CONTROL MODULE)
FIRE
SBM
3F-P3-L14-CM11 ACCESS CONTROL
CONFIGURE WRONG DIP SWITCH SETTING IN ACCESS CONTROL PANEL
SBM
11 DOORS HAS WRONG CONFIGURATION FOR FIRE INPUT
ACCESS CONTROL
‫اﻟﺼﺎﻧﻊ‬
3F-P3-L15-CM114
INTERFACE MODULE NOT TERMINATED
FIRE
SBM
3F-P3-L15-CM180
INTERFACE MODULE NOT TERMINATED
FIRE
SBM
3F-P3-L14-CM65
INTERFACE MODULE NOT TERMINATED
FIRE
SBM
AC PANELS TRIGGRED IN D0 IN CASE OF DETECTOR
FIRE
CSC
AC PANELS TRIGGRED IN D0 IN CASE OF DETECTOR
FIRE
CSC
13 DOORS HAS WRONG CONFIGURATION FOR FIRE INPUT
ACCESS CONTROL
‫اﻟﺼﺎﻧﻊ‬
SMS DAMPER TRIGERED FROM SMOKE DETECTORS ONLY ZONE 3
CSC
FIRE
SMS FANS TRIGGRED FROM BREAK GLASS ONLY ZONE 3
FIRE
CSC
WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1
ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE
CSC&SBM
FIRE
FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY
THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT
ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2
FIRE
CSC
GENERAL REMARK:SBM COMPANY HAS ONLY ONE FORMAN AND ONE TECHNICIAN IN THE SITE ,ONLY ETC TEAM WHO IS TESTING
AND SOLVE THE PROBLEMS IN THE SITE
STATUS
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEARED BY CSC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC
CLEADERD BY ETC