FLOOR SEVEN SEVEN SEVEN SEVEN SEVEN SEVEN SEVEN SEVEN SEVEN SEVEN SEVEN SIX SIX SIX SIX SIX SIX SIX SIX FIFE FIFE FIFE FIFE FIFE FIFE FIFE FIFE FOUR FOUR FOUR FOUR FOUR FOUR FOUR FOUR FOUR FOUR THIRD THIRD THIRD THIRD THIRD THIRD THIRD SECOND SECOND SECOND SECOND SECOND SECOND SAMPLES OF PROBLEMS THAT WE ARE FACING DURING SYSTEM CHECK(DONE BY ETC) FROM 7TH TO 2ND FLOOR DEVICE PROBLEM SYSTEM FAULT RESPONSIBLE 7F-P5-L23-CM109 CONTROL MODULE RELAY OF OUTPUT DAMAGE FIRE SBM 7F-P5-L23-CM109 INTERFACE MODULE WRONG TERMINATION FIRE SBM 7F-P5-L23-CM58 ACCESS CONTROL DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET اﻟﺼﺎﻧﻊ 7F-P5-L24-CM103 INTERFACE MODULE WRONG TERMINATION FIRE SBM 7F-P5-L23-CM18 INTERFACE MODULE WRONG TERMINATION FIRE SBM SMOKE DETECTOR HAVE DELY IN ZONE 3 FOR PRESSURIZATION FAN FIRE CSC SMS DAMPER TRIGERED FROM SMOKE DETECTORS ONLY ZONE 3 FIRE CSC SMS FANS TRIGGRED FROM BREAK GLASS ONLY ZONE 3 CSC FIRE NO ZONING FOR ELEVATORS CSC FIRE WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1 ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE FIRE CSC & SBM FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2 CSC 6F-P5-L21-CM103 INTERFACE MODULE WRONG TERMINATION FIRE SBM 6F-P5-L22-CM105 INTERFACE MODULE WRONG TERMINATION FIRE SBM 6F-P5-L22-CM55 ACCESS CONTROL DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET اﻟﺼﺎﻧﻊ ZONING MISTACKE BETWEEN ZONE 1 AND ZONE 2 (TREGERED IN SAME TIME IN D1 TIME) CSC FIRE SMS FANS TRIGGRED FROM SMOKE DETECTOR IN D03 FIRE CSC SMS FANS TRIGGERED FROM D2 ONLY FROM BREAK GLASS ZON3 FIRE CSC WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1 ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE FIRE CSC & SBM FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2 CSC FIRE 5F-P4-L20-CM105 INTERFACE MODULE WRONG TERMINATION FIRE SBM 5F-P4-L20-CM56 ACCESS CONTROL DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET اﻟﺼﺎﻧﻊ NO EVACUATION ALSO NO ALERTING (PUBLIC ADDRESS)IN THE FLOOR PUBLIC ADDRESS CSC ZONING MISTACKE BETWEEN ZONE 1 AND ZONE 2 (TREGERED IN SAME TIME IN D1 TIME) FIRE CSC SMS FANS TRIGGRED FROM SMOKE DETECTOR IN D03 CSC FIRE SMS FANS TRIGGERED FROM D2 ONLY FROM BREAK GLASS ZON3 FIRE CSC WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1 ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE CSC FIRE FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2 FIRE CSC 4F-P4-L18-CM103 ACCESS CONTROL DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET اﻟﺼﺎﻧﻊ 4F-P4-L18-CM44 ACCESS CONTROL DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET اﻟﺼﺎﻧﻊ 4F-P4-L18-CM171 ACCESS CONTROL DOOR OPEN IN CASE OF FIRE AND DIDN’T RECLOSE AFTER FIRE RESET اﻟﺼﺎﻧﻊ 4F-P4-L17-CM175 INTERFACE MODULE WRONG TERMINATION FIRE SBM 4F-P4-L18-CM67 PUBLIC ADDRESS VOLUME CONTROL WRONG TERMINATION FOR FIRE CASE SBM 4F-P4-L18-CM37 MODULE WAS NOT TERMINATED TO ACCESS CONTROL PANEL FIRE SBM SMS FANS TRIGGRED FROM SMOKE DETECTOR IN D03 CSC SMS FANS TRIGGERED FROM D2 ONLY FROM BREAK GLASS ZON3 CSC WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1 ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE CSC&SBM FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2 CSC 3F-P3-L14-CM133 USING WRONG MODULE (FIXING S434410 AS CONTROL MODULE) FIRE SBM 3F-P3-L14-CM11 ACCESS CONTROL CONFIGURE WRONG DIP SWITCH SETTING IN ACCESS CONTROL PANEL SBM 11 DOORS HAS WRONG CONFIGURATION FOR FIRE INPUT ACCESS CONTROL اﻟﺼﺎﻧﻊ 3F-P3-L15-CM114 INTERFACE MODULE NOT TERMINATED FIRE SBM 3F-P3-L15-CM180 INTERFACE MODULE NOT TERMINATED FIRE SBM 3F-P3-L14-CM65 INTERFACE MODULE NOT TERMINATED FIRE SBM AC PANELS TRIGGRED IN D0 IN CASE OF DETECTOR FIRE CSC AC PANELS TRIGGRED IN D0 IN CASE OF DETECTOR FIRE CSC 13 DOORS HAS WRONG CONFIGURATION FOR FIRE INPUT ACCESS CONTROL اﻟﺼﺎﻧﻊ SMS DAMPER TRIGERED FROM SMOKE DETECTORS ONLY ZONE 3 CSC FIRE SMS FANS TRIGGRED FROM BREAK GLASS ONLY ZONE 3 FIRE CSC WE HAVE AHU MACHINES SHARED FOR 3FLOORS OR MORE NOT TRIGGRED IN D1 ALTHOUGH SBM WHO MAKE SHEET FOR AHUS CONTROL MODULE BECAUSE THEY HAVE CSC&SBM FIRE FULL INFORMATION ABOUT AHUS BMS TO MAKE GRAFIC BMS THEY SEND TO US OFFICIALY THAT THEY NEED ONLY CONTROL MODULES OF SMOKE MANAGEMENT ALL DAMPERS TRIGGRED IN ALL FLOORS IN D2 FIRE CSC GENERAL REMARK:SBM COMPANY HAS ONLY ONE FORMAN AND ONE TECHNICIAN IN THE SITE ,ONLY ETC TEAM WHO IS TESTING AND SOLVE THE PROBLEMS IN THE SITE STATUS CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEARED BY CSC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC CLEADERD BY ETC