4. Medical gas installations
1.
2.
3.
4.
5.
The design parameters for internal spaces should be found in the detailed room-requirement sheets published in
the individual IUSS guidance documents of the various functional units. Where these room-requirement sheets are
absent or lacking adequate information, the data contained in this document may be used.
All units of a health establishment, except sub-acute and hospice facilities, where patients are accommodated and
treated, must have medial gases and vacuum provided by medical-grade piped services, with indexed terminal
connecter points. Bottle systems may be provided in sub-acute and outpatient facilities.
Mobile gas services must be available for crisis situations.
Sub-acute facilities must have one mobile oxygen cylinder per 10 patients and one suction machine for every 10
patients.
The minimum services to be supplied to all acute care areas are described in Table 11.1. Should the data in this
table be in conflict with the table presented in the individual departmental design guidance documents, those
individual guidance documents take precedence.
TABLE 5: MINIMUM GAS SERVICES
Description
Major theatre8
Minor theatre8
Cath lab
8
Oxygen
HP Air
LP Air
N2O
VAC
Theatre panel
1
1
1
1
2
Per pendant
2
2
2
1
2
Theatre panel
1
1
1
1
2
Per pendant
2
2
2
1
2
Theatre panel
1
1
1
1
2
1
1
Per pendant
1
Post operation
Bedhead trunking
1
1
1
Procedure room
Theatre panel
1
1
2
Resuscitation bay
1
1
2
Delivery room
2
1
2
High-care unit, per bed
1
1
2
Intensive-care unit, per bed
2
2
2
Casualty, per bed
1
1
1
Wards
1 per 2
beds
6.
7.
8.
8In
Scavenging
1
1
1
1 per 2
beds
A gas alarm system to monitor gases, excluding scavenging, must be installed in a location that is manned 24 hours
per day. A slave panel must also be installed in the intensive-care unit and in the theatre complex. This alarm
system must be connected to UPS.
All piped vacuum and oxygen systems must have mobile back-up systems with adequately trained staff to handle
them. The back-up service shall be automatically activated if the line pressure drops below the set operating
pressure. All back-up services and change-over valves shall be on UPS and diesel generator supplies.
Medical air (low pressure) for respiratory purposes must be provided at a fixed pipeline pressure of 400 kPa.
Medical air (high pressure) for driving surgical power tools must be provided at a terminal usage pressure between
700kPa and 1000 kPa, depending on the tools/equipment to be used. The ICU and operating rooms must be
cases where a second pendant is installed, the services in the theatre panel can be omitted.
INFRASTRUCTURE UNIT SUPPORT SYSTEMS (IUSS) PROJECT
Health Facility Guides:
Building Engineering Services - Gazetted 17 February 2016
36
1
Procedure rooms 1
Maternity delivery
rooms
Dialysis Treatment
Beds.
Note that the
equipment can include
water heating with
high kw loading so
care should be taken
when sizing the
isolating transformers
2
Pendant Panel fed
from MIT and UPS
Red dedicated SSO
with Blue DPS
INFRASTRUCTURE UNIT SUPPORT SYSTEMS (IUSS) PROJECT
Health Facility Guides: 25 October 2013
Building Engineering Services [APPROVAL V2]
4 x 16A Dedicated per bed
on the same isolating
transformer but two
separate circuits
4 x 16A per bed per
two circuits.
2
1 x Red 16A Dedicated
1 x 16A Normal per
Station
1 x Red 16A Dedicated
for Radiology Procedure
Crash Cart Position
1 x 16A Normal per
ward for cleaning +
1 x 16A in ceiling
for TV point per
bed. 2 x 16A per bed
1 x 16A Normal per
Ward for Cleaning
1 x 16A Normal per
every 15m of
corridor for
Cleaning
1 x 16A Normal
1 x 16A Normal per
Station
Dedicated Red SSO
fed from UPS on
Wall or Power
Skirting
Location on wall
or from UPS on
Wall or Power
Skirting
4 x 16A Dedicated per bed
on the same isolating
transformer but two
separate circuits (Note if
you are using a 8kva
isolating transformer you
can put 6 beds on one
transformer)
0
1
0
1
Casualty treatment
Rooms 1
Casualty ward
Corridor 0
Rooms Dedicated
125A supply to
dedicated
Radiology control
room
Group
Description
Location
Medical
Number and type of Switch Socket Outlets (SSO)
Hospital Service Panel
Bed Head Trunking
fed from MIT and
Theatre Panel fed
Bed Head
UPS. 16 A Red
from MIT and UPS
Trunking backed
dedicated SSO with
Red dedicated SSO
up by Standby
Blue DPS9
with Blue DPS
50
On Wall fed from
MIT and UPS Red
dedicated SSO with
Blue DPS
Download