What is Instrumentation? It is the collective term for Measuring Instruments. It is the study of Measuring Instruments which are used for indicating certain parameters . It is the “ART and SCIENCE’’ of measurement of Process variables in industry and its Control. Why Instrumentation is needed? Economic Operation of plant. Efficient Operation of plant. Safe operation of plant. Pollution Control. Why C& I ? Without automatic controllers, all regulation tasks will have to be done manually. For example: To keep constant the temperature of water discharged from an industrial gasfired heater, an operator has to watch a temperature gauge and adjust a gas control valve accordingly (Figure 1). If the water temperature becomes too high, the operator has to close the gas control valve a bit - just enough to bring the temperature back to the desired value. If the water becomes too cold, he has to open the valve To relieve our operator from the tedious task of manual control, we automate the controls - i.e. we install a PID controller (Figure 2). The controller has a Set Point (SP) that the operator can adjust to the desired temperature. We also have to automate the control valve by installing an actuator (and perhaps a positioner) so that the Controller's Output (CO) can change the valve's position. And finally, we'll provide the controller with an indication of the temperature or Process Variable (PV) by installing a temperature transmitter. The PV and CO are mostly transmitted via 4 - 20mA signals . So, when everything is up and running, our PID controller compares the process variable to its set point and then calculates the difference between the two signals, also called the Error (E). Then, based on the error, a few adjustable settings and its internal structure (described next), the controller calculates an output that positions the control valve. Decides Controller/ Receiving element Senses Influences Measuring Device/element Final control device/element Reacts The Process Process: Furnace Separator Boiler Measuring element: Sensor Transmitter Transducer Receiving element: Indicators Recorders Controller Alarm units Final Control element: Control Valves Dampers Drives MEASUREMENT DONE IN POWER PLANT Process measurements : Pressure, Temperature, Flow and Level. Analytical measurements (SWAS) : pH, Conductivity, Silica, Hydrazine and Dissolved Oxygen. • Condition monitoring measurements for rotating equipment : Vibration, speed, bearing temperatures, eccentricity, axial shift, displacement. • Emission monitoring (CEMS): CO, SOx, NOx • Environmental measurements : Wind velocity, Ambient temperature, Humidity, Rainfall etc. MEASUREMENT PARAMETER • Indication of the parameter can be either LOCAL or REMOTE • LOCAL means indication of the parameter at the field by a dial type gauge, liquid level gauge or flow glass. • REMOTE means that the primary signal is converted to an electrical analog signal and transmitted to the control room for indication / control. CONTROL SYSTEM • A control system is a device or set of devices to manage, command, direct or regulate the behavior of other devices or systems. • There are two common classes of control systems, with many variations and combinations: logic or sequential control and feedback or linear controls. There is also fuzzy logic, which attempts to combine some of the design simplicity of logic with the utility of linear control. Why DCS? • • • • • • • • • • • High Reliability Improved Response Time Improved Interface to plant Improved accessibility of plant data to engineering and management personnel. Historical Storage and Retrieval System Safe operation of Plant Lowest Cost of Generation Longest Equipment Life Minimum Environmental Effect Maximum Efficiency Energy Conversation DCS IN POWER PLANT • The control system is responsible for controlling action of all the measurement. • In power plant this DCS (Distributed Control System ) plays the role of this control system. • All interlocking, monitoring and annunciation operations are performed in DCS. Large Video Screen (Optional) Remote maxVUE (Optional) NETWORK PRINT : Operator Station # 1 Operator Station # 2 Peformance Operator Station # n Calcs. Station ENGG. STATION maxSTORIAN STATION … … CD R/W UNIT CONTROL DESK (minimum/trip related) ETHERNET SWITCH PB STN (TRIP). maxLINKS maxNET RPUs (I/O + DPU + Network Components) ETHERNET SWITCH RPU DPU I/O Modules RPU RPU DPU DPU I/O Modules I/O Modules … FG # Turbine … RPU RPU DPU DPU I/O Modules I/O Modules FG # Boiler LOCAL JB DPU I/O Modules I/O Modules FG # STN. C&I +ELECT. LOCAL JB + CONTACT INPUTS DPU … CJC BOX LOCAL JB RR RPU RPU RPU … DPU I/O Modules SWITCH YARD SCAD LOCAL JB ~ E - ANALOG (4-20mA) T/Cs RTDs P POWER AMP. MOTORISED VALVES/ DAMPERS MOTORS PUMPS/ BREAKERS DCS HARDWARE Controller card Input Cards (4-20 m A) Thermocouple, RTD, SOE Output Cards(4-20 m A, Digital) Power Supply Module Communication Card Cables • Controller with I/O card • • OPERATOR WORK STATION Alarm Monitoring Mimic Or Graphic Display Trend Display Operator Guidance Display System and Diagnostic Display Control Bar Chart Sequence Display Fault Analysis Display Pressure Pressure is the force exerted per unit area Pressure is the action of one force against another force. Pressure is force applied to, or distributed over, a surface. The pressure P of a force F distributed over an area A is defined as P = F/A GAUGE COMPOUND ABSOLUTE BAROMETRIC RANGE ATMOSPHERIC PRESSURE NOM. 14.7 PSIA PRESSURE TOTAL VACUUM - 0 PSIA PRESSURE GAUGES: A Pressure Gauge is used for measuring the pressure of a gas or liquid. A Vacuum Gauge is used to measure the pressure in a vacuum. A Compound Gauge is used for measuring both Vacuum and Pressure. Pressure Gauges are used for Indication only. Measuring Principle Bourdon tube measuring element is made of a thin-walled C-shape tube or spirally wound helical or coiled tube. When pressure is applied to the measuring system through the pressure port (socket), the pressure causes the Bourdon tube to straighten itself, thus causing the tip to move. The motion of the tip is transmitted via the link to the movement which converts the linear motion of the bourdon tube to a rotational motion that in turn causes the pointer to indicate the measured pressure. Helical Bourdon “C” Type Bourdon Coiled Bourdon Diaphragms Bellows: Snubber Used for dampening and filtering and reducing the damaging effects of pulsation on a gauge. The snubber has a metal Disc available in standard grades of porosity. Siphon Tubes Used to dissipate heat by trapping condensed liquid to keep high temperature steam or condensing vapor from damaging the pressure gauge. PIG TAIL COIL PIPE Electrical Pressure Sensors 1. Potentiometer Sensor 2. Inductive 3. Capacitive 4. Piezoelectric 5. Strain Gauge Usually generate output signals in the mV range (spans of 100 mV to 250mV). In transmitters, these are amplified to the voltage level (1to 5 V) and converted to current loops, usually 4-20 mA dc Pressure Switch A pressure switch turns an electric circuit on or off at a preset pressure.This pressure is referred to as the setpoint of the switch. A bourdon tube,a diaphragm, or a bellows can actuate the switch Deadband is the difference between the value at which a control action occurs and the value at which at which the control action is cancelled. Pressure Switches Applications Alarm (Status) Shutdown (Hi/Lo Limits) Control (ON/OFF) A “switch” is an instrument that automatically senses some process variable (such as pressure) and provides an on/off signal relative to some reference point. Pressure Transmitter A Pressure Transmitter is used where indication and/or record of pressure is required at a location not adjacent to the primary element. A Pressure Transmitter is used for both indication and control of a process. A Pressure Transmitter is used where overall high performance is mandatory. Both Electronic and Pneumatic Transmitters are used. These can be either Gauge, Absolute or Differential Pressure Transmitters. Pressure Transmitter Pressure Regulator Temperature: °C – degrees Celsius (or Centigrade) °F – degrees Fahrenheit K – Kelvin R – Rankine Relationship between different units °C = (°F - 32)/1.8 °F = 1.8 x °C + 32 K = °C + 273.15 R = °F + 459.67 Conversion tables or software can be utilized to facilitate with converting between these units. Types of Temperature Instruments: Thermocouple (T/C) Resistance Temperature Detector (RTD) Thermowell Thermistor Bi-metallic Thermometers Filled Thermal Systems RTD’s: RTDs (Resistance Temperature Detectors) operate under the principle that the electrical resistance of certain metals increases and decreases in a repeatable and predictable manner with a temperature change. Wire Wound Element Precise lengths of wire are wrapped around a ceramic mandrel, then inserted inside a ceramic shell which acts to support and protect the wire windings. Inner Coil Element Wires are coiled then slid into the holes of a ceramic insulator. Some manufacturers backfill the bores with ceramic powder after the coils are inserted. This keeps the coils from shorting against each other. Thin Film Element Metallic ink is deposited onto a ceramic substrate. Lasers then etch the ink to provide a resistance path. The entire assembly is encapsulated in ceramic to support and protect. Thermocouple measuring circuit Equivalent to 80ºC reading Iron (Fe) 100ºC Hot Junction: Copper (Cu) Constantan (CuNi) 10 0 20ºC mV Copper (Cu) In Process Cold Junction: Needs to be held constant to give a fixed reference. ( early methods held cold junction at 0ºC using ice or refrigeration unit). • Thermistors are temperature sensing devices that are similar to RTD’s in that their resistance changes as temperature changes. • The major difference is that for most thermistors the resistance decreases as temperature increases. • Thermistors are an inexpensive alternative to RTD’s when temperature ranges are below 150°C. Thermistors can be used from temperatures of –80°C to 300°C. A Bimetallic Thermometer consists of an indicating or recording device, a sensing element and a means for connecting the two. Thermowell Flow Flow is measured as a quantity (either volume or mass) per unit time Volumetric units Liquid gpm, bbl/day, m3/hr, liters/min, etc. Gas or Vapor ft3/hr, m3/hr, etc. Mass units (either liquid, gas or vapor) lb/hr, kg/hr, etc. Flow can be measured in accumulated (totalized) total amounts for a time period gallons, liters, meters passed in a day, etc. Flow Measurement COMMONLY USED FLOW DEVICES Differential Pressure (Head) Type Orifice Plate - Concentric, Eccentric, Segmental, Quadrant Edge, Integral, Conditioning Venturi Tube Flow Nozzles Elbow Pitot Tube, Averaging Pitot Tube (Annubar) Variable Area (Rotameter) Wedge Meter V-Cone Mass Type – measures the mass flow rate directly. Coriolis Thermal Velocity Type Magnetic Ultrasonic - Transit Time, Doppler Turbine Vortex Open Channel Type Weir Parshall Flume Other Types Positive Displacement Target Flow meters can further classified into four types: • Volumetric flow meters that measure volume directly Positive displacement meters • Velocity Magnetic, turbine and ultrasonic • Inferential flow meters Differential pressure, target, and variable area flow meters • Mass flow meters that measure mass directly Coriolis Level Instrumentation Concepts – Measurement Types Level Gauges Radar Differential Pressure Float / Displacer Ultrasonic Capacitance Nuclear Other Level Measurement Measures Hydrostatic Head of Liquid in a Vessel Liquid Height Multiplied by a Density Hydrastep The purpose of a float level switch is to open or close a circuit as the level of a liquid rises or falls. Oxygen Analyser: Principle of Measurement Zirconia oxygen analyzers determine oxygen concentration using the conductivity of a zirconia ceramic cell. Zirconia ceramic cells only allow oxygen ions to pass through at high temperatures. With reference gas on one side and sample gas on the other, oxygen ions move from the side with the highest concentration of oxygen to that with the lowest concentration. The movement of ions generates an EMF (Electro Motive Force) which can be measured to determine the oxygen content. Turbo supervisory Parameters: Eccentricity Vibrations Differential Expansion Overall Thermal Expansion Axial shift Turbine speed SPEED MEASUREMENT Tachometer is used for measuring rotational speed Classification of tachometers: • Mechanical Tachometers Revolution counter • Hand speed indicator • Tachoscope • Centrifugal tachometer • Resonance (vibrating read) tachometer • Electrical Tachometers • Eddy current or drag cup tachometer • Tachogenerator (DC and AC) • Contactless electrical Tachometers • Magnetic pickup tachometer • Photo-electric tachometer • Stroboscopebe Coal Usually, in a thermal power plant it is required or most compulsory requirement to measure the flow of coal which is to be sent into the boiler (Sometimes through pulveriser mill in PC Fired Boiler). For this we used to weight the coal that is fed in the conveyor belt continuously. to weight the coal we are using belt weighter - Beltweigher Usually the weight of the coal has been measured in Raw Coal Feeder (RC Feeder). The Raw Coal feeders are classified according to the method by which the rate of coal flow is determined Volumetric Coal Feeder the rate of coal flow through the feeder is derived as by R=QxBxN R - rate of coal flow in Kg/s Q - vol. of coal delivered by the feeder per rotation in m3/rotation B - bulk density of coal in m3/kg N - speed of feeder rotation per second Q & B - making these two contant N - adjusting the speed or varying the speed we can able to maintain the required coal flow in it. 2. Gravimetric Feeder the rate of coal flow is obtained by R=MxN R - rate of coal flow in kg/s M - mass of coal on unit length of feeder belt in kg/m N - speed of feeder belt in m/s Electric Actuator Pneumatic Actuator Actuator Accessories Thank You