Uploaded by Abdullah ALMughamisi

HW 6-4-Soluttions

advertisement
King Fahd University of Petroleum & Minerals
MECHANICAL ENGINEERING DEPARTMENT
ME 429 – Energy Efficiency and Auditing
HOMEWORK # 6 SOLUTION
(Instructor: Dr. Esmail M. A. Mokheimer)
1) A five ton air conditioner has an average electric load of 6 kW. What is its average COP
and what is its SEER?
Solution: Using Equation 6-2 gives:
SEER = (5 tons) (12,000 Btu/hr/ton)/(6 kW)(1000 W/kW)
= 60,000 Btu/6,000 Wh
= 10 Btu/Wh
2) A 100-ton chiller has a COP of 3.5. What is its electrical load?
Solution: Using Equation 6-2 and rearranging it gives:
electrical load = cooling capacity/EER
= (100 tons)(12,000 Btu/hr/ton)/(3.5)(3412 Btu/kWh)
= 100.5 kW
3) I) An industrial facility presently has a 5-hp ventilating fan that draws warm air from a
production area. The motor recently failed and they think they can replace it with a smaller
motor. They have determined that they can reduce the amount of ventilation air by one
third. What size motor is needed now?
II) What is the electrical load reduction for the smaller fan motor, above, if the 5-hp
motor had an efficiency of 84% and the new 1.5-hp motor has an efficiency of 85.2%.
Solution: Use Equation 6-14, and note that the ratio of the new to old cfm rate is 2/3.
Thus, the new hp needed is:
I)
New hp = (2/3)3 × 5 hp = 0.3 × 5 hp = 1.5 hp
II)
Old load = (5 hp) × (0.746 kW/hp)/(0.84) = 4.44 kW
New load = (1.5 hp) × (0.746 kW/hp)/(0.852) = 1.31 kW
Electric load reduction = 3.13 kW
4) You have measured the ventilation in a large truck bay and have found that you are using
12,000 cfm. An analysis shows that only 8000 cfm are required. Measurements at the fans
give the total electrical consumption of the ventilation system as 16.0 kW at the current
cfm rates. You are currently ventilating this area 16 hour each day, 250 days each year,
including the times of peak electrical usage. Your monthly electric rates are $.045/kWh
and $12.00/kW per month of demand. Assuming that both motors efficiency is 90% and
both fans are operating at full load, what is the amount of annual savings that you can
expect by the proposed reduction in ventilation rates?
Solution: Use Equation 6-14, and note that the ratio of the new to old cfm rate is 2/3.
Thus, the new power needed is:
New Power = (2/3)3 × 16 kW = 4.740741 kW
New load = 4.740741 kW/0.9 = 5.26749 kW
Old Power = 16 kW
Old load = 16 kW/0.9 = 17.77778 kW
Electric load reduction = Old load - New load = 17.77778 – 5.26749 = 12.51029 kW
Cost saving due to load reduction = Load Reduction × Demand cost
Cost saving due to load reduction = 12.51 kW × $ 12/(kW. Month) × 12 Month/year
Cost saving due to load reduction = $ 1,801.481 /year
Cost saving due to Energy use reduction = Load Reduction (kW) × Time (hr/year)
× Electric Tariff ($/kWh)
π‘ π‘Žπ‘£π‘–π‘›π‘” 𝑑𝑒𝑒 π‘‘π‘œ πΈπ‘›π‘’π‘Ÿπ‘”π‘¦ 𝑒𝑠𝑒 π‘Ÿπ‘’π‘‘π‘’π‘π‘‘π‘–π‘œπ‘› = 12.51029π‘˜π‘Š ×
16 β„Žπ‘Ÿ
250 π‘‘π‘Žπ‘¦ $ 0.045
×
×
π‘‘π‘Žπ‘¦
π‘¦π‘’π‘Žπ‘Ÿ
π‘˜π‘Šβ„Ž
π’”π’‚π’—π’Šπ’π’ˆ 𝒅𝒖𝒆 𝒕𝒐 π‘¬π’π’†π’“π’ˆπ’š 𝒖𝒔𝒆 π’“π’†π’…π’–π’„π’•π’Šπ’π’ = $ πŸπŸπŸ“πŸ. πŸ–πŸ“πŸ/π’šπ’†π’‚π’“
π‘‡π‘œπ‘‘π‘Žπ‘™ π‘ π‘Žπ‘£π‘–π‘›π‘”π‘  = $ 1,801.481 /year + $ 22516.852/π‘¦π‘’π‘Žπ‘Ÿ
𝑻𝒐𝒕𝒂𝒍 π’”π’‚π’—π’Šπ’π’ˆπ’” = $ πŸ’, πŸŽπŸ“πŸ‘. πŸ‘πŸ‘/π’šπ’†π’‚π’“
Download