Description
These York® Affinity™ packaged air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
Field-installed electric heater accessories are available to
provide electric heat, if required.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
294604-YTG-G-0511
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Component Location
Cooling Only
Direct Drive Condenser
Fan Motor
Highly Efficient Enhanced Copper
Tube/Aluminum Fin Indoor Coil
Highly Efficient Enhanced Copper Tube/Enhanced Aluminum Fin
OR Micro-Channel Aluminum Tube/Aluminum Fin Condenser
Back And Bottom
Return Air and Supply
Air Duct Opening
Decorative Protective
Coil Guard
High Voltage
Terminal Block
Low Voltage
Terminal Block
Long-Lasting
Powder Paint Finish
High-Efficiency Compressor
Rigidly Mounted
2
Direct Drive Blower Motor With
Slide-Out Blower Assembly
Heavy Gauge
Removable Base Rails
Johnson Controls Unitary Products
294604-YTG-G-0511
Nomenclature
Cooling Only
D 2
EZ
024 A
06
Product Category
Voltage Code
D = Single Package Air Conditioner
(Air Cooled)
06 = 208/230-1-60
25 = 208/230-3-60
46 = 460-3-60
58 = 575-3-60
Product Generation
2 = Second Generation
Product Identifier
EZ = R-410A 13 SEER
EQ = R-410A 14 SEER
EY = R-410A 14 SEER
EX = R-410A 15 SEER
Features and Benefits
Standard Features
• Operating Efficiency - All air conditioners provide
operating efficiencies of 13 to 15 SEER. All efficiencies
exceed legislated minimum levels.
• On Site Flexibility - All model sizes share a common,
compact design cabinet in a single footprint. The installer
has the flexibility of setting one curb and placing the
proper tonnage unit on that curb after the internal load has
been determined. Field convertible duct connections from
side shot to down shot allows the installer to have greater
flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections.
The small base dimension means less space is required
on the ground or roof, plus, the installer can fit this unit
between the wheel wells of full size pick-up truck.
All units are completely wired, charged with R-410A and
tested prior to shipment. Unique test stations using a new
state of the art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers at assembly. Vital
run test statistics such as system pressure, motor
currents, air velocity and temperature, unit vibration, and
gas system safeties are monitored and recorded by the
system to insure unit performance.
Equal size, side supply and return duct connections
allows easy hook-up of ducts to match low crawl spaces
without transition pieces.
• Utility Connections Made Easy - Electric utility knockouts
are provided through the bottom as well as the side of the
unit. Utility connections can be made quickly and with a
minimum amount of field labor. A field supplied and field
installed electrical disconnect switch must be installed.
• Convertible Airflow Design - The bottom duct openings
are covered when they leave the factory ready to be used
for a side supply/side return application. If a bottom
supply/bottom return application is desired, you simply
remove the two panels from the bottom of the unit and
place them in the side supply/side return duct openings.
No panel cutting is required and no accessory panel is
necessary. Convertible airflow design allows maximum
field flexibility and minimum inventory.
Johnson Controls Unitary Products
Factory Installed Electric Heat
A = No Electric Heat Installed
Nominal Cooling Capacity (MBH)
024 = 24,000 BTUH
030 = 30,000 BTUH
036 = 36,000 BTUH
042 = 42,000 BTUH
048 = 48,000 BTUH
060 = 60,000 BTUH
• Condensate Pan - A non-corrosive, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate. Less collection of stagnate
condensate will build-up. The condensate pan conforms
to ASHRAE 62-89 standards (Ventilation for Acceptable
Indoor Air Quality).
• Condensate Drain - The heavy duty, 3/4 inch NPTI copper
connection is more durable over time. The connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - With a heavy duty cabinet made of
powder-painted, galvanized steel the neutral color blends
into surrounding areas. The powdered paint provides a
better paint to steel bond, which resists corrosion and rust
creep. The special primer formulas and glossy finish
insures less fading when exposed to sunlight and offers a
more attractive on site appearance. This paint finish
meets ASTM-B117 standards for 1000 hours salt spray
rating. The highest in the industry.
• Full Perimeter Base Rails - The easily removable base
rails provide a solid foundation for the entire unit and
protects the unit during shipment. The rails provide fork lift
access from all sides, and rigging holes are also provided
so that an overhead crane can be used to place the units
on a roof. On applications where the unit is placed on a
pad, the base will keep the unit off the pad to deter
corrosion. On applications where height is limited, the inch
high base rails may be removed on location.
• More Attractive Appearance - A single piece Water Shed
top cover containing a top discharge condenser fan
arrangement requires less square footage on installation
and provides a wider variety of installations. The one piece
design adds greater water integrity. Rounded corners with
water drip edges add to the attractive appearance. The
cabinet panels have a non-fibrous insulation that will not
release insulation fibers into conditioned area.
• Top Discharge - The top discharge condenser fan does
not disrupt neighboring areas or dry-out vegetation
surrounding the unit. The warm air from the top mounted fan
is blown up away from the structure and any landscaping.
This allows compact location on multi-unit applications.
• Condenser Coil Grille - All DEZ models utilize a
decorative “Wire-Form” coil guard to provide impact
protection against large objects. All other models utilize a
stamped “Louvered” design which provides superior
3
294604-YTG-G-0511
•
•
•
•
•
•
•
•
•
•
4
impact protection against smaller objects during transit
and after installation.
Low Operating Sound Level - The upward air flow
carries the normal operating noise up and away from the
living area. The rigid top panel effectively isolates any
motor sound. Isolator mounted compressor and the
rippled fins of the condenser coil muffle the normal fan
motor and compressor operating sounds. The unique
formed base pan also aids in sound alterations with it's
Super-Structure design. This design strategically places
embossments in the pan for optimum strength and rigidity.
Fan System - All models operate over a wide range of
design conditions with an electrically commutated fan
motor. These units easily match all types of applications
and provide greater on site flexibility to match comfort
requirement. The cooling speed is factory set and can be
field adjusted to a second speed. The heating speed is
factory set but can be field adjusted. This allows
maximum comfort conditions.
Simple Control Circuit - A low voltage printed circuit
board contains a diagnostic indicator light and a low
voltage terminal strip. An additional set of pin connectors
is also provided to simplify the field interface of external
controls. Mate-n-lock plug connectors are used. The
electrical control box is not located in the compressor
compartment. The controls are mounted on a Control-Tilt
control panel to allow the access cover to be removed for
trouble shooting and maintenance without affecting the
normal system operating pressures. All wiring internal to
the unit is color/number coded.
Protected Compressor - The compressor is internally
protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high
pressure relief valve and a temperature sensor which protect
the compressor if undesirable operating conditions occur.
Pressure Switches - High pressure and low pressure/
loss of charge switches standard in all units. When
abnormal conditions are sensed through the pressure
switches, the unit will lock out preventing any further
operation until reset or problem is corrected.
Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat
transfer for maximum efficiency and durability.
Self Diagnostic Fan Control Module - Due to this self
diagnostic control, less on site time is required to trouble
shoot these units.
Low Maintenance - Long life, permanently lubricated
condenser and evaporator fan motor bearings need no
annual maintenance adding greater reliability to the unit.
Blower assembly can be easily cleaned by the unique
Slip- Track slide-out blower assembly.
Secured Service Access Ports - Protected, externally
mounted, re-usable service access ports are provided on
both the high and low lines for ease of evacuating and
charging the system. No final field mounting required.
Easy Service Access - A large, single panel covers the
electrical controls to make servicing easy. The blower
compartment has an additional large panel with a built-in
handle tab. Removing this panel will allow the blower
assembly to slide-out for easy removal for maintenance
and ease of trouble shooting.
• Replacement Parts - The installer requires no special
training to replace any of the components of these units
and does not need to maintain an inventory of unique parts.
• System Integration - Each unit has the internal ability to
integrate an electronic air cleaner or humidifier to work in
conjunction with the base unit.
Field Installed Accessories
• Economizer Down Discharge/Supply Kit - Modulating
integrated economizer provides simultaneous operation
between the mechanical cooling and economizer
operation. Independent blade design insures proper
control and less than 1% leak rate. Includes hood and
mesh bird screen filter integrated into the hood, dry bulb
sensor and relief damper. Separate field accessories of
single enthalpy and dual enthalpy are also available. A
built-in barometric relief of 25% is provided.
• Single Enthalpy Sensor - Sensor replaces dry bulb
sensor standard in economizer kit. Provides improved
economizer operation by sensing the dry bulb temperature
from outdoors plus the enthalpy content of the outdoor air.
• Dual Enthalpy Sensor - Additional sensor to single
enthalpy sensor. Sensor senses both the return air
temperature dry bulb and humidity in conjunction with the
single enthalpy to determine the most economical mix.
Single Enthalpy sensor also required.
• Hail Guard Kit - Kit contains protective grilles made of
expanded aluminum with full perimeter frame. Sloped
hoods are also included to assure maximum protection.
• Filter/Frame Kit (Single Phase Only) - Kit contains the
necessary hardware to field install return air filters into the
base unit. Pre-cut filter racks and appropriate cleanable
standard size filters are shipped in one kit. The filter rack
is suitable for either 1" or 2" filters. (1" filter is supplied)
This kit is available for single phase horizontal or vertical
duct application only. Standard in all 3 Phase models.
• Motorized Fresh Air Damper - Designed for duct
mounted side supply/return and unit mounted down
supply/return applications. Damper capable of providing
0% through 50% of outdoor air (field supplied). Closes on
power loss, includes hood and screen assembly.
• Rectangle To Round Adapters - Kit includes one supply
and one return air rectangle to round duct adapter.
Adapters are preformed and designed to fit over current
duct openings on the base unit. Transition is from side
square duct opening to 14" round duct opening.
• Roof Curbs - NRCA approved curbs provide proper fit to
base unit for rooftop installations. Curbs are designed to
be assembled through hinge pins in each corner. Kit also
provides seal strip to assure a water tight seal. 8 and 14
inch high roof curbs are available.
• Manual Outdoor Damper - Provides 0% through 50%
outdoor air capability (field adjustable). Designed for duct
mounted side supply/return applications. Includes hood
and screen assembly.
• Wall Thermostat - The units are designed to operate with
24-volt electronic and electro-mechanical thermostats. All
units can operate with single stage heat/single stage cool
thermostats - with or without the economizer.
Johnson Controls Unitary Products
294604-YTG-G-0511
• Low Ambient Kit - Kit provides necessary hardware to
convert unit to operate in cooling cycle down to 0º F.
Standard unit operation 45º F.
• Transformer Kit - Kit provides necessary hardware to
provide single phase models from factory furnished 40 VA
transformer capability to 75 VA transformer capability.
(Required on installations with economizer or motorized
damper.)
Guide Specifications
General
Units shall be manufactured by Johnson Controls Unitary
Products in an ISO 9001 certified facility. YORK’s Affinity™
package units give you the flexibility and choices you need in
today’s market. These packaged air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
Description
Units shall be factory-assembled, single packaged, Electric
Cooling units, designed for outdoor mounted installation. For
SEER ratings, refer to technical literature. They shall have built
in, equal size, field convertible duct connections for down
discharge supply/return or horizontal discharge supply/return.
The units shall be factory wired, piped, charged with R-410A
Refrigerant and factory tested prior to shipment. All unit wiring
shall be both numbered and color coded. All units shall be
manufactured in a facility certified to ISO 9001 standards, and
the cooling performance shall be rated in accordance with DOE
and ARI test procedures. Units shall be CSA listed and
classified to ANSI Z21.47/CAN/CSA 2.3 standards and UL
1995/CAN/CSA No. 236-M90 conditions.
Unit Cabinet
Unit cabinet shall be constructed of G90 galvanized steel, with
exterior surfaces coated with a non-chalking, powdered paint
finish, certified at 1000 hours salt spray test per ASTM-B117
standards. The unit top shall be a single piece “Water Shed”
design, with drip edges and no-seam corners to provide optimum
water integrity. Unit shall have a rigidly mounted condenser coil
guard to provide protection from objects and personnel after
installation. Indoor blower section shall be insulated with up to 3/4”
thick, aluminum, foil faced insulation, fastened to prevent insulation
from entering the air stream. Cabinet panels shall be “large” size,
easily removable for servicing and maintenance, with built-in lift
handles. Unit shall be built on a formed, “Super-Structure” design
base pan, with embossments at critical points to add strength,
rigidity and aid in minimizing sound. Full perimeter base rails shall
be provided to assure reliable transit of equipment, overhead
rigging, for truck access and proper sealing on roof curb
applications. Base rails shall be removable, when required, to
lower unit height. Filters shall be furnished and be accessible
through a removable access door, sealed airtight. Units vertical
discharge and return duct configuration shall be designed to fit
between standard 24” O.C. beams without modification to building
structure, duct work and base unit. Condensate pan shall be
internally sloped and conform to ASHRAE 62-89 self-draining
standards, with 3/4” NPTI copper, ridged mount connection.
Johnson Controls Unitary Products
Indoor (Evaporator) Fan Assembly
Fan shall be direct drive design. Fan wheel shall be double-inlet
type with forward-curved blades, dynamically balanced to
operate smoothly throughout the entire range of operation.
Airflow design shall be constant air volume. Bearings shall be
sealed and permanently lubricated for longer life and no
maintenance. Fan assembly shall be “Slip Track” (slide-out)
design for easy removal and cleaning.
Outdoor (Condenser) Fan Assembly
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to
corrosion resistant steel spider bracket and shall be statically
balanced for smooth operation. The outdoor fan motor shall be
totally enclosed with permanently lubricated bearings and
internally protected against overload conditions.
Refrigerant Components
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of +/- 10%
of the unit nameplate voltage.
b. Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed.
b. Evaporator coil shall be of the direct expansion, draw
through design.
c. Condenser coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed or Mircro-Channel
aluminum tube, aluminum fins.
d. Condenser coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed orifice expansion devices.
b. Filter/strainer to eliminate any foreign matter.
Electric Heating Section
(Field Install Accessory)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 25 KW. The heating
section shall have a primary limit control(s) (automatic reset) to
prevent the heating element system from operating at an
excessive temperature. The Heating Section assembly shall
slide out of the unit for easy maintenance and service. Units
with Electric Heating Sections shall be wired for a single point
power supply with branch circuit fusing (where required).
5
294604-YTG-G-0511
Physical Data
DEZ024-060 Physical Data
Component
Nominal Tonnage
Models
DEZ024
DEZ030
DEZ036
DEZ042
DEZ048
DEZ060
2.0
2.5
3.0
3.5
4.0
5.0
59.2
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (MBH)
24.4
30.7
35.3
42.8
49.5
ARI net capacity (MBH)
24.0
30.0
34.5
41.5
48.0
57.5
EER
12.62
11.55
11.36
11.78
11.92
11.03
SEER
13.0
13.0
13.0
13.0
13.0
13.0
Nominal CFM
780
1050
1200
1450
1500
1600
System power (KW)
1.90
2.60
3.04
3.52
4.03
5.21
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
3-2
3-7
3-6
4-4
4-0
4-8
Length
49 1/8
49 1/8
49 1/8
49 1/8
49 1/8
49 1/8
Width
47 1/4
47 1/4
47 1/4
47 1/4
47 1/4
47 1/4
33 1/2
33 1/2
33 1/2
33 1/2
41 1/2
41 1/2
374
375
379
400
401
405
Recip
Recip
Recip
Recip
Recip
Scroll
1
1
1
1
1
1
15
Refrigerant type
Refrigerant charge (lb-oz)
DIMENSIONS (inches)
Height
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.9
11.9
11.9
11.9
15
Rows
1
1
1
1
1
1
Fins per inch
23
23
23
23
23
23
0.71/18
0.71/18
0.71/18
0.71/18
0.71/18
0.71/18
Tube diameter (in.)
Circuitry Type
2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel 2-pass Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
4.38
4.38
4.38
5.63
5.63
Rows
2
2
2
3
2
5.63
3
Fins per inch
15
15
15
15
16
16
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Orifice
Orifice
Orifice
Orifice
Orifice
Orifice
Refrigerant control
CONDENSER FAN DATA
Fan diameter (Inch)
22
22
22
22
22
22
Type
Prop
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
1
Number of motors
1
1
1
1
1
1
Motor HP each
1/4
1/4
1/4
1/3
1/3
1/3
RPM
850
850
850
1120
1120
1100
Nominal total CFM
1800
1800
2400
3000
3000
3000
DIRECT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
1
10 x 8
10 x 8
11 x 10
11 x 10
11 x 10
11 x 10
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
No. speeds
5
5
5
5
5
5
Motor HP each
1/2
1/2
1/2
3/4
3/4
1
Variable
Variable
Variable
Variable
Variable
Variable
48
48
48
48
48
48
2 - 22 x 14 x 1
2 - 22 x 14 x 1
2 - 22 x 14 x 1
2 - 22 x 14 x 1
2 - 22 x 14 x 1
2 - 22 x 14 x 1
RPM
Frame size
FILTERS
Quantity - Size
6
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ024-060 Physical Data
Component
Nominal Tonnage
Models
DEQ024
DEQ030
DEQ036
DEQ042
DEQ048
DEQ060
2.0
2.5
3.0
3.5
4.0
5.0
59.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu)
23.3
32.3
36.9
43.5
49.3
ARI net capacity (Btu)
23.0
31.0
36.0
42.0
48.0
57.5
EER
12.0
12.0
12.0
12.1
12.2
12.0
SEER
14.3
14.1
14.0
14.2
14.0
14.0
Nominal CFM
800
900
1150
1400
1550
1500
System power (KW)
1.92
2.58
3.00
3.47
3.93
4.79
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
5-0
7-8
8-2
7-12
9-8
10-12
Length
49 1/8
49 1/8
49 1/8
49 1/8
49 1/8
49 1/8
Width
47 1/4
47 1/4
47 1/4
47 1/4
47 1/4
47 1/4
Height
33 1/2
33 1/2
33 1/2
41 1/2
41 1/2
41 1/2
346
386
396
406
440
452
Recip
Recip
Recip
Recip
Scroll
Scroll
1
1
1
1
1
1
16.4
Refrigerant type
Refrigerant charge (lb-oz)
DIMENSIONS (inches)
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.7
11.7
11.7
16.4
16.4
Rows
1
2
2
1
2
2
Fins per inch
20
20
20
20
20
20
Tube diameter (in.)
Circuitry Type
3/8
3/8
3/8
3/8
3/8
3/8
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
5.63
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
4.38
4.38
4.38
5.63
5.63
Rows
2
2
3
3
2
3
Fins per inch
15
15
15
16
16
16
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Orifice
Orifice
Orifice
Orifice
Orifice
TX Valve
Refrigerant control
CONDENSER FAN DATA
Fan diameter (Inch)
22
22
22
22
22
22
Type
Prop
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
1
Number of motors
1
1
1
1
1
1
Motor HP each
1/4
1/4
1/4
1/4
1/3
1/3
RPM
850
850
850
1100
1100
1100
Nominal total CFM
1800
1800
2400
3000
3000
3000
DIRECT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
1
10 x 8
10 x 8
10 x 8
11 x 10
11 x 10
11 x 10
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
No. speeds
1
1
1
1
1
1
Motor HP each
1/2
1/2
1/2
3/4
3/4
1
Variable
Variable
Variable
Variable
Variable
Variable
48
48
48
48
48
48
RPM
Frame size
FILTERS
Quantity - Size
2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1
Johnson Controls Unitary Products
7
294604-YTG-G-0511
DEX024-048 Physical Data
Component
DEX030
2.5
Models
DEX036
3.0
DEX042
DEX048
Nominal Tonnage
3.5
4.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu)
23.5
29.2
36.8
44.5
50.8
ARI net capacity (Btu)
23.2
28.6
36.0
43.5
49.0
EER
12.3
12.3
12.3
12.3
12.3
SEER
15
15
15
15
15
Nominal CFM
800
1000
1150
1400
1600
System power (KW)
1.9
2.3
2.9
3.5
4.0
Refrigerant type
R-410A
R-410A
R-410A
R-410A
R-410A
Refrigerant charge (lb-oz)
5-0
8-0
8-0
7-8
10-0
DIMENSIONS (inches)
Length
49 1/8
49 1/8
49 1/8
49 1/8
49 1/8
Width
47 1/4
47 1/4
47 1/4
47 1/4
47 1/4
Height
33 1/2
33 1/2
33 1/2
41 1/2
41 1/2
OPERATING WT. (lbs.)
355
390
400
410
440
COMPRESSORS
Type
Scroll 2-spd Scroll 2-spd Scroll 2-spd Scroll 2-spd Scroll 2-spd
Quantity
1
1
1
1
1
CONDENSER COIL DATA
Face area (Sq. Ft.)
11.7
11.7
11.7
16.4
16.4
Rows
1
2
2
1
2
Fins per inch
20
20
20
20
20
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
4.38
4.38
4.38
5.63
5.63
Rows
2
2
3
3
3
Fins per inch
15
15
15
16
16
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Refrigerant control
TX Valve
TX Valve
TX Valve
TX Valve
TX Valve
CONDENSER FAN DATA
Fan diameter (Inch)
22
22
22
22
22
Type
Prop.
Prop.
Prop.
Prop.
Prop.
Drive type
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
Number of motors
1
1
1
1
1
Motor HP each
1/4
1/4
1/4
1/4
1/3
RPM
850
850
850
1100
1100
Nominal total CFM
1800
1800
2400
3000
3000
DIRECT DRIVE EVAP FAN DATA
Quantity
1
1
1
1
1
Fan Size (Inch)
10 x 8
10 x 8
10 x 8
11 x 10
11 x 10
Type
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
No. speeds
2
2
2
2
2
Motor HP each
1/2
1/2
1/2
3/4
3/4
RPM
Variable
Variable
Variable
Variable
Variable
Frame size
48
48
48
48
48
FILTERS
Quantity - Size
2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1 2 - 22 x 14 x 1
8
DEX024
2.0
Johnson Controls Unitary Products
294604-YTG-G-0511
DEY060 Physical Data
Component
Models
DEY060
5.0
Nominal Tonnage
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu)
60.4
ARI net capacity (Btu)
58.5
EER
11.6
SEER
14.5
Nominal CFM
1750
System power (KW)
5.0
Refrigerant type
R-410A
Refrigerant charge (lb-oz)
10-8
DIMENSIONS (inches)
Length
49 1/8
Width
47 1/4
Height
41 1/2
OPERATING WT. (lbs.)
460
COMPRESSORS
Type
Scroll 2-spd
Quantity
1
CONDENSER COIL DATA
Face area (Sq. Ft.)
16.4
Rows
2
Fins per inch
20
Tube diameter (in.)
3/8
Circuitry Type
Interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
5.63
Rows
3
Fins per inch
16
Tube diameter
3/8
Circuitry Type
Interlaced
Refrigerant control
TX Valve
CONDENSER FAN DATA
Fan diameter (Inch)
22
Type
Prop.
Drive type
Direct
No. speeds
1
Number of motors
1
Motor HP each
1/3
RPM
1100
Nominal total CFM
3000
DIRECT DRIVE EVAP FAN DATA
Quantity
1
Fan Size (Inch)
11 x 10
Type
Centrifugal
No. speeds
2
Motor HP each
1
RPM
Variable
Frame size
48
FILTERS
Quantity - Size
2 - 22 x 14 x 1
Johnson Controls Unitary Products
9
294604-YTG-G-0511
Unit Limitations
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
Model
DEZ, DEQ
DEX
DEZ, DEQ
DEX
DEZ
DEQ
DEX
042
(3.5)
DEZ
DEQ
DEX
DEZ
048
(4.0)
DEQ
DEX
DEZ
060
(5.0)
DEQ
DEY
10
Unit Voltage
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
Min
187
187
187
187
187
187
432
540
187
187
432
187
187
432
540
187
187
432
187
187
432
540
187
187
432
540
187
187
432
187
187
432
540
187
187
432
540
187
187
432
Unit Limitations
Applied Voltage
Max
252
252
252
252
252
252
504
630
252
252
504
252
252
504
630
252
252
504
252
252
504
630
252
252
504
630
252
252
504
252
252
504
630
252
252
504
630
252
252
504
Outdoor DB Temp
Max (°F)
125
115
125
115
125
125
125
125
115
115
115
125
125
125
125
115
115
115
115
115
115
115
125
125
125
125
115
115
115
115
115
115
115
125
125
125
125
115
115
115
Johnson Controls Unitary Products
294604-YTG-G-0511
Capacity Performance
DEZ024-060 Cooling Capacities
DEZ024 (2.0 Ton)
Air on
Evaporator Coil
CFM
600
700
800
900
1000
600
700
800
900
1000
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
30.3
28.5
26.6
24.1
23.5
31.8
29.8
27.9
25.3
24.7
33.2
31.2
29.2
26.4
25.8
31.8
29.7
26.9
26.3
32.4
30.3
27.4
26.8
1.2
1.4
1.6
1.4
1.4
1.3
1.5
1.7
1.5
1.5
1.4
1.6
1.8
1.6
1.6
1.8
2.0
1.7
1.7
1.9
2.1
1.9
1.9
8.6
15.0
21.4
23.8
23.5
10.5
17.9
25.4
25.1
24.7
12.4
20.8
29.2
26.4
25.8
21.0
29.7
26.9
26.3
21.2
30.3
27.4
26.8
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
26.8
24.3
21.8
19.5
20.1
28.3
25.6
22.9
20.6
21.2
29.7
26.9
24.1
21.6
22.3
27.0
24.2
21.7
22.3
27.0
24.2
21.8
22.4
2.0
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.0
2.0
1.9
1.9
2.1
2.1
2.0
2.0
12.8
16.2
19.6
19.5
20.1
14.3
18.1
21.8
20.6
21.2
15.8
20.0
24.1
21.6
22.3
21.2
24.1
21.7
22.3
22.5
24.2
21.8
22.4
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
6.3
4.0
28.6
1.6
12.7
10.4
8.1
26.4
1.7
19.1
16.8
14.5
12.2
24.2
1.8
19.1
16.2
13.9
11.6
9.3
21.8
1.6
20.1
17.6
15.3
13.0
10.7
21.8
1.6
7.7
5.2
30.0
1.6
15.4
12.9
10.4
27.7
1.7
23.1
20.6
18.1
15.6
25.4
1.8
22.8
20.1
17.6
15.1
12.6
22.9
1.7
23.0
21.7
19.2
16.7
14.2
22.9
1.7
9.1
6.3
31.5
1.7
18.1
15.4
12.7
29.1
1.8
27.1
24.4
21.7
19.0
26.7
1.9
26.4
24.0
21.3
18.6
15.9
24.0
1.7
25.8
25.8
23.1
20.4
17.7
24.1
1.7
17.8
14.6
11.4
29.4
1.9
26.6
23.4
20.3
17.1
27.0
2.0
26.9
23.9
20.7
17.5
14.3
24.3
1.8
26.3
25.5
22.3
19.1
16.0
24.3
1.8
17.5
13.9
10.2
29.7
2.0
26.1
22.5
18.8
15.2
27.2
2.1
27.4
23.7
20.1
16.4
12.8
24.6
1.9
26.8
25.2
21.5
17.9
14.2
24.6
1.9
95°F
10.4
8.0
24.6
2.1
13.8
11.4
9.0
21.9
2.1
17.2
14.8
12.4
10.0
19.2
2.0
19.5
17.7
15.3
12.9
10.5
18.3
2.0
20.1
17.9
15.6
13.2
10.8
18.6
2.0
11.6
8.8
25.5
2.1
15.3
12.6
9.9
22.7
2.1
19.1
16.3
13.6
10.9
19.9
2.0
20.6
19.6
16.9
14.1
11.4
18.9
2.0
21.2
19.9
17.1
14.4
11.7
19.3
2.0
12.8
9.7
26.4
2.1
16.9
13.8
10.7
23.5
2.1
21.0
17.9
14.8
11.8
20.6
2.0
21.6
21.5
18.4
15.3
12.3
19.6
2.0
22.3
21.8
18.7
15.6
12.6
19.9
2.0
17.9
14.6
11.2
23.9
2.1
22.2
18.9
15.6
12.2
20.9
2.1
21.7
21.6
18.3
15.0
11.7
19.9
2.1
22.3
22.1
18.8
15.4
12.1
20.3
2.1
18.9
15.3
11.7
24.2
2.2
23.4
19.9
16.3
12.7
21.2
2.2
21.8
21.8
18.2
14.6
11.0
20.2
2.2
22.4
22.4
18.8
15.2
11.7
20.6
2.2
90
10.7
15.6
20.5
21.7
21.8
12.4
18.0
23.6
22.9
22.9
14.1
20.4
26.7
24.0
24.1
21.1
27.0
24.3
24.3
21.8
27.2
24.6
24.6
12.5
15.3
18.1
18.3
18.6
14.7
17.0
19.3
18.9
19.3
16.9
18.8
20.6
19.6
19.9
20.1
20.9
19.9
20.3
21.4
21.2
20.2
20.6
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
8.3
6.0
13.2
10.9
8.5
18.1
15.8
13.5
11.1
19.3
17.0
14.6
12.3
20.1
17.8
15.4
13.1
9.6
7.0
15.4
12.7
10.1
21.1
18.5
15.9
13.2
21.7
19.9
17.2
14.6
22.1
20.8
18.2
15.5
10.9
8.0
17.5
14.6
11.7
24.1
21.2
18.3
15.4
24.0
22.7
19.8
17.0
24.1
23.8
20.9
18.0
17.8
14.6
11.3
24.4
21.2
17.9
14.7
24.3
22.7
19.5
16.2
24.3
23.8
20.5
17.3
18.2
14.6
11.0
24.8
21.2
17.6
13.9
24.6
22.7
19.1
15.5
24.6
23.8
20.2
16.6
105°F
9.6
7.2
12.9
10.5
8.0
16.2
13.8
11.3
8.9
18.3
16.3
13.8
11.4
18.5
16.2
13.7
11.3
10.9
7.9
14.3
11.5
8.7
17.6
15.1
12.4
9.6
18.9
17.9
15.1
12.4
19.2
17.8
15.0
12.3
12.3
8.6
15.7
12.5
9.4
19.1
16.5
13.4
10.3
19.6
19.5
16.4
13.3
19.9
19.4
16.3
13.2
16.7
13.3
10.0
19.9
17.6
14.2
10.8
19.9
19.9
16.5
13.1
20.3
20.0
16.6
13.2
17.8
14.1
10.5
20.8
18.6
14.9
11.3
20.2
20.2
16.6
12.9
20.6
20.6
16.9
13.3
65
9.9
10.7
12.0
12.9
14.1
15.1
13.0
14.0
11.9
12.9
9.0
8.9
9.6
9.5
10.2
10.1
9.7
9.8
9.3
9.6
11
294604-YTG-G-0511
DEZ024 (2.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
600
700
800
900
1000
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
22.4
19.5
16.6
17.0
17.0
22.8
19.8
16.8
17.2
17.3
23.1
20.1
17.1
17.5
17.6
20.8
17.7
18.1
18.2
21.4
18.2
18.7
18.8
2.3
2.2
2.2
2.2
2.2
2.3
2.2
2.2
2.1
2.1
2.3
2.2
2.2
2.1
2.1
2.3
2.2
2.2
2.2
2.4
2.3
2.3
2.3
12.3
14.4
16.6
17.0
17.0
15.2
16.0
16.8
17.2
17.3
18.0
17.6
17.1
17.5
17.6
19.0
17.7
18.1
18.2
20.4
18.2
18.7
18.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
8.8
6.3
20.1
2.4
12.0
9.5
7.1
17.0
2.4
15.2
12.7
10.3
7.9
13.9
2.3
17.0
14.8
12.4
9.9
7.5
15.7
2.3
16.8
14.4
11.9
9.5
7.0
15.5
2.3
10.3
6.9
20.0
2.4
13.2
10.4
7.6
16.9
2.4
16.2
13.9
11.1
8.3
13.8
2.3
17.2
16.2
13.4
10.6
7.8
15.6
2.3
17.2
15.7
12.9
10.1
7.3
15.4
2.3
11.7
7.5
19.9
2.4
14.4
11.3
8.2
16.7
2.3
17.1
15.1
12.0
8.8
13.6
2.3
17.5
17.5
14.4
11.3
8.1
15.5
2.3
17.6
17.0
13.9
10.7
7.6
15.3
2.3
15.6
12.1
8.7
17.7
2.4
17.7
16.2
12.8
9.3
14.4
2.4
18.1
18.1
14.7
11.2
7.8
16.3
2.4
18.2
17.9
14.5
11.0
7.6
16.1
2.4
16.7
13.0
9.2
18.6
2.5
18.2
17.3
13.6
9.9
15.2
2.5
18.7
18.7
14.9
11.2
7.5
17.1
2.5
18.8
18.8
15.0
11.3
7.6
17.0
2.4
90
13.1
13.5
13.9
15.7
15.5
16.1
15.0
13.8
15.6
15.4
19.1
16.4
13.6
15.5
15.3
17.7
14.4
16.3
16.1
18.6
15.2
17.1
17.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
8.2
5.5
11.1
8.6
6.1
13.9
11.7
9.3
6.8
15.7
13.4
10.9
8.4
15.2
12.6
10.1
7.7
10.5
6.0
12.1
9.3
6.5
13.8
12.7
9.9
7.1
15.6
14.5
11.6
8.8
15.2
13.6
10.8
8.0
12.8
6.4
13.2
10.0
6.9
13.6
13.6
10.5
7.3
15.5
15.5
12.4
9.2
15.3
14.7
11.5
8.3
14.4
10.9
7.4
14.4
14.4
11.4
7.9
16.3
16.3
12.9
9.4
16.1
15.8
12.3
8.8
15.6
11.8
8.0
15.2
15.2
12.3
8.4
17.1
17.1
13.3
9.5
17.0
17.0
13.2
9.3
65
6.0
5.2
6.0
5.2
6.0
5.1
5.9
5.3
5.7
5.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
12
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ030 (2.5 Ton)
Air on
Evaporator Coil
CFM
750
875
1000
1125
1250
750
875
1000
1125
1250
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
35.0
33.6
32.2
29.9
29.9
35.9
34.5
33.1
30.7
30.7
36.8
35.4
34.0
31.5
31.5
35.9
34.4
31.9
32.0
36.4
34.9
32.4
32.4
2.5
2.4
2.4
2.4
2.4
2.5
2.4
2.4
2.4
2.3
2.4
2.4
2.4
2.3
2.3
2.5
2.4
2.4
2.4
2.5
2.5
2.4
2.4
16.1
20.8
25.5
29.9
29.9
17.4
22.4
27.4
30.7
30.7
18.7
24.0
29.3
31.5
31.5
25.0
30.8
31.9
32.0
26.0
32.2
32.4
32.4
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
32.5
30.1
27.7
25.1
25.6
33.7
31.2
28.8
26.0
26.6
34.9
32.4
29.8
27.0
27.5
32.5
29.9
27.1
27.7
32.7
30.1
27.3
27.8
2.9
2.8
2.8
2.7
2.7
2.9
2.8
2.8
2.7
2.7
2.9
2.8
2.7
2.7
2.7
2.9
2.8
2.7
2.7
2.9
2.8
2.8
2.8
15.2
19.5
23.8
25.1
25.6
16.7
21.3
25.9
26.0
26.6
18.1
23.1
28.0
27.0
27.5
24.2
29.1
27.1
27.7
25.3
30.1
27.3
27.8
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
13.5
11.0
33.8
2.7
18.2
15.6
13.1
31.9
2.6
22.9
20.3
17.8
15.2
30.0
2.6
26.9
24.3
21.7
19.2
16.6
27.5
2.5
29.9
28.1
25.6
23.0
20.4
27.8
2.5
14.5
11.6
34.8
2.7
19.5
16.6
13.7
32.9
2.6
24.5
21.6
18.7
15.8
30.9
2.6
29.2
25.8
22.9
20.0
17.2
28.4
2.5
30.7
29.9
27.0
24.1
21.2
28.6
2.5
15.5
12.3
35.9
2.7
20.8
17.6
14.4
33.9
2.6
26.1
22.9
19.7
16.5
31.9
2.6
31.5
27.3
24.1
20.9
17.7
29.2
2.5
31.5
31.5
28.5
25.3
22.0
29.5
2.5
21.7
18.3
15.0
34.2
2.7
27.2
23.8
20.5
17.2
32.2
2.6
31.9
28.7
25.4
22.0
18.7
29.5
2.6
32.0
32.0
28.7
25.3
22.0
29.8
2.6
22.6
19.1
15.6
34.6
2.7
28.3
24.8
21.3
17.8
32.5
2.7
32.4
30.1
26.6
23.2
19.7
29.8
2.6
32.4
32.4
28.9
25.4
22.0
30.1
2.6
95°F
12.5
9.8
30.8
3.1
16.8
14.1
11.4
27.9
3.0
21.1
18.4
15.7
12.9
25.1
2.9
24.9
22.2
19.5
16.8
14.1
22.7
2.9
25.6
23.7
21.0
18.3
15.5
23.8
2.9
13.6
10.6
31.5
3.1
18.3
15.2
12.1
28.6
3.0
22.9
19.8
16.7
13.7
25.8
2.9
25.9
23.9
20.9
17.8
14.7
23.3
2.9
26.6
25.5
22.5
19.4
16.3
24.4
2.9
14.7
11.3
32.3
3.1
19.7
16.3
12.9
29.3
3.0
24.6
21.2
17.8
14.4
26.4
2.9
27.0
25.6
22.2
18.8
15.4
23.8
2.9
27.5
27.4
24.0
20.5
17.1
25.0
2.9
20.6
16.9
13.3
29.8
3.0
25.7
22.1
18.5
14.9
26.8
3.0
27.1
26.5
22.9
19.2
15.6
24.2
2.9
27.7
27.6
24.0
20.4
16.8
25.4
2.9
21.4
17.6
13.8
30.3
3.1
26.8
23.0
19.2
15.3
27.2
3.0
27.3
27.3
23.5
19.6
15.8
24.6
3.0
27.8
27.8
24.0
20.2
16.4
25.8
3.0
90
15.7
20.2
24.6
27.5
27.8
17.1
21.9
26.7
28.4
28.6
18.4
23.6
28.7
29.2
29.5
24.6
29.9
29.5
29.8
25.6
31.2
29.8
30.1
14.8
18.9
23.1
22.7
23.8
16.7
20.5
24.3
23.3
24.4
18.7
22.1
25.5
23.8
25.0
23.4
26.4
24.2
25.4
24.7
27.2
24.6
25.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
13.0
10.4
17.5
14.9
12.2
22.0
19.4
16.7
14.1
25.9
23.3
20.6
18.0
27.8
25.9
23.3
20.6
14.1
11.1
18.9
15.9
12.9
23.7
20.7
17.7
14.8
27.6
24.9
21.9
18.9
28.6
27.7
24.7
21.8
15.1
11.8
20.2
16.9
13.6
25.4
22.0
18.7
15.4
29.2
26.5
23.2
19.9
29.5
29.5
26.2
22.9
21.1
17.6
14.2
26.4
23.0
19.5
16.0
29.5
27.6
24.1
20.6
29.8
29.8
26.3
22.9
22.0
18.4
14.7
27.5
23.9
20.2
16.6
29.8
28.7
25.1
21.4
30.1
30.1
26.5
22.8
105°F
12.0
9.2
16.1
13.3
10.5
20.3
17.5
14.7
11.9
22.6
20.3
17.5
14.7
23.8
21.8
19.0
16.2
12.9
9.8
17.4
14.2
11.1
21.8
18.7
15.6
12.4
23.2
21.8
18.6
15.5
24.4
23.3
20.2
17.1
13.9
10.4
18.7
15.2
11.7
23.4
19.9
16.4
13.0
23.8
23.2
19.7
16.2
25.0
24.9
21.4
17.9
19.7
16.0
12.3
24.5
21.0
17.2
13.5
24.2
23.9
20.2
16.5
25.4
25.3
21.6
17.9
20.7
16.8
12.8
25.6
22.0
18.1
14.1
24.6
24.6
20.7
16.7
25.8
25.8
21.9
17.9
65
15.3
18.0
15.9
18.8
16.6
19.6
17.2
19.4
17.8
19.2
11.9
13.4
12.3
13.9
12.8
14.5
12.8
14.2
12.7
13.9
13
294604-YTG-G-0511
DEZ030 (2.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
750
875
1000
1125
1250
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
29.0
25.7
22.5
20.3
22.0
29.3
26.0
22.8
20.5
22.2
29.6
26.3
23.0
20.7
22.5
27.1
23.7
21.3
23.1
27.8
24.4
21.9
23.8
3.3
3.2
3.1
3.1
3.1
3.3
3.2
3.1
3.1
3.1
3.3
3.2
3.1
3.0
3.1
3.2
3.1
3.1
3.1
3.3
3.2
3.1
3.2
14.3
18.3
22.3
20.3
22.0
16.8
19.7
22.7
20.5
22.2
19.3
21.2
23.0
20.7
22.5
22.6
23.7
21.3
23.1
24.1
24.4
21.9
23.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
11.4
8.5
27.2
3.5
15.4
12.5
9.6
23.5
3.4
19.4
16.5
13.7
10.8
19.9
3.3
20.3
18.4
15.6
12.7
9.8
17.9
3.3
22.0
19.9
17.0
14.1
11.3
20.2
3.3
12.3
9.0
27.1
3.5
16.5
13.3
10.1
23.4
3.4
20.8
17.6
14.4
11.1
19.8
3.3
20.5
19.6
16.4
13.2
10.0
17.7
3.2
22.2
21.2
17.9
14.7
11.5
20.1
3.3
13.1
9.6
27.0
3.5
17.6
14.1
10.5
23.3
3.4
22.1
18.6
15.1
11.5
19.6
3.3
20.7
20.7
17.2
13.7
10.1
17.6
3.2
22.5
22.4
18.9
15.3
11.8
20.0
3.2
18.8
15.0
11.2
24.4
3.4
23.2
19.8
16.0
12.2
20.6
3.3
21.3
21.3
17.5
13.7
9.9
18.4
3.3
23.1
23.1
19.3
15.5
11.7
20.9
3.3
20.0
15.9
11.8
25.4
3.5
24.4
21.0
17.0
12.9
21.5
3.4
21.9
21.9
17.8
13.8
9.7
19.3
3.3
23.8
23.8
19.7
15.6
11.5
21.8
3.4
90
15.5
17.7
19.9
17.9
20.2
18.1
18.9
19.8
17.7
20.1
20.7
20.2
19.6
17.6
20.0
21.9
20.6
18.4
20.9
23.5
21.5
19.3
21.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
10.8
7.9
14.7
11.7
8.8
18.6
15.6
12.7
9.7
17.9
16.6
13.6
10.6
20.2
18.0
15.1
12.1
12.2
8.3
15.7
12.4
9.1
19.7
16.5
13.2
9.9
17.7
17.4
14.1
10.8
20.1
19.0
15.7
12.4
13.5
8.7
16.6
13.0
9.4
19.6
17.3
13.7
10.1
17.6
17.6
14.7
11.1
20.0
19.9
16.3
12.7
17.9
14.0
10.1
20.6
18.7
14.8
10.9
18.4
18.4
14.9
10.9
20.9
20.8
16.9
13.0
19.3
15.1
10.9
21.5
20.1
15.8
11.6
19.3
19.3
15.0
10.8
21.8
21.8
17.5
13.3
65
7.6
9.1
7.6
9.1
7.5
9.1
7.0
9.1
6.6
9.1
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
14
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ036 (3.0 Ton)
Air on
Evaporator Coil
CFM
900
1050
1200
1300
1400
900
1050
1200
1300
1400
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
43.2
40.7
38.2
35.5
35.6
44.2
41.7
39.1
36.4
36.5
45.3
42.7
40.0
37.2
37.3
42.7
40.1
37.2
37.4
42.7
40.1
37.3
37.4
2.5
2.5
2.4
2.4
2.4
2.6
2.6
2.5
2.5
2.5
2.7
2.6
2.6
2.6
2.6
2.7
2.7
2.6
2.6
2.8
2.8
2.7
2.7
19.7
25.6
31.5
35.5
35.6
21.1
27.3
33.6
36.4
36.5
22.5
29.0
35.6
37.2
37.3
29.5
36.7
37.2
37.4
30.1
37.8
37.3
37.4
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
39.3
36.1
32.9
31.1
31.1
40.2
37.0
33.7
31.9
31.8
41.2
37.8
34.5
32.6
32.5
37.9
34.6
32.7
32.6
38.0
34.7
32.8
32.7
3.0
2.9
2.8
2.8
2.8
3.1
3.0
2.9
2.9
2.9
3.2
3.1
3.0
3.0
3.0
3.2
3.1
3.1
3.1
3.3
3.2
3.1
3.1
18.6
24.0
29.3
31.1
31.1
20.0
25.7
31.4
31.9
31.8
21.5
27.5
33.5
32.6
32.5
28.5
34.1
32.7
32.6
29.4
34.7
32.8
32.7
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
16.7
13.7
41.2
2.7
22.6
19.7
16.7
38.4
2.7
28.5
25.6
22.6
19.6
35.6
2.6
35.2
31.4
28.5
25.5
22.5
33.3
2.6
35.6
33.7
30.7
27.7
24.7
33.3
2.6
17.8
14.5
42.2
2.8
24.0
20.7
17.4
39.3
2.8
30.3
27.0
23.7
20.4
36.4
2.7
36.2
33.1
29.8
26.5
23.3
34.1
2.7
36.5
35.5
32.2
28.9
25.6
34.1
2.7
18.9
15.2
43.2
2.9
25.4
21.8
18.2
40.3
2.9
32.0
28.4
24.7
21.1
37.3
2.8
37.2
34.9
31.2
27.6
24.0
34.9
2.8
37.3
37.3
33.7
30.1
26.5
34.9
2.8
25.8
22.0
18.2
40.3
2.9
32.4
28.6
24.8
21.0
37.3
2.9
37.2
35.6
31.8
28.0
24.2
35.0
2.8
37.4
37.4
33.6
29.8
26.0
35.0
2.9
26.1
22.1
18.2
40.4
3.0
32.8
28.8
24.8
20.9
37.4
3.0
37.3
36.4
32.4
28.5
24.5
35.0
2.9
37.4
37.4
33.4
29.5
25.5
35.0
2.9
95°F
15.5
12.3
36.3
3.2
20.8
17.7
14.6
33.0
3.1
26.2
23.1
20.0
16.8
29.7
3.0
31.1
28.8
25.7
22.6
19.4
28.2
3.0
31.1
29.1
25.9
22.8
19.7
28.1
3.0
16.6
13.1
37.2
3.3
22.3
18.8
15.3
33.8
3.2
28.0
24.5
21.0
17.5
30.4
3.1
31.9
30.5
27.1
23.6
20.1
28.9
3.1
31.8
30.8
27.3
23.9
20.4
28.8
3.1
17.6
13.8
38.1
3.4
23.7
19.8
16.0
34.6
3.3
29.7
25.9
22.0
18.2
31.1
3.2
32.6
32.3
28.4
24.6
20.8
29.6
3.2
32.5
32.5
28.7
24.9
21.0
29.5
3.2
24.4
20.3
16.2
34.7
3.4
30.5
26.5
22.4
18.3
31.2
3.3
32.7
32.5
28.4
24.4
20.3
29.6
3.3
32.6
32.6
28.5
24.5
20.4
29.5
3.3
25.1
20.8
16.4
34.7
3.5
31.4
27.1
22.7
18.4
31.2
3.4
32.8
32.8
28.5
24.1
19.8
29.6
3.3
32.7
32.7
28.4
24.0
19.7
29.6
3.3
90
19.1
24.8
30.4
33.3
33.3
20.6
26.5
32.5
34.1
34.1
22.0
28.3
34.6
34.9
34.9
29.0
35.4
35.0
35.0
29.7
36.2
35.0
35.0
17.5
22.7
27.9
28.2
28.1
19.9
24.6
29.3
28.9
28.8
22.3
26.5
30.6
29.6
29.5
27.4
30.9
29.6
29.5
28.4
31.2
29.6
29.6
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
16.1
13.0
21.7
18.7
15.6
27.4
24.3
21.3
18.2
33.2
30.1
27.1
24.0
33.3
31.4
28.3
25.3
17.2
13.8
23.1
19.7
16.4
29.1
25.7
22.3
18.9
34.0
31.8
28.5
25.1
34.1
33.2
29.8
26.4
18.2
14.5
24.5
20.8
17.1
30.8
27.1
23.4
19.6
34.9
33.6
29.8
26.1
34.9
34.9
31.2
27.5
25.1
21.1
17.2
31.5
27.5
23.6
19.6
35.0
34.1
30.1
26.2
35.0
35.0
31.1
27.1
25.6
21.4
17.3
32.1
27.9
23.8
19.6
35.0
34.6
30.4
26.3
35.0
35.0
30.9
26.8
105°F
14.3
11.1
19.5
16.3
13.2
24.7
21.6
18.4
15.2
28.2
25.8
22.7
19.5
28.1
25.9
22.8
19.6
15.4
11.9
21.0
17.5
13.9
26.6
23.0
19.5
15.9
28.9
27.6
24.1
20.5
28.8
27.7
24.2
20.6
16.6
12.7
22.5
18.6
14.7
28.5
24.5
20.6
16.7
29.6
29.4
25.5
21.5
29.5
29.5
25.6
21.6
23.3
19.1
14.9
29.0
25.1
21.0
16.8
29.6
29.5
25.3
21.1
29.5
29.5
25.3
21.1
24.0
19.5
15.1
29.6
25.7
21.3
16.8
29.6
29.6
25.2
20.8
29.6
29.6
25.1
20.7
65
21.0
22.2
21.7
23.0
22.4
23.8
22.3
23.2
22.1
22.6
16.3
16.4
16.9
17.0
17.6
17.7
16.9
17.0
16.3
16.2
15
294604-YTG-G-0511
DEZ036 (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
900
1050
1200
1300
1400
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
33.4
29.9
26.4
25.3
25.2
34.2
30.7
27.1
25.9
25.8
35.1
31.4
27.8
26.5
26.5
31.4
27.7
26.5
26.4
31.4
27.7
26.5
26.4
3.4
3.3
3.2
3.2
3.2
3.5
3.4
3.3
3.3
3.3
3.6
3.5
3.4
3.4
3.4
3.6
3.5
3.5
3.5
3.7
3.6
3.6
3.6
16.4
21.4
26.4
25.3
25.2
19.8
23.4
27.1
25.9
25.8
23.2
25.5
27.8
26.5
26.5
26.4
27.7
26.5
26.4
27.4
27.7
26.5
26.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
13.1
9.9
30.4
3.6
18.2
15.0
11.7
26.8
3.5
23.2
20.0
16.8
13.6
23.2
3.4
25.3
22.9
19.6
16.4
13.2
22.3
3.4
25.2
22.8
19.6
16.3
13.1
22.3
3.4
14.3
10.7
31.2
3.7
19.8
16.2
12.5
27.5
3.6
25.3
21.6
18.0
14.4
23.8
3.5
25.9
24.7
21.1
17.4
13.8
22.9
3.5
25.8
24.6
21.0
17.4
13.7
22.8
3.5
15.6
11.5
32.0
3.9
21.4
17.4
13.3
28.2
3.7
27.3
23.2
19.2
15.1
24.4
3.6
26.5
26.5
22.5
18.4
14.4
23.5
3.6
26.5
26.5
22.4
18.4
14.3
23.4
3.6
22.1
17.8
13.5
28.1
3.8
27.5
23.8
19.5
15.2
24.3
3.7
26.5
26.5
22.2
17.9
13.6
23.4
3.7
26.4
26.4
22.1
17.8
13.5
23.4
3.7
22.8
18.3
13.7
28.0
3.9
27.7
24.4
19.9
15.3
24.2
3.8
26.5
26.5
21.9
17.4
12.8
23.4
3.8
26.4
26.4
21.9
17.3
12.7
23.3
3.8
90
17.0
20.1
23.2
22.3
22.3
20.8
22.3
23.8
22.9
22.8
24.6
24.5
24.4
23.5
23.4
25.4
24.3
23.4
23.4
26.4
24.2
23.4
23.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
12.0
8.7
16.8
13.6
10.3
21.7
18.5
15.2
11.9
22.3
19.9
16.6
13.3
22.3
19.6
16.4
13.1
14.1
9.5
18.6
14.9
11.1
23.8
20.2
16.5
12.8
22.9
21.8
18.1
14.3
22.8
21.5
17.8
14.1
16.2
10.4
20.3
16.1
12.0
24.4
21.9
17.8
13.6
23.5
23.5
19.5
15.4
23.4
23.4
19.3
15.1
21.0
16.6
12.2
24.3
22.5
18.1
13.7
23.4
23.4
19.1
14.7
23.4
23.4
18.9
14.5
21.7
17.0
12.3
24.2
23.1
18.4
13.8
23.4
23.4
18.7
14.0
23.3
23.3
18.6
13.9
65
10.1
9.8
10.6
10.4
11.2
10.9
10.3
10.1
9.3
9.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
16
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ042 (3.5 Ton)
Air on
Evaporator Coil
CFM
1050
1225
1400
1550
1700
1050
1225
1400
1550
1700
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
52.2
48.2
44.2
40.5
37.5
54.7
50.5
46.3
42.5
39.3
57.3
52.9
48.5
44.5
41.1
53.1
48.7
44.7
41.3
53.4
48.9
44.9
41.5
3.2
3.1
3.0
3.0
3.0
3.2
3.1
3.0
3.0
3.0
3.2
3.1
3.0
3.0
3.0
3.2
3.1
3.1
3.1
3.3
3.2
3.2
3.2
23.4
29.9
36.4
40.5
37.5
25.7
33.2
40.7
42.5
39.3
28.1
36.5
45.0
44.5
41.1
38.3
47.0
44.7
41.3
40.1
48.9
44.9
41.5
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
45.5
41.4
37.3
33.4
32.8
48.0
43.6
39.3
35.2
34.6
50.4
45.9
41.3
37.0
36.3
45.9
41.3
37.1
36.4
45.9
41.3
37.1
36.4
3.6
3.6
3.5
3.5
3.5
3.7
3.6
3.6
3.5
3.5
3.7
3.6
3.6
3.5
3.5
3.7
3.7
3.6
3.6
3.8
3.7
3.7
3.7
21.8
27.8
33.8
33.4
32.8
24.9
31.2
37.5
35.2
34.6
28.1
34.7
41.3
37.0
36.3
36.7
41.3
37.1
36.4
38.8
41.3
37.1
36.4
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
19.2
15.0
48.8
3.4
25.7
21.5
17.2
44.8
3.3
32.2
27.9
23.7
19.5
40.7
3.3
39.1
33.6
29.3
25.1
20.9
37.0
3.2
37.5
34.2
29.9
25.7
21.5
35.2
3.2
21.3
16.5
51.3
3.4
28.4
23.6
18.8
47.1
3.4
35.6
30.8
26.0
21.2
42.8
3.3
41.8
37.0
32.2
27.4
22.6
38.9
3.3
39.3
37.7
32.9
28.1
23.3
36.9
3.2
23.4
18.0
53.8
3.4
31.2
25.8
20.5
49.4
3.4
39.0
33.6
28.3
22.9
44.9
3.3
44.5
40.4
35.0
29.7
24.3
40.8
3.3
41.1
41.1
35.8
30.4
25.1
38.7
3.3
32.6
26.8
21.0
49.5
3.5
40.7
34.9
29.1
23.3
45.0
3.4
44.7
42.7
36.9
31.1
25.3
40.9
3.4
41.3
41.3
35.6
29.8
24.0
38.9
3.3
33.9
27.7
21.6
49.6
3.6
42.3
36.1
29.9
23.7
45.1
3.5
44.9
44.9
38.7
32.5
26.3
41.0
3.5
41.5
41.5
35.4
29.2
23.0
39.0
3.4
95°F
17.5
13.2
41.7
3.9
23.5
19.2
14.8
37.3
3.8
29.5
25.2
20.8
16.5
32.8
3.7
33.4
30.4
26.1
21.8
17.5
30.1
3.7
32.8
29.8
25.5
21.2
16.9
29.7
3.7
19.6
14.6
44.1
3.9
26.2
21.3
16.3
39.4
3.8
32.9
27.9
22.9
17.9
34.7
3.8
35.2
33.7
28.7
23.7
18.7
31.8
3.7
34.6
33.1
28.1
23.1
18.1
31.4
3.7
21.7
16.0
46.4
4.0
29.0
23.3
17.7
41.5
3.9
36.3
30.6
25.0
19.3
36.6
3.8
37.0
37.0
31.4
25.7
20.0
33.6
3.7
36.3
36.3
30.7
25.0
19.3
33.1
3.7
30.6
24.5
18.4
41.5
4.0
38.3
32.1
26.0
19.9
36.6
3.9
37.1
37.1
30.9
24.8
18.7
33.6
3.8
36.4
36.4
30.2
24.1
18.0
33.1
3.8
32.2
25.6
19.0
41.6
4.1
40.2
33.6
27.1
20.5
36.6
4.0
37.1
37.1
30.5
23.9
17.3
33.6
3.9
36.4
36.4
29.8
23.2
16.6
33.1
3.9
90
22.6
28.9
35.1
37.0
35.2
25.3
32.2
39.1
38.9
36.9
28.1
35.6
43.2
40.8
38.7
37.5
44.1
40.9
38.9
39.5
45.1
41.0
39.0
21.6
26.3
31.1
30.1
29.7
25.7
29.8
33.9
31.8
31.4
29.8
33.2
36.6
33.6
33.1
35.3
36.6
33.6
33.1
37.5
36.6
33.6
33.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
18.3
14.1
24.6
20.3
16.0
30.8
26.5
22.3
18.0
36.3
32.0
27.7
23.4
35.2
32.0
27.7
23.5
20.4
15.5
27.3
22.4
17.5
34.2
29.3
24.4
19.5
38.5
35.4
30.5
25.6
36.9
35.4
30.5
25.6
22.5
17.0
30.1
24.6
19.1
37.6
32.1
26.6
21.1
40.8
38.7
33.2
27.7
38.7
38.7
33.2
27.7
31.6
25.6
19.7
39.5
33.5
27.6
21.6
40.9
39.9
33.9
28.0
38.9
38.9
32.9
27.0
33.1
26.7
20.3
41.3
34.9
28.5
22.1
41.0
41.0
34.6
28.2
39.0
39.0
32.6
26.2
105°F
16.3
12.0
22.0
17.7
13.4
27.7
23.4
19.1
14.8
30.1
27.3
23.0
18.7
29.7
26.9
22.6
18.3
18.6
13.4
24.8
19.8
14.8
30.9
26.2
21.2
16.2
31.8
30.4
25.4
20.4
31.4
30.0
25.0
20.0
20.9
14.8
27.5
21.8
16.2
34.1
28.9
23.2
17.5
33.6
33.6
27.9
22.2
33.1
33.1
27.4
21.7
29.2
23.0
16.8
35.1
30.4
24.2
18.1
33.6
33.6
27.4
21.2
33.1
33.1
26.9
20.8
30.8
24.2
17.5
36.1
31.9
25.3
18.6
33.6
33.6
26.9
20.3
33.1
33.1
26.4
19.8
65
19.2
19.2
20.7
20.7
22.2
22.2
22.0
21.0
21.8
19.8
14.4
13.9
15.5
15.0
16.6
16.1
15.1
14.6
13.6
13.1
17
294604-YTG-G-0511
DEZ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1050
1225
1400
1550
1700
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
37.8
33.1
28.4
26.8
26.5
40.2
35.2
30.2
28.4
28.2
42.5
37.2
31.9
30.1
29.8
37.2
31.9
30.1
29.8
37.2
31.9
30.1
29.8
4.2
4.0
3.9
3.9
3.9
4.2
4.1
4.0
3.9
3.9
4.2
4.1
4.0
4.0
4.0
4.2
4.1
4.1
4.1
4.3
4.2
4.2
4.2
21.3
24.9
28.4
26.8
26.5
26.4
28.3
30.2
28.4
28.2
31.5
31.7
31.9
30.1
29.8
33.9
31.9
30.1
29.8
36.2
31.9
30.1
29.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
15.2
10.9
34.0
4.4
20.6
16.3
12.0
29.0
4.3
26.0
21.7
17.4
13.1
24.0
4.1
26.8
24.1
19.8
15.5
11.2
23.5
4.1
26.5
23.9
19.6
15.3
11.0
23.4
4.1
17.7
12.2
36.3
4.5
23.3
18.3
13.3
30.9
4.3
29.0
24.4
19.4
14.4
25.6
4.2
28.4
27.1
22.1
17.1
12.2
25.0
4.1
28.2
26.8
21.9
16.9
11.9
25.0
4.2
20.1
13.6
38.5
4.5
26.0
20.3
14.7
32.9
4.4
31.9
27.1
21.4
15.7
27.2
4.2
30.1
30.1
24.4
18.7
13.1
26.6
4.2
29.8
29.8
24.1
18.4
12.8
26.5
4.2
27.7
21.5
15.3
32.9
4.5
31.9
28.7
22.5
16.3
27.2
4.3
30.1
30.1
23.9
17.7
11.5
26.6
4.3
29.8
29.8
23.6
17.4
11.2
26.5
4.3
29.4
22.7
16.0
32.9
4.6
31.9
30.2
23.5
16.8
27.2
4.5
30.1
30.1
23.4
16.6
9.9
26.6
4.4
29.8
29.8
23.1
16.3
9.6
26.5
4.4
90
22.8
23.4
24.0
23.5
23.4
28.0
26.8
25.6
25.0
25.0
33.2
30.2
27.2
26.6
26.5
32.5
27.2
26.6
26.5
32.9
27.2
26.6
26.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
14.3
9.8
19.1
14.9
10.6
24.0
20.0
15.7
11.5
23.5
21.0
16.7
12.4
23.4
20.9
16.6
12.4
18.1
11.1
21.8
16.9
11.9
25.6
22.7
17.7
12.7
25.0
23.8
18.8
13.8
25.0
23.7
18.7
13.8
21.8
12.4
24.5
18.9
13.2
27.2
25.3
19.6
14.0
26.6
26.6
20.9
15.2
26.5
26.5
20.8
15.2
26.3
20.1
13.8
27.2
26.9
20.7
14.4
26.6
26.6
20.4
14.1
26.5
26.5
20.3
14.0
28.1
21.3
14.4
27.2
27.2
21.7
14.9
26.6
26.6
19.8
13.0
26.5
26.5
19.7
12.9
65
8.1
8.1
8.9
8.8
9.6
9.5
7.9
7.8
6.2
6.1
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
18
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ048 (4.0 Ton)
Air on
Evaporator Coil
CFM
1200
1400
1600
1700
1800
1200
1400
1600
1700
1800
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
59.7
57.1
54.5
49.7
51.4
61.0
58.3
55.7
50.7
52.5
62.3
59.6
56.9
51.8
53.6
59.4
56.7
51.7
53.5
59.2
56.6
51.5
53.3
3.6
3.5
3.5
3.5
3.5
3.6
3.6
3.5
3.5
3.5
3.6
3.6
3.5
3.5
3.5
3.7
3.6
3.6
3.6
3.7
3.7
3.7
3.7
26.9
34.5
42.1
49.7
51.4
29.0
37.1
45.3
50.7
52.5
31.1
39.7
48.4
51.8
53.6
40.3
49.0
51.7
53.5
40.9
49.7
51.5
53.3
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
55.5
51.3
47.2
44.3
45.4
56.4
52.1
47.9
45.0
46.1
57.3
53.0
48.7
45.7
46.8
53.3
49.0
46.0
47.1
53.7
49.3
46.3
47.4
4.2
4.2
4.1
4.0
4.1
4.3
4.2
4.1
4.1
4.1
4.3
4.2
4.1
4.1
4.1
4.3
4.2
4.2
4.2
4.4
4.3
4.3
4.3
24.5
32.2
39.8
44.3
45.4
26.5
34.7
42.8
45.0
46.1
28.5
37.2
45.8
45.7
46.8
38.1
46.9
46.0
47.1
39.0
48.0
46.3
47.4
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
22.8
18.7
57.6
3.9
30.4
26.3
22.2
54.2
3.9
38.0
33.9
29.8
25.7
50.9
3.8
43.2
39.1
35.0
30.9
26.8
47.0
3.8
50.3
46.2
42.1
37.9
33.8
48.4
3.8
24.5
19.9
58.7
3.9
32.6
28.1
23.5
55.2
3.9
40.7
36.2
31.7
27.1
51.8
3.8
47.5
41.8
37.2
32.7
28.2
47.9
3.8
52.0
49.3
44.8
40.2
35.7
49.3
3.8
26.1
21.2
59.8
3.9
34.8
29.8
24.9
56.3
3.9
43.4
38.5
33.6
28.6
52.8
3.8
51.8
44.4
39.5
34.6
29.6
48.7
3.8
53.6
52.4
47.5
42.6
37.6
50.2
3.8
35.2
30.1
25.0
56.4
4.0
43.9
38.9
33.8
28.7
52.9
3.9
51.7
44.8
39.8
34.7
29.6
48.8
3.9
53.5
52.9
47.9
42.8
37.7
50.3
3.9
35.6
30.4
25.2
56.4
4.1
44.5
39.2
34.0
28.8
52.9
4.0
51.5
45.2
40.0
34.8
29.5
48.9
4.0
53.3
53.3
48.2
43.0
37.8
50.4
4.0
95°F
20.1
15.8
54.4
4.6
27.8
23.4
19.1
48.5
4.5
35.4
31.1
26.7
22.4
42.6
4.4
43.0
38.7
34.3
30.0
25.6
41.3
4.3
44.3
39.9
35.6
31.2
26.9
41.7
4.3
21.7
16.8
54.5
4.6
29.8
25.0
20.1
48.6
4.5
38.0
33.1
28.3
23.5
42.7
4.4
44.4
41.2
36.4
31.6
26.7
41.4
4.4
45.5
42.6
37.7
32.9
28.0
41.9
4.4
23.2
17.9
54.7
4.6
31.9
26.5
21.2
48.8
4.5
40.5
35.2
29.9
24.5
42.9
4.5
45.7
43.8
38.5
33.1
27.8
41.6
4.4
46.8
45.2
39.9
34.6
29.2
42.0
4.4
32.6
27.0
21.5
49.7
4.6
41.4
35.8
30.3
24.8
43.7
4.6
46.0
44.6
39.1
33.5
28.0
42.4
4.5
47.1
46.0
40.5
35.0
29.4
42.8
4.5
33.3
27.5
21.8
50.7
4.7
42.2
36.5
30.7
25.0
44.5
4.7
46.3
45.4
39.7
33.9
28.2
43.2
4.6
47.4
46.9
41.1
35.4
29.6
43.7
4.6
90
25.7
33.3
41.0
47.0
48.4
27.8
35.9
44.0
47.9
49.3
29.8
38.5
47.1
48.7
50.2
39.2
48.0
48.8
50.3
39.9
48.8
48.9
50.4
24.3
31.2
38.1
41.3
41.7
27.4
33.6
39.8
41.4
41.9
30.5
36.0
41.5
41.6
42.0
37.2
42.7
42.4
42.8
38.5
43.9
43.2
43.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
21.5
17.2
29.1
24.9
20.6
36.7
32.5
28.3
24.0
43.1
38.9
34.7
30.4
47.3
43.1
38.8
34.6
23.1
18.4
31.2
26.5
21.8
39.4
34.7
30.0
25.3
45.9
41.5
36.8
32.1
48.8
45.9
41.3
36.6
24.7
19.5
33.3
28.2
23.1
42.0
36.8
31.7
26.6
48.7
44.1
39.0
33.9
50.2
48.8
43.7
38.6
33.9
28.6
23.3
42.7
37.4
32.0
26.7
48.8
44.7
39.4
34.1
50.3
49.5
44.2
38.9
34.5
29.0
23.5
43.3
37.9
32.4
26.9
48.9
45.3
39.8
34.3
50.4
50.2
44.7
39.2
105°F
19.9
15.4
26.8
22.3
17.8
33.6
29.2
24.7
20.3
40.6
36.1
31.7
27.2
41.1
36.6
32.2
27.7
21.3
16.4
28.6
23.7
18.7
35.9
31.0
26.0
21.1
41.1
38.4
33.4
28.5
41.5
38.9
34.0
29.0
22.8
17.3
30.5
25.1
19.6
38.3
32.8
27.4
21.9
41.6
40.6
35.2
29.7
42.0
41.2
35.8
30.3
31.5
25.8
20.1
39.5
33.7
28.0
22.3
42.4
41.7
36.0
30.3
42.8
42.3
36.6
30.9
32.5
26.5
20.5
40.7
34.7
28.7
22.7
43.2
42.8
36.8
30.8
43.7
43.4
37.4
31.5
65
26.2
30.3
27.5
31.9
28.7
33.4
28.8
33.6
28.9
33.7
22.7
23.3
23.5
24.0
24.3
24.8
24.6
25.2
24.9
25.5
19
294604-YTG-G-0511
DEZ048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1200
1400
1600
1700
1800
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
53.3
45.6
37.9
38.4
38.1
52.7
45.1
37.5
37.9
37.7
52.1
44.6
37.1
37.5
37.2
46.2
38.4
38.8
38.6
47.8
39.7
40.2
39.9
4.9
4.8
4.7
4.6
4.6
4.9
4.8
4.7
4.7
4.7
5.0
4.9
4.8
4.7
4.7
5.0
4.9
4.8
4.8
5.1
5.0
4.9
4.9
24.2
30.3
36.4
38.4
38.1
28.4
32.5
36.7
37.9
37.7
32.6
34.8
37.1
37.5
37.2
36.4
38.4
38.8
38.6
37.9
39.7
40.2
39.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
19.6
15.1
52.2
5.2
25.7
21.1
16.6
42.8
5.1
31.8
27.2
22.7
18.1
33.3
5.0
38.1
33.5
29.0
24.4
19.9
35.4
4.9
37.9
33.3
28.8
24.2
19.7
34.5
4.9
21.0
15.9
50.9
5.3
27.5
22.4
17.3
41.6
5.1
33.9
28.8
23.8
18.7
32.3
5.0
37.8
35.5
30.4
25.3
20.3
34.4
5.0
37.6
35.3
30.2
25.1
20.0
33.5
4.9
22.4
16.8
49.5
5.3
29.2
23.6
18.0
40.4
5.2
36.0
30.4
24.8
19.2
31.3
5.1
37.5
37.5
31.9
26.3
20.7
33.4
5.0
37.2
37.2
31.6
26.0
20.4
32.4
5.0
30.5
24.6
18.7
42.6
5.3
37.5
31.6
25.8
19.9
33.1
5.2
38.8
38.8
32.9
27.0
21.1
35.2
5.1
38.6
38.6
32.7
26.8
20.9
34.3
5.1
31.7
25.5
19.3
44.9
5.4
39.1
32.9
26.7
20.5
35.0
5.3
40.2
40.2
34.0
27.8
21.6
37.1
5.2
39.9
39.9
33.7
27.5
21.3
36.2
5.2
90
25.3
29.3
33.3
35.4
34.5
30.6
31.5
32.3
34.4
33.5
36.0
33.6
31.3
33.4
32.4
35.5
33.1
35.2
34.3
37.4
35.0
37.1
36.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
19.3
14.7
24.7
20.0
15.3
30.0
25.3
20.7
16.0
35.4
31.0
26.3
21.6
34.5
30.0
25.4
20.7
21.9
15.5
26.3
21.1
15.9
31.9
26.7
21.5
16.3
34.4
32.6
27.4
22.2
33.5
31.6
26.4
21.2
24.5
16.3
27.9
22.2
16.4
31.3
28.0
22.3
16.6
33.4
33.4
28.6
22.8
32.4
32.4
27.5
21.8
29.4
23.3
17.3
33.1
29.6
23.5
17.4
35.2
35.2
29.8
23.8
34.3
34.3
28.8
22.7
30.9
24.5
18.1
35.0
31.1
24.6
18.2
37.1
37.1
31.1
24.7
36.2
36.2
30.0
23.6
65
17.0
16.0
17.0
16.0
17.1
16.0
17.7
16.6
18.3
17.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
20
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ060 (5.0 Ton)
Air on
Evaporator Coil
CFM
1500
1550
1600
1800
2000
1500
1550
1600
1800
2000
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
78.1
71.7
65.2
58.7
51.3
78.7
72.2
65.7
59.1
51.6
79.3
72.7
66.2
59.6
52.0
74.1
67.5
60.7
53.0
75.6
68.8
61.9
54.1
4.6
4.5
4.4
4.3
4.2
4.6
4.5
4.3
4.2
4.2
4.6
4.5
4.3
4.2
4.1
4.6
4.5
4.4
4.3
4.8
4.6
4.5
4.5
35.6
44.2
52.7
58.7
51.3
36.6
45.3
54.0
59.1
51.6
37.5
46.4
55.3
59.6
52.0
49.1
58.5
60.7
53.0
51.9
61.7
61.9
54.1
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
68.5
62.3
56.1
50.7
49.4
69.4
63.1
56.8
51.4
50.0
70.2
63.9
57.5
52.0
50.6
64.5
58.1
52.5
51.1
65.2
58.7
53.1
51.7
5.6
5.4
5.3
5.2
5.1
5.6
5.4
5.2
5.1
5.1
5.5
5.4
5.2
5.1
5.1
5.5
5.4
5.3
5.2
5.7
5.6
5.4
5.4
31.9
40.2
48.4
50.7
49.4
32.7
41.2
49.7
51.4
50.0
33.5
42.3
51.1
52.0
50.6
44.9
54.1
52.5
51.1
47.6
57.1
53.1
51.7
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
29.7
23.9
73.3
5.1
38.3
32.4
26.5
67.0
5.0
46.8
40.9
35.0
29.1
60.6
4.8
56.0
49.4
43.5
37.6
31.7
54.7
4.7
51.3
50.1
44.2
38.3
32.5
50.3
4.7
30.5
24.4
74.0
5.1
39.2
33.1
27.1
67.6
4.9
47.9
41.9
35.8
29.7
61.3
4.8
57.8
50.5
44.5
38.4
32.3
55.2
4.7
51.6
51.3
45.2
39.1
33.1
50.8
4.6
31.2
25.0
74.7
5.1
40.2
33.9
27.7
68.3
4.9
49.1
42.8
36.6
30.3
61.9
4.8
59.6
51.7
45.4
39.2
32.9
55.8
4.7
52.0
52.0
46.2
40.0
33.7
51.3
4.6
42.4
35.6
28.9
69.3
5.1
51.8
45.0
38.3
31.5
62.8
4.9
60.7
54.3
47.6
40.8
34.1
56.6
4.8
53.0
53.0
46.5
39.8
33.0
52.1
4.8
44.6
37.4
30.1
70.4
5.3
54.5
47.2
40.0
32.7
63.7
5.1
61.9
57.0
49.8
42.5
35.3
57.5
5.0
54.1
54.1
46.8
39.6
32.4
52.9
4.9
95°F
26.1
20.4
63.9
6.2
34.4
28.7
22.9
57.6
6.0
42.7
36.9
31.2
25.5
51.3
5.8
50.7
45.7
40.0
34.2
28.5
45.9
5.7
49.4
47.3
41.6
35.9
30.1
45.9
5.7
26.9
21.0
64.7
6.1
35.4
29.5
23.7
58.3
6.0
43.9
38.0
32.2
26.3
51.9
5.8
51.4
47.1
41.2
35.4
29.5
46.5
5.7
50.0
48.8
42.9
37.1
31.2
46.4
5.7
27.6
21.6
65.4
6.1
36.3
30.4
24.4
59.0
5.9
45.1
39.1
33.2
27.2
52.5
5.8
52.0
48.4
42.5
36.5
30.6
47.0
5.7
50.6
50.2
44.2
38.3
32.3
47.0
5.7
38.3
31.7
25.0
59.4
6.1
47.4
40.8
34.2
27.6
52.9
6.0
52.5
50.5
43.9
37.2
30.6
47.4
5.8
51.1
50.9
44.3
37.7
31.0
47.3
5.8
40.3
33.0
25.7
59.9
6.3
49.8
42.5
35.2
27.9
53.3
6.1
53.1
52.6
45.2
37.9
30.6
47.7
6.0
51.7
51.7
44.4
37.1
29.8
47.7
6.0
90
33.8
42.2
50.6
54.7
50.3
34.6
43.3
51.9
55.2
50.8
35.5
44.4
53.2
55.8
51.3
47.0
56.3
56.6
52.1
49.7
59.4
57.5
52.9
29.6
37.8
45.9
45.9
45.9
30.5
38.8
47.2
46.5
46.4
31.3
39.9
48.5
47.0
47.0
42.4
50.5
47.4
47.3
44.8
52.5
47.7
47.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
27.9
22.1
36.3
30.5
24.7
44.7
38.9
33.1
27.3
53.4
47.5
41.7
35.9
50.3
48.7
42.9
37.1
28.7
22.7
37.3
31.3
25.4
45.9
40.0
34.0
28.0
54.6
48.8
42.8
36.9
50.8
50.0
44.1
38.1
29.4
23.3
38.2
32.1
26.0
47.1
41.0
34.9
28.8
55.8
50.1
44.0
37.9
51.3
51.3
45.2
39.1
40.3
33.7
27.0
49.6
42.9
36.2
29.5
56.6
52.4
45.7
39.0
52.1
52.1
45.4
38.7
42.4
35.2
27.9
52.1
44.8
37.6
30.3
57.5
54.8
47.5
40.2
52.9
52.9
45.6
38.3
105°F
24.0
18.4
32.2
26.5
20.9
40.3
34.7
29.1
23.5
45.9
42.8
37.1
31.5
45.9
44.2
38.6
33.0
24.7
18.9
33.1
27.3
21.5
41.5
35.7
29.9
24.2
46.5
44.0
38.2
32.5
46.4
45.5
39.7
34.0
25.4
19.5
34.0
28.1
22.2
42.6
36.7
30.8
24.9
47.0
45.2
39.3
33.4
47.0
46.7
40.8
34.9
35.8
29.3
22.8
44.8
38.3
31.8
25.3
47.4
46.3
39.8
33.3
47.3
47.2
40.7
34.2
37.7
30.6
23.4
47.1
39.9
32.8
25.7
47.7
47.4
40.3
33.2
47.7
47.7
40.6
33.5
65
30.1
31.3
30.9
32.1
31.8
33.0
32.4
32.0
32.9
31.1
25.9
27.4
26.7
28.2
27.5
29.0
26.8
27.7
26.1
26.3
21
294604-YTG-G-0511
DEZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1500
1550
1600
1800
2000
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
59.3
52.9
46.5
41.1
42.5
60.0
53.5
47.0
41.6
42.9
60.6
54.1
47.5
42.0
43.4
54.3
47.7
42.2
43.5
54.5
47.9
42.3
43.7
6.7
6.6
6.4
6.3
6.3
6.7
6.5
6.4
6.3
6.3
6.7
6.5
6.4
6.2
6.2
6.7
6.5
6.4
6.4
6.9
6.7
6.6
6.6
27.4
35.4
43.4
41.1
42.5
28.2
36.4
44.7
41.6
42.9
29.0
37.5
46.0
42.0
43.4
39.8
46.9
42.2
43.5
42.0
47.9
42.3
43.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
21.9
16.4
54.7
7.3
29.9
24.4
18.9
48.2
7.1
37.9
32.4
27.0
21.5
41.7
7.0
41.1
39.8
34.3
28.9
23.4
36.3
6.8
42.5
41.1
35.6
30.1
24.6
39.0
6.9
22.5
16.8
55.3
7.3
30.8
25.1
19.4
48.7
7.1
39.0
33.3
27.7
22.0
42.1
7.0
41.6
40.9
35.2
29.6
23.9
36.7
6.8
42.9
42.2
36.5
30.9
25.2
39.4
6.9
23.2
17.3
55.8
7.2
31.6
25.8
19.9
49.2
7.1
40.1
34.2
28.4
22.5
42.5
6.9
42.0
42.0
36.1
30.3
24.4
37.0
6.8
43.4
43.3
37.5
31.6
25.7
39.8
6.8
33.4
27.0
20.6
49.1
7.3
42.2
35.8
29.4
23.0
42.5
7.1
42.2
42.2
35.8
29.4
23.0
37.0
7.0
43.5
43.5
37.1
30.7
24.3
39.7
7.0
35.1
28.2
21.2
49.1
7.4
44.4
37.4
30.5
23.5
42.5
7.3
42.3
42.3
35.4
28.5
21.5
37.0
7.1
43.7
43.7
36.8
29.8
22.9
39.7
7.2
90
25.1
33.0
40.9
36.3
39.0
26.4
34.0
42.1
36.7
39.4
27.7
35.1
42.5
37.0
39.8
37.2
42.5
37.0
39.7
39.3
42.5
37.0
39.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
19.7
14.4
27.6
22.3
16.9
35.5
30.2
24.8
19.5
36.3
36.3
31.5
26.2
39.0
37.9
32.6
27.2
20.4
14.8
28.5
22.9
17.3
36.6
31.0
25.4
19.8
36.7
36.7
32.2
26.7
39.4
38.9
33.3
27.8
21.0
15.1
29.3
23.5
17.6
37.6
31.8
26.0
20.1
37.0
37.0
33.0
27.2
39.8
39.8
34.1
28.3
30.9
24.6
18.3
39.6
33.3
27.0
20.7
37.0
37.0
31.7
25.4
39.7
39.7
33.5
27.3
32.5
25.8
19.0
41.6
34.9
28.1
21.4
37.0
37.0
30.5
23.7
39.7
39.7
33.0
26.2
65
20.8
21.9
21.1
22.2
21.3
22.5
19.2
21.0
17.0
19.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
22
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ024-060 Cooling Capacities
DEQ024 (2.0 Ton)
Air on
Evaporator Coil
CFM
600
700
800
900
600
700
800
900
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
27.3
26.2
25.2
23.5
22.6
28.6
27.5
26.3
24.6
23.6
29.8
28.7
27.5
25.8
24.7
30.4
29.1
27.3
26.1
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
10.8
16.0
21.2
23.5
22.6
12.1
18.1
24.1
24.6
23.6
13.3
20.1
26.9
25.8
24.7
19.1
27.0
27.3
26.1
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
24.3
22.5
20.7
18.8
18.9
25.6
23.7
21.7
19.8
19.9
26.8
24.8
22.8
20.7
20.8
26.4
24.2
22.0
22.1
1.9
1.8
1.8
1.8
1.8
1.9
1.8
1.8
1.8
1.8
1.9
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
12.6
16.0
19.4
18.8
18.9
14.1
17.6
21.1
19.8
19.9
15.6
19.2
22.8
20.7
20.8
21.7
24.2
22.0
22.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
8.5
6.2
25.8
1.7
13.7
11.4
9.1
24.4
1.7
18.9
16.6
14.4
12.1
22.9
1.7
21.6
17.9
15.6
13.3
11.0
21.2
1.6
22.6
19.7
17.4
15.1
12.8
20.7
1.6
9.7
7.2
27.1
1.7
15.5
13.0
10.5
25.6
1.7
21.4
18.9
16.4
13.9
24.0
1.7
23.7
20.4
17.9
15.4
12.9
22.2
1.6
23.6
22.4
19.8
17.3
14.8
21.8
1.6
10.8
8.1
28.3
1.7
17.4
14.6
11.9
26.7
1.7
23.9
21.2
18.4
15.7
25.1
1.7
25.8
22.9
20.2
17.4
14.7
23.2
1.6
24.7
24.7
22.3
19.6
16.8
22.8
1.6
15.8
12.5
9.2
28.4
1.7
21.7
18.4
15.1
11.8
26.7
1.7
27.3
20.6
17.3
14.0
10.7
24.7
1.6
26.1
23.0
19.7
16.4
13.2
24.1
1.6
95°F
10.3
7.9
22.1
2.0
13.7
11.3
9.0
20.1
2.0
17.1
14.7
12.4
10.1
18.1
1.9
18.8
17.9
15.6
13.2
10.9
16.7
1.9
18.9
18.1
15.8
13.4
11.1
17.1
1.9
11.2
8.4
23.2
2.0
14.8
12.1
9.3
21.1
2.0
18.5
15.7
12.9
10.2
19.0
1.9
19.8
19.1
16.3
13.5
10.8
17.6
1.9
19.9
19.3
16.5
13.8
11.0
17.9
1.9
12.1
9.0
24.3
2.0
16.0
12.8
9.6
22.1
2.0
19.8
16.6
13.5
10.3
19.9
1.9
20.7
20.2
17.0
13.8
10.7
18.4
1.9
20.8
20.5
17.3
14.1
10.9
18.8
1.9
18.3
14.9
11.5
23.6
2.0
22.8
19.4
16.0
12.6
21.2
2.0
22.0
22.6
19.2
15.8
12.4
19.6
1.9
22.1
22.5
19.1
15.7
12.3
20.0
1.9
90
11.7
16.0
20.3
21.2
20.7
13.1
17.8
22.6
22.2
21.8
14.5
19.7
24.8
23.2
22.8
20.4
25.6
24.7
24.1
12.7
15.1
17.5
16.7
17.1
14.6
16.7
18.7
17.6
17.9
16.6
18.2
19.9
18.4
18.8
20.7
21.2
19.6
20.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
9.4
7.1
13.7
11.4
9.1
18.0
15.7
13.4
11.1
20.2
17.9
15.6
13.3
20.7
18.9
16.6
14.3
10.4
7.8
15.2
12.6
9.9
19.9
17.3
14.7
12.0
21.7
19.7
17.1
14.5
21.8
20.8
18.2
15.5
11.5
8.5
16.7
13.7
10.8
21.9
18.9
15.9
13.0
23.2
21.6
18.6
15.6
22.8
22.8
19.8
16.8
17.1
13.7
10.4
22.2
18.9
15.6
12.2
24.7
21.6
18.2
14.9
24.1
22.8
19.4
16.1
105°F
9.5
7.2
12.8
10.4
8.1
16.0
13.7
11.4
9.0
16.7
16.0
13.7
11.3
17.1
16.3
13.9
11.6
10.6
7.7
13.9
11.1
8.4
17.2
14.6
11.8
9.1
17.6
17.1
14.3
11.5
17.9
17.3
14.6
11.8
11.6
8.1
15.0
11.8
8.6
18.4
15.5
12.3
9.1
18.4
18.1
14.9
11.7
18.8
18.4
15.2
12.0
17.2
13.8
10.4
20.5
18.1
14.7
11.2
19.6
19.9
16.4
13.0
20.0
20.4
16.9
13.5
65
11.0
11.9
11.8
12.9
12.7
13.9
11.6
12.7
9.0
9.3
8.8
9.0
8.5
8.8
9.6
10.1
23
294604-YTG-G-0511
DEQ024 (2.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
600
700
800
900
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
19.9
17.7
15.5
14.7
15.3
20.8
18.5
16.3
15.3
16.0
21.7
19.4
17.0
16.0
16.7
20.7
18.2
17.2
17.9
2.2
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
12.8
14.2
15.5
14.7
15.3
15.2
15.7
16.3
15.3
16.0
17.5
17.2
17.0
16.0
16.7
19.6
18.2
17.2
17.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
8.8
6.5
17.7
2.4
11.9
9.6
7.2
15.3
2.3
15.0
12.6
10.3
8.0
13.0
2.2
14.7
14.1
11.8
9.5
7.2
12.6
2.2
15.3
14.4
12.1
9.8
7.5
13.5
2.2
10.0
6.9
18.5
2.4
13.0
10.2
7.4
16.0
2.3
16.0
13.5
10.7
8.0
13.5
2.2
15.3
15.0
12.3
9.5
6.8
13.1
2.2
16.0
15.4
12.6
9.9
7.1
14.0
2.2
11.1
7.3
19.2
2.4
14.0
10.8
7.6
16.6
2.3
17.0
14.3
11.1
7.9
14.1
2.2
16.0
16.0
12.8
9.6
6.4
13.6
2.2
16.7
16.3
13.1
9.9
6.7
14.6
2.2
16.1
12.7
9.2
17.9
2.3
18.2
16.8
13.3
9.8
15.2
2.2
17.2
17.2
13.7
10.2
6.8
14.7
2.2
17.9
18.2
14.8
11.3
7.8
15.8
2.2
90
13.6
13.3
13.0
12.6
13.5
16.0
14.8
13.5
13.1
14.0
18.5
16.3
14.1
13.6
14.6
18.2
15.2
14.7
15.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
8.9
5.7
11.0
8.7
6.4
13.0
11.6
9.3
7.0
12.6
12.2
9.9
7.6
13.5
12.5
10.2
7.9
10.5
6.1
12.0
9.3
6.5
13.5
12.4
9.6
6.9
13.1
13.0
10.3
7.5
14.0
13.4
10.7
7.9
12.1
6.5
13.1
9.9
6.6
14.1
13.2
10.0
6.8
13.6
13.6
10.7
7.5
14.6
14.3
11.1
7.9
15.1
11.6
8.1
15.2
15.4
11.9
8.4
14.7
14.7
10.9
7.4
15.8
16.1
12.6
9.1
65
5.3
5.6
4.8
5.2
4.3
4.7
3.9
5.6
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
24
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ030 (2.5 Ton)
Air on
Evaporator Coil
CFM
925
1000
1075
1150
925
1000
1075
1150
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
38.7
38.6
38.6
34.8
33.1
38.5
38.5
38.4
34.6
32.9
38.3
38.3
38.2
34.4
32.8
38.8
38.8
34.9
33.3
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
18.3
25.0
31.8
34.8
33.1
18.7
25.6
32.5
34.6
32.9
19.1
26.1
33.2
34.4
32.8
26.9
34.4
34.9
33.3
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
35.4
34.1
32.8
28.8
28.7
35.4
34.1
32.8
28.8
28.7
35.5
34.2
32.8
28.8
28.7
34.6
33.3
29.2
29.1
2.6
2.6
2.5
2.5
2.5
2.6
2.6
2.5
2.5
2.5
2.6
2.6
2.6
2.5
2.5
2.6
2.5
2.5
2.5
17.5
23.8
30.1
28.8
28.7
18.2
24.7
31.3
28.8
28.7
18.9
25.7
32.5
28.8
28.7
26.2
32.7
29.2
29.1
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
14.9
11.5
37.1
2.4
21.7
18.3
14.9
36.4
2.3
28.4
25.0
21.7
18.3
35.7
2.3
33.8
30.3
26.9
23.6
20.2
31.8
2.3
33.1
32.5
29.3
25.9
22.5
30.9
2.3
15.2
11.8
37.0
2.4
22.1
18.7
15.2
36.3
2.4
29.0
25.5
22.1
18.6
35.6
2.3
34.6
30.9
27.5
24.0
20.5
31.7
2.3
32.9
32.9
29.8
26.4
22.9
30.8
2.3
15.6
12.0
36.9
2.4
22.6
19.0
15.5
36.2
2.4
29.6
26.0
22.5
18.9
35.5
2.3
35.4
31.5
28.0
24.4
20.9
31.6
2.3
32.8
33.4
30.4
26.8
23.3
30.7
2.3
23.1
19.4
15.6
36.7
2.4
30.2
26.5
22.8
19.0
36.0
2.3
34.9
32.3
28.6
24.9
21.1
32.1
2.3
33.3
33.3
29.7
25.9
22.2
31.2
2.3
95°F
13.9
10.3
33.0
2.8
20.2
16.7
13.1
31.1
2.8
26.6
23.0
19.4
15.9
29.3
2.7
28.5
26.9
23.4
19.8
16.2
25.7
2.7
28.5
27.3
23.8
20.2
16.6
26.0
2.7
14.4
10.7
33.0
2.8
21.0
17.3
13.5
31.1
2.8
27.6
23.8
20.1
16.4
29.3
2.7
28.8
27.9
24.2
20.4
16.7
25.7
2.7
28.7
28.3
24.6
20.9
17.1
26.0
2.7
15.0
11.1
33.0
2.9
21.8
17.9
14.0
31.1
2.8
28.6
24.7
20.8
16.9
29.3
2.7
29.1
28.9
25.0
21.1
17.2
25.7
2.7
28.8
29.3
25.4
21.5
17.6
26.0
2.7
22.1
18.0
13.9
31.5
2.8
29.0
24.8
20.7
16.6
29.7
2.7
29.2
28.8
24.7
20.6
16.5
26.1
2.7
29.1
28.9
24.8
20.7
16.6
26.4
2.7
90
17.9
24.4
31.0
31.8
30.9
18.4
25.2
31.9
31.7
30.8
19.0
25.9
32.8
31.6
30.7
26.5
33.5
32.1
31.2
17.7
22.7
27.7
25.7
26.0
18.8
23.7
28.5
25.7
26.0
20.0
24.6
29.3
25.7
26.0
25.2
29.4
26.1
26.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
14.4
10.9
20.9
17.5
14.0
27.5
24.0
20.6
17.1
31.2
28.6
25.1
21.7
30.9
30.0
26.5
23.0
14.8
11.2
21.6
18.0
14.4
28.3
24.7
21.1
17.5
31.7
29.4
25.8
22.2
30.8
30.8
27.2
23.6
15.3
11.6
22.2
18.5
14.7
29.1
25.4
21.6
17.9
32.2
30.2
26.5
22.7
30.7
31.6
27.9
24.2
22.6
18.7
14.8
29.6
25.7
21.7
17.8
32.1
30.6
26.7
22.7
31.2
31.2
27.2
23.3
105°F
13.1
9.5
19.1
15.5
11.9
25.1
21.5
18.0
14.4
25.6
24.3
20.7
17.2
25.9
24.8
21.2
17.6
13.7
9.9
19.9
16.1
12.4
26.2
22.4
18.6
14.9
25.7
25.3
21.5
17.8
26.0
25.8
22.0
18.2
14.2
10.3
20.7
16.7
12.8
27.2
23.2
19.3
15.0
25.9
26.2
22.3
17.7
26.1
26.7
22.8
18.1
21.1
16.9
12.7
27.3
23.4
19.3
15.1
26.1
25.9
21.7
17.6
26.4
26.3
22.1
17.9
65
18.2
19.6
18.6
20.0
19.0
20.5
18.8
19.4
13.6
14.0
14.0
14.5
13.7
14.1
13.4
13.8
25
294604-YTG-G-0511
DEQ030 (2.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
925
1000
1075
1150
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
30.5
28.1
25.7
22.7
23.4
30.5
28.1
25.7
22.7
23.4
30.5
28.1
25.7
22.7
23.4
28.5
26.1
23.0
23.7
3.0
3.0
2.9
2.8
2.8
3.1
3.0
2.9
2.9
2.9
3.1
3.0
2.9
2.9
2.9
3.0
2.9
2.9
2.9
17.9
21.6
25.4
22.7
23.4
19.5
22.6
25.7
22.7
23.4
21.0
23.6
26.1
22.7
23.4
24.2
26.1
23.0
23.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
12.3
8.7
28.0
3.3
18.0
14.4
10.8
25.1
3.2
23.7
20.1
16.5
12.9
22.2
3.1
22.7
21.7
18.1
14.5
10.9
19.6
3.0
23.3
22.3
18.7
15.0
11.4
20.7
3.0
12.9
9.1
28.0
3.3
18.8
15.0
11.2
25.1
3.2
24.7
21.0
17.2
13.4
22.2
3.1
22.7
22.7
18.9
15.1
11.3
19.6
3.0
23.4
23.2
19.4
15.6
11.8
20.7
3.0
13.4
9.4
28.0
3.3
19.6
15.6
11.7
25.1
3.2
25.8
21.8
17.8
13.9
22.2
3.1
22.7
23.6
19.6
15.7
11.7
19.6
3.1
23.4
24.2
20.2
16.2
12.3
20.7
3.1
20.0
15.8
11.6
25.4
3.2
25.7
22.0
17.8
13.6
22.5
3.1
23.0
23.0
18.8
14.5
10.3
19.9
3.0
23.7
23.6
19.4
15.2
11.0
21.0
3.1
90
18.8
20.5
22.2
19.6
20.7
20.9
21.5
22.2
19.6
20.7
22.9
22.5
22.2
19.6
20.7
23.2
22.5
19.9
21.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
12.3
7.9
16.9
13.3
9.6
21.8
18.6
15.0
11.4
19.6
19.0
15.5
11.9
20.7
19.7
16.1
12.5
13.2
8.2
17.7
13.9
10.1
22.2
19.5
15.7
11.9
19.6
19.6
16.2
12.4
20.7
20.7
16.9
13.0
14.1
8.6
18.5
14.5
10.5
22.6
20.4
16.4
12.0
19.6
20.3
17.0
12.0
20.7
21.6
17.6
12.7
18.9
14.7
10.4
22.5
20.6
16.3
12.1
19.9
19.9
15.8
11.5
21.0
21.0
16.7
12.4
65
8.3
8.8
8.6
9.2
7.9
8.7
7.2
8.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
26
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ036 (3.0 Ton)
Air on
Evaporator Coil
CFM
1000
1100
1200
1300
1000
1100
1200
1300
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
46.0
44.1
42.2
39.0
32.9
46.5
44.6
42.6
39.4
33.3
47.0
45.0
43.1
39.8
33.6
44.7
42.8
39.6
33.4
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
23.9
29.4
34.9
39.0
32.9
24.9
30.6
36.3
39.4
33.3
25.8
31.8
37.7
39.8
33.6
34.1
41.5
39.6
33.4
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
40.8
38.2
35.7
31.9
28.3
41.3
38.7
36.2
32.3
28.7
41.9
39.3
36.6
32.7
29.0
39.6
36.9
33.0
29.3
2.8
2.8
2.8
2.7
2.7
2.8
2.8
2.8
2.7
2.7
2.8
2.8
2.8
2.7
2.7
2.8
2.8
2.7
2.7
20.6
27.1
33.6
31.9
28.3
21.7
28.4
35.1
32.3
28.7
22.9
29.8
36.6
32.7
29.0
30.9
36.9
33.0
29.3
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
20.3
16.4
43.4
2.6
25.6
21.7
17.9
41.2
2.5
30.9
27.0
23.1
19.3
38.9
2.5
38.3
34.5
30.7
26.8
23.0
35.4
2.5
32.9
32.6
28.7
24.9
21.0
30.6
2.5
21.0
16.7
43.9
2.6
26.3
22.1
17.8
41.7
2.5
31.6
27.4
23.1
18.8
39.4
2.5
39.1
35.0
30.8
26.5
22.2
35.8
2.5
33.3
33.1
28.8
24.6
20.3
31.0
2.5
21.7
17.1
44.4
2.6
27.1
22.4
17.7
42.1
2.5
32.4
27.7
23.0
18.3
39.9
2.5
39.8
35.6
30.9
26.2
21.5
36.3
2.5
33.6
33.6
28.9
24.3
19.6
31.3
2.5
29.0
24.0
18.9
42.1
2.6
34.8
29.8
24.7
19.7
39.9
2.5
39.6
38.1
33.1
28.0
23.0
36.3
2.5
33.4
33.4
28.4
23.3
18.3
31.3
2.5
95°F
15.9
11.3
37.9
3.1
22.6
18.0
13.5
34.7
3.0
29.3
24.8
20.2
15.7
31.4
3.0
31.9
28.9
24.4
19.9
15.3
28.8
2.9
28.3
26.0
21.4
16.9
12.4
26.6
2.9
16.7
12.0
38.3
3.1
23.8
19.1
14.5
35.1
3.0
30.9
26.2
21.6
16.9
31.8
3.0
32.3
30.6
26.0
21.3
16.6
29.1
2.9
28.7
27.5
22.8
18.2
13.5
26.9
2.9
17.5
12.7
38.8
3.1
25.0
20.2
15.4
35.5
3.0
32.5
27.7
22.9
18.1
32.2
3.0
32.7
32.3
27.5
22.7
18.0
29.5
2.9
29.0
29.0
24.2
19.5
14.7
27.3
2.9
25.7
20.6
15.4
35.8
3.1
33.4
28.2
23.0
17.9
32.5
3.0
33.0
32.9
27.8
22.6
17.5
29.8
2.9
29.3
29.3
24.1
19.0
13.8
27.5
3.0
90
22.3
28.3
34.3
35.4
30.6
23.3
29.5
35.7
35.8
31.0
24.3
30.8
37.2
36.3
31.3
32.5
39.2
36.3
31.3
21.3
25.8
30.4
28.8
26.6
23.1
27.2
31.3
29.1
26.9
25.0
28.6
32.2
29.5
27.3
30.3
32.5
29.8
27.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
18.1
13.9
24.1
19.9
15.7
30.1
25.9
21.7
17.5
35.1
31.7
27.5
23.3
30.6
29.3
25.1
20.9
18.8
14.4
25.0
20.6
16.1
31.3
26.8
22.3
17.9
35.7
32.8
28.4
23.9
31.0
30.3
25.8
21.4
19.6
14.9
26.0
21.3
16.5
32.4
27.7
23.0
18.2
36.3
33.9
29.2
24.5
31.3
31.3
26.6
21.9
27.4
22.3
17.2
34.1
29.0
23.9
18.8
36.3
35.5
30.4
25.3
31.3
31.3
26.2
21.1
105°F
15.6
11.1
21.4
17.0
12.6
27.3
23.0
18.6
14.2
28.8
26.4
22.0
17.6
26.6
24.6
20.2
15.8
16.5
11.7
22.6
18.0
13.3
28.7
24.2
19.6
15.0
29.1
27.9
23.2
18.6
26.9
25.9
21.3
16.7
17.3
12.3
23.7
18.9
14.0
30.1
25.4
20.6
15.8
29.5
29.3
24.4
19.6
27.3
27.3
22.4
17.6
25.0
19.8
14.6
30.7
26.7
21.5
16.3
29.8
29.7
24.5
19.3
27.5
27.5
22.3
17.1
65
19.1
16.7
19.4
16.9
19.7
17.1
20.2
16.0
13.2
11.4
14.0
12.1
14.7
12.7
14.1
11.9
27
294604-YTG-G-0511
DEQ036 (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1000
1100
1200
1300
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
35.0
31.1
27.2
25.7
25.0
35.3
31.4
27.4
26.0
25.2
35.7
31.7
27.7
26.2
25.5
32.1
28.1
26.6
25.8
3.3
3.3
3.2
3.1
3.1
3.3
3.3
3.2
3.1
3.1
3.4
3.3
3.2
3.1
3.1
3.3
3.2
3.2
3.2
22.0
24.6
27.2
25.7
25.0
24.5
26.0
27.4
26.0
25.2
27.0
27.4
27.7
26.2
25.5
29.6
28.1
26.6
25.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
15.3
10.9
32.1
3.6
20.3
16.0
11.8
27.5
3.5
25.3
21.2
16.9
12.7
22.9
3.4
25.7
24.0
19.7
15.4
11.2
22.6
3.3
25.0
23.3
19.0
14.8
10.5
23.3
3.3
16.2
11.4
32.3
3.6
21.4
16.8
12.2
27.7
3.5
26.5
22.2
17.6
13.0
23.1
3.4
26.0
25.1
20.5
15.9
11.3
22.8
3.3
25.2
24.4
19.8
15.2
10.6
23.5
3.3
17.2
11.9
32.6
3.6
22.5
17.6
12.7
27.9
3.5
27.7
23.2
18.3
13.4
23.3
3.4
26.2
26.2
21.3
16.4
11.5
23.0
3.4
25.5
25.5
20.6
15.7
10.8
23.7
3.4
24.4
19.1
13.8
28.4
3.6
28.1
25.2
19.9
14.7
23.7
3.4
26.6
26.6
21.3
16.0
10.7
23.4
3.4
25.8
25.8
20.6
15.3
10.0
24.1
3.4
90
23.7
23.3
22.9
22.6
23.3
26.4
24.7
23.1
22.8
23.5
29.1
26.2
23.3
23.0
23.7
28.4
23.7
23.4
24.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
15.7
10.7
19.2
15.0
10.9
22.8
19.4
15.3
11.2
22.6
21.5
17.3
13.2
23.3
22.0
17.8
13.7
17.4
11.1
20.2
15.6
11.1
23.1
20.2
15.6
11.1
22.8
22.3
17.8
13.2
23.5
22.8
18.3
13.7
19.2
11.5
21.2
16.3
11.3
23.3
21.0
16.0
11.0
23.0
23.0
18.2
13.2
23.7
23.7
18.8
13.8
23.7
18.4
13.0
23.7
23.7
18.4
13.1
23.4
23.4
18.0
12.7
24.1
24.1
18.8
13.4
65
9.1
9.6
8.7
9.2
8.3
8.8
7.4
8.1
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
28
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ042 (3.5 Ton)
Air on
Evaporator Coil
CFM
1200
1300
1400
1500
1200
1300
1400
1500
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
58.6
54.7
50.8
46.3
45.4
58.7
54.8
50.9
46.3
45.4
58.7
54.8
50.9
46.3
45.4
55.8
51.8
47.2
46.2
2.9
2.8
2.8
2.7
2.6
2.9
2.8
2.7
2.7
2.5
2.9
2.8
2.7
2.7
2.5
2.8
2.8
2.7
2.5
27.7
36.7
45.7
46.3
45.4
27.9
37.7
47.6
46.3
45.4
28.1
38.8
49.4
46.3
45.4
41.3
51.1
47.2
46.2
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
51.2
46.8
42.5
39.3
39.3
51.3
47.0
42.7
39.4
39.5
51.5
47.2
42.8
39.5
39.6
47.3
42.9
39.6
39.7
3.4
3.3
3.2
3.2
3.1
3.4
3.3
3.2
3.2
3.1
3.4
3.3
3.2
3.1
3.1
3.3
3.2
3.1
3.1
27.9
34.2
40.6
39.3
39.3
29.7
35.7
41.7
39.4
39.5
31.5
37.2
42.8
39.5
39.6
38.3
42.9
39.6
39.7
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
23.2
17.8
54.9
3.2
31.3
25.8
20.4
50.8
3.1
39.3
33.9
28.4
23.0
46.7
3.0
46.2
42.8
37.3
31.9
26.5
42.8
2.9
45.4
43.0
37.5
32.1
26.7
42.3
2.9
23.9
18.3
55.0
3.2
32.1
26.6
21.0
50.9
3.1
40.4
34.8
29.2
23.6
46.8
3.0
46.3
44.0
38.4
32.8
27.2
42.9
2.9
45.4
44.2
38.6
33.0
27.4
42.4
2.8
24.5
18.8
55.1
3.2
33.0
27.3
21.5
51.0
3.1
41.5
35.8
30.0
24.3
46.8
3.0
46.3
45.2
39.4
33.7
27.9
42.9
2.9
45.4
45.4
39.7
33.9
28.2
42.5
2.8
35.1
28.9
22.8
51.5
3.1
44.1
38.0
31.8
25.7
47.4
3.0
47.2
46.6
40.5
34.3
28.2
43.4
2.9
46.2
46.2
40.1
33.9
27.8
43.0
2.8
95°F
21.3
15.6
46.6
3.7
28.6
22.9
17.2
42.2
3.6
35.8
30.1
24.5
18.8
37.8
3.5
39.2
35.8
30.1
24.4
18.8
34.7
3.4
39.3
36.8
31.1
25.4
19.7
35.2
3.4
22.2
16.2
46.9
3.7
29.7
23.7
17.8
42.5
3.6
37.3
31.3
25.3
19.3
38.1
3.4
39.4
37.2
31.2
25.2
19.2
34.9
3.4
39.5
38.2
32.2
26.2
20.3
35.5
3.4
23.1
16.8
47.2
3.7
30.9
24.6
18.3
42.8
3.6
38.7
32.4
26.2
19.9
38.4
3.4
39.5
38.5
32.3
26.0
19.7
35.2
3.4
39.6
39.6
33.3
27.0
20.8
35.7
3.4
31.6
25.0
18.3
42.6
3.6
39.6
32.9
26.2
19.6
38.2
3.4
39.6
39.1
32.4
25.8
19.1
35.0
3.4
39.7
39.7
33.0
26.4
19.7
35.6
3.4
90
27.8
35.5
43.1
42.8
42.3
28.8
36.7
44.6
42.9
42.4
29.8
38.0
46.1
42.9
42.5
39.8
47.0
43.4
43.0
28.1
32.5
36.9
34.7
35.2
30.4
34.0
37.6
34.9
35.5
32.7
35.5
38.4
35.2
35.7
36.4
38.2
35.0
35.6
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
22.3
16.7
29.9
24.4
37.6
32.0
26.5
20.9
42.7
39.3
33.7
28.2
42.3
39.9
34.3
28.8
23.0
17.2
30.9
25.2
19.4
38.8
33.1
27.3
21.5
42.8
40.6
34.8
29.0
42.4
41.2
35.4
29.6
23.8
17.8
32.0
25.9
19.9
40.1
34.1
28.1
22.1
42.9
41.9
35.8
29.8
42.5
42.5
36.5
30.5
33.4
27.0
20.5
41.8
35.4
29.0
22.6
43.4
42.9
36.5
30.0
43.0
43.0
36.6
30.1
105°F
20.0
14.1
26.8
21.2
15.5
33.7
28.3
22.6
16.9
34.7
31.7
26.1
20.4
35.2
33.0
27.3
21.7
21.1
14.6
28.0
22.0
16.1
35.0
29.5
23.5
17.5
34.9
33.0
27.1
21.1
35.5
34.4
28.4
22.4
22.1
15.2
29.2
22.9
16.6
36.3
30.6
24.3
18.1
35.2
34.4
28.1
21.8
35.7
35.7
29.4
23.2
29.7
23.0
16.3
36.5
30.7
24.0
17.3
35.0
34.5
27.8
21.1
35.6
35.6
28.9
22.2
65
22.6
23.2
23.2
23.8
23.8
24.5
23.6
23.7
14.7
16.0
15.1
16.4
15.5
16.9
14.4
15.5
29
294604-YTG-G-0511
DEQ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1200
1300
1400
1500
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
42.0
37.6
33.2
30.1
31.2
42.4
38.0
33.5
30.4
31.5
42.9
38.4
33.9
30.8
31.9
38.0
33.5
30.4
31.5
4.0
3.8
3.7
3.6
3.6
4.0
3.8
3.7
3.6
3.6
4.0
3.8
3.7
3.6
3.6
3.8
3.7
3.6
3.6
28.4
30.8
33.2
30.1
31.2
31.1
32.3
33.5
30.4
31.5
33.8
33.9
33.9
30.8
31.9
34.5
33.5
30.4
31.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
18.7
12.5
37.4
4.2
25.1
19.5
13.8
32.9
4.0
31.5
26.4
20.7
15.1
28.5
3.9
30.1
27.6
22.0
16.3
10.7
25.5
3.8
31.2
29.2
23.5
17.9
12.2
27.1
3.9
19.9
13.1
38.0
4.2
26.3
20.3
14.4
33.5
4.0
32.7
27.6
21.6
15.7
29.0
3.9
30.4
28.9
22.9
16.9
11.0
26.0
3.8
31.5
30.5
24.5
18.6
12.6
27.5
3.9
21.2
13.7
38.6
4.2
27.5
21.2
14.9
34.0
4.1
33.9
28.8
22.5
16.2
29.5
3.9
30.8
30.2
23.9
17.6
11.3
26.4
3.8
31.9
31.9
25.6
19.3
13.0
28.0
3.9
27.8
21.0
14.3
33.3
4.0
33.5
28.5
21.8
15.1
28.8
3.9
30.4
29.9
23.1
16.4
9.7
25.9
3.8
31.5
31.5
24.8
18.1
11.3
27.4
3.9
90
29.6
29.0
28.5
25.5
27.1
32.2
30.6
29.0
26.0
27.5
34.9
32.2
29.5
26.4
28.0
32.6
28.8
25.9
27.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
18.3
11.0
23.4
17.7
12.1
28.5
24.5
18.9
13.2
25.5
23.5
17.9
12.3
27.1
25.4
19.7
14.1
20.3
11.5
24.6
18.7
12.7
29.0
25.8
19.8
13.8
26.0
24.8
18.8
12.8
27.5
26.7
20.7
14.7
22.3
12.1
25.9
19.6
13.2
29.5
27.0
20.7
14.4
26.4
26.0
19.7
13.4
28.0
28.0
21.7
15.4
25.8
19.1
12.3
28.8
26.4
19.6
12.8
25.9
25.3
18.5
11.8
27.4
27.4
20.7
13.9
65
6.6
8.5
6.8
8.8
7.0
9.0
5.0
7.2
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
30
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ048 (4.0 Ton)
Air on
Evaporator Coil
CFM
1400
1500
1600
1700
1400
1500
1600
1700
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
56.8
54.4
51.9
48.9
47.3
56.7
54.3
51.9
48.9
47.3
56.6
54.2
51.8
48.8
47.2
55.2
52.8
49.7
48.1
2.9
2.8
2.7
2.8
2.7
2.9
2.8
2.7
2.8
2.7
2.9
2.8
2.7
2.8
2.7
2.8
2.8
2.8
2.8
26.1
35.7
45.3
48.9
47.3
26.8
36.7
46.6
48.9
47.3
27.6
37.7
47.9
48.8
47.2
38.2
48.7
49.7
48.1
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
53.5
50.5
47.5
44.5
44.6
53.9
50.9
47.9
44.8
44.9
54.4
51.3
48.3
45.2
45.3
51.4
48.4
45.3
45.4
3.5
3.5
3.6
3.5
3.5
3.5
3.5
3.6
3.5
3.5
3.5
3.5
3.6
3.5
3.5
3.5
3.6
3.5
3.5
27.0
35.1
43.3
44.5
44.6
28.0
36.5
44.9
44.8
44.9
29.0
37.8
46.6
45.2
45.3
38.8
47.7
45.3
45.4
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
21.1
16.2
55.1
3.2
30.7
25.8
20.8
52.4
3.2
40.4
35.4
30.4
25.5
49.7
3.2
46.6
42.1
37.1
32.2
27.2
46.7
3.2
47.3
45.5
40.5
35.5
30.6
46.0
3.1
21.7
16.6
55.3
3.2
31.6
26.5
21.4
52.6
3.2
41.5
36.4
31.3
26.2
49.9
3.2
47.7
43.3
38.2
33.1
28.0
46.9
3.2
47.3
46.4
41.7
36.6
31.5
46.1
3.1
22.3
17.1
55.5
3.2
32.5
27.2
22.0
52.8
3.2
42.7
37.4
32.2
26.9
50.1
3.2
48.8
44.5
39.2
34.0
28.8
47.0
3.2
47.2
47.2
42.8
37.6
32.3
46.3
3.1
32.9
27.5
22.1
53.3
3.2
43.2
37.8
32.4
27.0
50.6
3.2
49.7
45.1
39.8
34.4
29.0
47.5
3.2
48.1
48.1
43.1
37.7
32.3
46.7
3.1
95°F
21.7
16.4
51.0
4.0
29.9
24.6
19.4
47.6
4.0
38.1
32.8
27.5
22.3
44.2
4.0
44.0
40.9
35.6
30.3
25.1
41.1
4.0
44.3
41.5
36.2
30.9
25.7
41.7
4.0
22.5
17.0
51.4
4.0
31.0
25.5
20.0
48.0
4.0
39.5
34.0
28.5
23.0
44.5
4.0
44.6
42.3
36.9
31.4
25.9
41.4
4.0
44.8
43.0
37.5
32.0
26.5
42.0
4.0
23.3
17.6
51.8
4.0
32.1
26.4
20.7
48.3
4.0
40.9
35.2
29.4
23.7
44.9
4.0
45.2
43.8
38.1
32.4
26.7
41.7
4.0
45.3
44.4
38.7
33.0
27.3
42.3
4.0
33.0
27.1
21.2
48.3
4.0
42.0
36.1
30.2
24.3
44.8
4.0
45.3
44.7
38.8
33.0
27.1
41.7
4.0
45.4
45.0
39.1
33.3
27.4
42.2
4.0
90
26.5
35.4
44.3
46.7
46.0
27.4
36.6
45.8
46.9
46.1
28.3
37.8
47.2
47.0
46.3
38.5
48.2
47.5
46.7
26.8
34.1
41.4
41.1
41.7
28.3
35.5
42.7
41.4
42.0
29.9
36.9
44.0
41.7
42.3
37.8
44.4
41.7
42.2
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
21.4
16.3
30.3
25.2
20.1
39.2
34.1
29.0
23.9
45.3
41.5
36.4
31.3
45.9
43.5
38.4
33.2
22.1
16.8
31.3
26.0
20.7
40.5
35.2
29.9
24.6
46.2
42.8
37.5
32.2
46.1
44.9
39.6
34.3
22.8
17.3
32.3
26.8
21.3
41.8
36.3
30.8
25.3
47.0
44.1
38.7
33.2
46.3
46.3
40.8
35.3
32.9
27.3
21.7
42.6
36.9
31.3
25.7
47.5
44.9
39.3
33.7
46.7
46.7
41.1
35.5
105°F
20.6
15.3
28.8
23.5
18.1
36.9
31.6
26.3
21.0
40.8
38.1
32.8
27.4
41.3
38.4
33.1
27.8
21.5
15.9
30.0
24.4
18.8
38.4
32.9
27.3
21.7
41.3
39.6
34.0
28.4
41.8
39.9
34.3
28.8
22.3
16.5
31.1
25.3
19.5
39.9
34.1
28.3
22.5
41.7
41.0
35.2
29.4
42.3
41.4
35.6
29.8
31.8
25.8
19.9
40.8
34.8
28.8
22.8
41.7
41.4
35.4
29.4
42.2
41.9
35.9
29.9
65
26.1
28.1
26.9
29.0
27.7
29.8
28.1
29.9
22.1
22.5
22.9
23.2
23.6
24.0
23.4
23.9
31
294604-YTG-G-0511
DEQ048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1400
1500
1600
1700
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
48.6
44.7
40.8
37.7
38.7
48.9
45.0
41.1
38.0
39.0
49.3
45.3
41.4
38.3
39.3
45.1
41.2
38.1
39.1
4.5
4.5
4.4
4.4
4.4
4.5
4.5
4.4
4.4
4.4
4.5
4.5
4.4
4.4
4.4
4.5
4.4
4.4
4.5
26.7
33.1
39.5
37.7
38.7
28.7
34.6
40.5
38.0
39.0
30.7
36.1
41.4
38.3
39.3
36.8
41.2
38.1
39.1
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
19.6
14.2
46.1
5.0
27.7
22.3
16.9
41.8
4.9
35.8
30.4
25.1
19.7
37.5
4.8
37.7
35.3
29.9
24.5
19.1
34.4
4.9
38.2
35.4
30.0
24.6
19.2
35.8
4.9
20.5
14.8
46.4
5.0
28.9
23.3
17.6
42.1
4.9
37.4
31.7
26.1
20.4
37.8
4.8
38.0
36.8
31.1
25.5
19.8
34.6
4.9
38.8
36.9
31.2
25.6
19.9
36.0
4.9
21.3
15.4
46.7
5.0
30.1
24.2
18.3
42.4
4.9
38.9
33.0
27.1
21.2
38.0
4.8
38.3
38.3
32.3
26.4
20.5
34.8
4.9
39.3
38.4
32.4
26.5
20.6
36.3
4.9
30.7
24.6
18.5
42.0
5.0
39.7
33.6
27.5
21.4
37.7
4.9
38.1
38.1
32.0
25.9
19.8
34.5
4.9
39.1
38.7
32.6
26.5
20.4
35.9
4.9
90
27.0
32.1
37.5
34.4
35.8
29.7
33.6
37.8
34.6
36.0
32.4
35.2
38.0
34.8
36.3
35.8
37.7
34.5
35.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
18.5
13.1
26.6
21.2
15.7
34.7
29.3
23.8
18.4
34.4
32.5
27.1
21.6
35.2
32.3
26.9
21.4
19.4
13.7
27.9
22.2
16.4
36.4
30.6
24.9
19.1
34.6
33.7
28.3
22.5
35.7
33.8
28.1
22.4
20.3
14.3
29.2
23.1
17.1
38.0
32.0
25.9
19.9
34.8
34.8
29.5
23.4
36.3
35.3
29.3
23.3
29.6
23.4
17.2
37.7
32.3
26.1
19.9
34.5
34.5
28.6
22.3
35.9
35.6
29.4
23.1
65
16.2
16.0
16.8
16.6
17.4
17.2
16.1
16.9
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
32
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ060 (5.0 Ton)
Air on
Evaporator Coil
CFM
1500
1600
1650
1800
1900
1500
1600
1650
1800
1900
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
76.2
71.6
67.1
59.1
55.5
76.5
71.9
67.3
59.4
55.7
76.7
72.1
67.5
59.5
55.8
77.1
72.5
67.9
59.9
56.2
77.5
72.8
68.1
60.1
56.4
3.8
3.6
3.4
3.5
3.4
3.8
3.6
3.4
3.5
3.5
3.9
3.7
3.5
3.6
3.5
4.0
3.8
3.6
3.7
3.6
4.0
3.8
3.6
3.7
3.7
34.4
44.7
55.1
59.1
55.5
35.8
46.5
57.1
59.4
55.7
36.4
47.3
58.2
59.5
55.8
38.5
49.9
61.3
59.9
56.2
39.9
51.6
63.3
60.1
56.4
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
69.3
63.6
57.9
54.1
51.9
69.3
63.6
58.0
54.1
51.9
69.3
63.7
58.0
54.1
52.0
69.4
63.7
58.0
54.1
52.0
69.4
63.7
58.0
54.1
52.0
4.6
4.6
4.5
4.4
4.4
4.7
4.6
4.5
4.5
4.4
4.7
4.6
4.5
4.5
4.4
4.7
4.6
4.5
4.5
4.5
4.7
4.6
4.5
4.5
4.5
30.3
40.7
51.2
54.1
51.9
31.5
42.2
53.0
54.1
51.9
32.1
43.0
53.9
54.1
52.0
33.8
45.2
56.6
54.1
52.0
35.0
46.7
58.4
54.1
52.0
Johnson Controls Unitary Products
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
28.1
21.7
72.8
4.2
38.4
32.1
25.8
67.6
4.1
48.8
42.4
36.1
29.8
62.5
3.9
51.8
45.4
39.1
32.8
26.5
56.6
4.0
55.5
51.8
45.5
39.1
32.8
53.7
3.9
29.1
22.4
72.9
4.2
39.8
33.1
26.5
67.8
4.1
50.5
43.8
37.2
30.5
62.6
4.0
54.2
47.0
40.3
33.7
27.0
56.7
4.0
55.7
53.5
46.8
40.2
33.5
53.8
4.0
29.6
22.8
73.0
4.3
40.5
33.7
26.9
67.9
4.1
51.4
44.5
37.7
30.9
62.7
4.0
55.5
47.7
40.9
34.1
27.3
56.8
4.0
55.8
54.3
47.5
40.7
33.9
53.9
4.0
31.2
23.9
73.3
4.3
42.6
35.3
28.0
68.1
4.2
54.0
46.7
39.3
32.0
62.9
4.0
59.2
50.0
42.7
35.3
28.0
57.0
4.1
56.2
56.9
49.6
42.3
35.0
54.1
4.0
32.2
24.6
73.4
4.4
44.0
36.3
28.7
68.2
4.2
55.7
48.1
40.4
32.8
63.1
4.1
61.6
51.5
43.8
36.2
28.5
57.1
4.1
56.4
58.6
51.0
43.3
35.7
54.2
4.1
95°F
24.1
18.0
63.8
5.2
34.6
28.5
22.3
58.4
5.1
45.1
38.9
32.8
26.7
52.9
5.0
51.5
45.4
39.2
33.1
26.9
50.5
4.9
51.9
48.4
42.3
36.1
30.0
49.2
4.9
25.0
18.5
63.9
5.2
35.8
29.3
22.8
58.5
5.1
46.5
40.1
33.6
27.1
53.0
5.0
52.5
46.7
40.2
33.8
27.3
50.6
4.9
51.9
49.8
43.4
36.9
30.4
49.3
4.9
25.4
18.8
64.0
5.2
36.4
29.7
23.1
58.5
5.1
47.3
40.7
34.0
27.4
53.1
5.1
53.1
47.4
40.7
34.1
27.5
50.6
4.9
52.0
50.5
43.9
37.3
30.6
49.3
4.9
26.7
19.6
64.2
5.2
38.1
31.0
23.9
58.7
5.2
49.5
42.4
35.2
28.1
53.2
5.1
54.6
49.4
42.2
35.1
28.0
50.8
5.0
52.0
52.7
45.6
38.4
31.3
49.5
5.0
27.6
20.1
64.3
5.3
39.3
31.8
24.4
58.8
5.2
51.0
43.5
36.1
28.6
53.3
5.1
55.7
50.7
43.2
35.8
28.3
50.9
5.0
52.0
54.1
46.7
39.2
31.7
49.6
5.0
90
32.3
42.7
53.1
56.6
53.7
33.6
44.3
55.1
56.7
53.8
34.2
45.1
56.0
56.8
53.9
36.2
47.6
59.0
57.0
54.1
37.5
49.2
60.9
57.1
54.2
29.7
39.5
49.3
50.5
49.2
31.5
41.0
50.4
50.6
49.3
32.4
41.7
50.9
50.6
49.3
35.2
43.9
52.6
50.8
49.5
37.0
45.4
53.8
50.9
49.6
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
26.1
19.9
36.5
30.3
24.0
46.9
40.7
34.5
28.2
51.6
45.4
39.2
32.9
53.7
50.1
43.9
37.6
27.0
20.5
37.8
31.2
24.7
48.5
42.0
35.4
28.8
53.4
46.8
40.3
33.7
53.8
51.7
45.1
38.5
27.5
20.8
38.4
31.7
25.0
49.3
42.6
35.9
29.2
54.3
47.5
40.8
34.1
53.9
52.4
45.7
39.0
29.0
21.7
40.3
33.1
25.9
51.7
44.5
37.3
30.1
56.9
49.7
42.4
35.2
54.1
54.8
47.6
40.4
29.9
22.4
41.6
34.1
26.5
53.3
45.8
38.2
30.7
58.6
51.1
43.5
36.0
54.2
56.4
48.8
41.3
105°F
23.6
17.6
33.4
27.3
21.2
43.2
37.1
31.0
24.9
49.2
43.6
37.5
31.4
49.2
46.0
39.9
33.8
24.5
18.1
34.6
28.1
21.7
44.6
38.2
31.8
25.4
49.8
44.9
38.5
32.1
49.3
47.4
41.0
34.6
24.9
18.4
35.1
28.5
22.0
45.3
38.7
32.2
25.6
50.1
45.6
39.0
32.4
49.3
48.1
41.5
34.9
26.2
19.1
36.8
29.8
22.7
47.5
40.4
33.3
26.3
51.1
47.5
40.4
33.4
49.5
50.1
43.1
36.0
27.1
19.7
38.0
30.6
23.2
48.9
41.5
34.1
26.7
51.7
48.8
41.4
34.0
49.6
51.5
44.1
36.7
65
26.7
31.4
27.1
32.0
27.4
32.3
28.0
33.1
28.4
33.7
25.4
27.8
25.7
28.2
25.8
28.3
26.3
28.9
26.7
29.3
33
294604-YTG-G-0511
DEQ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM
1500
1600
1650
1800
1900
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
58.3
53.1
47.9
46.9
46.5
58.6
53.3
48.1
47.1
46.6
58.7
53.4
48.2
47.2
46.7
59.0
53.8
48.5
47.5
47.0
59.2
54.0
48.7
47.7
47.2
5.7
5.6
5.6
5.4
5.4
5.7
5.7
5.6
5.4
5.4
5.7
5.7
5.6
5.4
5.4
5.7
5.7
5.7
5.4
5.4
5.8
5.7
5.7
5.5
5.5
29.2
38.2
47.3
46.9
46.5
31.6
39.7
47.7
47.1
46.6
32.8
40.4
48.0
47.2
46.7
36.5
42.6
48.6
47.5
47.0
38.9
44.0
49.1
47.7
47.2
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
23.2
17.1
52.8
6.2
32.2
26.2
20.2
47.9
6.2
41.3
35.2
29.2
23.2
42.9
6.1
46.9
41.9
35.8
29.8
23.8
43.4
5.8
46.5
43.6
37.6
31.5
25.5
43.7
5.8
24.0
17.7
53.2
6.2
33.3
27.0
20.6
48.2
6.2
42.7
36.3
30.0
23.6
43.2
6.2
47.1
43.1
36.8
30.4
24.1
43.6
5.9
46.6
44.9
38.6
32.2
25.9
44.0
5.9
24.4
17.9
53.3
6.2
33.9
27.4
20.9
48.3
6.2
43.4
36.8
30.3
23.8
43.4
6.2
47.2
43.8
37.2
30.7
24.2
43.8
5.9
46.7
45.6
39.1
32.6
26.1
44.1
5.9
25.7
18.7
53.8
6.3
35.6
28.6
21.6
48.8
6.2
45.4
38.4
31.4
24.5
43.8
6.2
47.5
45.7
38.7
31.7
24.7
44.2
5.9
47.0
47.6
40.6
33.6
26.6
44.5
5.9
26.5
19.2
54.2
6.3
36.7
29.4
22.0
49.1
6.3
46.8
39.5
32.2
24.9
44.0
6.3
47.7
46.9
39.6
32.3
25.0
44.4
6.0
47.2
48.9
41.6
34.3
26.9
44.8
6.0
90
31.1
37.0
42.9
43.4
43.7
33.6
38.4
43.2
43.6
44.0
34.9
39.1
43.4
43.8
44.1
38.7
41.2
43.8
44.2
44.5
41.2
42.6
44.0
44.4
44.8
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
22.7
16.7
31.0
25.0
19.1
39.4
33.4
27.4
21.4
43.4
40.1
34.1
28.1
43.7
41.2
35.2
29.3
23.5
17.2
32.1
25.8
19.5
40.7
34.4
28.1
21.8
43.6
41.3
35.0
28.8
44.0
42.5
36.2
29.9
23.9
17.5
32.7
26.2
19.7
41.4
34.9
28.5
22.0
43.8
42.0
35.5
29.1
44.1
43.1
36.7
30.2
25.2
18.2
34.3
27.4
20.4
43.4
36.5
29.5
22.6
44.2
43.8
36.9
30.0
44.5
45.0
38.1
31.2
26.0
18.8
35.4
28.1
20.9
44.7
37.5
30.3
23.0
44.4
45.0
37.8
30.6
44.8
46.3
39.0
31.8
65
22.2
23.3
22.5
23.6
22.6
23.8
23.0
24.2
23.3
24.6
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
34
Johnson Controls Unitary Products
294604-YTG-G-0511
DEX024-048 Cooling Capacities
DEX024 (2.0 Ton)
Air on
Evaporator Coil
CFM
600
800
600
800
600
800
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
21.5
21.3
21.2
20.2
19.4
30.1
28.4
26.7
24.0
24.4
1.1
1.1
1.1
1.1
1.1
1.6
1.6
1.5
1.5
1.5
7.5
14.3
21.2
20.2
19.4
13.1
19.9
26.7
24.0
24.4
77
72
67
62
57
77
72
67
62
57
21.8
20.0
18.3
16.6
17.0
27.8
25.5
23.2
21.4
21.6
1.4
1.4
1.4
1.4
1.4
2.0
1.9
1.9
1.9
1.8
12.1
15.2
18.3
16.6
17.0
14.7
18.9
23.2
21.4
21.6
77
72
67
62
57
77
72
67
62
57
18.7
16.8
15.0
14.2
14.1
23.7
21.7
19.6
18.4
18.3
1.8
1.8
1.8
1.8
1.8
2.5
2.4
2.3
2.3
2.3
13.2
14.1
15.0
14.2
14.1
15.7
17.6
19.6
18.4
18.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
7.8
6.8
21.6
1.3
12.7
11.0
9.3
20.7
1.3
17.6
15.2
12.9
10.6
19.7
1.3
20.2
19.9
15.6
11.4
7.1
18.4
1.3
19.4
19.4
15.1
10.9
6.6
18.2
1.3
12.3
10.2
28.9
1.8
17.3
14.8
12.2
26.9
1.8
22.4
19.3
16.2
13.1
24.9
1.7
24.0
24.0
20.6
17.1
13.7
22.7
1.7
24.4
24.4
20.8
17.3
13.7
23.0
1.7
95°F
8.8
7.0
20.2
1.6
13.0
10.7
8.4
18.4
1.6
17.1
14.3
11.6
8.8
16.6
1.6
16.6
16.6
12.4
8.2
3.9
15.4
1.6
17.0
17.0
12.7
8.3
4.0
15.5
1.6
11.2
9.0
25.8
2.3
16.2
13.4
10.7
23.6
2.2
21.2
17.9
14.6
11.3
21.4
2.2
21.4
21.4
17.9
14.4
10.9
19.9
2.1
21.6
21.6
18.1
14.6
11.1
20.0
2.1
115°F
8.5
6.0
11.8
9.4
7.1
15.0
12.9
9.0
5.1
14.2
14.2
10.1
6.0
1.9
14.1
14.1
11.3
8.4
5.6
10.1
7.6
14.8
11.9
9.1
19.5
16.2
13.0
9.7
18.4
18.4
15.0
11.5
8.0
18.3
18.3
14.8
11.3
7.8
90
9.8
14.8
19.7
18.4
18.2
13.9
19.4
24.9
22.7
23.0
12.7
14.7
16.6
15.4
15.5
15.2
18.3
21.4
19.9
20.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
8.3
6.9
12.8
10.8
8.9
17.3
14.8
12.2
9.7
18.4
18.3
14.0
9.8
18.2
18.2
13.9
9.6
11.7
9.6
16.8
14.1
11.4
21.8
18.6
15.4
12.2
22.7
22.7
19.2
15.7
23.0
23.0
19.5
15.9
105°F
8.7
6.5
12.4
10.1
7.8
16.0
13.6
10.3
6.9
15.4
15.4
11.2
7.1
15.5
15.5
12.0
8.4
10.6
8.3
15.5
12.7
9.9
20.4
17.1
13.8
10.5
19.9
19.9
16.4
12.9
20.0
20.0
16.5
13.0
65
5.5
5.3
12.3
12.4
2.9
4.8
9.4
9.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Johnson Controls Unitary Products
35
294604-YTG-G-0511
DEX030 (2.5 Ton)
Air on
Evaporator Coil
CFM
675
1000
675
1000
675
1000
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
29.5
27.2
25.0
22.8
20.1
37.4
36.3
35.3
31.0
30.5
1.3
1.3
1.3
1.4
1.4
2.1
2.1
2.1
1.9
1.9
14.1
18.6
23.0
22.8
20.1
16.7
24.7
32.7
31.0
30.5
77
72
67
62
57
77
72
67
62
57
26.3
24.2
22.0
20.2
19.9
37.1
32.9
28.6
27.5
27.3
1.7
1.7
1.7
1.7
1.7
2.7
2.5
2.3
2.4
2.4
12.6
17.3
21.9
20.2
19.9
18.1
23.4
28.6
27.5
27.3
77
72
67
62
57
77
72
67
62
57
22.3
20.3
18.3
16.5
16.8
30.8
28.2
25.6
23.8
23.7
2.2
2.2
2.2
2.2
2.2
3.1
3.1
3.0
2.9
2.9
12.8
15.5
18.3
16.5
16.8
17.4
21.5
25.6
23.8
23.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
12.0
9.9
27.9
1.5
16.2
13.7
11.3
25.7
1.5
20.3
17.5
14.8
12.0
23.5
1.5
22.8
21.4
17.3
13.3
9.2
21.5
1.5
20.1
20.3
15.8
11.2
6.6
20.0
1.5
14.7
12.0
37.2
2.3
21.5
18.3
15.1
34.6
2.2
28.3
24.5
20.8
17.0
32.0
2.2
31.0
28.8
24.8
20.7
16.6
29.2
2.1
30.5
30.5
26.3
22.1
17.9
28.9
2.1
95°F
10.6
8.6
24.3
2.0
14.8
12.4
10.0
22.2
2.0
19.1
16.2
13.4
10.6
20.2
2.0
20.2
20.0
15.7
11.5
7.3
18.3
2.0
19.9
20.2
15.9
11.6
7.4
18.3
2.0
14.7
12.0
34.0
2.9
20.1
16.9
13.7
30.5
2.8
25.5
21.8
18.0
14.3
27.1
2.7
27.5
27.1
23.0
18.9
14.8
25.6
2.7
27.3
27.2
23.1
18.9
14.8
25.5
2.7
115°F
8.1
7.1
13.2
10.8
8.5
18.3
14.6
10.8
7.1
16.5
16.7
12.5
8.4
4.2
16.8
17.0
13.8
10.6
7.4
12.5
9.8
18.3
15.1
11.9
24.1
20.4
16.7
12.9
23.8
23.7
19.7
15.6
11.5
23.7
23.7
19.6
15.5
11.4
90
13.4
17.9
22.5
21.5
20.0
17.4
24.0
30.7
29.2
28.9
12.7
16.4
20.1
18.3
18.3
17.7
22.4
27.1
25.6
25.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
11.3
9.2
15.5
13.1
10.6
19.7
16.9
14.1
11.3
21.5
20.7
16.5
12.4
20.0
20.2
15.8
11.4
14.7
12.0
20.8
17.6
14.4
26.9
23.2
19.4
15.7
29.2
28.0
23.9
19.8
28.9
28.8
24.7
20.5
105°F
9.3
7.8
14.0
11.6
9.2
18.7
15.4
12.1
8.8
18.3
18.3
14.1
10.0
18.3
18.6
14.9
11.1
13.6
10.9
19.2
16.0
12.8
24.8
21.1
17.4
13.6
25.6
25.4
21.3
17.3
25.5
25.4
21.3
17.2
65
8.3
7.0
15.7
16.3
5.8
7.4
13.2
13.1
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
36
Johnson Controls Unitary Products
294604-YTG-G-0511
DEX036 (3.0 Ton)
Air on
Evaporator Coil
CFM
800
1150
800
1150
800
1150
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
36.6
31.9
27.2
26.6
23.8
48.0
44.5
41.1
37.5
37.6
1.5
1.5
1.5
1.5
1.5
2.4
2.4
2.4
2.3
2.3
17.4
21.9
26.5
26.6
23.8
23.1
30.7
38.3
37.5
37.6
77
72
67
62
57
77
72
67
62
57
31.4
28.4
25.4
23.5
23.5
44.2
40.1
36.0
33.9
33.7
1.9
1.9
1.9
1.9
1.9
3.2
3.1
2.9
2.9
2.9
16.9
21.2
25.4
23.5
23.5
21.3
28.6
36.0
33.9
33.7
77
72
67
62
57
77
72
67
62
57
26.1
23.8
21.6
19.8
20.3
38.0
34.8
31.6
29.2
29.6
2.4
2.4
2.4
2.4
2.4
3.8
3.8
3.7
3.6
3.6
16.2
18.9
21.6
19.8
20.3
21.2
26.4
31.6
29.2
29.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
15.3
12.6
34.0
1.7
18.9
15.9
12.9
30.1
1.7
22.6
19.2
15.7
12.3
26.3
1.7
26.6
25.4
21.2
17.0
12.8
25.1
1.7
23.8
24.0
19.8
15.5
11.2
23.6
1.7
19.5
15.9
46.1
2.7
26.6
22.5
18.4
42.3
2.7
33.7
29.1
24.5
19.9
38.5
2.6
37.5
36.4
31.4
26.4
21.4
35.7
2.5
37.6
37.8
32.6
27.4
22.3
35.7
2.5
95°F
13.6
10.7
28.7
2.2
18.0
14.9
11.8
26.1
2.2
22.5
19.1
15.7
12.3
23.5
2.2
23.5
23.1
19.0
14.9
10.8
21.6
2.2
23.5
23.2
19.0
14.9
10.7
21.9
2.2
17.8
14.3
41.1
3.4
24.6
20.6
16.5
37.4
3.3
31.4
26.8
22.3
17.7
33.8
3.2
33.9
32.9
28.0
23.0
18.0
31.5
3.2
33.7
33.5
28.5
23.4
18.3
31.7
3.1
115°F
10.5
8.3
15.8
12.8
9.8
21.2
17.3
13.5
9.6
19.8
19.8
15.7
11.6
7.6
20.3
20.1
16.5
12.9
9.3
15.2
11.7
22.4
18.3
14.3
29.6
25.0
20.5
15.9
29.2
29.2
24.4
19.7
14.9
29.6
29.5
24.7
19.8
15.0
90
17.2
21.6
25.9
25.1
23.6
22.2
29.7
37.1
35.7
35.7
16.5
20.0
23.5
21.6
21.9
21.3
27.5
33.8
31.5
31.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
14.4
11.7
18.5
15.4
12.3
22.5
19.1
15.7
12.3
25.1
24.2
20.1
15.9
23.6
23.6
19.4
15.2
18.7
15.1
25.6
21.5
17.5
32.6
28.0
23.4
18.8
35.7
34.7
29.7
24.7
35.7
35.7
30.5
25.4
105°F
12.0
9.5
16.9
13.9
10.8
21.9
18.2
14.6
11.0
21.6
21.4
17.3
13.3
21.9
21.7
17.8
13.9
16.5
13.0
23.5
19.4
15.4
30.5
25.9
21.4
16.8
31.5
31.1
26.2
21.3
31.7
31.5
26.6
21.6
65
11.8
11.0
19.7
20.3
9.2
10.0
16.5
16.6
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Johnson Controls Unitary Products
37
294604-YTG-G-0511
DEX042 (3.5 Ton)
Air on
Evaporator Coil
CFM
925
1400
925
1400
925
1400
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
40.2
37.1
34.0
30.5
29.4
61.7
55.5
49.4
44.5
46.0
1.9
1.9
1.9
1.9
1.8
3.4
3.1
3.1
3.0
2.9
21.0
26.3
31.6
30.5
29.4
29.1
37.9
46.7
44.5
46.0
77
72
67
62
57
77
72
67
62
57
34.4
31.8
29.2
25.7
25.6
51.7
47.6
43.5
39.2
39.8
2.4
2.3
2.3
2.4
2.4
3.8
3.7
3.5
3.5
3.5
17.5
23.3
29.1
25.7
25.6
25.3
34.3
43.3
39.2
39.8
77
72
67
62
57
77
72
67
62
57
28.9
26.2
23.4
21.3
21.5
43.2
39.4
35.6
33.2
33.6
2.9
2.9
2.9
2.9
2.9
4.5
4.4
4.3
4.2
4.2
17.9
20.6
23.4
21.3
21.5
24.6
30.1
35.6
33.2
33.6
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
17.4
13.7
37.3
2.2
22.4
18.5
14.7
34.5
2.1
27.5
23.3
19.2
15.1
31.6
2.1
30.5
27.7
23.2
18.8
14.3
28.1
2.1
29.4
29.4
24.8
20.1
15.5
27.5
2.1
24.8
20.4
56.7
3.3
32.7
27.6
22.4
51.6
3.3
40.7
34.7
28.8
22.8
46.5
3.3
44.5
42.4
36.2
30.1
23.9
41.8
3.2
46.0
45.5
39.2
32.8
26.4
42.9
3.1
95°F
14.0
10.6
31.7
2.6
19.5
15.7
11.9
29.0
2.6
24.9
20.8
16.7
12.6
26.3
2.6
25.7
25.3
20.9
16.5
12.1
23.5
2.6
25.6
25.6
21.0
16.5
11.9
23.6
2.7
20.8
16.3
47.4
4.1
29.2
24.1
19.0
43.5
4.0
37.6
31.9
26.2
20.5
39.5
3.9
39.2
39.2
33.0
26.8
20.7
36.2
3.8
39.8
39.8
33.6
27.4
21.2
36.7
3.8
115°F
11.5
8.6
17.1
13.5
9.9
22.6
18.4
14.3
10.1
21.3
21.3
16.9
12.6
8.2
21.5
21.4
17.2
13.0
8.8
16.5
12.6
25.4
20.7
16.0
34.2
28.7
23.3
17.8
33.2
33.3
27.2
21.2
15.2
33.6
33.8
27.8
21.9
15.9
90
19.2
24.8
30.3
28.1
27.5
27.2
36.1
45.0
41.8
42.9
17.7
21.9
26.2
23.5
23.6
24.9
32.2
39.4
36.2
36.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
15.7
12.2
20.9
17.1
13.3
26.2
22.1
18.0
13.8
28.1
26.5
22.0
17.6
27.5
27.5
22.9
18.3
22.8
18.4
31.0
25.8
20.7
39.1
33.3
27.5
21.7
41.8
40.8
34.6
28.4
42.9
42.7
36.4
30.1
105°F
12.8
9.6
18.3
14.6
10.9
23.8
19.6
15.5
11.4
23.5
23.3
18.9
14.5
23.6
23.5
19.1
14.7
18.7
14.5
27.3
22.4
17.5
35.9
30.3
24.7
19.1
36.2
36.2
30.1
24.0
36.7
36.8
30.7
24.6
65
13.2
13.7
22.3
23.8
10.1
10.4
17.9
18.5
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
38
Johnson Controls Unitary Products
294604-YTG-G-0511
DEX048 (4.0 Ton)
Air on
Evaporator Coil
CFM
1050
1600
1050
1600
1050
1600
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
47.3
43.7
40.1
35.9
35.5
66.0
61.0
56.0
51.7
50.8
2.2
2.1
2.1
2.1
2.1
3.6
3.5
3.4
3.3
3.2
23.6
30.5
37.3
35.9
35.5
30.9
42.4
53.9
51.7
50.8
77
72
67
62
57
77
72
67
62
57
42.1
38.5
35.0
31.8
31.3
58.1
53.6
49.0
45.6
44.9
2.7
2.7
2.7
2.7
2.7
4.2
4.1
4.0
3.9
3.9
21.6
28.3
35.0
31.8
31.3
29.0
39.0
49.0
45.6
44.9
77
72
67
62
57
77
72
67
62
57
34.3
31.6
28.9
26.4
26.7
48.7
44.4
40.2
37.7
37.9
3.4
3.4
3.3
3.3
3.3
4.9
4.8
4.8
4.6
4.6
22.6
25.7
28.9
26.4
26.7
31.7
36.0
40.2
37.7
37.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
19.9
16.0
44.7
2.4
26.1
21.8
17.5
41.1
2.4
32.3
27.6
22.9
18.1
37.5
2.4
35.9
33.2
28.9
24.6
20.3
33.8
2.4
35.5
35.5
30.9
26.3
21.6
33.4
2.4
26.5
21.0
62.1
3.8
36.3
30.1
24.0
57.3
3.7
46.0
39.2
32.4
25.7
52.5
3.6
51.7
48.9
41.6
34.2
26.8
48.7
3.5
50.8
50.7
43.0
35.4
27.7
47.8
3.5
95°F
17.3
13.2
38.2
3.1
23.8
19.4
14.9
35.1
3.0
30.4
25.6
20.7
15.9
31.9
3.0
31.8
30.9
26.4
22.0
17.5
29.1
3.0
31.3
31.3
26.8
22.2
17.7
29.0
3.0
22.5
17.1
53.4
4.5
32.9
26.8
20.7
49.0
4.4
43.4
36.5
29.7
22.9
44.6
4.3
45.6
45.5
38.0
30.5
23.0
41.6
4.2
44.9
44.8
37.4
29.9
22.4
41.4
4.2
115°F
15.4
10.8
21.3
16.9
12.6
27.2
23.1
18.9
14.7
26.4
26.4
22.0
17.5
13.0
26.7
26.7
21.6
16.5
11.4
19.6
14.4
29.9
23.8
17.8
40.2
33.3
26.4
19.5
37.7
37.7
30.2
22.8
15.3
37.9
37.9
30.6
23.4
16.2
90
22.6
29.4
36.1
33.8
33.4
29.9
40.7
51.5
48.7
47.8
22.1
27.0
31.9
29.1
29.0
30.3
37.5
44.6
41.6
41.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
18.6
14.6
25.0
20.6
16.2
31.4
26.6
21.8
17.0
33.8
32.1
27.7
23.3
33.4
33.4
28.8
24.2
24.5
19.1
34.6
28.5
22.3
44.7
37.9
31.1
24.3
48.7
47.2
39.8
32.4
47.8
47.7
40.2
32.6
105°F
16.4
12.0
22.6
18.2
13.7
28.8
24.3
19.8
15.3
29.1
28.7
24.2
19.7
29.0
29.0
24.2
19.4
21.0
15.7
31.4
25.3
19.3
41.8
34.9
28.1
21.2
41.6
41.6
34.1
26.6
41.4
41.3
34.0
26.7
65
18.9
19.7
24.9
25.1
15.3
14.6
19.2
19.3
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
Johnson Controls Unitary Products
39
294604-YTG-G-0511
DEY060 Cooling Capacities
DEY060 (5.0 Ton)
Air on
Evaporator Coil
CFM
1150
1750
1150
1750
1150
1750
WB
(°F)
Net
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
57
77
72
67
62
57
58.8
53.4
47.9
45.5
44.6
73.6
69.7
65.8
61.0
58.9
2.7
2.7
2.8
2.7
2.7
4.5
4.2
4.0
4.0
3.9
27.2
33.7
40.3
45.5
44.6
30.7
44.0
57.4
61.0
58.9
77
72
67
62
57
77
72
67
62
57
51.8
47.1
42.5
40.3
38.9
71.9
65.2
58.5
53.3
54.0
3.5
3.4
3.4
3.4
3.4
5.1
5.1
5.1
4.8
4.8
23.5
31.5
39.5
40.3
38.9
33.0
43.7
54.5
53.3
54.0
77
72
67
62
57
77
72
67
62
57
45.1
41.6
38.1
34.8
34.1
61.9
56.3
50.7
46.2
47.9
4.3
4.3
4.3
4.3
4.3
6.2
6.1
6.0
5.8
5.8
23.6
29.6
35.6
34.8
34.1
30.2
40.4
50.7
46.2
47.9
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
75°F
22.9
18.6
55.3
3.1
29.3
24.9
20.5
50.3
3.1
35.8
31.3
26.8
22.4
45.2
3.1
44.0
39.0
34.6
30.2
25.8
42.9
3.1
44.6
42.8
38.3
33.8
29.4
41.8
3.1
26.7
22.7
72.7
4.9
38.8
33.5
28.2
67.4
4.8
50.9
44.3
37.8
31.3
62.1
4.6
61.0
54.7
47.2
39.6
32.0
57.1
4.5
58.9
58.2
50.7
43.3
35.8
56.4
4.5
95°F
19.9
16.3
48.4
3.9
27.2
22.8
18.4
44.4
3.9
34.4
29.3
24.2
19.0
40.3
3.9
40.3
36.6
32.3
27.9
23.6
37.6
3.9
38.9
37.7
33.2
28.6
24.1
36.5
3.8
27.3
21.6
66.9
5.8
37.5
31.3
25.1
60.7
5.7
47.7
41.0
34.2
27.5
54.6
5.7
53.3
49.6
42.7
35.7
28.7
49.7
5.5
54.0
53.0
45.2
37.5
29.8
50.9
5.5
115°F
18.7
13.8
25.1
20.6
16.2
31.6
27.5
23.4
19.4
34.8
33.7
29.3
25.0
20.7
34.1
33.0
27.5
22.1
16.7
23.6
18.0
34.2
28.0
21.8
44.8
38.0
31.1
24.3
46.2
46.2
38.8
31.3
23.9
47.9
46.7
39.1
31.5
23.9
90
25.4
32.6
39.9
42.9
41.8
31.8
43.9
55.9
57.1
56.4
23.6
30.6
37.6
37.6
36.5
31.6
42.1
52.6
49.7
50.9
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
21.4
17.4
28.2
23.9
19.5
35.1
30.3
25.5
20.7
42.2
37.8
33.4
29.1
41.8
40.3
35.7
31.2
27.0
22.1
38.1
32.4
26.6
49.3
42.6
36.0
29.4
57.1
52.2
44.9
37.6
56.4
55.6
48.0
40.4
105°F
19.3
15.0
26.1
21.7
17.3
33.0
28.4
23.8
19.2
37.6
35.1
30.8
26.5
36.5
35.3
30.4
25.4
25.4
19.8
35.9
29.6
23.4
46.3
39.5
32.7
25.9
49.7
47.9
40.7
33.5
50.9
49.9
42.2
34.5
65
24.7
26.7
30.3
32.8
22.1
20.4
26.3
26.8
1. These capacities are Net Capacities.
2. These ratings include the compressor, condenser fan and supply air blower motors.
40
Johnson Controls Unitary Products
294604-YTG-G-0511
Airflow Performance
Side Duct Application
DEY/DEX024-060
Size
(Tons)
Model
Mode
Low
Cool
024
(2.0)
DEX
High
Heat
Low
Cool
030
(2.5)
DEX
High
Heat
Low
Cool
036
(3.0)
DEX
High
Heat
Low
Cool
042
(3.5)
DEX
High
Heat
Low
Cool
048
(4.0)
DEX
High
Heat
Low
Cool
060
(5.0)
DEY
High
Heat
Thermostat
Input
Speed
Tap
CFM
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
600
450
525
675
800
600
700
900
800
720
880
670
620
720
770
1000
925
1075
1150
1000
900
1100
1000
900
750
830
980
1200
1000
1100
1300
1200
1080
1275
1200
920
790
850
980
1400
1200
1300
1500
1225
1100
1350
1225
1050
920
980
1120
1600
1400
1500
1700
1600
1440
1760
1600
1170
1110
1210
1270
1750
1650
1800
1900
1900
1975
2150
2070
Johnson Controls Unitary Products
External Static Pressure (Inch Water Gauge)
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
57
74
91
108
126
143
161
179
197
39
54
69
84
100
117
134
152
171
47
63
79
95
112
129
146
164
182
71
88
106
124
142
161
179
198
216
99
117
137
156
176
196
217
237
258
57
74
91
108
126
143
161
179
197
76
94
112
130
148
167
186
205
224
126
146
166
187
208
231
253
277
300
99
117
137
156
80
98
116
135
120
140
160
180
61
78
95
113
130
148
166
184
201
54
70
87
104
121
138
156
173
191
70
88
106
124
142
160
178
197
215
81
99
118
136
155
174
193
213
232
159
179
200
222
246
270
296
323
350
129
148
169
190
211
233
256
280
304
194
214
236
260
285
312
341
371
403
233
254
277
302
330
360
392
427
463
159
179
200
222
120
139
159
180
206
227
249
274
159
179
200
222
120
139
159
180
201
222
244
267
291
76
94
113
131
150
168
187
206
225
97
116
135
155
174
194
215
236
256
150
170
191
213
236
260
285
311
337
261
283
306
333
362
394
429
467
507
159
179
200
222
246
270
296
323
350
206
227
249
274
300
328
357
389
422
325
346
372
401
434
471
511
556
604
261
283
306
333
196
217
239
263
308
330
355
383
261
283
306
333
139
166
195
224
255
286
319
352
386
100
124
149
176
205
235
266
299
333
117
143
170
198
227
257
289
322
356
159
188
218
249
281
313
346
379
414
338
383
426
468
509
549
589
627
664
245
281
318
354
390
426
462
497
533
290
330
370
409
447
485
523
560
596
391
439
486
532
576
618
660
700
739
256
293
330
367
203
237
270
304
314
356
397
438
256
293
330
367
184
216
248
280
313
346
380
414
449
139
166
195
224
255
286
319
352
386
159
188
218
249
281
313
346
379
414
211
245
279
313
348
382
417
452
486
448
500
551
600
647
693
736
779
819
338
383
426
468
509
549
589
627
664
391
439
486
532
576
618
660
700
739
508
565
620
672
723
772
818
863
905
448
500
551
600
647
359
405
449
493
535
546
606
663
718
771
448
500
551
600
647
235
283
328
368
404
435
463
485
505
205
258
304
345
381
410
434
451
465
255
301
344
384
420
454
483
509
533
286
329
371
410
448
483
516
547
576
559
608
658
710
762
815
870
925
981
498
542
588
634
683
732
783
835
888
590
643
696
750
805
860
916
973
1030
654
715
775
836
895
955
1013 1072
654
715
775
836
895
703
772
839
904
968
823
913
999
1079 1154
767
847
923
997
1066
-
41
294604-YTG-G-0511
DEQ024-060
Size
(Tons)
Model
Thermostat
Input
Speed
Tap
CFM
Y1
Y1
Y1
Y1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
800
600
700
900
800
720
880
1000
925
1075
1150
1000
900
1100
1000
1200
1000
1100
1300
1200
1080
1275
1200
1400
1200
1300
1500
1225
1100
1350
1225
1600
1400
1500
1700
1600
1440
1760
1600
1500
1650
1800
1900
1900
1975
2150
2070
Unit Speed
0.2
W
87
97
131
170
110
153
214
269
168
215
255
301
354
221
299
376
466
-
Mode
Cool
024
(2.0)
DEQ
Heat
Cool
030
(2.5)
DEQ
Heat
Cool
036
(3.0)
DEQ
Heat
Cool
042
(3.5)
DEQ
Heat
Cool
048
(4.0)
DEQ
Heat
Cool
060
(5.0)
DEQ
Heat
External Static Pressure (Inch Water Gauge)
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
99
117
137
156
176
196
217
237
258
57
74
91
108
126
143
161
179
197
76
94
112
130
148
167
186
205
224
126
146
166
187
208
231
253
277
300
99
117
137
156
80
98
116
135
120
140
160
180
159
179
200
222
246
270
296
323
350
129
148
169
190
211
233
256
280
304
194
214
236
260
285
312
341
371
403
233
254
277
302
330
360
392
427
463
159
179
200
222
120
139
159
180
206
227
249
274
159
179
200
222
261
283
306
333
362
394
429
467
507
159
179
200
222
246
270
296
323
350
206
227
249
274
300
328
357
389
422
325
346
372
401
434
471
511
556
604
261
283
306
333
196
217
239
263
308
330
355
383
261
283
306
333
338
383
426
468
509
549
589
627
664
245
281
318
354
390
426
462
497
533
290
330
370
409
447
485
523
560
596
391
439
486
532
576
618
660
700
739
256
293
330
367
203
237
270
304
314
356
397
438
256
293
330
367
408
461
512
562
610
657
703
747
790
290
334
378
422
465
508
550
592
633
349
397
445
492
537
582
626
669
711
467
524
579
632
683
732
779
825
868
408
461
512
562
610
657
313
359
405
450
494
537
503
562
619
674
726
777
408
461
512
562
610
657
404
438
475
512
555
597
644
692
728
498
542
588
634
683
732
783
835
888
590
643
696
750
805
860
916
973
1030
654
715
775
836
895
955
1013 1072
654
715
775
836
895
703
772
839
904
968
823
913
999
1079 1154
767
847
923
997
1066
-
DEZ024-060
Size
(Tons)
Model
024
(2.0)
DEZ
030
(2.5)
DEZ
036
(3.0)
DEZ
042
(3.5)
DEZ
42
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
SCFM
726
768
883
990
828
953
1091
1189
966
1148
1258
1361
1458
1241
1406
1536
1656
-
RPM
632
651
704
755
673
735
807
861
771
763
766
778
797
702
759
808
858
-
SCFM
629
679
812
934
759
894
1041
1144
1235
890
1062
1167
1267
1362
1151
1325
1461
1584
1687
External Static Pressure (Inch Water Gauge)
0.4
0.6
0.8
W
RPM SCFM
W
RPM SCFM
W
99
739
110
754
147
797
736
162
889
651
177
187
839
868
202
920
791
216
985
245
952
913
257
125
771
172
823
824
189
909
234
883
983
253
958
910
269
288
927
1091
305
994
1027
318
347
970
1186
360
1028 1125
368
186
860
237
841
975
259
918
278
839
1075
301
911
980
325
325
845
1170
349
913
1070
372
379
859
1262
402
923
1156
423
245
778
1058
268
853
324
826
1242
349
893
1158
373
403
869
1384
427
928
1305
449
492
912
1509
515
966
1430
533
590
955
1611
610
1004 1527
620
RPM
979
1000
1022
1033
1061
1086
983
981
986
959
988
1019
1051
SCFM
696
813
785
912
1007
964
1040
1072
1223
1344
1428
1.0
W
227
261
273
316
352
393
436
396
468
542
615
RPM
1078
1090
1106
1132
1147
1048
1048
1025
1046
1070
1097
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ024-060 (Continued)
Size
(Tons)
Model
048
(4.0)
DEZ
060
(5.0)
DEZ
Unit Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
SCFM
1287
1596
1705
1806
1898
1580
1650
1854
2120
2214
0.2
W
222
397
476
561
652
394
448
605
856
968
RPM
695
817
858
895
929
859
888
972
1073
1104
SCFM
1513
1624
1726
1819
1504
1579
1783
2021
2089
External Static Pressure (Inch Water Gauge)
0.4
0.6
0.8
W
RPM SCFM
W
RPM SCFM
W
422
875
1432
447
934
1354
474
501
911
1545
526
966
1466
549
587
945
1646
610
995
1564
628
679
977
1736
698
1023 1646
709
420
917
476
945
1499
478
1003 1401
494
629
1020 1703
646
1065 1605
648
840
1102 1908
815
1127 1769
772
918
1121 1949
859
1136 1785
787
RPM
995
1021
1046
1069
1049
1104
1148
1148
SCFM
1276
1386
1476
1547
1528
1567
1576
1.0
W
501
571
639
706
659
685
689
RPM
1058
1077
1096
1112
1146
1154
1154
Bottom Duct Application
DEY/DEX024-060
Size
(Tons)
Model
Mode
Low
Cool
024
(2.0)
DEX
High
Heat
Low
Cool
030
(2.5)
DEX
High
Heat
Low
Cool
036
(3.0)
DEX
High
Heat
Low
Cool
042
(3.5)
DEX
High
Heat
Low
Cool
048
(4.0)
DEX
High
Heat
Thermostat
Input
Speed
Tap
CFM
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
600
450
525
675
800
600
700
900
800
720
880
670
620
720
770
1000
925
1075
1150
1000
900
1100
1000
900
750
830
980
1200
1000
1100
1300
1200
1080
1275
1200
920
790
850
980
1400
1200
1300
1500
1225
1100
1350
1225
1050
920
980
1120
1600
1400
1500
1700
1600
1440
1760
1600
Johnson Controls Unitary Products
External Static Pressure (Inch Water Gauge)
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
57
74
91
108
126
143
161
179
197
39
54
69
84
100
117
134
152
171
47
63
79
95
112
129
146
164
182
71
88
106
124
142
161
179
198
216
99
117
137
156
176
196
217
237
258
57
74
91
108
126
143
161
179
197
76
94
112
130
148
167
186
205
224
126
146
166
187
208
231
253
277
300
99
117
137
156
80
98
116
135
120
140
160
180
61
78
95
113
130
148
166
184
201
54
70
87
104
121
138
156
173
191
70
88
106
124
142
160
178
197
215
81
99
118
136
155
174
193
213
232
159
179
200
222
246
270
296
323
350
129
148
169
190
211
233
256
280
304
194
214
236
260
285
312
341
371
403
233
254
277
302
330
360
392
427
463
159
179
200
222
120
139
159
180
206
227
249
274
159
179
200
222
120
139
159
180
201
222
244
267
291
76
94
113
131
150
168
187
206
225
97
116
135
155
174
194
215
236
256
150
170
191
213
236
260
285
311
337
261
283
306
333
362
394
429
467
507
159
179
200
222
246
270
296
323
350
206
227
249
274
300
328
357
389
422
325
346
372
401
434
471
511
556
604
261
283
306
333
196
217
239
263
308
330
355
383
261
283
306
333
139
166
195
224
255
286
319
352
386
100
124
149
176
205
235
266
299
333
117
143
170
198
227
257
289
322
356
159
188
218
249
281
313
346
379
414
338
383
426
468
509
549
589
627
664
245
281
318
354
390
426
462
497
533
290
330
370
409
447
485
523
560
596
391
439
486
532
576
618
660
700
739
256
293
330
367
203
237
270
304
314
356
397
438
256
293
330
367
184
216
248
280
313
346
380
414
449
139
166
195
224
255
286
319
352
386
159
188
218
249
281
313
346
379
414
211
245
279
313
348
382
417
452
486
448
500
551
600
647
693
736
779
819
338
383
426
468
509
549
589
627
664
391
439
486
532
576
618
660
700
739
508
565
620
672
723
772
818
863
905
448
500
551
600
647
359
405
449
493
535
546
606
663
718
771
448
500
551
600
647
-
43
294604-YTG-G-0511
DEY/DEX024-060 (Continued)
Size
(Tons)
Model
Mode
Thermostat
Input
Speed
Tap
CFM
Y1
Y1
Y1
Y1
Y1+Y2
Y1+Y2
Y1+Y2
Y1+Y2
W1
W1
W1
W1
COOL-A
COOL-B
COOL-C
COOL-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
1170
1110
1210
1270
1750
1650
1800
1900
1900
1975
2150
2070
Low
Cool
060
(5.0)
DEY
High
Heat
External Static Pressure (Inch Water Gauge)
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
235
283
328
368
404
435
463
485
505
205
258
304
345
381
410
434
451
465
255
301
344
384
420
454
483
509
533
286
329
371
410
448
483
516
547
576
559
608
658
710
762
815
870
925
981
498
542
588
634
683
732
783
835
888
590
643
696
750
805
860
916
973
1030
654
715
775
836
895
955
1013 1072
654
715
775
836
895
703
772
839
904
968
823
913
999
1079 1154
767
847
923
997
1066
-
DEQ024-060
Size
(Tons)
Model
Mode
Cool
024
(2.0)
DEQ
Heat
Cool
030
(2.5)
DEQ
Heat
Cool
036
(3.0)
DEQ
Heat
Cool
042
(3.5)
DEQ
Heat
Cool
048
(4.0)
DEQ
Heat
Cool
060
(5.0)
DEQ
Heat
44
Thermostat
Input
Speed
Tap
CFM
Y1
Y1
Y1
Y1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
Y1
Y1
Y1
Y1
W1
W1
W1
W1
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
COOL-A
COOL-B
COOL-C
COOL-D
HEAT-A
HEAT-B
HEAT-C
HEAT-D
800
600
700
900
800
720
880
1000
925
1075
1150
1000
900
1100
1000
1200
1000
1100
1300
1200
1080
1275
1200
1400
1200
1300
1500
1225
1100
1350
1225
1600
1400
1500
1700
1600
1440
1760
1600
1500
1650
1800
1900
1900
1975
2150
2070
External Static Pressure (Inch Water Gauge)
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
99
117
137
156
176
196
217
237
258
57
74
91
108
126
143
161
179
197
76
94
112
130
148
167
186
205
224
126
146
166
187
208
231
253
277
300
99
117
137
156
80
98
116
135
120
140
160
180
159
179
200
222
246
270
296
323
350
129
148
169
190
211
233
256
280
304
194
214
236
260
285
312
341
371
403
233
254
277
302
330
360
392
427
463
159
179
200
222
120
139
159
180
206
227
249
274
159
179
200
222
261
283
306
333
362
394
429
467
507
159
179
200
222
246
270
296
323
350
206
227
249
274
300
328
357
389
422
325
346
372
401
434
471
511
556
604
261
283
306
333
196
217
239
263
308
330
355
383
261
283
306
333
338
383
426
468
509
549
589
627
664
245
281
318
354
390
426
462
497
533
290
330
370
409
447
485
523
560
596
391
439
486
532
576
618
660
700
739
256
293
330
367
203
237
270
304
314
356
397
438
256
293
330
367
408
461
512
562
610
657
703
747
790
290
334
378
422
465
508
550
592
633
349
397
445
492
537
582
626
669
711
467
524
579
632
683
732
779
825
868
408
461
512
562
610
657
313
359
405
450
494
537
503
562
619
674
726
777
408
461
512
562
610
657
404
438
475
512
555
597
644
692
728
498
542
588
634
683
732
783
835
888
590
643
696
750
805
860
916
973
1030
654
715
775
836
895
955
1013 1072
654
715
775
836
895
703
772
839
904
968
823
913
999
1079 1154
767
847
923
997
1066
-
Johnson Controls Unitary Products
294604-YTG-G-0511
DEZ024-060
Size
(Tons)
Model
024
(2.0)
DEZ
030
(2.5)
DEZ
036
(3.0)
DEZ
042
(3.5)
DEZ
048
(4.0)
DEZ
060
(5.0)
DEZ
Unit Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
SCFM
726
768
883
990
828
953
1091
1189
966
1148
1258
1361
1458
1241
1406
1536
1656
1287
1596
1705
1806
1898
1580
1650
1854
2120
2214
Johnson Controls Unitary Products
0.2
W
87
97
131
170
110
153
214
269
168
215
255
301
354
221
299
376
466
222
397
476
561
652
394
448
605
856
968
RPM
632
651
704
755
673
735
807
861
771
763
766
778
797
702
759
808
858
695
817
858
895
929
859
888
972
1073
1104
SCFM
629
679
812
934
759
894
1041
1144
1235
890
1062
1167
1267
1362
1151
1325
1461
1584
1687
1513
1624
1726
1819
1504
1579
1783
2021
2089
External Static Pressure (Inch Water Gauge)
0.4
0.6
0.8
W
RPM SCFM
W
RPM SCFM
W
99
739
110
754
147
797
736
162
889
651
177
187
839
868
202
920
791
216
985
245
952
913
257
125
771
172
823
824
189
909
234
883
983
253
958
910
269
288
927
1091
305
994
1027
318
347
970
1186
360
1028 1125
368
186
860
237
841
975
259
918
278
839
1075
301
911
980
325
325
845
1170
349
913
1070
372
379
859
1262
402
923
1156
423
245
778
1058
268
853
324
826
1242
349
893
1158
373
403
869
1384
427
928
1305
449
492
912
1509
515
966
1430
533
590
955
1611
610
1004 1527
620
422
875
1432
447
934
1354
474
501
911
1545
526
966
1466
549
587
945
1646
610
995
1564
628
679
977
1736
698
1023 1646
709
420
917
476
945
1499
478
1003 1401
494
629
1020 1703
646
1065 1605
648
840
1102 1908
815
1127 1769
772
918
1121 1949
859
1136 1785
787
RPM
979
1000
1022
1033
1061
1086
983
981
986
959
988
1019
1051
995
1021
1046
1069
1049
1104
1148
1148
SCFM
696
813
785
912
1007
964
1040
1072
1223
1344
1428
1276
1386
1476
1547
1528
1567
1576
1.0
W
227
261
273
316
352
393
436
396
468
542
615
501
571
639
706
659
685
689
RPM
1078
1090
1106
1132
1147
1048
1048
1025
1046
1070
1097
1058
1077
1096
1112
1146
1154
1154
45
294604-YTG-G-0511
Additional Static Resistance
Size
(Tons)
Model
024
(2.0)
DEZ
DEQ
DEX
030
(2.5)
DEZ
DEQ
DEX
036
(3.0)
DEZ
DEQ
DEX
042
(3.5)
DEZ
DEQ
DEX
048
(4.0)
DEZ
DEQ
DEX
060
(5.0)
DEZ
DEQ
DEX
CFM
Wet Indoor Coil
Economizer1
Filter/Frame Kit
Electric Heat
500
600
700
800
900
1000
1100
1200
700
800
900
1000
1100
1200
1300
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.01
0.01
0.01
0.02
0.03
0.04
0.07
0.01
0.01
0.01
0.02
0.03
0.04
0.04
0.04
0.03
0.04
0.04
0.04
0.05
0.06
0.03
0.04
0.04
0.04
0.04
0.04
0.05
0.05
0.06
0.07
0.03
0.04
0.04
0.04
0.04
0.04
0.05
0.05
0.06
0.07
0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.01
0.02
0.03
0.04
0.05
0.06
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.08
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.08
0.01
0.02
0.02
0.02
0.02
0.02
0.03
0.03
0.02
0.02
0.02
0.02
0.03
0.03
0.17
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.03
0.04
0.05
0.03
0.03
0.03
0.03
0.04
0.05
0.05
0.06
0.06
0.07
0.03
0.03
0.03
0.03
0.04
0.05
0.05
0.06
0.06
0.07
0.02
0.03
0.03
0.03
0.04
0.04
0.05
0.06
0.03
0.03
0.04
0.04
0.05
0.06
0.03
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.05
0.06
0.07
0.08
0.09
0.10
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.11
0.11
0.12
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.11
0.11
0.12
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
46
Johnson Controls Unitary Products
294604-YTG-G-0511
Electric Heat Minimum Supply Air
Size
(Tons)
Model
Voltage
DEZ
DEQ
DEX
DEZ
DEQ
DEX
024
(2.0)
030
(2.5)
DEX
036
(3.0)
DEZ
DEQ
DEX
042
(3.5)
DEZ
DEQ
DEX
048
(4.0)
DEZ
DEQ
DEY
060
(5.0)
DEZ
DEQ
Minimum Supply Air (CFM)
Heater kW
10.0
15.0
5.0
7.5
20.0
25.0
208/230-1-60
630
630
800
-
-
-
208/230-1-60
630
630
800
800
-
-
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
575-3-60
1070
1070
1070
1070
1070
1070
1070
1225
1225
1225
1225
1225
1225
1225
-
1070
1070
1070
1070
1070
1070
1070
1225
1225
1225
1225
1225
1225
1225
-
1070
1070
1070
1070
1070
1070
1070
1225
1225
1225
1225
1225
1225
1225
1200
1200
1200
1200
1200
1200
1200
1615
1615
1615
1615
1615
1615
1615
1070
1070
1070
1070
1070
1070
1070
1225
1225
1225
1225
1225
1225
1225
1430
1430
1430
1430
1430
1430
1430
1615
1615
1615
1615
1615
1615
1615
1430
1430
1430
1430
1430
1430
1430
1955
1955
1955
1955
1955
1955
1955
1430
1430
1430
1430
1430
1430
1430
1955
1955
1955
1955
1955
1955
1955
Indoor Blower Specifications
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)
Model
DEZ
DEQ
DEX
DEZ
DEQ
DEX
DEZ
DEQ
DEX
DEZ
DEQ
DEX
DEZ
DEQ
DEX
DEZ
DEQ
DEX
HP
RPM
Motor
Eff.
SF
Frame
1/2
Variable
0.8
1.0
48
1/2
Variable
0.8
1.0
48
1/2
Variable
0.8
1.0
48
3/4
Variable
0.8
1.0
48
3/4
Variable
0.8
1.0
48
1
Variable
0.8
1.0
48
Johnson Controls Unitary Products
47
294604-YTG-G-0511
Electric Heat Multipliers
Voltage
Nominal
Applied
208
230
460
575
240
480
600
kW Capacity Multipliers1
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Outdoor Sound Power Levels
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)
Model
Sound Rating1
dB (A)
DEZ, DEQ
DEX
DEZ, DEQ
DEX
DEZ, DEQ
DEX
DEZ, DEQ
DEX
DEZ, DEQ
DEX
DEZ, DEQ
DEY
80
73
79
77
74
78
74
76
80
79
80
79
125
72
61.5
66
60
65
63
64
67.5
71
71.5
68
68
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
70
65
76
66
72
64.5
68.5
66.5
62
60
67
67
76
75
66
62.5
64.5
75.5
62.5
59.5
64
67
68
67
65
65
76
73
64.5
62.5
65
68
69
63
59
68.5
69.5
69
66
63.5
72
74
73
69
67
69.5
71.5
75.5
68
67
71
74
73
72
72
70
73.5
73
68.5
66.5
8000
58
54
57
58.5
59
60
57
60
62
62
60
62.5
1. Rated in accordance with ARI 270 standard.
48
Johnson Controls Unitary Products
294604-YTG-G-0511
Electrical Data
DEZ024-060 Cooling Only With/Without Electric Heat
Size
(Tons)
Volt
OD Fan Supply
Motors Blower
(each) Motor
RLA LRA MCC FLA
FLA
Compressors
(each)
024
(2.0)
208/230-1-60 8.3
43
13
1.3
4.1
030
(2.5)
208/230-1-60 13.1
74
21
1.3
4.1
208/230-1-60 14.7
74
23
1.3
4.1
208/230-3-60 9.1
68
14
1.3
4.1
036
(3.0)
042
(3.5)
460-3-60
4.5
34
7
0.8
4.1
575-3-60
3.8
28
6
0.6
6.0
208/230-1-60 15.7
88
25
1.7
6.0
208/230-3-60 9.3
68
15
1.7
6.0
460-3-60
5.1
34
8
1.0
6.0
575-3-60
3.8
28
6
0.8
6.0
208/230-1-60 16.8 115
25
1.7
6.0
208/230-3-60 11.2 120
18
1.7
6.0
048
(4.0)
460-3-60
5.1
50
8
1.0
6.0
575-3-60
4.5
40
7
0.8
6.0
Johnson Controls Unitary Products
Electric Heat Option
Model
None
2NH04500506
2NH04500706
2NH04501006
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04501025
2NH04501525
None
2NH04501046
2NH04501546
None
2NH04501058
2NH04501558
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04501025
2NH04501525
None
2NH04501046
2NH04501546
None
2NH04501058
2NH04501558
None
2NH04501006
2NH04501506
2NH04502006
2NH04502506
None
2NH04501025
2NH04501525
2NH04502025
2NH04502525
None
2NH04501046
2NH04501546
2NH04502046
2NH04502546
None
2NH04501058
2NH04501558
2NH04502058
2NH04502558
MCA1
(Amps)
kW
Stages
Amps
15.8
3.8 / 5
1
18.1 / 20.8 27.7 / 31.2
5.6 / 7.5
2
27.1 / 31.3
39 / 44.2
7.5 / 10
2
36.1 / 41.7 50.3 / 57.2
21.8
3.8 / 5
1
18.1 / 20.8 27.7 / 31.2
5.6 / 7.5
2
27.1 / 31.3
39 / 44.2
7.5 / 10
2
36.1 / 41.7 50.3 / 57.2
11.3 / 15
2
54.2 / 62.5 72.8 / 83.3
23.8
3.8 / 5
1
18.1 / 20.8 27.7 / 31.2
5.6 / 7.5
2
27.1 / 31.3
39 / 44.2
7.5 / 10
2
36.1 / 41.7 50.3 / 57.2
11.3 / 15
2
54.2 / 62.5 72.8 / 83.3
16.8
7.5 / 10
1
20.8 / 24.1 31.2 / 35.2
11.3 / 15
1
31.3 / 36.1 44.2 / 50.2
10.5
10
1
12
20.2
15
1
18
27.7
11.9
10
1
9.6
19.5
15
1
14.4
25.5
27.3
3.8 / 5
1
18.1 / 20.8 30.1 / 33.5
5.6 / 7.5
2
27.1 / 31.3 41.4 / 46.6
7.5 / 10
2
36.1 / 41.7 52.6 / 59.6
11.3 / 15
2
54.2 / 62.5 75.2 / 85.6
19.3
7.5 / 10
1
20.8 / 24.1 33.6 / 37.6
11.3 / 15
1
31.3 / 36.1 46.6 / 52.6
13.6
10
1
12
22.5
15
1
18
30.1
12.1
10
1
9.6
19.5
15
1
14.4
25.5
28.7
7.5 / 10
2
36.1 / 41.7 52.6 / 59.6
11.3 / 15
2
54.2 / 62.5 75.2 / 85.6
15 / 20
2
72.2 / 83.3 97.8 / 111.7
18.8 / 25
2
90.3 / 104.2 120.3 / 137.7
21.7
7.5 / 10
1
20.8 / 24.1 33.6 / 37.6
11.3 / 15
1
31.3 / 36.1 46.6 / 52.6
15 / 20
2
41.7 / 48.1 59.6 / 67.6
18.8 / 25
2
52.1 / 60.1 72.7 / 82.7
13.6
10
1
12
22.5
15
1
18
30.1
20
2
24.1
37.6
25
2
30.1
45.1
12.8
10
1
9.6
19.5
15
1
14.4
25.5
20
2
19.2
31.6
25
2
24.1
37.6
Max Fuse2/
Breaker3 Size
(Amps)
20
30 / 35
40 / 45
60 / 60
30
30 / 35
40 / 45
60 / 60
80 / 90
30
35 / 35
40 / 45
60 / 60
80 / 90
25
35 / 40
45 / 60
15
25
30
15
20
30
35
40 / 40
45 / 50
60 / 60
80 / 90
25
35 / 40
50 / 60
15
25
35
15
20
30
35
60 / 60
80 / 90
100 / 125
125 / 150
30
35 / 40
50 / 60
60 / 70
80 / 90
15
25
35
40
50
15
20
30
35
40
49
294604-YTG-G-0511
DEZ024-060 Cooling Only With/Without Electric Heat (Continued)
Size
(Tons)
Volt
OD Fan Supply
Motors Blower
(each) Motor
RLA LRA MCC FLA
FLA
Compressors
(each)
208/230-1-60 26.2 150
41
2.2
7.6
208/230-3-60 17.9 120
28
2.2
7.6
060
(5.0)
460-3-60
9.6
70
15
1.1
7.6
575-3-60
7.4
53
12
0.8
7.6
Electric Heat Option
Model
None
2NH04501006
2NH04501506
2NH04502006
2NH04502506
None
2NH04501025
2NH04501525
2NH04502025
2NH04502525
None
2NH04501046
2NH04501546
2NH04502046
2NH04502546
None
2NH04501058
2NH04501558
2NH04502058
2NH04502558
MCA1
(Amps)
kW
Stages
Amps
42.6
7.5 / 10
2
36.1 / 41.7 54.6 / 61.6
11.3 / 15
2
54.2 / 62.5 77.2 / 87.6
15 / 20
2
72.2 / 83.3 99.8 / 113.7
18.8 / 25
2
90.3 / 104.2 122.3 / 139.7
32.2
7.5 / 10
1
20.8 / 24.1 35.6 / 39.6
11.3 / 15
1
31.3 / 36.1 48.6 / 54.6
15 / 20
2
41.7 / 48.1 61.6 / 69.6
18.8 / 25
2
52.1 / 60.1 74.7 / 84.7
20.7
10
1
12
24.5
15
1
18
32.1
20
2
24.1
39.6
25
2
30.1
47.1
16.9
10
1
9.6
21.5
15
1
14.4
27.5
20
2
19.2
33.6
25
2
24.1
39.6
Max Fuse2/
Breaker3 Size
(Amps)
60
60 / 70
80 / 90
100 / 125
125 / 150
40
45 / 50
50 / 60
70 / 70
80 / 90
25
30
35
40
50
20
25
30
35
40
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
50
Johnson Controls Unitary Products
294604-YTG-G-0511
DEQ024-060 Cooling Only With/Without Electric Heat
Size
(Tons)
Volt
OD Fan Supply
Motors Blower
(each) Motor
RLA LRA MCC FLA
FLA
Compressors
(each)
024
(2.0)
208/230-1-60 8.3
43
13
1.2
4.3
030
(2.5)
208/230-1-60 13.1
74
21
1.2
4.3
208/230-1-60 14.7
74
23
1.2
4.3
208/230-3-60 9.1
68
14
1.2
4.3
036
(3.0)
042
(3.5)
460-3-60
4.5
34
7
0.8
2.2
575-3-60
3.8
28
6
0.6
1.7
208/230-1-60 15.7
88
25
1.4
6.8
208/230-3-60 9.3
68
15
1.4
6.8
460-3-60
5.1
34
8
0.8
3.4
575-3-60
3.8
28
6
0.6
2.7
208/230-1-60 20.5 115
32
1.7
6.8
208/230-3-60 16.0 120
25
1.7
6.8
048
(4.0)
460-3-60
7.7
50
12
1.0
3.4
575-3-60
6.4
40
10
0.8
2.7
Johnson Controls Unitary Products
Electric Heat Option
Model
None
2NH04500506
2NH04500706
2NH04501006
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04501025
2NH04501525
None
2NH04501046
2NH04501546
None
2NH04501058
2NH04501558
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04501025
2NH04501525
None
2NH04501046
2NH04501546
None
2NH04501058
2NH04501558
None
2NH04501006
2NH04501506
2NH04502006
2NH04502506
None
2NH04501025
2NH04501525
2NH04502025
2NH04502525
None
2NH04501046
2NH04501546
2NH04502046
2NH04502546
None
2NH04501058
2NH04501558
2NH04502058
2NH04502558
MCA1
(Amps)
kW
Stages
Amps
15.9
3.8 / 5
1
18.1 / 20.8 27.9 / 31.4
5.6 / 7.5
2
27.1 / 31.3 39.2 / 44.4
7.5 / 10
2
36.1 / 41.7 50.5 / 57.5
--21.9
3.8 / 5
1
18.1 / 20.8 27.9 / 31.4
5.6 / 7.5
2
27.1 / 31.3 39.2 / 44.4
7.5 / 10
2
36.1 / 41.7 50.5 / 57.5
11.3 / 15
2
54.2 / 62.5 73.1 / 83.5
23.9
3.8 / 5
1
18.1 / 20.8 27.9 / 31.4
5.6 / 7.5
2
27.1 / 31.3 39.2 / 44.4
7.5 / 10
2
36.1 / 41.7 50.5 / 57.5
11.3 / 15
2
54.2 / 62.5 73.1 / 83.5
16.9
7.5 / 10
1
20.8 / 24.1 31.4 / 35.4
11.3 / 15
1
31.3 / 36.1 44.5 / 50.5
8.6
10
1
12
17.8
15
1
18
25.3
7.1
10
1
9.6
14.2
15
1
14.4
20.2
27.8
3.8 / 5
1
18.1 / 20.8 31.1 / 34.5
5.6 / 7.5
2
27.1 / 31.3 42.4 / 47.6
7.5 / 10
2
36.1 / 41.7 53.6 / 60.6
11.3 / 15
2
54.2 / 62.5 76.2 / 86.6
19.8
7.5 / 10
1
20.8 / 24.1 34.6 / 38.6
11.3 / 15
1
31.3 / 36.1 47.6 / 53.6
10.6
10
1
12
19.3
15
1
18
26.8
8.1
10
1
9.6
15.4
15
1
14.4
21.4
34.1
7.5 / 10
2
36.1 / 41.7 53.6 / 60.6
11.3 / 15
2
54.2 / 62.5 76.2 / 86.6
15 / 20
2
72.2 / 83.3 98.8 / 112.7
18.8 / 25
2
90.3 / 104.2 121.3 / 138.7
28.5
7.5 / 10
1
20.8 / 24.1 34.6 / 38.6
11.3 / 15
1
31.3 / 36.1 47.6 / 53.6
15 / 20
2
41.7 / 48.1 60.6 / 68.6
18.8 / 25
2
52.1 / 60.1 73.7 / 83.7
14
10
1
12
19.3
15
1
18
26.8
20
2
24.1
34.3
25
2
30.1
41.8
11.5
10
1
9.6
15.4
15
1
14.4
21.4
20
2
19.2
27.4
25
2
24.1
33.4
Max Fuse2/
Breaker3 Size
(Amps)
20
30 / 35
40 / 45
60 / 60
30
30 / 35
40 / 45
60 / 60
80 / 90
30
35 / 35
40 / 45
60 / 60
80 / 90
25
35 / 40
45 / 60
15
20
30
15
15
25
35
40 / 40
45 / 50
60 / 70
80 / 90
25
35 / 40
50 / 60
15
20
30
15
20
25
45
60 / 70
80 / 90
100 / 125
125 / 150
35
40 / 40
50 / 60
70 / 70
80 / 90
20
20
30
35
45
15
20
25
30
35
51
294604-YTG-G-0511
DEQ024-060 Cooling Only With/Without Electric Heat (Continued)
Size
(Tons)
Volt
OD Fan Supply
Motors Blower
(each) Motor
RLA LRA MCC FLA
FLA
Compressors
(each)
208/230-1-60 26.2 150
41
2.8
9.1
208/230-3-60 17.9 120
28
2.8
9.1
060
(5.0)
460-3-60
8.3
70
13
1.4
4.6
575-3-60
7.4
53
12
1.1
3.6
Electric Heat Option
Model
None
2NH04501006
2NH04501506
2NH04502006
2NH04502506
None
2NH04501025
2NH04501525
2NH04502025
2NH04502525
None
2NH04501046
2NH04501546
2NH04502046
2NH04502546
None
2NH04501058
2NH04501558
2NH04502058
2NH04502558
MCA1
(Amps)
kW
Stages
Amps
44.7
7.5 / 10
2
36.1 / 41.7 56.5 / 63.5
11.3 / 15
2
54.2 / 62.5 79.1 / 89.5
15 / 20
2
72.2 / 83.3 101.7 / 115.5
18.8 / 25
2
90.3 / 104.2 124.2 / 141.6
34.3
7.5 / 10
1
20.8 / 24.1 37.4 / 41.4
11.3 / 15
1
31.3 / 36.1 50.5 / 56.5
15 / 20
2
41.7 / 48.1 63.5 / 71.5
18.8 / 25
2
52.1 / 60.1 76.5 / 86.6
16.4
10
1
12
20.8
15
1
18
28.3
20
2
24.1
35.8
25
2
30.1
43.3
14
10
1
9.6
16.5
15
1
14.4
22.5
20
2
19.2
28.6
25
2
24.1
34.6
Max Fuse2/
Breaker3 Size
(Amps)
60
70 / 70
80 / 90
110 / 125
125 / 150
45
45 / 50
60 / 60
70 / 80
80 / 90
20
25
30
40
45
20
20
25
30
35
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
DEX024-048 Cooling Only With/Without Electric Heat
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
FLA
Supply
Blower
Motor
FLA
024
(2.0)
208/230-1-60 10.2
52
16
1.2
4.3
030
(2.5)
208/230-1-60 14.1
70
22
1.2
4.3
208/230-1-60 16.6
82
26
1.2
4.3
208/230-3-60 11.1
58
17
1.2
4.3
4.5
29
7
0.8
4.3
208/230-1-60 16.6
96
26
1.4
6.8
208/230-3-60 13.4
88
21
1.4
6.8
44
10
0.8
6.8
036
(3.0)
460-3-60
042
(3.5)
460-3-60
52
6.1
Electric Heat Option
Model
None
2NH04500506
2NH04500706
2NH04501006
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04501025
2NH04501525
None
2NH04501046
2NH04501546
None
2NH04500506
2NH04500706
2NH04501006
2NH04501506
None
2NH04501025
2NH04501525
None
2NH04501046
2NH04501546
kW
Stages Amps
3.8/5
1
18.1/20.8
5.6/7.5
2
27.1/31.3
7.5/10
2
36.1/41.7
3.8/5
1
18.1/20.8
5.6/7.5
2
27.1/31.3
7.5/10
2
36.1/41.7
11.3/15
2
54.2/62.5
3.8/5
1
18.1/20.8
5.6/7.5
2
27.1/31.3
7.5/10
2
36.1/41.7
11.3/15
2
54.2/62.5
7.5/10
1
20.8/24.1
11.3/15
1
31.3/36.1
10
1
12
15
1
18
3.8/5
1
18.1/20.8
5.6/7.5
2
27.1/31.3
7.5/10
2
36.1/41.7
11.3/15
2
54.2/62.5
7.5/10
1
20.8/24.1
11.3/15
1
31.3/36.1
10
1
12
15
1
18
MCA1
(Amps)
18.3
27.9 / 31.4
39.2 / 44.4
50.5 / 57.5
23.1
27.9 / 31.4
39.2 / 44.4
50.5 / 57.5
73.1 / 83.5
26.3
27.9 / 31.4
39.2 / 44.4
50.5 / 57.5
73.1 / 83.5
19.4
31.4 / 35.4
44.5 / 50.5
10.7
20.4
27.9
29
31.1 / 34.5
42.4 / 47.6
53.6 / 60.6
76.2 / 86.6
25
34.6 / 38.6
47.6 / 53.6
15.4
23.5
31.1
Max Fuse2/
Breaker3
Size
(Amps)
25
30 / 35
40 / 45
60 / 60
30
35 / 35
40 / 45
60 / 60
80 / 90
35
35 / 40
40 / 45
60 / 60
80 / 90
25
35 / 40
45 / 60
15
25
30
35
40 / 45
45 / 50
60 / 70
80 / 90
30
35 / 40
50 / 60
20
25
35
Johnson Controls Unitary Products
294604-YTG-G-0511
DEX024-048 Cooling Only With/Without Electric Heat (Continued)
Size
(Tons)
Volt
RLA LRA
048
(4.0)
MCC
OD Fan
Motors
(each)
FLA
Supply
Blower
Motor
FLA
Compressors
(each)
208/230-1-60 21.1
96
33
1.7
6.8
208/230-3-60 13.4
88
21
1.7
6.8
41
10
1.0
6.8
460-3-60
6.4
Electric Heat Option
Model
None
2NH04501006
2NH04501506
2NH04502006
2NH04502506
None
2NH04501025
2NH04501525
2NH04502025
2NH04502525
None
2NH04501046
2NH04501546
2NH04502046
2NH04502546
MCA1
(Amps)
kW
Stages Amps
34.9
7.5/10
2
36.1/41.7 53.6 / 60.6
11.3/15
2
54.2/62.5 76.2 / 86.6
15/20
2
72.2/83.3 98.8 / 112.7
18.8/25
2
90.3/104.2 121.3 / 138.7
25.3
7.5/10
1
20.8/24.1 34.6 / 38.6
11.3/15
1
31.3/36.1 47.6 / 53.6
15/20
2
41.7/48.1 60.6 / 68.6
18.8/25
2
52.1/60.1 73.7 / 83.7
15.9
10
1
12
23.5
15
1
18
31.1
20
2
24.1
38.6
25
2
30.1
46.1
Max Fuse2/
Breaker3
Size
(Amps)
45
60 / 70
80 / 90
100 / 125
125 / 150
35
35 / 40
50 / 60
70 / 70
80 / 90
20
25
35
40
50
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
DEY060 Cooling Only With/Without Electric Heat
Size
(Tons)
Volt
RLA LRA
060
(5.0)
MCC
OD Fan
Motors
(each)
FLA
Supply
Blower
Motor
FLA
Compressors
(each)
208/230-1-60 25.6
118
40
1.7
9.1
208/230-3-60 17.6
123
28
1.7
9.1
62
14
1.0
9.1
460-3-60
9.0
Electric Heat Option
Model
None
2NH04501006
2NH04501506
2NH04502006
2NH04502506
None
2NH04501025
2NH04501525
2NH04502025
2NH04502525
None
2NH04501046
2NH04501546
2NH04502046
2NH04502546
MCA1
(Amps)
kW
Stages Amps
42.8
7.5/10
2
36.1/41.7 56.5 / 63.5
11.3/15
2
54.2/62.5 79.1 / 89.5
15/20
2
72.2/83.3 101.7 / 115.5
18.8/25
2
90.3/104.2 124.2 / 141.6
32.8
7.5/10
1
20.8/24.1 37.4 / 41.4
11.3/15
1
31.3/36.1 50.5 / 56.5
15/20
2
41.7/48.1 63.5 / 71.5
18.8/25
2
52.1/60.1 76.5 / 86.6
21.4
10
1
12
26.4
15
1
18
33.9
20
2
24.1
41.4
25
2
30.1
49
Max Fuse2/
Breaker3
Size
(Amps)
60
60 / 70
80 / 90
110 / 125
125 / 150
40
45 / 50
60 / 60
70 / 80
80 / 90
30
30
35
45
50
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Johnson Controls Unitary Products
53
294604-YTG-G-0511
Typical Wiring Diagrams
Typical DEZ024-060 Cooling Only 208/230-1-60 volt Wiring Diagram
54
Johnson Controls Unitary Products
294604-YTG-G-0511
Typical DEZ036-060 Cooling Only 208/230-3-60 volt Wiring Diagram
Johnson Controls Unitary Products
55
294604-YTG-G-0511
Typical DEZ036-060 Cooling Only 460/575-3-60 volt Wiring Diagram
56
Johnson Controls Unitary Products
294604-YTG-G-0511
Typical DEQ024-048 Cooling Only 208/230-1-60 volt Wiring Diagram
Johnson Controls Unitary Products
57
294604-YTG-G-0511
Typical DEQ060 Cooling Only 208/230-1-60 volt Wiring Diagram
58
Johnson Controls Unitary Products
294604-YTG-G-0511
Typical DEQ036-048 Cooling Only 208/230-3-60 volt Wiring Diagram
Johnson Controls Unitary Products
59
294604-YTG-G-0511
Typical DEQ060 Cooling Only 208/230-3-60 volt Wiring Diagram
60
Johnson Controls Unitary Products
294604-YTG-G-0511
Typical DEQ036-048 Cooling Only 460/575-3-60 volt Wiring Diagram
Johnson Controls Unitary Products
61
294604-YTG-G-0511
Typical DEQ060 Cooling Only 460/575-3-60 volt Wiring Diagram
62
Johnson Controls Unitary Products
294604-YTG-G-0511
Typical DEX024-048/DEY060 Cooling Only 208/230-1-60 volt Wiring Diagram
Johnson Controls Unitary Products
63
294604-YTG-G-0511
Typical DEX036-048/DEY060 Cooling Only 208/230-3-60 volt Wiring Diagram
64
Johnson Controls Unitary Products
294604-YTG-G-0511
Typical DEX036-048/DEY060 Cooling Only 460-3-60 volt Wiring Diagram
Johnson Controls Unitary Products
65
294604-YTG-G-0511
Weights and Dimensions
Unit 4 Point Load Weight
"D"
CENTER OF
GRAVITY
FRONT
OF
UNIT
"C"
"A"
49-1/8
"B"
X
Weight (lbs.)
Center of Gravity
Size
Model
(Tons)
Shipping Operating
X
Y
DEZ
379
374
23
23.25
024
DEQ
351
346
22.25
25
(2.0)
DEX
360
355
22.25
25
DEZ
380
375
23
22.25
030
DEQ
391
386
22.25
25
(2.5)
DEX
395
390
22.25
25
DEZ
384
379
23
22.25
036
DEQ
401
396
22.25
25
(3.0)
DEX
405
400
22.25
25
DEZ
405
400
23
21.25
042
DEQ
411
406
22.25
25
(3.5)
DEX
415
410
22.25
25
DEZ
406
401
21.5
21.75
048
DEQ
445
440
22.25
25
(4.0)
DEX
445
440
22.25
25
DEZ
410
405
23.5
22.75
060
DEQ
457
452
22.25
25
(5.0)
DEY
465
460
22.25
25
Y
47-1/4
4 Point Load Location (lbs.)
A
B
C
D
92
85
95
102
94
82
79
91
96
84
81
93
88
82
99
106
105
92
88
101
106
92
89
102
89
83
100
107
108
94
91
104
109
95
92
105
90
83
109
118
110
96
93
106
111
97
94
108
98
80
101
123
120
104
101
115
120
104
101
115
95
92
107
110
123
107
103
119
125
109
105
121
Unit Accessory Weights
Unit Accessory
Model
Add Economizer
Add Electric Heat1
All
DEZ, DEQ, DEY, DEX
Weight (lbs.)
Shipping
Operating
45
40
13
12
1. Weight given is for the maximum heater size available (25 kW).
66
Johnson Controls Unitary Products
294604-YTG-G-0511
Cooling Only Unit Dimensions
HIGH VOLTAGE CONN.
7/8" DIA. KNOCKOUT
FRONT
COMPRESSOR SERVICE
ACCESS COMPARTMENT
PANEL
HIGH VOLTAGE CONN.
1-31/32" DIA. KNOCKOUT
LOW VOLTAGE CONN.
7/8" DIA. KNOCKOUT
“A”
2-3/8
(OVERALL)
SIDE SUPPLY
AIR OPENING
REFRIGERANT
CONNECTIONS
SIDE RETURN
AIR OPENING
ELECTRICAL/FILTER
SERVICE ACCESS
COMPARTMENT PANEL
17-1/4
28-1/4
22-1/4
49-1/8
(OVERALL)
17-1/4
2-1/2
28-1/4
22-1/4
47-1/4
HIGH VOLTAGE CONN.
1-23/64" DIA. KNOCKOUT
(OVERALL)
3-3/4
1-1/2
4-1/2
UNIT CONDENSATE
CONNECTION 3/4" NPTF
(TRAP REQUIRED)
Cooling Only Unit Dimensions
Unit Size
Dimensions
“A”
024, 030, 036, 0421
33-1/2
0422, 048, 060
41-1/2
1. DEZ Models.
2. DEX Models.
Cooling Only Unit Clearances
Distance
(in.)
Direction
Distance
(in.)
Direction
Top1
36
Right
24
Front
12
Left
24
Rear
0
Bottom2 3
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air
discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering
materials.
3. Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of duct for 20 & 25 kW., zero
inches there after. For all other heaters, zero inch clearance all sides for entire length of duct.
Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch
between combustible roof curb material and this supply air duct.
Johnson Controls Unitary Products
67
294604-YTG-G-0511
Unit Dimensions Front and Bottom
HIGH VOLTAGE
CONN. 1-3/32"
DIA. KNOCKOUT
8-7/8
11-7/8
19-1/4
FRONT
GAS SUPPLY 1-5/8"
DIA. KNOCKOUT (1/2"
NPTF CONNECTION)
LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT
LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT
HIGH VOLTAGE
CONN. 1-31/32" x 7/8"
KNOCKOUT
4-5/8
CONDENSATE
DRAIN 3/4" NPTF
40-1/2
26-3/4
22-1/2
43-1/2
6
Unit Dimensions Back and Bottom
SIDE SUPPLY
AIR OPENING
*CONDENSER
COIL
14-1/2
28-3/8
14-1/2
BACK
BOTTOM SUPPLY
AIR OPENING
3-3/8
SIDE RETURN
AIR OPENING
14-1/2
4 4-1/4
1-3/4
15
15
1-3/4
15
28-9/16
68
3-1/2
1-3/4
BOTTOM RETURN
AIR OPENING
Johnson Controls Unitary Products
294604-YTG-G-0511
Unit Typical Duct Applications
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON GROUND
INSTALLATION
Unit Typical Slab on Ground Installation
SUPPLY AIR
DUCT
RETURN AIR
DUCT
FIELD SUPPLIED
DISCONNECT SWITCH
LOCATED TO REAR OF UNIT
TO POWER SUPPLY
CONTROL WIRING
TO INDOOR
THERMOSTAT
Johnson Controls Unitary Products
69
294604-YTG-G-0511
Unit Typical Roof Curb Installation
FIELD SUPPLIED
DISCONNECT SWITCH
MOUNTED ON UNIT
TO POWER SUPPLY
CONTROL WIRING
TO INDOOR THERMOSTAT
SUPPLY AIR
DUCT
RETURN AIR
DUCT
Unit Accessory Dimensions
Roof Curb1
RECOMMENDED
DUCT SIZE
17-1/2" x 16-3/4"
42-2/3
40-3/4
3-1/2
45-1/8
17-5/8
17-1/4
43-1/4
OPENING FOR
RETURN AIR DUCT
22
OPENING FOR
SUPPLY AIR DUCT
14
1
RECOMMENDED
DUCT SIZE
17-1/8" x 21-1/2"
1. 8” Roof Curb also available.
70
Johnson Controls Unitary Products
294604-YTG-G-0511
Roof Curb Cross Section
\
1"
3/4" x 1" WIDE GASKETING FOR CURB FRAME
AND ALL DUCT SUPPORT SURFACES
UNIT BASE
UNIT BASE RAIL
WOOD NAILER
COUNTERFLASHING
8" MIN. ABOVE FINISHED ROOF
14"
CANT STRIP
CURB FRAME
INSULATION AND ROOFING MATERIAL
INSULATION
ROOF DECK AND ROOFING MATERIAL
Johnson Controls Unitary Products
71
Subject to change without notice. Printed in U.S.A.
Copyright © 2011 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
5005 York Drive
294604-YTG-G-0511
Supersedes: 294604-YTG-F-1210
Download