Gas-Insulated Substations
Our Solutions – Our Profile
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Our High Voltage Substations
Solutions
Gas-Insulated Substations
Gas-Insulated
Switchgear GIS
Page 2
Highly Integrated
Switchgear HIS®
Oct-11
Air-Insulated Substations
Switchgear Bay
SIMOBREAKER
SIMOVER®
Dead Tank
Switchgear Bay
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Product Portfolio
8DN8
Product Line
8DN9
8DQ1
8DR1
- Q0
Solution
Rated voltage
72.5 kV
145 kV
170 kV
245 kV
300 kV
420 kV
420 kV
550 kV
800 kV
Rated shortcircuit current
31.5 kA
40 kA
63 kA
50 kA
63 kA
63 kA
80 kA
63 kA
50 kA
Rated current
2500 A
3150 A
4000 A
4000 A
4000 A
4000 A
6300 A
5000 A
5000 A
Page 3
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Product Line 8DN8
8DN8
Product Line
8DN9
8DQ1
8DR1
- Q0
Solution
Rated voltage
72.5 kV
145 kV
170 kV
245 kV
300 kV
420 kV
420 kV
550 kV
800 kV
Rated shortcircuit current
31.5 kA
40 kA
63 kA
50 kA
63 kA
63 kA
80 kA
63 kA
50 kA
Rated current
2500 A
3150 A
4000 A
4000 A
4000 A
4000 A
6300 A
5000 A
5000 A
Page 4
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN8 up to 72.5 kV / 31.5 kA / 2500 A
Technical Data
Voltage
72.5 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
140 kV
Lightning impulse withstand voltage (1.2/50 µs)
325 kV
Busbar Current
2500 A
Feeder Current
2500 A
Short-circuit breaking current
31.5 kA
Short-time withstand current (3 s)
31.5 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
650 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 5
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN8 up to 72.5 kV / 31.5 kA / 2500 A
7
2
10
8
M
4
3
M
1
6
5
7
4
5
M
1
8
9
6
3
9
1
2
3
4
5
Circuit-breaker
Circuit-breaker control unit with spring operating mechanism
Busbar I with disconnecting and earthing switch
Busbar II with disconnecting and earthing switch
Outgoing module with disconnecting and earthing switch
Page 6
Oct-11
6
7
8
9
10
Make-proof earthing switch
Current transformer
Voltage transformer
Cable sealing end
Integrated local control cubicle
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN8 up to 145 kV / 40 kA / 3150 A
Technical Data
Voltage
145 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
275 kV
Lightning impulse withstand voltage (1.2/50 µs)
650 kV
Busbar Current
3150 A
Feeder Current
3150 A
Short-circuit breaking current
40 kA
Short-time withstand current (3 s)
40 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width: common drive
800 mm
single drive
1200 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 7
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN8 up to 145 kV / 40 kA / 3150 A
2 7
M
4
M
3
10
8
1
7
6
5
4
1
M
5
8
3
6
9
9
1
2
3
4
5
Circuit-breaker
Circuit-breaker control unit with spring operating mechanism
Busbar I with disconnecting and earthing switch
Busbar II with disconnecting and earthing switch
Outgoing module with disconnecting and earthing switch
Page 8
Oct-11
6
7
8
9
10
Make-proof earthing switch
Current transformer
Voltage transformer
Cable sealing end
Integrated local control cubicle
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type HIS 8DN8 up to 145 kV / 40 kA / 3150 A
Technical Data
Voltage
145 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
275 kV
Lightning impulse withstand voltage (1.2/50 µs)
650 kV
Busbar Current
3150 A
Feeder Current
3150 A
Short-circuit breaking current
40 kA
Short-time withstand current (3 s)
40 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
n.a.
Driving mechanism of circuit-breaker
spring operated
(Single and common drive)
Ambient temperature
-25°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 9
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type HIS 8DN8 up to 145 kV / 40 kA / 3150 A
10
6
3
5
7
5
1
3
8
9
1
2
3
4
5
Circuit-breaker interrupter unit
Circuit-breaker control unit with spring operating mechanism
Outgoing feeder module with disconnecting and earthing switch
Splitting module
Current transformer
Page 10
Oct-11
6
7
8
9
10
11
Voltage transformer
Transformer terminal box
High-speed earthing switch
Cable sealing end
SF6/Air bushing
Supporting structure
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN8 up to 170 kV / 63 kA / 4000 A
Technical Data
Voltage
170 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
325 kV
Lightning impulse withstand voltage (1.2/50 µs)
750 kV
Busbar Current
4000 A
Feeder Current
4000 A
Short-circuit breaking current
63 kA
Short-time withstand current (3 s)
63 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width: common drive
1000 mm
single drive
1200 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE / GOST
other values on request
* type tested
Page 11
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN8 up to 170 kV / 63 kA / 4000 A
7
8
2
M
4
M
3
10
6
5
1
7
4
1
9
M
5
8
3
6
9
1
2
3
4
5
Circuit-breaker
Circuit-breaker control unit with spring operating mechanism
Busbar I with disconnecting and earthing switch
Busbar II with disconnecting and earthing switch
Outgoing module with disconnecting and earthing switch
Page 12
Oct-11
6
7
8
9
10
Make-proof earthing switch
Current transformer
Voltage transformer
Cable sealing end
Integrated local control cubicle
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Product Line 8DN9
8DN8
Product Line
8DN9
8DQ1
8DR1
- Q0
Solution
Rated voltage
72.5 kV
145 kV
170 kV
245 kV
300 kV
420 kV
420 kV
550 kV
800 kV
Rated shortcircuit current
31.5 kA
40 kA
63 kA
50 kA
63 kA
63 kA
80 kA
63 kA
50 kA
Rated current
2500 A
3150 A
4000 A
4000 A
4000 A
4000 A
6300 A
5000 A
5000 A
Page 13
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN9 up to 245 kV / 50 kA / 4000 A
Technical Data
Voltage
245 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
460 kV
Lightning impulse withstand voltage (1.2/50 µs)
1050 kV
Busbar Current
4000 A
Feeder Current
4000 A
Short-circuit breaking current
50 kA
Short-time withstand current (3 s)
50 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
1500 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 14
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN9 up to 245 kV / 50 kA / 4000 A
6
4
M
3
5
M
M 8
1
11
M 9
7M
12
10
13
1 Circuit-breaker interrupter unit
2 Circuit-breaker control unit
with spring operating mechanism
3 Busbar disconnector I
4 Busbar I
Page 15
Oct-11
5 Busbar disconnector II
6 Busbar II
7 Outgoing disconnector
8 Earthing switch
9 Earthing switch
10 Make-proof earthing switch
11 Current transformer
12 Voltage transformer
13 Cable sealing end
14 Integrated local control cubicle
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN9 up to 300 kV / 63 kA / 4000 A
Technical Data
Voltage
300 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
460 kV
Lightning impulse withstand voltage (1.2/50 µs)
1050 kV
Busbar Current
4000 A
Feeder Current
4000 A
Short-circuit breaking current (2 cycles)
63 kA
Short-time withstand current (3 s)
63 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
2200 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 16
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DN9 up to 300 kV / 63 kA / 4000 A
3
5
4 6
6
5
4
3
5
5
9
6
1
2
7
8
10
8
6
5
1
7
9
10
1 Circuit-breaker
2 Circuit-breaker control unit with spring operating mechanism
3 Busbar I
4 Busbar II
5 Disconnecting switch
Page 17
Oct-11
6
7
8
9
10
Earthing switch
Make-proof earthing switch
Current transformer
Voltage transformer
Cable sealing end
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Product Line 8DQ1
8DN8
Product Line
8DN9
8DQ1
8DR1
- Q0
Solution
Rated voltage
72.5 kV
145 kV
170 kV
245 kV
300 kV
420 kV
420 kV
550 kV
800 kV
Rated shortcircuit current
31.5 kA
40 kA
63 kA
50 kA
63 kA
63 kA
80 kA
63 kA
50 kA
Rated current
2500 A
3150 A
4000 A
4000 A
4000 A
4000 A
6300 A
5000 A
5000 A
Page 18
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DQ1 up to 420 kV / 63 kA / 4000 A
Technical Data
Voltage
420 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
650 kV
Lightning impulse withstand voltage (1.2/50 µs)
1425 kV
Switching impulse withstand voltage (250/2500 µs)
1050 kV
Busbar Current
4500 A
Feeder Current
4000 A
Short-circuit breaking current (2 cycles)
63 kA
Short-time withstand current (3 s)
63 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
2200 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 19
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DQ1 up to 420 kV / 63 kA / 4000 A
3
5
6
4
6
5
9
4
3
5
5
6
1
8
7
8
2
10
1
6
5
7
9
10
1 Circuit-breaker
2 Circuit-breaker control unit with spring operating mechanism
3 Busbar I
4 Busbar II
5 Disconnecting switch
Page 20
Oct-11
6
7
8
9
10
Earthing switch
Make-proof earthing switch
Current transformer
Voltage transformer
Cable sealing end
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DQ1 up to 420 kV / 80 kA / 6300 A
Technical Data
Voltage
420 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
650 kV
Lightning impulse withstand voltage (1.2/50 µs)
1425 kV
Switching impulse withstand voltage (250/2500 µs)
1050 kV
Busbar Current
6300 A
Feeder Current
5000 A
Short-circuit breaking current (2 cycles)
80 kA
Short-time withstand current (3 s)
80 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
3600 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 21
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DQ1 up to 420 kV / 80 kA / 6300 A
1
2
3
4
5
6
Circuit-breaker interrupter unit
Spring-stored energy mechanism
Busbar disconnecting switch I
Busbar I
Busbar disconnecting switch II
Busbar II
Page 22
Oct-11
7 Outgoing feeder
disconnecting switch
8 Earthing switch
9 Earthing switch
10 Make-proof earthing switch
11
12
13
14
15
Current transformer
Voltage transformer
Cable sealing end
Circuit-breaker control cubicle
Local control cubicle
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DQ1 up to 550 kV / 63 kA / 5000 A
Technical Data
Voltage
550 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
740 kV
Lightning impulse withstand voltage (1.2/50 µs)
1675 kV
Switching impulse withstand voltage (250/2500 µs)
1250 kV
Busbar Current
5000 A
Feeder Current
5000 A
Short-circuit breaking current (2 cycles)
63 kA
Short-time withstand current (3 s)
63 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
3600 mm
Driving mechanism of circuit-breaker
spring operated
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 23
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DQ1 up to 550 kV / 63 kA / 5000 A
1
2
3
4
5
6
Circuit-breaker interrupter unit
Spring-stored energy mechanism
Busbar disconnecting switch I
Busbar I
Busbar disconnecting switch II
Busbar II
Page 24
Oct-11
7 Outgoing feeder
disconnecting switch
8 Earthing switch
9 Earthing switch
10 Make-proof earthing switch
11
12
13
14
15
Current transformer
Voltage transformer
Cable sealing end
Circuit-breaker control cubicle
Local control cubicle
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Product Line 8DR1
8DN8
Product Line
8DN9
8DQ1
8DR1
- Q0
Solution
Rated voltage
72.5 kV
145 kV
170 kV
245 kV
300 kV
420 kV
420 kV
550 kV
800 kV
Rated shortcircuit current
31.5 kA
40 kA
63 kA
50 kA
63 kA
63 kA
80 kA
63 kA
50 kA
Rated current
2500 A
3150 A
4000 A
4000 A
4000 A
4000 A
6300 A
5000 A
5000 A
Page 25
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Type 8DR1 up to 800 kV / 50 kA / 5000 A
Technical Data
Voltage
800 kV
Frequency
50 / 60 Hz
Power-frequency withstand voltage (1 min.)
960 kV
Lightning impulse withstand voltage (1.2/50 µs)
2100 kV
Switching impulse withstand voltage (250/2500 µs)
1425 kV
Busbar Current
5000 A
Feeder Current
5000 A
Short-circuit breaking current (2 cycles)
50 kA
Short-time withstand current (3 s)
50 kA
Leakage rate per year and gas compartment
< 0.1* %
Bay width
4500 mm
Ambient temperature
-30°C up to +40°C
Installation
indoor/outdoor
Expected life time
> 50 years
Standard
IEC / IEEE
other values on request
* type tested
Page 26
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Main Drivers for the Application of GIS-Solutions (1)
Restricted space availability
High land acquisition costs
Short planning, delivery and installation periods
Minimal maintenance efforts
High degree of safety for operating personnel
Long operating life > 50 year
Page 27
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Main Drivers for the Application of GIS-Solutions (2)
Factory pre-assembled and tested units
Protection from aggressive environmental conditions
Impervious to wind and ice
Low earthquake-sensitivity due to low centre of gravity
Customer-tailored solutions due to modular design
Extension / Refurbishment of AIS
under restricted space availability or during operation
Fast and easy erection of pre-assembled bays or bay sections
Only a few foundations are required for outdoor-GIS
(low civil work efforts)
Page 28
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
61500
AIS / Gas-Insulated Switchgear 245 kV - Indoor
Comparison of Space Requirements 50:1
137500
Page 29
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
67500
101000
AIS / Gas-Insulated Switchgear 420 kV - Indoor
Comparison of Space Requirements 30:1
14000
298000
65400
Page 30
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Experience and Innovation
More than 40 years experience with gas-insulated switchgear
1964
1960
1968
1974
1997
Start of fundamental studies in research and development of SF6-technology
Delivery of first SF6-circuit breaker
Delivery of first GIS
Delivery of first GIL ( 420 kV )
Introduction of intelligent, bay integrated control, monitoring and diagnostic
of newest GIS generation:
1999 Introduction
Self-compression interrupter unit and spring operated mechanism
Introduction of the trendsetting switchgear concept HIS (Highly Integrated Switchgear) for
2000 extension, retrofit and new compact AIS substations
2005 First GIS with electrical endurance capability (class E2)
2007 Introduction of 72.5 kV GIS – a new dimension in compactness
2009 New generation of cast resin insulators for GIS
2011 Introduction of 420 kV / 63 kA GIS – powerful and compact
More than 26,000 bays installed worldwide
More than 286,000 bay-years of operation
Page 31
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Worldwide Experience of Current GIS-Types
Rated voltage up to
145 kV
300 kV
550 kV
Delivered bays
17,200
6,500
2,500
Bay-years of operation
197,000
64,000
25,000
total 26,200 delivered bays
total 286,000 bay-years of operation
Page 32
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Quality
All-encompassing state-of-the-art quality
and environmental management system,
certified in accordance with ISO 9001 and
ISO 14001
Special clean room conditions in the
production
Largest, accredited, manufacturer-owned
testing laboratory
Comprehensive manufacturing inspections
and routine tests on individual components
and complete modules
Type, routine and site-tests according to
IEC 62217-203
Page 33
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Assembly Hall
Factory Berlin
Area 8000 m²
Clean room conditions
Assembly
Locks for material
Routine tests (IEC)
Page 34
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Machining of Vessels
Factory Berlin
Computerized technology
In-house machining of vessels ensures
high quality of sealing surfaces
Own paint shop
Page 35
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Manufacturing of
Cast Resin Insulators
Product range
Excellent quality through:
Spacers, gas tight, - gas permeable
State-of-the-art machinery
Insulated supports, support insulators
Solid know how
Insulated shafts, -flanges, -3 ph.-spacer
Special fabrications such as sinter parts,
manual casting parts
Page 36
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Test and Research Laboratories Berlin
Over 75 years experience
1
High-Power testing laboratory incl. basic laboratory
Switching capability tests
Making and breaking tests
Short-circuit current carrying and withstand tests
Tests of arcing due to internal fault
Max. power for direct tests
Equivalent power for synthetic tests
Short-circuit current for 3s at 35kV
2
High-Voltage testing laboratory incl. outdoor area
Dielectric tests up to
AC voltage (hall)
Partial discharge testing, noise level
Lightning impulse voltage (hall)
Switching impulse voltage (hall)
DC voltage (hall)
AC voltage (outdoor)
3
6400 MVA
114 GVA
238/95 kA
1200
<2
3000
2000
600
1800
kV
pC
kV
kV
kV
kV
Mechanical testing laboratory incl. temperature rise
Temperature-rise tests up to 6300 A (50 / 60 Hz)
Mech. tests (Operation, Endurance, kinematic chain)
Gas-tightness / Airborn noise measurements
Low- and high temperature / Ice condition tests
Degree of protection / Vibrations tests
Page 37
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Voltage Test on Site
Application of test voltage with
frequency-tuned resonant test sets via
direct mounted test transformers
regular SF6-air-bushing
regular test bushing
Page 38
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Self-Compression Interrupter Unit
Page 39
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Self-Compression Interrupter Unit
Arc Quenching Principle up to 145 kV
1
2
3
4
5
1 Contact support
2 Quenching nozzle
3 Main contact
4 Arcing contact
5 Contact cylinder
6 Base
6
Breaker in
“on“-position
Page 40
Oct-11
Opening:
Main contact
open
Opening:
Arcing contact
open
Breaker in
“off“-position
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Self-Compression Interrupter Unit
Arc Quenching Principle above 145 kV
1
2
3
4
5
6
7
8
9
10
11
Breaker in
“on”
position
Page 41
Opening:
Main contact
open
Oct-11
Moving arcing contact
Main contact
Check valve
Compression volume
Check valve
Steering gear
Moving arcing rod
Insulating nozzle
Auxiliary nozzle
Contact cylinder
Heating volume
Opening:
Breaker in
Arcing contact “off” position
open
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Spring Operated Mechanism
1
2
3
4
5
6
On
Off
Page 42
„off“ position
(Closing spring loaded)
Oct-11
7
8
9
10
11
12
13
14
15
16
17
Closing release
Cam plate
Coupling linkage
Operating rod
Closing spring
connection rod
Opening spring
connection rod
Closing spring
Hand-wound mechanism
Charging mechanism
Charging shaft
Roller lever
Closing damper
Operating shaft
Opening damper
Opening release
Mechanism housing
Opening spring
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Customer benefits of self-compression circuitbreakers and spring operated mechanism platforms
General
Interrupter units
Reliable basic
components
Production of key
components at one
location
High availability
High reliability
Page 43
Oct-11
Low demand of
operating forces
Low wear and tear
High breaking capacity
Operating mechanism
Robust & simple
Low operating forces
Low wear and tear
Low load transfer onto
the foundation
High accessibility
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Gas-Insulated Switchgear
Innovation and Trendsetting Technologies
Self-compression interrupter unit combining superior latest technical
requirements with highest reliability
Spring operated mechanism, reliable and maintenance-free
Superior reliability through platform solution of interrupter unit and
operating mechanism for
Live Tank
Dead Tank and
GIS-Solutions
Most compact design worldwide
Page 44
Oct-11
© Siemens AG 2011. All rights reserved
Energy Sector / Power Transmission / High Voltage Substations
Download