SYSTEM COMPONENTS MANUAL SIEX-HC 227 360 & 610 psi (25 & 42 bar) SIEX-HC 227 S-FLOW 465, 490, 725, 780 psi (32, 34, 50 & 55 bar) HFC-227ea HALOCARBON GAS at 360, 465, 490, 610, 725 and 780 psi (25, 32, 34, 42, 50 and 55 bar) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 1/239 INDEX 1. HFC-227EA GAS CONTAINER ....................................................................................................................... 10 1.1. 1.2. 1.3. 2. CYLINDER BRIDLE............................................................................................................................................ 12 PROTECTIVE CAPS ........................................................................................................................................... 12 CONTAINER STICKERS ...................................................................................................................................... 13 CONTAINER VALVES .................................................................................................................................... 16 2.1. 2.2. 2.3. 2.4. 2.5. 2.6. 3. RGS-MAM-11-4 CONTAINER VALVE ............................................................................................................... 17 RGS-MAM-12-4 CONTAINER VALVE ............................................................................................................... 17 RGS-MAM-20 CONTAINER VALVE .................................................................................................................. 18 RGS-MAM-40 CONTAINER VALVE .................................................................................................................. 18 RGS-MAM-50 CONTAINER VALVE .................................................................................................................. 19 RGS-MAM-80 CONTAINER VALVE .................................................................................................................. 19 BURST DISC ................................................................................................................................................. 20 3.1. 3.2. 4. BURST DISC OF CONTAINER VALVES .................................................................................................................... 20 BURST DISC OF CYLINDER ................................................................................................................................. 21 PRESSURE GAUGE ....................................................................................................................................... 22 4.1. 4.2. 4.3. 4.4. 4.5. 4.6. 5. PRESSURE GAUGE TO PILOT CARTRIDGE AND PILOT CYLINDER................................................................................... 22 PRESSURE GAUGE FOR PILOT CARTRIDGE ............................................................................................................. 23 PRESSURE GAUGE ........................................................................................................................................... 24 PRESSURE GAUGE TO PILOT CARTRIDGE AND PILOT CYLINDER WITH ELECTRICAL CONTACTS ............................................ 25 PRESSURE GAUGE TO PILOT CARTRIDGE WITH ELECTRICAL CONTACTS ........................................................................ 26 PRESSURE GAUGE WITH ELECTRICAL CONTACTS..................................................................................................... 27 PNEUMATIC TIME DELAYER ........................................................................................................................ 28 5.1. 5.2. 6. RGS-MAM-4 CONTAINER VALVE ..................................................................................................................... 28 INDIRECT PNEUMATIC TIME DELAYER .................................................................................................................. 29 PRESSURE SWITCH FOR CONTAINER VALVE ................................................................................................ 30 6.1. 6.2. 7. POPRENAXX / POPRENCXX PRESSURE SWITCH ................................................................................................ 30 APRESAXX / APRESCXX PRESSURE SWITCH * .................................................................................................... 31 HAZARDOUS LOCATIONS PRESSURE SWITCH .............................................................................................. 32 7.1. 7.2. 8. POPRECO-AD PSX HAZARDOUS LOCATIONS PRESSURE SWITCH 725 TO 4350 PSI (50 TO 300 BAR)* ......................... 32 POPRECO-ADXXX HAZARDOUS LOCATIONS PRESSURE SWITCHES * ........................................................................ 33 MANUAL ACTUATOR ................................................................................................................................... 34 8.1. 8.2. 8.3. 227DM MANUAL ACTUATOR HEAD ................................................................................................................... 34 227DMR MANUAL ACTUATOR HEAD ................................................................................................................. 35 227DMS MANUAL ACTUATOR HEAD................................................................................................................. 36 9. 227CNM PNEUMATIC-MANUAL ACTUATOR HEAD ...................................................................................... 37 10. PNEUMATIC ACTUATOR HEAD .................................................................................................................... 38 10.1. 10.2. 10.3. 10.4. 10.5. 11. 227CN PNEUMATIC ACTUATOR HEAD ................................................................................................................ 38 227CNTK PNEUMATIC ACTUATOR HEAD............................................................................................................ 39 227TE “T” MALE .......................................................................................................................................... 40 227CO MALE ELBOW..................................................................................................................................... 40 POAD10MM MALE - MALE UNION ADAPTER ..................................................................................................... 41 SUPERVISION SAFETY SYSTEMS................................................................................................................... 42 11.1. 227SOLFC/GLC ACTUATOR MONITORING DEVICE .............................................................................................. 42 11.1.1. 227SOLFC Actuator monitoring device ............................................................................................ 42 11.1.2. 227SOLGLC Actuator monitoring device .......................................................................................... 43 11.1. USTS SECURITY SEAL FOR ELECTRICAL ACTUATOR HEADS........................................................................................ 43 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 2/239 11.2. 11.3. 11.4. 11.5. 12. MRS-1 MAIN/RESERVE SWITCH ...................................................................................................................... 44 RCDS-1 MAINTENANCE SWITCH....................................................................................................................... 44 MRS-2 MAIN/RESERVE SWITCH ....................................................................................................................... 45 RCDS-2 REALISING CIRCUIT DISABLE SWITCH....................................................................................................... 45 ELECTRICAL ACTUATOR HEADS ................................................................................................................... 46 12.1. RE-ASSEMBLED ELECTRICAL ACTUATOR HEAD (24 VDC) ........................................................................................ 46 12.1.1. 227SOL (24 VDC) Re-assembled electrical actuator head................................................................ 47 12.1.2. 227SOLR (24 VDC) Re-assembled electrical actuator head ............................................................. 48 12.2. RE-ASSEMBLED ELECTRICAL ACTUATOR HEAD (24 VDC) ........................................................................................ 49 12.2.1. 227SOLC (24 VDC) Re-assembled electrical actuator head ............................................................. 50 12.2.2. 227SOLCR (24 VDC) Re-assembled electrical actuator head ........................................................... 51 12.3. RE-ASSEMBLED ELECTRICAL ACTUATOR HEAD (125 VAC)....................................................................................... 52 12.3.1. 227SOLC125 (125 VAC) Re-assembled electrical actuator head ...................................................... 53 12.3.2. 227SOLCR125 (125 VAC) Re-assembled electrical actuator head ................................................... 54 12.4. POSOLUFO-V / POSOLUFO-T ELECTRICAL ACTUATOR HEAD.............................................................................. 55 13. EXPLOSION PROOF ELECTRICAL ACTUATOR HEAD....................................................................................... 56 13.1. 13.2. 13.3. 13.4. 14. PNEUMATIC TRIP ........................................................................................................................................ 61 14.1. 14.2. 15. TK-DMS REMOTE MANUAL PULL STATION WITHOUT TENSION ................................................................................ 66 TK-DMS2 REMOTE MANUAL PULL STATION WITHOUT TENSION TO BUILD IN ............................................................. 67 REMOTE MANUAL PULL STATION WITH TENSION ....................................................................................... 69 17.1. 17.2. 18. 227CMCC CABLE-OPERATED MANUAL ACTUATOR HEAD WITH PROTECTIVE BOX ........................................................ 64 227CMC CABLE-OPERATED MANUAL ACTUATOR HEAD ......................................................................................... 65 REMOTE MANUAL PULL STATION WITHOUT TENSION ................................................................................ 66 16.1. 16.2. 17. POSX-NAU PNEUMATIC TRIP .......................................................................................................................... 61 POSX-NAUC PNEUMATIC TRIP WITH PROTECTION BOX ........................................................................................ 62 CABLE-OPERATED MANUAL ACTUATOR HEAD AND WITH PROTECTIVE BOX ............................................... 64 15.1. 15.2. 16. POSOLUFX-V / POSOLUFX-T ELECTRICAL ACTUATOR HEAD ............................................................................... 56 227DEFLAG ELECTRICAL ACTUATOR HEAD* ...................................................................................................... 57 227DEFLAG1 ELECTRICAL ACTUATOR HEAD* .................................................................................................... 58 ELECTRICAL MANUAL ACTUATOR HEAD 227SOLC-AD HAZLOC ............................................................................ 59 TK-DMC REMOTE MANUAL PULL STATION WITH TENSION ..................................................................................... 69 TK-DMC2 REMOTE MANUAL PULL STATION WITH TENSION ................................................................................... 69 MECANICAL CONTROL UNIT ........................................................................................................................ 71 18.1. TK- SIMPLEX MECHANICAL CONTROL UNIT ....................................................................................................... 71 18.1.1. TK-SIMPLEX ...................................................................................................................................... 72 18.1.2. TK-SIMPLEX-B .................................................................................................................................. 72 18.1.3. TK-SIMPLEX-C................................................................................................................................... 72 18.2. TK-COMPLEX MECHANICAL CONTROL UNIT ...................................................................................................... 74 18.2.1. TK-COMPLEX .................................................................................................................................... 75 18.2.2. TK-COMPLEX-B................................................................................................................................. 75 18.2.3. TK-COMPLEX-C ................................................................................................................................. 75 19. MECHANICAL DETECTION KITS TK-KIT-T-F / TK-KIT-T-B / TK-KIT-C-F / TK-KIT-C-B / TK-KIT-A-F / TK-KIT-A-B 77 20. COMPONENTS TO MECHANICAL DETECTION .............................................................................................. 78 20.1. TK-ST SCISSORS ............................................................................................................................................ 78 20.2. TK-EMT ADAPTOR ........................................................................................................................................ 78 20.3. KFTXXX FUSIBLE LINK ..................................................................................................................................... 78 20.4. KBTXXXX THERMO BULB ............................................................................................................................... 79 20.5. KFTTL TEST LINK ........................................................................................................................................... 79 20.6. KWR-50 INOX STEEL CABLE ............................................................................................................................. 80 20.7. KWR-100 INOX STEEL CABLE ........................................................................................................................... 80 UL-EX15547 “UF-MC-HC” - 27-01-2016 3/239 FM-3053302 20.8. 20.9. 20.10. 21. TK-FL END OF LINE ........................................................................................................................................ 80 TK-FL2 END OF LINE ...................................................................................................................................... 81 TK-DPDT DOUBLE MICRO-SWITCH .............................................................................................................. 81 PULLEY ELBOW ............................................................................................................................................ 82 21.1. 21.2. 21.3. TK-CP ......................................................................................................................................................... 82 TK-CP2 ....................................................................................................................................................... 82 TK-CP3* ..................................................................................................................................................... 82 22. TK-TE PULLEY TEE FOR DOUBLE MANUAL ACTUATOR ................................................................................. 83 23. TK-TEC PULLEY TEE FOR DOUBLE MANUAL ACTUATOR ............................................................................... 85 24. THERMAL-MANUAL ACTUATOR HEAD ........................................................................................................ 86 24.1. 24.2. 24.3. KCTM THERMAL-MANUAL ACTUATOR HEAD ....................................................................................................... 86 KCTM-R THERMAL-MANUAL ACTUATOR HEAD .................................................................................................... 88 KCTM-C THERMAL-MANUAL ACTUATOR HEAD .................................................................................................... 89 25. SIEX-NTD-C008 / SIEX-NTD-C018 THERMIC PNEUMATIC-MECHANICAL DETECTOR ...................................... 90 26. PRESSURE SWITCH ...................................................................................................................................... 93 26.1. 26.2. 27. POINPRE PRESSURE SWITCH ........................................................................................................................... 93 POINPRE-GLE PRESSURE SWITCH* ................................................................................................................. 94 HAZARDOUS LOCATIONS PRESSURE SWITCH .............................................................................................. 95 27.1. 27.2. 27.3. 27.4. 27.5. 27.6. POINPREAD-BX PRESSURE SWITCH* ............................................................................................................... 95 POINPREAD-LX PRESSURE SWITCH* ............................................................................................................... 96 POINPREAD-9007 PRESSURE SWITCH* ........................................................................................................... 97 POINPREAD-802X PRESSURE SWITCH* ........................................................................................................... 98 POINPREAD-ATEX PRESSURE SWITCH*........................................................................................................... 99 TABLE OF HAZARDOUS LOCATIONS LIMIT SWITCHES FOR POINPREAD-XX ............................................................. 100 28. POID DISCHARGE INDICATOR MODEL ....................................................................................................... 101 29. SIEX-WD WEIGHING DEVICE ...................................................................................................................... 102 29.1. 29.2. 29.3. 30. HAZARDOUS LOCATIONS WEIGHING DEVICE ............................................................................................ 104 30.1. 30.2. 30.3. 30.4. 30.5. 30.6. 30.7. 30.8. 30.9. 31. SIEX-WD-BX WEIGHING DEVICE*.................................................................................................................. 104 SIEX-WD-LX WEIGHING DEVICE* .................................................................................................................. 105 SIEX-WD-9007 WEIGHING DEVICE* .............................................................................................................. 106 SIEX-WD-802X WEIGHING DEVICE* .............................................................................................................. 107 SIEX-WD-ATEX WEIGHING DEVICE*.............................................................................................................. 108 SIEX-WD-871 WEIGHING DEVICE* ................................................................................................................ 109 SIEX-WD-E51 WEIGHING DEVICE* ................................................................................................................ 110 SIEX-WD-E52 WEIGHING DEVICE* ................................................................................................................ 111 TABLE OF HAZARDOUS LOCATION LIMIT SWITCHES FOR SIEX-WD-XX .................................................................... 112 FIXING BRACKETS (MODULAR, SINGLE AND DOUBLE ROW) ...................................................................... 113 31.1. 31.2. 31.3. 32. SIEX-WD LIMIT SWITCH FOR WEIGHING DEVICE ................................................................................................ 103 SIEX-WD LIMIT SWITCH FOR WEIGHING DEVICE ................................................................................................ 103 SIEX-WD LIMIT SWITCH FOR WEIGHING DEVICE* .............................................................................................. 103 MODULAR CYLINDER ..................................................................................................................................... 113 MANIFOLD SYSTEM IN SIMPLE LINE .................................................................................................................. 113 MANIFOLD SYSTEM IN DOUBLE LINE ................................................................................................................. 114 FIXING BRACKETS ANCHORED TO THE FLOOR WITHOUT WEIGHING DEVICE............................................. 115 32.1. 32.2. 32.3. MODULAR CYLINDER ..................................................................................................................................... 115 MANIFOLD SYSTEM IN SIMPLE LINE .................................................................................................................. 116 MANIFOLD SYSTEM IN DOUBLE LINE ................................................................................................................. 117 33. FIXING BRACKETS WITH WEIGHING DEVICE .............................................................................................. 119 UL-EX15547 “UF-MC-HC” - 27-01-2016 4/239 FM-3053302 33.1. 33.2. 33.3. 34. MANIFOLD FIXING BRACKET IN MANIFOLD CYLINDERS ............................................................................. 124 34.1. 34.2. 35. SIMPLE LINE ................................................................................................................................................ 125 DOUBLE LINE ............................................................................................................................................... 125 FLEXIBLE DISCHARGE HOSE ....................................................................................................................... 126 36.1. 36.2. 36.3. 36.4. 36.5. 36.6. 36.7. 36.8. 36.9. 36.10. 36.11. 36.12. 36.13. 36.14. 36.15. 36.16. 36.17. 37. SIMPLE LINE ................................................................................................................................................ 124 DOUBLE LINE ............................................................................................................................................... 124 MANIFOLD FIXING BRACKET IN MANIFOLD CYLINDERS FOR WEIGHING DEVICE IN MANIFOLD CYLINDERS. 125 35.1. 35.2. 36. MODULAR CYLINDER ..................................................................................................................................... 119 MANIFOLD CYLINDERS IN SIMPLE LINE .............................................................................................................. 120 MANIFOLD CYLINDERS IN DOUBLE LINE ............................................................................................................. 122 FH-15CO FLEXIBLE HOSE .............................................................................................................................. 126 DH-15 FLEXIBLE HOSE .................................................................................................................................. 127 DH-15 I FLEXIBLE HOSE ................................................................................................................................ 127 DH-16 FLEXIBLE HOSE .................................................................................................................................. 128 DH-16 I FLEXIBLE HOSE ................................................................................................................................ 128 DH 20 FLEXIBLE HOSE................................................................................................................................... 129 DH 20 I FLEXIBLE HOSE ................................................................................................................................. 129 DH 21 FLEXIBLE HOSE................................................................................................................................... 130 DH 21 I FLEXIBLE HOSE ................................................................................................................................. 130 FH-20HC FLEXIBLE HOSE ......................................................................................................................... 131 FH-25HC FLEXIBLE HOSE......................................................................................................................... 131 FH-40HC RIGID HOSE ............................................................................................................................. 132 FH-50HC RIGID HOSE ............................................................................................................................. 132 FH-80HC RIGID-GROOVED HOSE ............................................................................................................... 133 FH-80HC34 RIGID-GROOVED HOSE ........................................................................................................... 133 FH-81HC ELBOW RIGID GROOVED ............................................................................................................. 134 FH-81HC34 ELBOW RIGID GROOVED ......................................................................................................... 134 DISCHARGE HOSE ADAPTERS .................................................................................................................... 135 37.1. 37.2. 37.3. POADXXHH LOCA ADAPTERS ........................................................................................................................ 135 POADXXMH ADAPTERS ............................................................................................................................... 135 POADXXHH ADAPTERS ................................................................................................................................ 135 38. POADPMXX WALL BYPASS ........................................................................................................................ 136 39. ACTIVATION FLEXIBLE HOSES .................................................................................................................... 137 39.1. 39.2. 39.3. 39.4. 39.5. 39.6. 39.7. 39.8. FH-6PO ACTIVATION FLEXIBLE HOSE ............................................................................................................... 137 DH 10 ACTIVATION FLEXIBLE HOSE .................................................................................................................. 138 DH 10 I ACTIVATION FLEXIBLE HOSE ................................................................................................................ 138 FH-7PO ACTIVATION FLEXIBLE HOSE ............................................................................................................... 139 DH 11 ACTIVATION FLEXIBLE HOSE .................................................................................................................. 139 DH 11 I ACTIVATION FLEXIBLE HOSE ................................................................................................................ 140 FH-2PO ACTIVATION FLEXIBLE HOSE ............................................................................................................... 140 FH-2POH ACTIVATION FLEXIBLE HOSE ............................................................................................................. 141 40. POLATCU COPPER PIPE 0.24X0.16 IN (6X4 MM) ........................................................................................ 141 41. CHECK VALVES .......................................................................................................................................... 142 41.1. 41.2. 41.3. 41.4. 41.5. 41.6. 41.7. VALAN-80 CHECK VALVE ............................................................................................................................. 142 VALAN-50-125 CHECK VALVE ...................................................................................................................... 143 VALAN-40-23 CHECK VALVE ........................................................................................................................ 143 VALAN-21A CHECK VALVE ........................................................................................................................... 144 VALAN-20A CHECK VALVE ........................................................................................................................... 144 VALAN-15CO CHECK VALVE......................................................................................................................... 145 VALAN-15CO-VF CHECK VALVE ................................................................................................................... 145 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 5/239 42. CVAD15 DIAPHRAGM VALVE* ................................................................................................................... 146 43. MAIN – RESERVE CHECK VALVE ................................................................................................................. 147 43.1. 43.2. 43.3. 227VALAN40-23L CHECK VALVE .................................................................................................................. 147 227VALAN50-125L CHECK VALVE ................................................................................................................ 148 227VALAN-80L CHECK VALVE ...................................................................................................................... 149 44. VALAN-WFR8 / WFR8-316 NON-RETURN VALVE IN LINE ........................................................................... 150 45. VALAN-62 SHUTTLE VALVE ........................................................................................................................ 152 46. PILOT BOTTLE ............................................................................................................................................ 153 46.1. ADAPTERS FOR PILOT BOTTLES ........................................................................................................................ 156 46.1.1. POA8CU Adapter ........................................................................................................................... 156 46.1.2. POA218 Adapter ............................................................................................................................ 156 46.1.3. POA21CU Adapter ......................................................................................................................... 156 46.1.4. POADT8CU Adapter ....................................................................................................................... 156 47. PILOT CARTRIDGE...................................................................................................................................... 157 48. FEDRXX DISCHARGE NOZZLE ..................................................................................................................... 159 48.1. 49. SELECTOR VALVES ..................................................................................................................................... 165 49.1. 49.2. 49.3. 49.4. 49.5. 50. POPCXXX CALIBRATED PLATE ......................................................................................................................... 164 SVDXXX SELECTOR VALVES ............................................................................................................................ 166 SVDXXXSH SELECTOR VALVE.......................................................................................................................... 167 SELECTOR CABINET FOR SELECTOR VALVES ......................................................................................................... 168 SIEX-SVS ELECTRICAL-MANUAL ACTUATOR FOR SELECTOR VALVES ........................................................................ 169 PILOT CARTRIDGE FOR SELECTOR VALVES ACTIVATION .......................................................................................... 169 DISABLE DEVICE VALVE ............................................................................................................................. 172 50.1. SVAXXX DISABLE DEVICE VALVE ...................................................................................................................... 173 50.2. SVAXXXSH DISABLE DEVICE VALVE .................................................................................................................. 174 50.3. END LINE FOR SELECTOR OR DISABLE DEVICE VALVES ............................................................................................ 175 50.3.1. SVAFC End line for selector or disable device valves ...................................................................... 175 50.3.2. SVAGLC End line for selector or disable device valves ................................................................... 175 51. MONITORING OF SELECTOR AND DISABLE DEVICE VALVES FOR HAZARDOUS LOCATIONS ........................ 176 51.1. 51.2. 51.3. 51.4. 51.5. 51.6. 51.7. SVAFC-BX SELECTOR AND DISABLE DEVICE VALVE* ........................................................................................... 176 SVAFC-LX DISABLE DEVICE VALVE* ................................................................................................................ 177 SVAFC-9007 DISABLE DEVICE VALVE* ............................................................................................................ 177 SVAFC-802X DISABLE DEVICE VALVE* ............................................................................................................ 178 SVAFC-871 DISABLE DEVICE VALVE* .............................................................................................................. 178 SVAFC-ATEX DISABLE DEVICE VALVE* ............................................................................................................ 179 TABLE OF HAZARDOUS LOCATIONS LIMIT SWITCHES FOR SVA-XX .......................................................................... 180 52. SVA6-3W THREE WAYS ISOLATED VALVE .................................................................................................. 181 53. POVV8 BLEED VALVE ................................................................................................................................. 182 54. DISCHARGE MANIFOLD FOR CYLINDERS BATTERIES .................................................................................. 183 55. 227CMSXXX DISTRIBUTOR FOR CYLINDERS BATTERIES ............................................................................. 184 55.1. 55.2. 56. VREC / VREC-O MANIFOLD PRESSURE RELIEF VALVE ................................................................................. 185 56.1. 56.2. 57. 227CMSX2XX DISTRIBUTOR ........................................................................................................................ 184 227CMSX3XX DISTRUBUTOR ....................................................................................................................... 184 VREC MANIFOLD PRESSURE RELIEF VALVE ........................................................................................................ 186 VREC-O MANIFOLD PRESSURE RELIEF VALVE .................................................................................................... 186 CSIRN PNEUMATIC SIREN .......................................................................................................................... 187 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 6/239 58. D20 / D15 ODORIZER ................................................................................................................................ 188 58.1. 58.2. D20 ODORIZER ........................................................................................................................................... 189 D15 ODORIZER ........................................................................................................................................... 189 59. POSEÑALES WARNNING SIGN ................................................................................................................... 190 60. COMBINATIONS TO CONTAINER VALVES .................................................................................................. 191 60.1. 60.2. 60.3. RGS-MAM-11-4 / 12-4 ............................................................................................................................. 191 RGS-MAM-20 / 40 / 50 / 80 ..................................................................................................................... 192 RGS-MAM-03/03A ................................................................................................................................... 193 61. ANNEX 1: HFC-227EA CYLINDERS FILL DENSITIES U.S.UNITS ...................................................................... 194 62. ANNEX 1: HFC-227EA CYLINDERS FILL DENSITIES S.I. UNITS ...................................................................... 198 63. ANNEX 2: HFC-227EA CYLINDERS LENGTHS U.S. UNITS ............................................................................. 202 64. ANNEX 2: HFC-227EA CYLINDERS LENGTHS S.I. UNITS ............................................................................... 206 65. ANNEX 3: PILOT CYLINDERS LENGTHS U.S. UNITS ...................................................................................... 210 66. ANNEX 3: PILOT CYLINDERS LENGTHS S.I. UNITS ....................................................................................... 211 67. ANNEX 4: PART NUMBERS LIST ................................................................................................................. 212 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 7/239 References to other manuals of the system -DESIGN MANUAL. SIEX-HC SYSTEM HFC-227EA 1. 2. 3. 4. 5. 6. DESIGN DISTRIBUTION PIPING AND FITTINGS NOZZLE SELECTION SUMMARY OF THE STEPS TO FOLLOW TO CALCULATE A HFC-227EA SYSTEM SOTWARE DISCHARGE CALCULATION INSTALLATION AND MAINTENANCE -INSTALLATION MANUAL. SIEX-HC SYSTEM HFC-227EA 1. 2. 3. 4. 5. 6. 7. 8. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. 46. 47. RELEASING CIRCUIT DISABLE SWITCH RCDS – 1 RELEASING CIRCUIT DISABLE SWITCH RCDS – 2 MAIN/RESERVE SWITCH MRS – 1 MAIN/RESERVE SWITCH MRS – 2 END OF LINE DIODE EOL INSTALLATION OF THE RE-ASSEMBLED ELECTRICAL ACTUATOR INSTALLATION OF THE TAMPER SEAL USTS INSTALLATION OF THE 227SOLFC/GLC END LINE FOR ELECTRICAL ACTUATOR DISTRIBUTION PIPING AND FITTINGS INSTALLING DISCHARGE NOZZLES, WITH A CALIBRATED ORIFICE INSTALLING CYLINDER FIXING BRACKETS INSTALLING THE CONTAINER, CYLINDER OR BOTTLE INSTALLING THE MANIFOLD AND MANIFOLD BRACKETS INSTALLING MAIN / RESERVE CHECK VALVES MODELS 227VALAN40-23L / 227VALAN50-125L / 227VALAN-80L INSTALLING SELECTOR VALVES INSTALLING THE WEIGHING DEVICE SIEX-WD INSTALLING DISCHARGE HOSES INSTALLING FLEXIBLE ACTIVATION HOSES INSTALLATION OF THE BLEED VALVE IN THE RELEASE LINE POVV8 INSTALLING THE 0.24X0.16 (6X4 MM) CUPPER TUBE POLATCU INSTALLING THE PILOT BOTTLE PILOT CARTRIDGE INSTALLING THE REMOTE RELEASE PNEUMATIC LINE INSTALLATION REMOTE RELEASE MANUAL PULL STATION TK-DMS / TK-DMS2 AND PULLEY ELBOWS TK-CP INSTALLATION REMOTE RELEASE MANUAL PULL STATION WITHOUT TENSION TK-DMS2 INSTALLING THE PULLEY-ELBOWS TK-CP INSTALLING THE INOX STEEL CABLE KWR-50 OR KWR-100 INSTALLATING THE END OF LINE TK-FL OR TK-FL2 INSTALLATING THE PRESSURE SWITCH POINPRE INSTALLING THE DISCHARGE INDICATOR MODEL POID. INSTALLING ACTUATOR HEADS INSTALLING THE POSX-NAU PNEUMATIC ACTUATOR INSTALLING THE POSX-NAUC PNEUMATIC ACTUATOR INSTALLING THE TK-SIMPLEX / TK-SIMPLEX-B MECHANICAL CONTROL UNIT INSTALLING THE TK-DMC REMOTE WIRE PULL WITH TENSION (TK-DMC / TK-DMC2) INSTALLING THE PULLEY TEE FOR DOUBLE REMOTE CABLE PULL TKTE INSTALLING THE TEE PULLEY FOR DOUBLE MANUAL CABLE PULL TK-TEC INSTALLING TK-KIT THE MECHANICAL DETECTION KITS INSTALLING PNEUMATIC SIREN CSIRN INSTALLING PNUMATIC TIME DELAYER INSTALLING OR REPLACEMENT THE PRESSURE GAUGE INSTALLING OR REPLACEMENT THE PRESSURE SWITCH INSTALLING THE WARNING SIGNS ANNEX A: MSDS HFC-227EA ANNEX B: MSDS IG-100 -MAINTENANCE MANUAL. SIEX HC. HFC-227EA 1. INTRODUCTION 2. MAINTENANCE PROCEDURES 3. INSPECTION PROGRAMME 4. SERVICE AND MAINTENANCE (BY SPECIALISED PERSONNEL) 5. HYDROSTATIC PRESSURE TEST OF THE CYLINDER 6. SERVICE 7. REMOVING A SINGLE CYLINDER FROM A MODULAR SYSTEM 8. NITROGEN PILOT BOTTLE SERVICE AND MAINTENANCE ANNEX A. GUIDE FOR INSPECTION OF SYSTEM AFTER INSTALLATION ANNEX B. REFILLING PROCEDURE ANNEX C. LIST OF REPLACEMENT PARTS UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 8/239 System components manual This section describes the individual components which make up the system. Some components are optional depending on the application, and are shown as such. NOTE: The fixed extinguishing systems manufactured by SIEX, containing HFC-227ea extinguishing agent, are custom designed for a specific application. If the components described here are assembled with another manufacturer’s components, or are used for another application not described in this manual, the component operation will not be correct. In this case, SIEX does not guarantee nor will be responsible for improper use or application of the product. Any non-approved use or application and/or any non-approved modification of the product or its operation may result in serious accidents and/or personal injury. SIEX is not responsible for any nonapproved use or application. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 9/239 1. HFC-227ea gas container Other names: container, cylinder or bottle The extinguishing agent storage vessel consists of steel container (seamless or welded) fitted with a valve and an internal siphon tube, factory filled with the relevant agent. HFC-227ea Cylinders fill densities SEE ANNEX 1 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 10/239 A A HFC-227ea Cylinders lengths SEE ANNEX 2 A Pilot cilindres lengths SEE ANNEX 3 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 11/239 1.1. Cylinder bridle They are used for the protection of the valve during its transport and handling, all the cylinders have a bridle with the corresponding protective cap. In this way accidents during its transport or handling are avoided. 1.2. Protective caps It consists in a safety and protection device in case of hit of the cylinder. For the protection of the valve during its transport and handling, all the cylinders have a protective cap. In this way accidents during its transport or handling are avoided. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 12/239 1.3. Container stickers In the cylinder are placed stickers as shown in the following figure: UL – FM Sticker Company Sticker Cylinder Sticker UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 13/239 UL – FM sticker Company Sticker Cylinder sticker UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 14/239 PILOT CARTRIDGE Cartridge Sticker Cartridge sticker UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 15/239 2. Container valves Their function is to allow the discharge of extinguishing agent from the cylinders via the various types of release mechanism. The valve, designed and manufacture for gas containers, is the result of extensive R&D and has unique built-in safety features. The valve is factory fitted to the container. The valve is provided with a pressure gauge, pressure switch and bursting disc which meet the DOT and TPED requirements. Valve (21,8x1/14" G outlet) Component RGS-MAM-11-4 Valve (3/4" BSP outlet) Component RGS-MAM-11-4 Valve (21,8x1/14" G outlet) Component RGS-MAM-12-4 Valve (3/4" BSP outlet) Component RGS-MAM-12-4 Valve (3/4" BSP outlet) Component RGS-MAM-20 Valve (1" BSP outlet) Component RGS-MAM-40 Valve (1 1/2" BSP outlet) Component RGS-MAM-40 Valve (2” BSP outlet) Component RGS-MAM-50 Valve (3” Grooved outlet) Component RGS-MAM-80 Operating principles The HFC227ea valve is a high flow, quick opening valve specially designed for fire protection use. It operates using a differential pressure piston mechanism. The container pressure is used with the valve to create a positive force on the piston, thus sealing the valve. The valve opens when pressure is relieved from the upper chamber and the piston move upwards, thus allowing HFC to flow out through the piping network. The upper chamber pressure is relieved via an actuator. Each valve includes the following elements: Bust disc to relieve pressure in case of needed. Discharge port complete with safety cap Actuation port for connecting an electrical discharge head, complete with safety cap. Pneumatic connection (pilot port) for operation as a main valve in cylinder banks. Ports to connect the pressure gauge and/or the pressure switch. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 16/239 2.1. RGS-MAM-11-4 Container Valve Used in SIEX-SMS and as a pilot bottle. Technical Information Container valve RGS-MAM-11-4 Connection to pressure switch Connection to pressure gauge Pilot port Actuation port Valve outlet thread (female thread) (female thread) (female thread) (male thread) (male thread) Thread of bursting disc cap (female thread) Connection to container (male thread) Approvals NO 1/8” NPT NO 3/4” BSP W21.8x1/14” 3/4" BSP 1/4” BSP W28.8x1/14” 1”NPT UL-EX15547 FM-3053302 2.2. RGS-MAM-12-4 Container Valve Used in SIEX-SMS and as a pilot bottle. Technical Information Container valve RGS-MAM-12-4 Connection to pressure switch Connection to pressure gauge Pilot port Actuation port Valve outlet thread Thread of bursting disc cap Connection to container (female thread) (female thread) (female thread) (male thread) (male thread) (female thread) (male thread) Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 1/8” NPT 1/8” NPT 1/4” BSP 3/4” BSP W21.8x1/14” 3/4" BSP 1/4” BSP W28.8x1/14” 1”NPT UL-EX15547 FM-3053302 17/239 2.3. RGS-MAM-20 Container Valve Technical Information Container valve RGS-MAM-20 Connection to pressure switch (female thread) 1/8” NPT Connection to pressure gauge (female thread) 1/8” NPT Pilot port (female thread) 1/4” BSP Actuator port (male thread) 3/4” BSP Valve outlet thread (male thread) 3/4” BSP (female thread) 1/4" BSP UL-EX15547 FM-3053302 Thread of bursting disc cap Approvals 2.4. RGS-MAM-40 Container Valve Technical Information Container valve RGS-MAM-40 Connection to pressure switch (female thread) 1/8” NPT Connection to pressure gauge (female thread) 1/8” NPT Pilot port (female thread) 1/4” BSP Actuator port (male thread) Valve outlet thread (male thread) 3/4” BSP 1” BSP 1 1/2" BSP Thread of bursting disc cap (female thread) Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 3/8” BSP UL-EX15547 FM-3053302 18/239 2.5. RGS-MAM-50 Container Valve Technical Information Container valve RGS-MAM-50 Connection to pressure switch (female thread) 1/8” NPT Connection to pressure gauge (female thread) 1/8” NPT Pilot port (female thread) 1/4” BSP Actuator port (male thread) 3/4” BSP Valve outlet thread (male thread) 2” BSP 1/2" BSP 3/8” BSP UL-EX15547 FM-3053302 Thread of bursting disc cap (female thread) Approvals 2.6. RGS-MAM-80 Container Valve Technical Information Container valve RGS-MAM-80 Connection to pressure switch (female thread) 1/8” NPT Connection to pressure gauge (female thread) 1/8” NPT Pilot port (female thread) 1/4” BSP (male thread) 3/4” BSP (male thread) 3” Grooved (female thread) 3/8” BSP UL-EX15547 FM-3053302 Actuator port Valve outlet thread Thread of bursting disc cap Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 19/239 3. Burst disc This burst disc is a safety mechanism that protects the system against excess pressure. 3.1. Burst disc of container valves This disc is a safety mechanism that protects against excess pressure. It is housed in a side port of the container valve and is locked by a hollow hex-head screw drilled transversely to allow controlled exit of gas when the disc is burst. This burst disc meets the DOT and TPED requirements. 2 1 3 The burst disc assembly consists of: 1- Disc housing in the valve 2- Burst disc 3- Exhaust plug Burst disc of container valves Diameter of the bursting disc RGS-MAM-11-4 / 12-4 / 20 RGS-MAM-40 RGS-MAM-50 0.43x0.23 in (11x6 mm) 0.55x1.02 in (13.9x8 mm) 0.55x1.02 or 0.71x0.43 in Exhaust plug thread RGS-MAM-80 RGS-MAM-11-4 / 12-4 / 20 RGS-MAM-40 RGS-MAM-50 RGS-MAM-80 0.55x1.02 in (13.9x8 mm) 1/4” BSP 3/8” BSP 3/8” BSP or 1/2” BSP 3/8” BSP UL-EX15547 FM-3053302 (13.9x8 or 18x11 mm) Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 20/239 3.2. Burst disc of cylinder This disc is a safety mechanism that protects against excess pressure. It is housed in a side port of the cylinder when the cylinder has installed the RGS-MAM-80 container valve and is locked by a hollow hexhead screw drilled transversely to allow controlled exit of gas when the disc is burst. This burst disc meets the DOT requirements. 3 2 4 1 The burst disc is compounded by: 1234- Housing of the disc in the cylinder Cupper washer Exhaust plug Burst disc Burst disc in the cylinder Diameter of the bursting disc RGS-MAM-80 3/4” BSP Thread of the cylinder bursting disc cap UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 0.93x0.71 in (23,5x18 mm) “UF-MC-HC” - 27-01-2016 21/239 4. Pressure gauge 4.1. Pressure gauge to pilot cartridge and pilot cylinder Assembled in the factory directly on the pilot cartridge, it indicates at all times the pressure (in bar and psi) in the pilot cartridge charged with extinguishing agent. The connection of the pressure gauge to the valves has a non-return mechanism which allows the pressure gauge to be changed or removed with the pilot cartridge pressurised. Technical Information Pressure gauges Part number UF40I-P150 UF40I-P200 Approvals UL-EX15547 FM-3053302 Working pressure 2170 psi (150 Bar) 2900 psi (200bar) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 22/239 4.2. Pressure gauge for pilot cartridge Assembled in the factory directly on the pilot cartridge, it indicates at all times the pressure (in bar and psi) in the cylinder charged with extinguishing agent. The connection of the pressure gauge to the valves has a non-return mechanism which allows the pressure gauge to be changed or removed with the pilot cartridge pressurised. *Remark Technical Information Pressure gauges Part number Approvals UF40I-P0-XXX UL-EX15547 FM-3053302 *Remark: The pressure range of the gauge will correspond to the charge of the pilot cartridge and may not look identical to the illustration. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 23/239 4.3. Pressure gauge Assembled in the factory directly on the side port of the container valve, it indicates at all times the pressure (in bar and psi) in the cylinder charged with extinguishing agent. The connection of the pressure gauge for SIEX-HC227 and Inert Gas (Pilot bottle) to the container valves have a non-return mechanism which allows the pressure gauge to be changed or removed with the cylinder pressurised. M Technical Information Pressure gauges Part number 362 psi (25 Bar) UF40H-P32 464 psi (32 Bar) UF40H-P34 493 psi (34 Bar) UF40H-P42 609 psi (42 Bar) UF40H-P50 725 psi (50 Bar) UF40H-P55 798 psi (55 Bar) Approvals UL-EX15547 FM-3053302 Working pressure UF40H-P25 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 24/239 4.4. Pressure gauge to pilot cartridge and pilot cylinder with electrical contacts Assembled in the factory directly on the pilot cartridge, it indicates at all times the pressure (in bar and psi) in the pilot cartridge charged with extinguishing agent. In option exists the same pressure gauge with electrical contacts. The connection of the pressure gauge to the valves has a non-return mechanism which allows the pressure gauge to be changed or removed with the pilot cartridge pressurised. Technical Information Pressure gauges with electrical contacts Part number UF40I-E150 UF40I-E200 Approvals UL-EX15547 FM-3053302 Working pressure 2170 psi (150 Bar) 2900 psi (200 bar) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 25/239 4.5. Pressure gauge to pilot cartridge with electrical contacts Assembled in the factory directly on the pilot cartridge, it indicates at all times the pressure (in bar and psi) in the pilot cartridge charged with extinguishing agent. The connection of the pressure gauge to the valves has a non-return mechanism which allows the pressure gauge to be changed or removed with the pilot cartridge pressurised. *Remark Technical Information Pressure gauges with electrical contacts Part number Approvals UF40I-E0-xxx UL-EX15547 FM-3053302 *Remark: The pressure range of the gauge will correspond to the charge of the pilot cartridge and may not look identical to the illustration. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 26/239 4.6. Pressure gauge with electrical contacts Assembled in the factory directly on the side port of the container valve, it indicates at all times the pressure (in bar and psi) in the cylinder charged with extinguishing agent. This pressure gauge has electrical contacts to send a signal to the control panel in order to monitoring the pressure of the cylinder. The connection of the pressure gauge for SIEX-HC227 and Inert Gas (Pilot bottle) to the valves have a non-return mechanism which allows the pressure gauge to be changed or removed with the cylinder pressurised. M Technical Information Pressure gauges with electrical contacts Part number UF40H-E25 362 psi (25 Bar) UF40H-E32 464 psi (32 Bar) UF40H-E34 493 psi (34 Bar) UF40H-E42 609 psi (42 Bar) UF40H-E50 725 psi (50 Bar) UF40H-E55 798 psi (55 Bar) Approvals UL-EX15547 FM-3053302 Working pressure UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 27/239 5. Pneumatic time delayer The pilot bottle with the pneumatic delayer has the function of delay the activation of the cylinders (during 30 or 60 seconds) in order to give time to evacuate the protected area. It is installed between the pilot bottle filled with nitrogen and the first slave cylinder in battery systems (indirect pneumatic delayer). When the activation of the pilot bottle or master cylinder is done, the gas goes inside the pneumatic delayer slowly. When it reaches a determinate pressure, the valve opens and allows the gas goes to the pneumatic activation line, activating the cylinder battery. The pneumatic delayer is supplied from factory assembled to an empty bottle, with adaptors in the inlet and outlet connections in order to be able to connect it to the activation line and with a manual actuator which abort the delay in case of need. 5.1. RGS-MAM-4 Container valve Actuation Port OUTLET INLET Cylinder connection Technical Information Container valve RGS-MAM-4 Inlet Outlet Actuation port Connection to the cylinder Approvals UL-EX15547 FM-3053302 1/2” BSP 1/2” BSP 3/4” BSP W28.8x1/14” 1” NPT (female thread) (female thread) (male thread) (male thread) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 28/239 5.2. Indirect pneumatic time delayer Manual actuator head Pneumatic delayer Container valve Adaptor 1/2” BSP – 1/4" BSP Activation hose Activation hose Adaptor 1/2” BSP – 1/4" BSP Support brackets 2 liters Cylinder Indirect Pneumatic Time Delayer installed between pilot bottle and battery system Limitation in the use of the Indirect Pneumatic Time Delayer Indirect pneumatic Time Delayer Cylinder capacity Delayed time with pilot bottle of 0.23 ft³ at 2175 psi (6.7 liters at 150 bar) Delayed time with pilot bottle of 0.47 ft³ at 2175 psi (13.4 liters at 150 bar) 0.071 ft ³ (2 l) SIEX-RNI-6/30 SIEX-RNI-13/30 SIEX-RNI-13/60 Working temperature range 26.3 seconds 28.1 seconds 55.2 seconds 23º to 122ºF (-5º to 50º C) UL-EX15547 FM-3053302 Approvals Pneumatic delayer Container valve Discharge manifold Pilot bottle UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 29/239 6. Pressure switch for container valve The pressure switch is a monitoring device which sends an electrical signal to the fire control panel when the pressure in the cylinder falls. 6.1. POPRENAxx / POPRENCxx Pressure switch It is connected to the container valve and there are two variants NC (Normally closed, it opens with pressure) or NO (normally open, it closes with pressure). Inside of this device is housed a dry contact which opens or closes an electrical circuit depending on the variant mentioned above. They are supplied from the factory assembled in the container valve in the proper port. The container valves in their connection for the pressure switch have a non-return mechanism which allows the pressure switch to be changed or removed with the cylinder pressurized. Pressure switch POPRENAxx / POPRENCxx Regulation field for HFC-227ea: Option 1 IP54 Regulation field for Inert gases: (Pilot cylinders) N.O. POPRENA20 POPRENA50 POPRENA80 145-290 psi (10-20 bar) 290-725 psi (20-50 bar) 725-1160 psi (50-80 bar) N.C. POPRENC20 POPRENC50 POPRENC80 145-290 psi (10-20 bar) 145-725 psi (10-50 bar) 725-1160 psi (50-80 bar) N.O. POPRENA150 POPRENA250 POPRENA300 725-2175 psi (50-150 bar) 1450-3625 psi (100-250 bar) 725-4350 psi (50-300 bar) N.C. POPRENC150 POPRENC250 POPRENC300 725-2175 psi (50-150 bar) 1450-3625 psi (100-250 bar) 750-4350 psi (50-300 bar) 1/8” NPT Faston 48 V 0.2 A 0.5 A Valve connection Electrical terminals Maximum voltage Inductive current Resistant current Protection index options Option 1 Option 2 Option 2 IP67 CAP+ Flying leads + connector UL-EX15547 FM-3053302 Mechanical life Contact type IP 54 IP 67 6 10 cicles NO / NC UL-EX15547 FM-3053302 Approvals “UF-MC-HC” - 27-01-2016 30/239 6.2. APRESAxx / APRESCxx Pressure switch * It is connected to the container valve and there are two variants NC (Normally closed, it opens with pressure) or NO (normally open, it closes with pressure). Inside of this device is housed a dry contact which opens or closes an electrical circuit depending on the variant mentioned above. They are supplied from the factory assembled in the container valve in the proper port. The container valves in their connection for the pressure switch have a non-return mechanism which allows the pressure switch to be changed or removed with the cylinder pressurized. Pressure switch APRESAxx / APRESCxx Regulation field for HFC-227ea: N.O. N.C. Regulation field for Inert gases: (Pilot cylinders) N.O. N.C. Valve connection Electrical terminals Maximum voltage Inductive current Resistant current Protection index Mechanical life Contact type APRESA20 APRESA50 APRESA80 APRESC20 APRESC50 APRESC80 APRESA150 APRESA250 APRESC150 APRESC250 145-290 psi (10-20 bar) 290-725 psi (20-50 bar) 725-1160 psi (50-80 bar) 145-290 psi (10-20 bar) 145-725 psi (10-50 bar) 725-1160 psi (50-80 bar) 725-2175 psi (50-150 bar) 1450-3625 psi (100-250 bar)) 725-2175 psi (50-150 bar) 1450-3625 psi (100-250 bar) 1/8” NPT Faston 48 V 0.2 A 0.5 A IP 65 6 10 cicles NO / NC UL , CE Approvals * This is not part of the FM Approval. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 31/239 7. Hazardous locations pressure switch 7.1. POPRECO-AD PSX Hazardous locations Pressure switch 725 to 4350 psi (50 to 300 bar)* Its function is to warn against a partial lose or total discharge of extinguishing agent of a cylinder. It has both variants included, NC (normally closed, with open pressure) or NO (normally open, with closed pressure). Inside of this device is housed a dry contact which opens or closes an electrical circuit depending on the variant mentioned above. The valves in their connection for the pressure switch have a non-return mechanism which allows the pressure switch to be changed or removed with the cylinder pressurized. It has special design features which make this device suitable for being used in areas with atmospheres with explosion risk. It is said that an atmosphere has risk of explosion when in normal conditions it would have not this danger, but due to foreseeable events, the composition of this atmosphere could change in a such way that an explosion could happen. Technical Information Pressure switch POPRECO- AD PSX Valve connection 1/8” NPT Max. imput power Pi 0.75mA Ii 100mA Input current IP65 Protection index POPRECO-AD PSM 145 to 725psi (10 to 50 bar) POPRECO-AD PSP 725 to 4350 psi (50 to 300 bar) Pressure setting at 725 psi (50 bar) Pressure setting at 798 psi (55 bar) Pressure setting at 1450 psi (100 bar) Pressure setting at 1740 psi (120 bar) Pressure setting at 2170 psi (150 bar) Pressure setting at 2900 psi (200 bar) 435 psi (30 bar) decreasing 580 psi (40 bar) decreasing 1305 psi (90 bar)decreasing 1595 psi (110 bar) decreasing 2030 psi (140 bar) decreasing 2610 psi (180Bar) decreasing Approvals EUROPEAN UNION ATEX Directive 94/9/EC II 1 G Ex ia IIC T6 IP 65 ATEX EN 60079-0, 60079-1, 50281-1-1 EN 50014, 50020 * This is not part of the UL Listed & FM Approval. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 32/239 7.2. POPRECO-ADxxx switches * Hazardous locations pressure Its function is to warn against a partial lose or total discharge of extinguishing agent of a cylinder. It has both variants included, NC (normally closed, it opens with pressure) or NO (normally open, it closes with pressure). Inside of this device is housed a dry contact which opens or closes an electrical circuit depending on the variant mentioned above. The valves in their connection for the pressure switch have a non-return mechanism which allows the pressure switch to be changed or removed with the cylinder pressurized. It has special design features which make this device suitable for being used in areas with atmospheres with explosion risk. It is said that an atmosphere has risk of explosion when in normal conditions it would have not this danger, but due to foreseeable events, the composition of this atmosphere could change in a such way that an explosion could happen. Pressure switch POPRECO- AD xxx Regulation field for HFC-227ea: POPRECO-AD 24, Pressure setting at 362 psi (25 bar) POPRECO-AD 48,3 Pressure setting at 362 psi (25 bar) Pressure setting at 464 psi (32 bar) Pressure setting at 493 psi (34 bar) Pressure setting at 609 psi (42 bar) POPRECO-AD 103,4 Pressure setting at 464 psi (32 bar) Pressure setting at 493 psi (34 bar) Pressure setting at 609 psi (42 bar) Pressure setting at 725 psi (50 bar) Pressure setting at 798 psi (55 bar) Pressure setting at 1450 psi (100 bar) 1/8´´ NPT 275 psi (19 bar) 377 psi (26 bar) 406 psi (28 bar) 522 psi (36 psi) 406 psi (28 bar) 435 psi (30 bar) 522 psi (36 psi) 638psi (44 bar) 725 psi (50bar) 1305 psi (90 bar) Regulation field for Inert gases: (Pilot cylinders) POPRECO-AD 413.7 Pressure setting at 2170 psi (150 bar) Pressure setting at 2900 psi (200 bar) 1740 psi (120 psi) 2466 psi (170 bar) Valve connection 1/8” NPT Maximum voltage 250 VAC Current 5A Protection index IP66 Contact type SC (NO and NC) Approvals Approvals * This is not part of the FM Approval. UNITED STATES AND CANADA UL Listed, cUL Certified Class I, Division 1 and 2, Groups A, B, C & D Class II, Division 1 and 2, Groups E, F & G Class III Class I, Zone 1, Group IIC Enclosure Type 4X Low voltage Directive (LVD) 73/23/EC & 93/68/EEC Compliant to LVD Products rated lower than 50 VAC and 75 VCD are outsider the scope of the LVD The Low Voltage Directive does not apply products for use in hazardous locations EUROPEAN UNION ATEX Directive 94/9/EC II 2 G Ex d IIC T6 II 2 D T+85C Tamb = -50°C to +80°C IP 66 II 1 G EEx ia IIC T6 Pressure Equipament Directive (PED) 97/23/EC UL-EX15547 FM-3053302 UL-EX15547 FM-3053302 RUSSIA Gosgortechnadzor Permit (OPTIONAL – code M406) 0ExiaIICT6 1ExdIICT6X UKRAINE Gosnadzorohrantruda Permit 1ExdIICT6X “UF-MC-HC” - 27-01-2016 33/239 8. Manual actuator 8.1. 227DM manual actuator head The purpose of this actuator head is to actuate by manual force the valves of the cylinders on which it is fitted. Once the safety ring is removed from the actuator, the manual lever can be turned in the opposite direction from its resting position to produce the release. The manual actuator 227DM can be installed in the upper actuation port of the container valve RGSMAM-20/40/50/80/11-4 and 12-4 by means of a revolving nut which allows its right orientation also, it can be installed in the electrical actuator. STAND BY ACTIVATED Level 227DM Safety ring POSITION 1: STAND-BY POSITION 2: ACTIVATED 2 1- 2- Reassembled electrical actuator head 227SOL/ 227SOLR/ 227SOLC/ 227SOLCR/ 227SOLC125 /227SOLCR125 Manual actuator 227DM With holes 1 Technical Information Manual actuator head 227DM Code 227DM Re-assembled requirements Manual (lever) Connection to the container valve RGS-MAM-20/40/50/80 and RGS-MAM-11/12 and to Re-assembled electrical actuator head 3/4” BSP Female Route of the lever to obtain the activation 86º UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 34/239 8.2. 227DMR manual actuator head The purpose of this actuator head is to actuate by manual force the valves of the cylinders on which it is fitted. Once the safety ring is removed from the actuator, the manual lever can be turned in the opposite direction from its resting position to produce the release. The manual actuator 227DMR ONLY can be installed in the actuation port of the valve RGS-MAM-03/03A and it shall be fixed with an o-ring between the revolving nut (which allows its right orientation) and the RGS-MAM-03/03A. STAND BY ACTIVATED Level 227DMR Safety ring POSITION 1: STAND-BY POSITION 2: ACTIVATED Without holes Technical Information Manual actuator head 227DMR Code 227DMR Re-assembled requirements Manual (lever) RGS-MAM-03/03A (only the 227DMR) (actuation port) Route of the lever to obtain the activation 86º UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 3/4” BSP Female “UF-MC-HC” - 27-01-2016 35/239 8.3. 227DMS Manual actuator head The purpose of this actuator head 227DMS is to actuate by manual force the valves of the cylinders on which it is fitted. Once the safety ring is removed from the actuator, the manual lever can be turned in the opposite direction from its resting position to produce the release. The 227DMS manual actuator head is connected ONLY to the upper actuation port of the electrical actuator 227SOL / 227SOLR / 227SOLC / 227SOLCR / 227SOLC125 / 227SOLCR125 by means of a revolving nut which allows its right orientation. 2 1 1- Re-assembled electrical actuator head 227SOL / 227SOLR / 227SOLC / 227SOLCR / 227SOLC125 / 227SOLCR125 2- Manual actuator head 227DMS Technical Information Manual actuator head 227DMS Code 227DMS Re-assembled requirements Activation push button UL-EX15547 FM-3053302 Manual (safety ring) 227DMS 227DMSP Aluminium Plastic Connection to electrical actuator 227SOL / 227SOLR / 227SOLC / 227SOLCR / 227SOLC125 / 227SOLCR125 3/4” BSP Female Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 36/239 9. 227CNM Pneumatic-manual actuator head This actuator head consists in a combination of the manual actuator and the pneumatic actuator and its purpose is to actuate by any of both forces, the valves where it is installed. The pneumatic-manual actuator head 227CNM is connected to the upper actuation port of the valve. The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction. All the pneumatic-manual actuator heads have a tee 227TE or an elbow 227CO fitted or an adaptor POA8CU for copper tube in their pneumatic actuation ports. This item is supplied from the factory already fitted with its corresponding o-ring or metal-to-plastic gasket or Teflon tape. 227CO 227TE POA8CU O-ring, metal-plastic joint or teflon tape Technical Information Pneumatic-manual actuator head 227CNM Code 227CNM Automatic (spring) Lever (Manual) Re-assembled requirements Connection to the upper and side actuation port of the container valve RGSMAM-11/12 and RGS-MAM-20/40/50/80 or to all the re-assembled electrical actuator heads 227SOLXX 3/4” BSP Female Thread of the pneumatic actuation port (for 227TE or 227CO) 1/4” BSP Female Joint between the pneumatic-manual actuator head and the Tee or the elbow O-ring or metal-plastic joint or Teflon tape Route of the lever to obtain the activation 86º UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 37/239 10. Pneumatic actuator head 10.1. 227CN Pneumatic actuator head The purpose of this actuator head is to pneumatically actuate the valves of the cylinders on which it is fitted. Once all the discharge hoses are connected the head will activate when the system is released and pressure from the pressurised gas in the pilot cylinder or bottle reaches the head. The 227CN pneumatic actuator head is connected to the upper actuation port of the RGS-MAM20/40/50/80 and RGS-MAM-11-4 / 12-4 valves. The mechanism for fitting the 227CN actuator to the cylinder valve is using a swivel nut which allows it to face the right direction. It can be connected to the electrical actuator head 227SOL / 227SOLR / 227SOLC / 227SOLCR / 227SOLC125 / 227SOLCR125. All the pneumatic actuator heads have a tee 227TE or an elbow 227CO fitted in their pneumatic actuation ports. This item is supplied from the factory already fitted with its corresponding o-ring or optionally by a metal-to-plastic gasket or Teflon tape. “Tee” or elbow connecting release hoses O-ring or metal-plastic joint Revolving nut Technical Information Pneumatic actuator head 227CN Code Re-assembled requirements Connection to container valve RGS-MAM-20/40/50/80/11-4/12-4 (actuation port) or to all the re-assembled electrical actuator heads 227SOLXX Thread of the pneumatic actuation port (for 227TE or 227CO) Joint between the pneumatic actuator head (227CN) and the Tee (227TE) or the elbow (227CO) 3/4” BSP Female 1/4" BSP Female O-ring or metal-to-plastic joint or Teflon tape UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 227CN Automatic (spring) “UF-MC-HC” - 27-01-2016 38/239 10.2. 227CNTK Pneumatic actuator head The purpose of this actuator head is to pneumatically actuate the valves of the cylinders on which it is fitted. Once all the discharge hoses are connected the head will activate when the system is released and pressure from the pressurised gas in the pilot cylinder or bottle reaches the head. The 227CNTK pneumatic actuator head is connected to the upper actuation port of the RGS-MAM20/40/50/80 and RGS-MAM-11-4 / 12-4 valves. The mechanism for fitting the 227CNTK actuator to the cylinder valve is directly by its body, so install it in its correct direction is done by the tee 227TE or elbow 227CO with teflon tape. It can be connected to the electrical actuator head 227SOL / 227SOLR / 227SOLC / 227SOLCR / 227SOLC125 / 227SOLCR125. “Tee” or elbow connecting release hoses Teflon tape Technical Information Pneumatic actuator head 227CNTK Code Re-assembled requirements Connection to container valve RGS-MAM-20/40/50/80/11-4/12-4 (actuation port) or to all the re-assembled electrical actuator heads 227SOLXX Thread of the pneumatic actuation port (for 227TE or 227CO) Joint between the pneumatic actuator head (227CNTK) and the Tee (227TE)or the elbow (227CO) 3/4” BSP Female 1/4" BSP Female Teflon tape UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 227CNTK Automatic (spring) “UF-MC-HC” - 27-01-2016 39/239 10.3. 227TE “T” male It is used in cylinder bank systems to connect the release hose to the pneumatic actuators. They are installed in the upper thread of the pneumatic actuator of every slave valves, except in the last valve where an elbow is installed. Technical Information “T” male 227TE Body Connection to both ends Brass CuZn39Pb3 1/4” BSP UL-EX15547 FM-3053302 Approvals 10.4. 227CO Male elbow They are used in cylinder bank system for connecting the release hose to the last pneumatic discharge head. As well, it is installed in the pilot port of the master valve (pilot bottle) in this way the valve of the master valve is connected with the slave. Technical Information Male elbow 227CO Body Connection to both ends Approvals UL-EX15547 FM-3053302 Brass CuZn39Pb3 1/4” BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 40/239 10.5. POAD10MM Male - male union adapter They are used to connect the pneumatic actuator, the pneumatic-manual actuator or the pressure trip with the pilot hose or copper tube. The sealing between the adaptor and the device is made by a metal-toplastic joint, an o-ring or Teflon tape. Technical Information Male POAD10MM Body Connection to both ends Approvals UL-EX15547 FM-3053302 Steel 1/4” BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 41/239 11. Supervision Safety Systems 11.1. 227SOLFC/GLC Actuator monitoring device It has the function of detect at every moment the status of the electrical actuator (connected or disconected). When you disconnect the electrical actuator the micro switch send electrical signal to the control panel with its status information. The micro switch is integrated in the solenoid and pneumatic actuator nut. Inside, it has two contacts, one NC (normally closed) and another one NO (normally open) that changes the status when the switch is activated. Both can be used depending on the installation requeriments. 11.1.1. 227SOLFC Actuator monitoring device Technical Information Actuator monitoring device 227SOLFC Location Box Plastic Tensión 24V (DC) Intensity 3A Velocity response in miliseconds >1,5 Mechanical durability in millons of operations 10 Minimum torque of activation 6N Minimum torque of positive openning 10 N Protection range Connection for cables UL-EX15547 FM-3053302 RGS-MAM-11-4/ 12-4/ 20/40/50/80 IP65 1 threaded inlet M20x1.5 Instalation Non corrosive; inside Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 42/239 11.1.2. 227SOLGLC Actuator monitoring device Actuator monitoring device 227SOLGLC Location RGS-MAM-11-4/ 12-4/ 20/40/50/80 Box Metal Tensión 24V (AC) Intensity 3A Mechanical durability in millons of operations Protection range 15 IP67 NEMA 1, 4, 12, 13. 1 threaded inlet 1/2” NPT Connection for cables Instalation Non corrosive; inside Certifications CE, UL, CSA and CCC UL-EX15547 FM-3053302 Approvals 11.1. USTS Security seal for electrical actuator heads This seal is obligatory for all solenoids, when you installing the solenoid you must put the seal across the prisioner screw and encircle the solenoid. The function of this, when you are going to do maintenance, you must disconnect the solenoid and cut the seal, when you cut the seal you remember change the safety switches. Security seal Prisioner screw UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 43/239 11.2. MRS-1 Main/Reserve Switch This main/reserve panel is a key switch; wich enables a user to switch to reserve protection after the main protection has been released in order to maintain protection of that área. Two leds indicate “main” and “reserve”. When the key is inserted and turned towards the “reserve”, the red illuminates and the green led indicatin “main”turns off. The key can only be removed in the “main” position. The information is silk- screend on a two-gang stainless steel plate. Technical Information Main / Reserve switch MRS-1 Switch rated at Leds rated at Mounting screws supplied Approvals 10A 250VAC, 15A 125250 VAC, the rating is 15A up to 30VDC. 10mA each for a total current draw of 20mA (4) 6-32 x ½” & (4) 6-32 x 1” UL-EX15547 FM-3053302 11.3. RCDS-1 Maintenance switch This Release Circuit Disable Switch is listed by UL to meet the NFPA 2001 requirements. This maintenance switch panel is a key switch; wich disconnects actuation circuits in the system to prevent accidental discharge during maintenance operations. This switch has two leds. When the key is inserted and turned towards system inactive, the red led illuminates and the green led indicating system armed turn off. The key can be removed either with the system armed or inactive. After maintenance, is mandatory to place back the electrical actuator (solenoid) in its position with the securement device. Also, the key of the maintenance switch must be turned towards system armed, in order to left the system under service. Technical Information Maintenance Switch RCDS-1 Switch rated at Leds rated at Mounting screws supplied Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 10A 250VAC, 15A 125250 VAC, the rating is 15A up to 30VDC. 10mA each for a total current draw of 20mA (4) 6-32 x ½” & (4) 6-32 x 1” UL-EX15547 FM-3053302 44/239 11.4. MRS-2 Main/reserve Switch The device consists of a stainless steel faceplate, green Led, amber Led, and a switch assembly. It is designed to mount on a standard single gang electrical enclosure. The MRS-2 complies with the requirements of NFPA Standards: For easy changeover between primary and reserve agent supplies when uninterrupted protection is required With the key in the Main position, the green LED will be lit and the release circuit will be connected to the main bank of the extinguishing agent. Turning the key to the Reserve position turns off the green LED and lights the yellow LED while disconnecting the release circuit from the main bank of the extinguishing agent and connecting it to the reserve bank. Technical Information Main / Reserve switch MRS-2 Dimensions Contact Rating Power Requirements Environmental Specifications Approvals 2 3/4” W x 4- 1/2" Hx 2”D (Aproximate) Mount son single gang or Handy box. 1 AMP 40 VDC 24 VDC, 10mA Indoor use only UL-EX15547 FM-3053302 11.5. RCDS-2 Realising circuit disable switch The device consists of a key operated DPDT switch and 1 green and 1 amber LED. It is mounted to a stainless steel faceplate designed to mount to a single gang electrical enclosure. The RCDS-2 complies with the requirements of NFPA Standards: NFPA 12 - Carbon Dioxide Extinguishing Systems. NFPA 2001 - Clean Agent Fire Extinguishing Systems. Also, it complies with the NFPA 72 in the following way: Specifying a physical switch to disconnect the release circuit in placer of a software controlled disconnect. Creating a supervisory condition on the associated release panel. The green Led indicates the RCDS-2 is in the normal condition and the release circuit is enabled. The amber Led indicates that the release circuit is disabled. Technical Information Realising circuit disable switch RCDS - 2 Dimensions Contact Rating Power Requirements Environmental Specifications Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 2 3/4” W x 4- 1/2" Hx 2”D (Aproximate) Mount son single gang or Handy box. 1 AMP 40 VDC 24 VDC, 10mA Indoor use only UL-EX15547 FM-3053302 45/239 12. Electrical actuator heads 12.1. Re-assembled electrical actuator head (24 VDC) The purpose of this actuator head is to actuate the valves of the cylinders on which it is fitted electromechanically. It will activate when the coil is energised, which will cause the solenoid to operate and actuate the valve. This actuator can be reseted (pointer goes back to the stand by position) by threading a reset screw in its revolving nut. The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction. All devices are to be installed in accordance with NFPA 70 “National Electrical Code” and with local electrical code requirements. If installation conditions require special protection, please contact Siex to discuss availability of suitably rated enclosures. Nº xx Stand by Activation 3/4" BSP Circuit diagram 1(+) 1 + - 2(-) D1 24 V (DC) D2 Electromagnet 2(-) 2 1(+) Inside the connector, two diodes are located. The one connected in parallel with the winding (D2) eliminates the tension ends that take place when disconnecting, avoiding that the electronic components can be deteriorated. The diode in series (D1) protects the electromagnet avoiding that is damaged by tensions of inverse polarity. The non-correct polarization of the feeding, necessarily implies the nonoperation of the apparatus, therefore it is essential to respect the feeding polarizations. Connections of the connector: The terminal with mark 1 corresponds to the positive of the continuous feed. The terminal with mark 2 corresponds to the negative of the continuous feed. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 46/239 12.1.1. 227SOL (24 VDC) Re-assembled electrical actuator head The 227SOL electrical actuator head is connected to the upper actuation port of the RGS-MAM20/40/50/80/11/12 valve. The manual actuator head 227DM / 227DMS, the cable-operated manual actuator head 227CMC, cable-operated manual actuator head with protective box 227CMCC, pneumatic actuator head 227CN / 227CNTK, pneumatic-manual actuator head 227CNM can all be fitted to the 227SOL and 227SOLR actuator heads. ATTENTION Connection of actuator head 3/4” BSP Revolving nut 227CN 3/4” BSP With holes Technical Information Re-assembled electrical actuator head 227SOL Code 227SOL Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-20/40/50/80, RGS-MAM-11/12 (actuation port) 3/4” BSP Female Protection range IP65 Nominal voltage 24V (DC) Nominal current 0.58 A Nominal power at 68º F (20º C) 14 W 3-pin electrical plug (2 poles + earth) Electrical connection UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 47/239 12.1.2. 227SOLR (24 VDC) Re-assembled electrical actuator head The electrical actuator head 227SOLR ONLY can be connected to the actuation port of the valve RGSMAM-03/03A, and it shall be fixed with an o-ring between the revolving nut (which allows its right orientation) and the RGS-MAM-03/03A. Connection of actuator head 3/4” BSP ATTENTION Revolving nut 227CN 3/4" BSP Without holes Technical Information Re-assembled electrical actuator head 227SOLR Code 227SOLR Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-03/03A 3/4” BSP Female Protection range IP65 Nominal voltage 24V (DC) Nominal current 0.58 A Nominal power at 68º F (20º C) 14 W 3-pin electrical plug (2 poles + earth) Electrical connection UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 48/239 12.2. Re-assembled electrical actuator head (24 VDC) The purpose of this discharge head is to actuate the valves of the cylinders on which it is fitted electromechanically. It will activate when the coil is energised, which will cause the solenoid to operate and actuate the valve. This actuator can be reseted (pointer goes back to the stand by position) by threading a reset screw in its revolving nut. The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction. All devices are to be installed in accordance with NFPA 70 “National Electrical Code” and with local electrical code requirements. If installation conditions require special protection, please contact Siex to discuss availability of suitably rated enclosures. Nº xx Stand by Activation 3/4" BSP Circuit diagram 1(+) 1 + - 2(-) D1 24 V (DC) D2 Electromagnet 2(-) 2 1(+) Inside the connector, two diodes are located. The one connected in parallel with the winding (D2) eliminates the tension ends that take place when disconnecting, avoiding that the electronic components can be deteriorated. The diode in series (D1) protects the electromagnet avoiding that is damaged by tensions of inverse polarity. The non-correct polarization of the feeding, necessarily implies the nonoperation of the apparatus, therefore it is essential to respect the feeding polarizations. Connections of the connector: The terminal with mark 1 corresponds to the positive of the continuous feed. The terminal with mark 2 corresponds to the negative of the continuous feed. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 49/239 12.2.1. 227SOLC (24 VDC) Re-assembled electrical actuator head The 227SOLC electrical actuator head is connected to the upper actuation port of the RGS-MAM20/40/50/80/11/12 valve. The manual actuator head 227DM / 227DMS, cable-operated manual actuator head 227CMC, cable-operated manual actuator head with protective box 227CMCC, pneumatic actuator head 227CN / 227CNTK, pneumatic-manual actuator head 227CNM can all be fitted to the 227SOLC and 227SOLCR actuator heads. Connection of actuator head 3/4” BSP ATTENTION Revolving nut 227CN 3/4" BSP With holes Technical Information Re-assembled electrical actuator heads 227SOLC Code 227SOLC Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-20/40/50/80, RGS-MAM-11/12 (actuation port) 3/4” BSP Female Protection range IP65 Nominal tension 24V (DC) Nominal current 0,66 A Nominal power at 68º F (20º C) 15,9 W 3-pin electrical plug (2 poles + earth) Electrical connection UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 50/239 12.2.2. 227SOLCR (24 VDC) Re-assembled electrical actuator head The electrical discharge head 227SOLCR ONLY can be connected to the actuation port of the valve RGSMAM-03/03A and it shall be fixed with an o-ring between the revolving nut (which allows its right orientation) and the RGS-MAM-03/03A. Connection of actuator head 3/4” BSP ATTENTION Revolving nut 227CN 3/4" BSP Without holes Technical Information Re-assembled electrical actuator heads 227SOLCR Code 227SOLCR Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-03/03A 3/4” BSP Female Protection range IP65 Nominal tension 24V (DC) Nominal current 0,66 A Nominal power at 68º F (20º C) 15,9 W 3-pin electrical plug (2 poles + earth) Electrical connection UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 51/239 12.3. Re-assembled electrical actuator head (125 VAC) This actuator head is identical to the previous actuators; the only difference is that it can be activated with 125 volts. This actuator can be reseted (pointer goes back to the stand by position) by threading a reset screw in its revolving nut. The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction. All devices are to be installed in accordance with NFPA 70 “National Electrical Code” and with local electrical code requirements. If installation conditions require special protection, please contact Siex to discuss availability of suitably rated enclosures. Nº xx Stand by Activation 3/4" BSP Circuit diagram 227SOLC125 / 227SOLCR125 1(+) 1 2(-) D 1 Electromagnet 125 V (AC) 2 1 2 Inside the connector, an electronic board is located to rectify the signal from alternating to direct current, it has a 4 diode bridge and a varistor for protection against the voltage peaks during the disconnection of the coil. The alternating signal must be connected to terminals 1 and 2. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 52/239 12.3.1. 227SOLC125 (125 VAC) Re-assembled electrical actuator head The 227SOLC125 / 227SOLCR125 re-assembled electrical actuator head is connected to the upper actuation port of the RGS-MAM-20/40/50/80/11-4/12-4 valve. The manual actuator head 227DM / 227DMS, cable-operated manual actuator head 227CMC, cable-operated manual actuator head with protective box 227CMCC, pneumatic actuator head 227CN, pneumatic-manual actuator head 227CNM can all be fitted to the these actuator heads. Connection of actuator head 3/4” BSP ATTENTION Revolving nut 227CN 3/4" BSP With holes Technical information Re-assembled electrical actuator head 227SOLC125 Code 227SOLC125 Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-20/40/50/80, RGS-MAM-11/12 (actuation port) 3/4” BSP Female Protection range IP65 Nominal voltage AC 125 V AC Nominal voltage DC 112 V DC Nominal current 0,132 A dc Nominal power at 68º F (20º C) 14,8 W 3-pin electrical plug (2 poles + earth) Electrical connection UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 53/239 12.3.2. 227SOLCR125 actuator head (125 VAC) Re-assembled electrical The electrical discharge head 227SOLCR125 ONLY can be connected to the actuation port of the valve RGS-MAM-03/03A and it shall be fixed with an o-ring between the revolving nut (which allows its right orientation) and the RGS-MAM-03/03A. Connection of actuator head 3/4” BSP ATTENTION Revolving nut 227CN 3/4" BSP Without holes Technical information Re-assembled electrical actuator head 227SOLCR125 Code 227SOLCR125 Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-03/03A 3/4” BSP Female Protection range IP65 Nominal voltage AC 125 V AC Nominal voltage DC 112 V DC Nominal current 0,132 A dc Nominal power at 68º F (20º C) 14,8 W 3-pin electrical plug (2 poles + earth) Electrical connection UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 54/239 12.4. POSOLUFO-V / POSOLUFO-T Electrical Actuator head The POSOLUFO-V / POSOLUFO-T electrical actuator head is connected to the pressure switch port of the RGS-MAM-12-4/20/40/50/80 or RGS-MAM-03/03A container valve. The pneumatic-manual actuator head 227CNM is fitted to the actuator port of the RGS-MAM-12-4/20/40/50/80 or RGS-MAM-03/03A container valve. The electrical actuator determines the flow of gas to the pneumatic-manual actuator, allowing this pneumatic-manual actuator the activation of the container valve. This electrical actuator head is allowed to be used in vibration areas, etc. Electrical actuator head POSOLUFO-V / POSOLUFO-T Nominal voltage Wattage Class 24V (DC) 10 H 3-pin electrical plug (2 poles + earth) DIN 43650A / ISO 4400 NEMA Types 1, 2, 3, 4 and 4X protection with a suitable conduit installation or mating DIN connector and gasket. UL-EX15547 FM-3053302 Electrical connection Type of termination Protection index Approvals Activation hose 1/8” Activation hose 1/8” Electrical actuator head Electrical actuator head Adaptor 227 DEFLAG Adaptor 227 DEFLAG UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 55/239 13. Explosion proof electrical actuator head 13.1. POSOLUFX-V / POSOLUFX-T Electrical Actuator head Explosion proof coil for installations in hazardous areas in which explosive gas- vapour- or dust atmospheres are present. The enclosure of these explosion proofs coils "dm" is made entirely in synthetic material. The integrated sealing and O-rings assure the classification of protection NEMA 7/9. Therefore, these products look into account not only the suitability with hazardous areas but also extremely corrosive environment, for example, Chemical, Petrochemical and Refineries industries (CPR). Due to the compact size and easy connection, these coils may be mounted in confined spaces. Electrical Actuator POSOLUFX-V / POSOLUFX-T Voltage 24 VDC 10 Wattage Protection index Agency Certifications Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 NEMA 7/9 Class I, Div. 1&2, Groups A,B,C, D; Class II, Div 1&2, Groups E,F,G; Class III, Div 1. UL, or cULus 4 Canada, USA UL-EX15547 FM-3053302 56/239 13.2. 227DEFLAG Electrical Actuator head* Explosion proof coil with flameproof enclosure, encapsulation, "dm" according to ATEX directive 94/9/EC and Standards EN 50014, EN 50018, EN 50028 and EN 50281-1-1. Application: Control of coils valves intended for installations in hazardous areas in which explosive gas- vapour- or dust atmospheres are present, for example, zones 1.21 or zones 2.22 (ATEX: Group II, apparatus categories 2G/D or 3G/D). The enclosure of these explosion proofs coils "dm" is made entirely in synthetic material. All external metallic components in contact with the atmosphere are made in stainless steel. The integrated sealing and O-rings assure the degree of protection IP67. Therefore, these products look into account not only the suitability with hazardous areas but also extremely corrosive environment, for example, Chemical, Petrochemical and Refineries industries (CPR). Due to the compact size and easy cable connection by screw terminals, these coils may be mounted in confined spaces. Features: The coil winding (copper wires of insulation Class H) and magnetic iron path are encapsulated in synthetic material Class H and meet "m" protection. The connection box and cover of selected high quality synthetic material (Class H) in order to meet the Standard EN 50018 for type of protection "d" flameproof enclosure. The cable gland assembly M20x1.5 makes part of the "d" certificated enclosure. The coils are provided with an embedded non-reselting thermal fuse to prevent excessive heating, for example, assuring the maximum allowed surface temperatures T4/T5. A varistor for peak voltages suppression is potted-in, in Epoxy resin Class H. Additional safety assures a built in replaceable fus easily accessible in the connection box. Low power version is available. Electrical Actuator 227DEFLAG Input current Voltage Protection index Certifications 360mA 24 VDC Ex db mb IIC T4 Ex tb IIIC II 2 G D IP67 LCIE 03 ATEX 6451 X IECEx LCI 06.0004 X POCC CH. 605.B03757 KOSHA 11-AV4B0-0048 Agency Certifications * This is not part of the UL Listed & FM Approval. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 57/239 13.3. 227DEFLAG1 Electrical Actuator head* Solenoid Coils for use in potentially explosive environments Siex offers special components for use in hazardous and potentially explosive environments. These component have been approved in accordance to IECEx, ATEX 2086 X and PTB 03 by the federal physical/technical institute (PTB). Protection against explosions is granted when the matched components specified in the catalogue are being used. Electrical Actuator 227DEFLAG1 Voltage Protection index Certifications 24 VDC ll 2 G Ex mb ll T6, T5, T4 Gb ll 2 D Ex tb IIIC T80 °C, T95 °C T130 °C Db IP65 PTB 03 ATEX 2086 X, IECEx PTB 05.0005X Agency Certifications * This is not part of the UL Listed & FM Approval. Activation hose 1/8” Activation hose 1/8” Electrical actuator head Electrical actuator head Adaptor 227 DEFLAG Adaptor 227 DEFLAG UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 58/239 13.4. Electrical Manual Actuator head 227SOLC-AD HAZLOC The purpose of this discharge head is to actuate the valves of the cylinders on which it is fitted electromechanically. It will activate when the coil is energised, which will cause the solenoid to operate and actuate the valve. This actuator can be reseted (pointer goes back to the stand by position) by threading a reset screw in its revolving nut. The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction. All devices are to be installed in accordance with NFPA 70 “National Electrical Code” and with local electrical code requirements.This actuator is able to be installed in hazardous locations in which explosive gas, vapor or dust atmospheres are present. Circuit diagram 1(+) 1 + - 2(-) D1 24 V (DC) D2 Electromagnet 2(-) 2 1(+) Inside the connector, two diodes are located. The one connected in parallel with the winding (D2) eliminates the tension ends that take place when disconnecting, avoiding that the electronic components can be deteriorated. The diode in series (D1) protects the electromagnet avoiding that is damaged by tensions of inverse polarity. The non-correct polarization of the feeding, necessarily implies the nonoperation of the apparatus, therefore it is essential to respect the feeding polarizations. Connections of the connector: The terminal with mark 1 corresponds to the positive of the continuous feed. The terminal with mark 2 corresponds to the negative of the continuous feed. Nº xx Stand by Activation 3/4" BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 59/239 The 227SOLC-AD HAZLOC electrical manual actuator head is connected to the upper actuation port of the RGS-MAM-11-4, RGS-MAM-12-4, RGS-MAM-20/40/50/80, RGS-MAM-03/03A and also, it can be installed to the side port of the container valves RGS-MAM-12-1C/2C. Technical Information Elextrical Manual Actuator Head for Hazardous Locations 227SOLC-AD HAZLOC UL-EX15547 FM-3053302 Code 227SOLC-AD HAZLOC Actuation type Launching Re-assembled requirements Manual force Connection to the cylinder valve RGS-MAM-11/12 (actuation port) 3/4” BSP Female Protection range IP65 Nominal tension 24V (DC) Nominal current 0.66 A Nominal power at 68º F (20º C) 15.9 W Electrical connection 3-pin electrical plug (2 poles + earth) Protection index In process Certifications In process Agency Certifications In process “UF-MC-HC” - 27-01-2016 60/239 14. Pneumatic trip 14.1. POSX-NAU Pneumatic trip The purpose of this pneumatic trip model POSX-NAU is to close doors, duct dampers, swing doors, gas shut-off valves, etc. in the moment when the extinguishing system is activated. The activation of the actuator is by pneumatically means through a pilot or cylinder bottle of the fixed extinguishing system or manually by means of the pin or pull knob (see examples). The correct orientation of the copper tube (POLATCU) is made by given Teflon tape to the male-male union adaptor (POAD10MM) or elbow (227CO). 6 5 4 3 7 2 1 Nº 1 2 3 4 5 6 7 Description Fixing screw Pneumatic actuator Teflon tape or o-ring or metal-plastic joint Elbow or Tee 1/4" BSP Adapter 1/4" BSP – Ø0.24x0.16 in (6x4mm) Copper tube Ø0.24x0.16 in (6x4mm) Actuation knob Type POSX-NAU 227CO / 227TE POA8CU POLATCU Aluminium Pneumatic trip POSX-NAU Type of actuation Pneumatic and manual Minimum pressure for opening Pneumatic connection thread 72.5 psi (5 bar) 1/4" BSP (Female) Re-assembled requirements Push the knob Maximun load Activation knob Approvals UL-EX15547 FM-3053302 130 lb (60 Kg) POSX-NAU POSX-NAUP Aluminium Plastic UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 61/239 14.2. POSX-NAUC Pneumatic trip with protection box This pneumatic trip is the same than the device showing above and has the same activation (see point 14.1). The only difference it has is that it it is installed in a metallic box to protect the pneumatic trip. The manual pull knob remains outside the box for an easier handling in case that the manual activation is needed. Pneumatic trip POSX-NAUC Type of actuation Pneumatic and manual Minimum pressure for opening Pneumatic connection thread 72.5 psi (5 bar) 1/4" BSP (Female) Re-assembled requirements Push the knob Maximun load Activation knob Approvals 130 lb (60 Kg) POSX-NAUC POSX-NAUCP Aluminium Plastic UL-EX15547 FM-3053302 GAS OR LIQUID SHUT-OFF VALVE UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 62/239 WINDOWS DAMPER VENTING DUCT UL-EX15547 FM-3053302 SLIDING DOOR “UF-MC-HC” - 27-01-2016 63/239 15. Cable-operated manual actuator head and with protective box It is used interchangeably in modular cylinders or in cylinder banks to remotely actuate the extinguishing system. The cable-operated manual actuator head is assembled in the container valve of the pilot bottle or master cylinder or in the re-assembled electrical actuator and it is linked with cable inside a pipe (protective pipe) to the remote manual pull station. It has a hole in the end of its lever which allows to be tied to the cable. The only difference between the model 227CMC and 227CMCC is that the last one (227CMCC) it is housed inside a protective box. The cable is installed inside a steel pipe, using pulley elbows which allow the changes in direction required by the obstacles and elevation changes which are needed to be avoided and to reach the cableoperated manual actuator head 227CMC or 227CMCC. 15.1. 227CMCC Cable-operated manual actuator head with protective box Diameter 0.06 in (1.5mm) stainless steel cable Level 227 CMC Revolving nut 227CN POSITION 1 : STAND BY POSITION 2 : ACTIVATION Technical Information Cable-operated manual actuator head with protective box 227CMCC Material of the components Brass, Zinc coated carbon steel and aluminium Protective pipe Cable UL-EX15547 FM-3053302 Ø 0.71 in (18 mm) pipe Ø 0.06 in (1.5 mm) Stainless steel Pipe joint By means of adapter for Ø 0.71 in (18 mm) pipe Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 64/239 15.2. 227CMC Cable-operated manual actuator head Diameter 0.06 in (1.5mm) Stainless steel cable Level 227 CMC Revolving nut 227CN POSITION 1 : STAND BY POSITION 2 : ACTIVATION Technical Information Cable-operated manual actuator head 227CMC Material of the components Cable Approvals UL-EX15547 FM-3053302 Brass, Zinc coated and carbon steel Ø 0.06 in (1.5 mm) Stainless steel UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 65/239 16. Remote manual pull station without tension 16.1. TK-DMS Remote manual pull station without tension It is used interchangeably in modular cylinders or in cylinder banks to remotely actuate the extinguishing system. The remote manual pull station is linked with cable inside a pipe (protective pipe) to the cableoperated manual actuator head (227CMC or 227CMCC) or to the mechanical control unit (TK-SIMPLEX or TK-COMPLEX) in the pilot bottle or master cylinder. Once installed, when you remove out the safety pin and pull the handler of the remote manual pull station, it translate the movement to the cable operated manual actuator which activates the system. The cable is installed inside a steel pipe, using pulley elbows which allow the changes in direction required by the obstacles and elevation changes which are needed to be avoided to reach the cableoperated manual actuator head 227CMC or 227CMCC. Protection pipe Stainless steel cable Cover Adaptor for tube diameter 0.71 in (18mm) Manual actuator Screw for framework cover Technical information Remote manual pull station without tension TK-DMS Material of the components Zinc coated carbon steel and aluminium Protective pipe Cable UL-EX15547 FM-3053302 Ø 0.71 in (18 mm) pipe Ø 0.06 in (1.5 mm) Stainless steel Pipe joint By means of adapter for Ø 0.71 in (18 mm) pipe Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 66/239 16.2. TK-DMS2 Remote manual pull station without tension to build in It is used interchangeably in modular cylinders or in cylinder banks to remotely actuate the extinguishing system. The remote manual pull station is linked with cable inside a pipe (protective pipe) to the cableoperated manual actuator head (227CMC or 227CMCC) or to the mechanical control unit (TK-SIMPLEX or TK-COMPLEX) in the pilot bottle or master cylinder. Once installed, when you remove out the safety pin and pull the handler of the remote manual pull station, it translate the movement to the cable operated manual actuator which activates the system. The cable is installed inside a steel pipe, using pulley elbows which allow the changes in direction required by the obstacles and elevation changes which are needed to be avoided to reach the cableoperated manual actuator head 227CMC or 227CMCC. This model is in the pladur wall, the cable cames out through the back side of the box. Cover Manual actuator Screw for framework cover Technical information Remote manual pull station without tension to build in TK-DMS2 Material of the components Protective pipe Cable Pipe joint Zinc coated carbon steel and aluminium Ø 0.71 in (18 mm) pipe Ø 0.06 in (1.5 mm) Stainless steel By means of adapter for Ø 0.71 in (18 mm) pipe UL-EX15547 FM-3053302 Approvals TKCP 227 CMC WALL TK2-DMS FRONT UL-EX15547 FM-3053302 TOP “UF-MC-HC” - 27-01-2016 67/239 Limits in the use of the TK-DMS / TK-DMS2 TKCP 227 CMC TK-DMS Fitted in 227CMC / 227CMCC Maximum cable length 124.5 ft (38.01 m) Maximum number of pulley elbows TK-CP 36 pcs CONTROL UNIT TK-COMPLEX CONTROL UNIT TK-SIMPLEX Fitted in the mechanical control unit TK-COMPLEX / TK-COMPLEX-B / TK-COMPLEX-C Maximum cable length Maximum number of pulley elbows TK-CP UL-EX15547 FM-3053302 124.5 ft (38.01 m) 36 pcs Fitted in the mechanical control unit TK-SIMPLEX / TK-SIMPLEX-B / TK-SIMPLEX-C Maximum cable length Maximum number of pulley elbows TK-CP “UF-MC-HC” - 27-01-2016 124.5 ft (38.01 m) 36 pcs 68/239 17. Remote manual pull station with tension It is used to have a manual activation of the mechanical control unit distantly. It is connected by means of inox steel cable (KWR-50) under pipe to the network of mechanical detection line of any type of mechanical control unit (TK-SIMPLEX, TK-SIMPLEX-B, TK-SIMPLEX-C, TK-COMPLEX, TK-COMPLEX-B or TK-COMPLEX-C). The inox steel cable connects the network of mechanical detection kits from the mechanical control unit to the end of line (TK-FL) of this manual handle (TK-DMC2), in such a way that in case of activation of this manual handle TK-DMC or TK-DMC2 there takes place the expansion of the detection line and therefore it activates the mechanical control unit. This remote manual pull station with tension TK-DMC / TK-DMC2 will have to be located in the route of evacuation of the risk but meeting the limits showing below (maximum distance between TK-DMC2 and the mechanical control unit). The TK-DMC is allways installed in the middle of the detection line and the TK-DMC2 is allways installed at the end of the detection line. To make easier the changes of directions, the pulley elbows TK-CP are used. 17.1. TK-DMC Remote manual pull station with tension Steel cable KWR-50 Technical Information: Remote manual pull station with tension TKDCM Material of components Pipe protection Cable Unión to pipe Remote manual actuator with tension TK-DMC Zinc plated steel and aluminum Pipe Ø 0.71 in (18 mm) Stainless steel Ø 0.06 in (1.5 mm) By means of adapter for pipe Ø 0.71 in (18mm) UL-EX15547 FM-3053302 Approvals 17.2. TK-DMC2 Remote manual pull station with tension End of line TK-FL Steel cable KWR-50 Technical Information: Remote manual pull station with tension TKDCM2 Material of components Pipe protection Cable Unión to pipe Adaptor for tube diameter 0.71 in (18mm) (the TKFL is inside of it) Zinc plated steel and aluminum Pipe Ø 0.71 in (18 mm) Stainless steel Ø 0.06 in (1.5 mm) By means of adapter for pipe Ø 0.71 in (18mm) Approvals UL-EX15547 FM-3053302 Remote manual actuator with tension TK-DMC2 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 69/239 Limitation in the use of TK-DMC / TK-DMC2 TK-TEC TK-CP TK-CP TK-KIT-T-F TK-DMC TK-DMC2 TK-SIMPLEX Mechanical central control TK-SIMPLEX / TK-SIMPLEX-B / TK-SIMPLEX-C 205.9 ft Maximum length of cable (62,77 m) Maximum elbows pulley TK-CP 42 units Maximum tee pulley TK-TEC 1 units TK-TEC TK-CP TK-CP TK-KIT-T-F TK-DMC TK-DMC2 TK-COMPLEX Mechanical central control TK-COMPLEX / TK-COMPLEX-B / TK-COMPLEX-C Maximum length of cable UL-EX15547 FM-3053302 205.9 ft (62,77 m) Maximum elbows pulley TK-CP 42 units Maximum tee pulley TK-TEC 1 units “UF-MC-HC” - 27-01-2016 70/239 18. Mecanical control unit 18.1. TK- SIMPLEX Mechanical control unit The mechanical control unit, model TK-SIMPLEX / TK-SIMPLEX-B / TK-SIMPLEX-C, has one mechanical detection network which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. The mechanical control unit has an internal mechanical device which is able of activating the valve core of the valve where it is installed. It has the possibility of manual actuation in order to release the system in case of emergency. The difference between the TK-SIMPLEX, TK-SIMPLEX-B and TK-SIMPLEX-C are the valve on which it is assembled. All mechanical control units have the possibility of install a microswitch which send a signal in case that the system is activated (see point 20.10). In accordance with NFPA 2001 and NFPA 72, the mechanical detection system can be used as spot-type heat detectors (for use only where acceptable to the Authority having jurisdiction) as the primary automatic detection device or a redundant automatic detection device and complementary to the primary automatic detection device. Connection to mechanical detection line Connection to manual actuator without tension TKDMS Manual actuation Connection to actuation port of the valve TK-SIMPLEX All containers valves unless RGS-MAM-03/03A TK-SIMPLEX-B RGS-MAM-03/03A TK-SIMPLEX-C All containers valves Approvals UL-EX15547 FM-3053302 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 71/239 18.1.1. TK-SIMPLEX TK-SIMPLEX can be installed on all container valves unless the RGS-MAM-03/03A. With holes 18.1.2. TK-SIMPLEX-B TK-SIMPLEX-B only can be installed (with an o-ring) on the pilot cartridge, acting on the RGS-MAM03/03A valve. Without holes 18.1.3. TK-SIMPLEX-C TK-SIMPLEX-C can be installed on the RGS-MAM-03/03A valves (with an o-ring) and on the rest of the container valves (with a joint). Without holes + O-ring RGS-MAM-03/03A UL-EX15547 FM-3053302 Joint Rest of the container valves “UF-MC-HC” - 27-01-2016 72/239 Limitation on mechanical control unit TK-SIMPLEX / TK-SIMPLEX-B / TK-SIMPLEX-C LINE OF DETECTION DETECTION KIT TK-KIT-T-F MECHANICAL CENTRAL CONTROL UNIT TK-SIMPLEX PULLEY ELBOW TK-CP REMOTE MANUAL PULL TK-DMS Mechanical central control TK-SIMPLEX / TK-SIMPLEX-B / TK-SIMPLEX-C Maximum length of cable in the line of detection 205.9 ft (62,77 m) 41 units Maximum KIT of detection in the line of detection (15 units type TK-KIT-T-B / TK-KIT-T-F + 26 units type TK-KIT-C-B / TK-KIT-C-F / TK-KIT-A-B / TK-KIT-A-F) Maximum elbows pulley TK-CP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 42 units 73/239 18.2. TK-COMPLEX Mechanical control unit The mechanical control unit, model TK-COMPLEX / TK-COMPLEX-B / TK-COMPLEX-C, has two versions, regular detection or cross detection, in both versions there are two detection networks. In the regular system, the mechanical control unit is released when a fusible link or thermo link in any of both detection networks is activated due to a rising of heat caused by a fire. In the cross detection system the mechanical control unit is released when at least one fusible link or thermo bulb from both detection networks are activated due to a rising of heat caused by a fire. The mechanical control unit has an internal mechanical device which is able of activating the valve core of the valve where it is installed. It has the possibility of manual actuation in order to release the system in case of emergency. The difference between the TK-COMPLEX, TK-COMPLEX-B and TK-COMPLEX-C are the valve on which it is assembled. All mechanical control units have the possibility of install a microswitch which send a signal in case that the system is activated (see point 20.10). In accordance with NFPA 2001 and NFPA 72, the mechanical detection system can be used as spot-type heat detectors (for use only where acceptable to the Authority having jurisdiction) as the primary automatic detection device or a redundant automatic detection device and complementary to the primary automatic detection device. Connection to mechanical detection line Connection to manual actuator without tension TK-DMS Manual actuation Connection to actuation port of the valve UL-EX15547 FM-3053302 TK-COMPLEX All containers valves unless RGS-MAM-03/03A TK-COMPLEX-B RGS-MAM-03/03A TK-COMPLEX-C All containers valves Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 74/239 18.2.1. TK-COMPLEX TK-COMPLEX can be installed on all container valves unless the RGS-MAM-03/03A. With holes 18.2.2. TK-COMPLEX-B TK-COMPLEX-B only can be installed (with an o-ring) on the pilot cartridge, acting on the RGS-MAM03/03A valve Without holes 18.2.3. TK-COMPLEX-C TK-COMPLEX-C can be installed on the RGS-MAM-03/03A valves (whith an o-ring) and on the rest of the container valves (with a joint) Without holes + O-ring Joint RGS-MAM-03/03A UL-EX15547 FM-3053302 Rest of the container valves “UF-MC-HC” - 27-01-2016 75/239 Limitation on mechanical control unit TK-COMPLEX / TK-COMPLEX-B / TK-COMPLEX-C DETECTION KITS TK-KIT-T-F TKCP TK-DMS Mechanical central control TK-COMPLEX / TK-COMPLEX-B / TK-COMPLEX-C UL-EX15547 FM-3053302 Maximum length of cable in the line of detection 1 (62,77 m) Maximum length of cable in the line of detection 2 (62,77 m) 205.9 ft 205.9 ft Maximum KIT of detection in the line of detection 1 41 units (15 units type TK-KIT-T-B / TK-KIT-T-F + 26 units type TK-KIT-C-B / TK-KIT-C-F / TK-KIT-A-B / TK-KIT-A-F) Maximum KIT of detection in the line of detection 2 41 units (15 units type TK-KIT-T-B / TK-KIT-T-F + 26 units type TK-KIT-C-B / TK-KIT-C-F / TK-KIT-A-B / TK-KIT-A-F) Maximum elbows pulley in the line of detection 1 TK-CP 42 units Maximum elbows pulley in the line of detection 2 TK-CP 42 units “UF-MC-HC” - 27-01-2016 76/239 19. Mechanical detection kits TK-KIT-T-F / TK-KIT-T-B / TK-KIT-C-F / TK-KIT-C-B / TK-KIT-A-F / TK-KIT-A-B The purpose of the mechanical detection kit is the detection of the fire through the temperature by means of a fusible link or thermo bulb for different temperatures which are joined by means of a steel cable. The breakage of the fusible link or the thermo bulb at a certain temperature causes the relaxation of the cable and, therefore, the actuation of the mechanical control unit (TK-SIMPLEX, TK-SIMPLEX-B, TK-SIMPLEXC, TK-COMPLEX, TK-COMPLEX-B, TK-COMPLEX-C) to activate the extinguishing system. In accordance with NFPA 2001 and NFPA 72, the mechanical detection system can be used as spot-type heat detectors (for use only where acceptable to the Authority having jurisdiction) as the primary automatic detection device or a redundant automatic detection device and complementary to the primary automatic detection device. TK-KIT-T-F TK-KIT-T-B Braket Braket Adaptor Scissors Scissors Adaptor Termal Bulb Fusible Bulb Braker Cable Cable TK-KIT-C-F TK-KIT-C-B Braket Braket Adaptor Adaptor End of line Fusible End of line Termal bulb Bulb braker Cable Cable TK-KIT-A-B TK-KIT-A-F Braket Braket Adaptor Adapto r Crimp sleeve Crimp sleeve Bulb Braker Termal bulb ´´S´´ hook Fusible ´´S´´ hook Cable Cable UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 77/239 20. Components to mechanical detection 20.1. TK-ST Scissors This scissors model TK-ST is used to create the tension in the detection line cable and fix the fusible link or thermo bulb. When the fusible link or thermo bulb brokes, the scissors liberates the tension of the cable and activates of the mechanical control unit. Scissors TK-ST Material Inox steel Approvals UL-EX15547 FM-3053302 20.2. TK-EMT Adaptor The adaptor model TK-EMT is used to make possible the installation of the protective tube for the inox cable. This adaptor is usually used in the detector kits, remote manual pull stations, mechanical control units, etc. and it has a 1/2" thread connection in one side and a ring with a nut in the other side. The ring and nut fix the pipe used to protect the cable. Adaptor TK-EMT Material Inox steel Thread 1/2" Approvals UL-EX15547 FM-3053302 20.3. KFTxxx Fusible link This fusible link is a welded union that breaks when the required temperature is reached by the rising temperature caused by a fire. This fusible link is listed by UL. Fusible link KFTxxx Temperature Rating FUSIBLE KFT57 ºF 135º ºC 57º KFT74 KFT100 KFT138 165º 212º 280º 74º 100º 138 KFT182 360º 182º KFT232 450º Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 232º UL-EX15547 FM-3053302 78/239 20.4. KBTXXXX Thermo bulb This thermo bulb is a union device that breaks when the required temperature is reached by the rising temperature caused by a fire. This fusible link is UL listed and FM approved. Thermo bulb KBTxxxS Bulb Braker Termal bulb STANDART Response thermo Bulb Temperature Rating BULB Colour ºF ºC KBT57S Orange 135º 57º KBT68S Red 155º 68º KBT74S Red 165º 74º KBT79S Yellow 175º 79º KBT93S Green 200º 93º KBT100S Green 212º 100º KBT141S Blue 286º 141º KBT182S Mauve 360º 182º KBT232S Black 450º 232º KBT260S Black 500º 260º UL-EX15547 FM-3053302 Approvals Thermo bulb KBTxxxQ KBT57Q KBT68Q KBT74Q KBT79Q KBT93Q KBT100Q KBT141Q KBT182Q KBT232Q KBT260Q QUICK Response thermo Bulb Temperature Rating Colour ºF ºC Orange 135º 57º Red 155º 68º Red 165º 74º Yellow 175º 79º Green 200º 93º Green 212º 100º Blue 286º 141º Mauve 360º 182º Black 450º 232º Black 500º 260º Approvals UL-EX15547 FM-3053302 BULB 20.5. KFTTL Test link Used for testing the detection line, without destroying a fusible link or the thermal bulb. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 79/239 20.6. KWR-50 Inox steel cable The cable model KWR-50 are intended for use in the mechanical detection line, in the remote manual activation line, in the mechanical gas shut off valve line or in the pneumatic trip line. The steel cable is made in inox steel and it connects the cable operated devices between them, for example it connects the 227CMCC cable-operated manual actuator with protective box with the TK-DMS remote manual pull station. This type of cable needs to be installed with a pipe to protect them, normally the protective pipe has a diameter of 0.71 in (18 mm). Inox steel cable KWR-50 Material Diameter Inox steel Ø 0.06 in (1.5 mm) UL-EX15547 FM-3053302 Approvals 20.7. KWR-100 Inox steel cable The cable model KWR-100 are intended for use in the mechanical detection line, in the remote manual activation line, in the mechanical gas shut off valve line or in the pneumatic trip line. The steel cable is made in inox steel and it connects the cable operated devices between them, for example it connects the 227CMCC cable-operated manual actuator with protective box with the TK-DMS remote manual pull station. The difference between both inox steel cables (KWR-50 and KWR-100) are that the first one (KWR-50) needs a protective pipe to protect the cable and the second one (KWR-100) does not need the protective pipe because it is covered by a plastic case. Inox steel cable KWR-100 Material Diameter Inox steel, plastic Ø 0.06 in (1.5mm) UL-EX15547 FM-3053302 Approvals 20.8. TK-FL End of line This end of line model TK-FL is used to fix the cable in their ends in order to block the cable. For example, it can be installed at the end of the mechanical detection line or in the cable operated manual actuator. End of line TK-FL Material Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Brass UL-EX15547 FM-3053302 80/239 20.9. TK-FL2 End of line This end of line model TK-FL2 is used to fix the cable in their ends in order to block the cable. For example, it can be installed at the end of the pneumatic trip or in the mechanical gas shut off valve. End of line TK-FL2 Material TK-FL2 TK-FL2C Approvals Aluminium Copper UL-EX15547 FM-3053302 20.10. TK-DPDT Double micro-switch This double micro-switch is used to provide an electrical signal to the fire control panel in case the system is activated. It is installed in the mechanical control unit model TK-SIMPLEX, TK-SIMPLEX-B, TKSIMPLEX-C, and with TK-COMPLEX, TK-COMPLEX-B, TK-COMPLEX-C, (both versions, regular detection and cross detection). This device is activated when a fusible link from a mechanical detection kit brokes or a remote manual pull station is activated and this action activates the mechanical control unit. The signal supplied is monitorized by the control panel. Technical information Double micro-switch TK-DPDT 0,1 A 0,25 A Approvals UL-EX15547 FM-3053302 125 VAC 30 VDC UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 81/239 21. Pulley elbow Its function is to drive the inox steel cable to avoid the obstacles and the changes of direction to connect the remote manual pull station (TK-DMS) with the cable-operated manual actuator (227CMC or 227CMCC). Also, it connects the mechanical detection kits with the mechanical control units and all components which are intended to use with cable and needs to change the direction of the cable. It has a little bearing whit channel for the cable, like a little pulley that allows changes of direction of 90º. 21.1. TK-CP Technical Information Elbow pulley type compression TK-CP Protection pipe 0.71in (18 mm) Ø pipe Stainless steel Ø 0.06 in (1.5 mm) With prisoner screw UL-EX15547 FM-3053302 Cable Union to pipe Approvals 21.2. TK-CP2 Technical Information Elbow pulley type compression TK-CP2 Protection pipe 0.71in (18 mm) Ø pipe Stainless steel Ø 0.06 in (1.5 mm) With compression nuts UL-EX15547 FM-3053302 Cable Union to pipe Approvals 21.3. TK-CP3* Technical Information Elbow pulley type compression TK-CP3* Protection pipe Cable Union to pipe Approvals 0.71in (18 mm) Ø pipe Stainless steel Ø 0.06 in (1.5 mm) With pipe thread UL-EX15547 FM-3053302 * This is not part of the UL Listed UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 82/239 22. TK-TE Pulley tee for double manual actuator The pulley tee, model TK-TE, are used to take two remote manual actuators from the mechanical control unit or from the cable operated manual actuator. The mechanical control unit or the cable operated manual actuator has only one possible remote manual actuation, for only one cable. Using this pulley tee, we get two cables from one. Connection to the manual actuator without tension TK-DMS Connection to the mechanical control unit or to the cable operated manual actuator Technical Information Pulley tee double manual actuator TK-TE Material components Carbonated steel Zinc Plated and Aluminium Protecction pipe Cable Ø 0.71 in (18 mm) pipe Stainless steel Ø 0.06 in (1.5 mm) With adaptor for tube Ø 0.71in (18mm) Pipe union Approvals UL-EX15547 FM-3053302 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 83/239 Limitation on the pulley tee for double manual actuator TK-TE 7 8 3 6 4 4 3 5 3 7 2 5 1 Nº Description Type 1 Container valve RGS-MAM-03/03A/11/12/20/40/50/80 2 Mechanical control cabinet TK-SIMPLEX / TK-SIMPLEX-B / TKSIMPLEX-C / TK-COMPLEX / TKCOMPLEX-B / TK-COMPLEX-C 3 Adaptor TK-EMT 4 Protection pipe - 5 Pulley elbow TK-CP 6 Pulley tee TK-TE 7 Manual actuator without tension TK-DMS 8 Inox steel cable - Fitted in the mechanical control line (TK-SIMPLEX / TK-SIMPLEX-B / TK-SIMPLEX-C / TK-COMPLEX / TK-COMPLEX-B / TK-COMPLEX-C) Or in the cable operated manual actuator line (227CMC / 227CMCC) Maximum cable length 124.7 ft (38,01 m) Maximum number of pulley elbows TK-CP 36 pcs Maximum tee pulley TK-TE 1 units UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 84/239 23. TK-TEC Pulley tee for double manual actuator The main function of the TK-TEC pulley is allow to connect several remote manual pull stations in the same extinguishing system. The tee is installed in the detection line allowed in this way installing a remote manual pull station with tension (TK-DMC) for remote activation. Inside it, there are two little bearings with a canal for the cable, simulating a little pulley that allows install a remote manual pull station with tension (TK-DMC) for remote activation in the middle of the detection line. Protection pipe Pulley tee TK-TEC EMT adaptor for tube Detection line Remote manual pull station with tension TK-DMC Technical Information Pulley tee for double manual actuator TK-TEC Body Protecction pipe Cable Pipe union Approvals UL-EX15547 FM-3053302 Aluminium Ø 0.71 in (18 mm) pipe Stainless steel Ø 0.06 in (1.5 mm) Whit nut and bicone UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 85/239 24. Thermal-manual actuator head This actuator head is a combination of manual or thermal activation, and functions to activate the valves of the cylinders where it is mounted. This is an autonomous and automatic detection and extinguishing system which does not require electrical power. This thermal-manual actuator head is fitted from the factory. After each actuation, it is necessary to check if it has been thermally o manually activated. If the actuation was manual, it is necessary to reset the head, but if the actuation was thermal it is compulsory the replacement of the thermal fusible. The mechanism for fitting it to the cylinder valve using a swivel nut allows it to face the right direction. 24.1. KCTM Thermal-manual actuator head The thermal-manual actuator head model KCTM is fitted on the upper side, actuation port, of the container valves RGS-MAM-11-4/12-4/20/40/50/80. This actuator has a manual actuation by pulling through a safety ring, and a thermal actuation, by means of a fusible which breaks at a settled temperature. Safety pin Manual activation Fusible links Termical activation ATTENTION Revolving nut 227CN Without holes Technical Information Thermal-manual actuator head KCTM Type of valve RGS-MAM-11-4/12-4/20/40/50/80 Re-assembled requirements It means manual strength Connection to the activacion port of the valve 3/4" G (Hembra / Female) Temperatures of the fusibe links 135º F, 165º F, 212º F, 280º F, 360º F, 450º F (57º C, 74º C, 100º C, 138º C, 182º C, 232º C) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 86/239 2 3 1 Nº Denomination 1 Nozzle 2 Thermal manual actuator head 3 Container valve Type FEDRxx KCTM RGS-MAM-xx 4 3 2 1 Nº 1 2 3 4 UL-EX15547 FM-3053302 Denomination Nozzle Container valve Thermal manual actuator head Pulley elbow Type FEDRxx RGS-MAM-xx KCTM TK-CP “UF-MC-HC” - 27-01-2016 87/239 24.2. KCTM-R Thermal-manual actuator head The thermal-manual actuator head model KCTM-R is fitted on the upper side, actuation port, of the container valves RGS-MAM-03/03A valve. This actuator has a manual actuation by pulling through a safety ring, and a thermal actuation, by means of a fusible which breaks at a settled temperature. Safety pin Manual activation Fusible links Termical activation ATTENTION Revolving nut 227CN With holes Thermal-manual actuator head KCTM-R Type of valve Re-assembled requirements Connection to the activacion port of the valve Temperatures of the fusibe links RGS-MAM-03/03A It means manual strength 3/4" G (Hembra / Female) 135º F, 165º F, 212º F, 280º F, 360º F, 450º F (57º C, 74º C, 100º C, 138º C, 182º C, 232º C) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 88/239 24.3. KCTM-C Thermal-manual actuator head The thermal-manual actuator head model KCTM-C can be installed on the RGS-MAM-03/03A valves (with an o-ring) and on the rest of the container valves (with a joint) his actuator has a manual actuation by pulling through a safety ring, and a thermal actuation, by means of a fusible which breaks at a settled temperature. .T Safety pin Manual activation Fusible links Termical activation ATTENTION Revolving nut 227CN Without holes + O-ring Joint RGS-MAM-03/03A Rest of the container valves Thermal-manual actuator head KCTM-C Type of valve O-ring Joint RGS-MAM-03/03A RGS-MAM-20/40/50/80/11-4/12-4 Re-assembled requirements It means manual strength Connection to the activacion port of the valve Temperatures of the fusibe links 3/4" G (Hembra / Female) 135º F, 165º F, 212º F, 280º F, 360º F, 450º F (57º C, 74º C, 100º C, 138º C, 182º C, 232º C) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 89/239 25. SIEX-NTD-C008 / SIEX-NTD-C018 Thermic pneumatic-mechanical detector The KCTM actuator in combination with the pilot cartridge (100MxxxUFA) and inside of a protective box has the ability to activate the extinction pneumatically. It can be released thermally or manually, in both cases the activation of the extinguishing is pneumatically through the cartridge filled with nitrogen. When the system is activated, by means of thermal or manual actuation, the gas contained in the pilot cartridge, flows through flexible or copper release hose to the pneumatic actuator(s) assembled in all the cylinders and they are activated pneumatically. 3 4 5 2 6 1 Nº Denomination 1 Copper tube Ø0.24x0.16in (6x4mm) POLATCU 2 Elbow + Adaptor 1/4" G F – Ø0.24x0.16in (6x4mm) 227CO + POA8CU 3 Thermal manual actuator head KCTM 4 Metalic box 5 Pressure gauge 6 Pilot cartridge Approvals UL-EX15547 FM-3053302 SIEX-NTD-C008 16.54x4.17in (42Omm x 106mm) SIEX-NTD-C018 20.63x4.17in (524mm x 106mm) UF40I-xxxx 0.003 ft³ (0.080 L) 0.006 ft³ (0.180 L) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 90/239 Roof Copper tube Ø0.24x0.16in (6x4 mm) Thermal pneumatic-mecanical detector 5 4 6 2 3 1 Nº UL-EX15547 FM-3053302 Denomination 1 Modular cylinder 2 Pneumatic-manual actuator head 3 Discharge nozzle 4 Copper tube Ø0.24x0.16in (6x4mm) 5 Suttle valve 6 Thermal pneumatic-mecanical detector Type 227CNM FEDRXX POLATCU - “UF-MC-HC” - 27-01-2016 KCTM 91/239 Limitations in the use of SIEX-NTD-Cxxx LIMITATIONS OF THE SYSTEM Capacity of the cartridge and filling Maximum distance between detector and pressure the extinguishing system Cartridge: 0.003 ft³ (0.080 litres) 49.21 ft (15 m) Pressure: 2175 psi (150 bar) Cartridge: 0.006 ft³ (0.180 litres) 98.42 ft (30 m) Pressure: 2175 psi (150 bar) 6 4 3 7 5 2 1 Nº 1 2 3 4 5 6 7 Denomination Modular cylinder Discharge hose Discharge pipe Copper tube Ø0.24x0.16in (6x4mm) Discharge nozzle Thermal pneumatic-mecanical detector Pneumatic-manual actuator head Type POLATCU FEDRXX KCTM 227CNM 3 5 2 1 4 Nº 1 2 3 4 5 UL-EX15547 FM-3053302 Denomination Nozzle Discharge pipe Elbow 90º Cupper pipe Pneumatic-mechanical-thermal detector Type FEDRxx POLATCU SIEX-NTD-Cxx “UF-MC-HC” - 27-01-2016 92/239 26. Pressure switch Its function is detects the discharge of the fire-extinguishing agent in the immediate moment in which this one takes place. When it takes place this situation issues an electrical sign that can be used in order that the head office of fires interpreter that the system has disburdened. It has two contacts, one NC (normally closed, it opens with pressure) and another NO (normally opened) that change condition when the switch is activated and both can be used indifferently according to requirements of the installation. Also it incorporates am imterlock mechanism that it must be rearmed after every discharge in order that the device returns to work. Once activated, the rearmament must be done manually, pulling the ball towards out. 26.1. POINPRE Pressure switch Technical Information Pressure switch POINPRExx Discharge Manifold or Network of pipelines Location Case Metallic Tensión 24V (DC) Current 3. A Protection grade IP66 Contacts Normally closed / normally opened UL-EX15547 FM-3053302 Approvals OFF/ON Reactivate everytime that actuates ØA ØA UL-EX15547 FM-3053302 POINPRE 6-6L 1/4" BSP POINPRE 15-6L 1/2" BSP POINPRE 6-40L 1/4" BSP POINPRE 15-40L 1/2" P POINPRE 6-6I 1/4" BSP POINPRE 15-6I 1/2" BSP POINPRE 6-40I 1/4" BSP POINPRE 15-40I 1/2" BSP Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 93/239 26.2. POINPRE-GLE Pressure switch* Technical Information Pressure switch POINPRE-GLExx Discharge Manifold or Network of pipelines Location Case Metallic Tensión 24V (AC) Current 3. A Protection grade IP67 Contacts Normally closed / normally opened Approvals CE, UL, CSA and CCC * This is not part of the FM Approval. ØA UL-EX15547 FM-3053302 POINPRE-GLE 6-6L 1/4" BSP POINPRE-GLE 15-6L 1/2" BSP POINPRE-GLE 6-40L 1/4" BSP POINPRE-GLE 15-40L 1/2" P POINPRE-GLE 6-6I 1/4" BSP POINPRE-GLE 15-6I 1/2" BSP POINPRE-GLE 6-40I 1/4" BSP POINPRE-GLE 15-40I 1/2" BSP Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 94/239 27. Hazardous locations pressure switch His function it´s detect the discharge of the agent fire-extinguisher in the immediate moment in which this one takes place. When it takes place this situation issues an electrical sign that can be used in order that the head office of fires interpreter that the system has disburdened. It has two contacts, one NC (normally closed) and another NO (normally opened) that change condition when the switch is activated and both can be in use indifferently according to requirements of the installation. Also it incorporates a drawer that it must be rearmed after every discharge in order that the device returns to work. Once activated, the rearmament must be done manually, pulling the ball towards out. It has special design features which make this device suitable for being used in areas with atmospheres with explosion risk. It is said that an atmosphere has risk of explosion when in normal conditions it would have not this danger, but due to foreseeable events, the composition of this atmosphere could change in a such way that an explosion could happen. 27.1. POINPREAD-BX Pressure switch* Technical Information Pressure switch POINPREAD-BXxx Circuitry Electrical Housing material Termination types Sealing Vdc Amps Inductive Amps Resistive 1NC 1NO SPDT snap action, double break 10 A thermal Aluminium 1/2 in – 14NPT conduit NEMA 1, 3, 4, 6, 13; IP67 24 10 10 NEMA 7 Div 1&2, Class I, Groups B,C, & D; NEMA 9 Div 1&2, Class II, Groups E,F, & G NEMA 1, 2, 4, 6, 13; IP 67 II 2 G; Exd IIC T6 II 2 D; Ex d tD A21 Protection range Agency Certifications 1 BXA3K, BXA4L, and BXB4L catalog listings are KOSHA certified. 2 ATEX & IEC Ex: [(Gas) II 2 G; Exd IIC T6: (Dust) II 2 D; Ex d tD A21 T85°C] 3 NEPSI Ex: GYJ111016 4 CSA, cUL, UL: NEMA 7 (Gas) Div 1&2, Class I, Groups B, C, & D; NEMA 9 (Dust) Div 1&2, Class II, Groups E, F, & ATEX (CE)² CSA, UL, or IEC Ex² cULus 4 International Canada, USA KOSHA¹ Korea NEPSI EX³ China * This is not part of the FM Approval. ØA UL-EX15547 FM-3053302 POINPREAD-BX 6-6L 1/4" BSP POINPREAD-BX 15-6L 1/2" BSP POINPREAD-BX 6-40L 1/4" BSP POINPREAD-BX 15-40L 1/2" BSP POINPREAD-BX 6-6I 1/4" BSP POINPREAD-BX 15-6I 1/2" BSP POINPREAD-BX 6-40I 1/4" BSP POINPREAD-BX 15-40I 1/2" BSP Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 95/239 27.2. POINPREAD-LX Pressure switch* Technical Information Pressure switch POINPREAD-LXxx Circuitry Housing material Termination types 1NC 1NO SPDT snap action Aluminium 1/2 – 14NPT conduit NEMA 7 Div 1, clas 1 BCD; NEMA 9 Div 1, Class II, EFG. Sealing Agency Certifications CSA, UL, or cULus 4 Canada, USA Protection range Class I, Div.I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 7,9 * This is not part of the FM Approval. ØA UL-EX15547 FM-3053302 POINPREAD-LX 6-6L 1/4" BSP POINPREAD-LX 15-6L 1/2" BSP POINPREAD-LX 6-40L 1/4" BSP POINPREAD-LX 15-40L 1/2" BSP POINPREAD-LX 6-6I 1/4" BSP POINPREAD-LX 15-6I 1/2" BSP POINPREAD-LX 6-40I 1/4" BSP POINPREAD-LX 15-40I 1/2" BSP Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 96/239 27.3. POINPREAD-9007 Pressure switch* Technical Information Pressure switch POINPREAD-9007xx Circuitry 1NC 1NO SPDT snap action Electrical 10 A thermal Housing material Aluminium Termination types 1/2 – 14NPT conduit Sealing NEMA 250, EN 60947-1, EN 60947-5-1, IEC 60947, UL 508, C22-2-14-95, CE conformity documentation IP 67 Electrical Durability 1 million operating cycles Protection range Class I, Div.I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 1, 2, 4, 6, 6P, 12, 13 IP 67 ATEX (CE)² CSA, UL, or cULus 4 Canada, USA Agency Certifications * This is not part of the FM Approval. POINPREAD-9007 6-6L ØA 1/4" BSP POINPREAD-9007 15-6L 1/2" BSP POINPREAD-9007 6-40L 1/4" BSP POINPREAD-9007 15-40L 1/2" BSP POINPREAD-9007 6-6I 1/4" BSP POINPREAD-9007 15-6I 1/2" BSP POINPREAD-9007 6-40I 1/4" BSP POINPREAD-9007 15-40I 1/2" BSP UL-EX15547 FM-3053302 Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 97/239 27.4. POINPREAD-802X Pressure switch* Technical Information Characteristic Parameter Circuitry 1NC 1NO Housing material Aluminium Termination types Conduit pipe opening ½ in.Npt Sealing NEMA 7 and 9 Ambient operating temperature (-18º to 121ºC ) CSA, UL, or cULus 4 Canada, USA Agency Certifications Protection range Class 1,Groups B,C and D or Class II,Groups E,F and G or Class III;NEMA 4/nonharzardous locations * This is not part of the FM Approval. ØA UL-EX15547 FM-3053302 Bar Material POINPREAD-802X 6-6L 1/4" BSP 90±30 psi (6 ± 2 Bar) Brass CuZn40Pb2 (CW617N) POINPREAD-802X 15-6L 1/2" BSP 90±30 psi (6 ± 2 Bar) Brass CuZn40Pb2 (CW617N) POINPREAD-802X 6-40L 1/4" BSP 580 ± 120 psi (40 ± 8 Bar) Brass CuZn40Pb2 (CW617N) POINPREAD-802X 15-40L 1/2" BSP 580 ± 120 psi (40 ± 8 Bar) Brass CuZn40Pb2 (CW617N) POINPREAD-802X 6-6I 1/4" BSP 90±30 psi (6 ± 2 Bar) Stainless Steel AISI 303 POINPREAD-802X 15-6I 1/2" BSP 90±30 psi (6 ± 2 Bar) Stainless Steel AISI 303 POINPREAD-802X 6-40I 1/4" BSP 580 ± 120 psi (40 ± 8 Bar) Stainless Steel AISI 303 POINPREAD-802X 15-40I 1/2" BSP 580 ± 120 psi (40 ± 8 Bar) Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 98/239 27.5. POINPREAD-ATEX Pressure switch* Technical Information Pressure switch POINPREAD-ATEXxx Circuitry 1NC 1NO SPDT snap action, double break Housing material Aluminium Termination types M20x1.5 Sealing NEMA 13, Class 1, division 2, Groups A, B, C, D. Agency Certifications ATEX (CE)² IEC Ex² International IP66 II 2 D; Ex tb IIIC T85ºc Protection range * This is not part of the UL Listed & FM Approval. ØA UL-EX15547 FM-3053302 POINPREAD-ATEX 6-6L 1/4" BSP POINPREAD-ATEX 15-6L 1/2" BSP POINPREAD-ATEX 6-40L 1/4" BSP POINPREAD-ATEX 15-40L 1/2" BSP POINPREAD-ATEX 6-6I 1/4" BSP POINPREAD-ATEX 15-6I 1/2" BSP POINPREAD-ATEX 6-40I 1/4" BSP POINPREAD-ATEX 15-40I 1/2" BSP Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 580 ± 120 psi (40 ± 8 Bar) 580 ± 120 psi (40 ± 8 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 Stainless Steel AISI 303 “UF-MC-HC” - 27-01-2016 99/239 27.6. Table of Hazardous Locations limit switches for POINPREAD-XX Material Contact type POINPREAD-BX POINPREAD-9007 POINPREAD-LX POINPREAD-802X POINPREAD-ATEX Aluminium Aluminium Aluminium Aluminium Aluminium 1 N.O.- 1 N.C. 1 N.O.- 1 N.C. 1 N.O.- 1 N.C. 1 N.O.- 1 N.C. 1 N.O.- 1 N.C. Tension 24 Vdc 24 Vdc 24 Vdc 24 Vdc 24 Vdc Conduit entrance 1/2 in – 14 NPT 1/2 in – 14 NPT 1/2 in – 14 NPT 1/2 in – 14 NPT M20x1.5 Div.I, Class I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 1, 2, 4, 6, 6P, 12, 13 IP 67 Div.I, Class I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 7,9 Class 1,Groups B,C and D or Class II,Groups E,F and G or Class III;NEMA 4/nonharzardous locations NEMA 7 and 9 UL CSA UL, CSA Protection range Certifications UL-EX15547 FM-3053302 NEMA 7 Div 1&2, Class I, Groups B,C, & D; NEMA 9 Div 1&2, Class II, Groups E,F, & G NEMA 1, 2, 4, 6, 13; IP 67 II 2 G; Exd IIC T6 II 2 D; Ex d tD A21 Atex (CE) UL, CSA IEC EX KOSHA NEPSI EX Atex (CE) UL, CSA “UF-MC-HC” - 27-01-2016 IP66 II 2 D; Ex tb IIIC T85ºc Atex (CE) IEC EX 100/239 28. POID Discharge indicator model Discharge indicator is activated by gas pressure during discharge. Discharge indicator oncludes one button or ball that can be rearmed after discharge in order to the new actuation of the device. Once is activated, the re-arm is manual, throwing the ball outside. OFF POSITION ON POSITION Discharge indicator POID ØA POID66L 1/4" G POID156L 1/2” G POID66I 1/4" G POID156I 1/2” G Approvals UL-EX15547 FM-3053302 Bar 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) 90±30 psi (6 ± 2 Bar) Material Brass CuZn40Pb2 (CW617N) Brass CuZn40Pb2 (CW617N) Inox. Steel AISI 303 Inox. Steel AISI 303 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 101/239 29. SIEX-WD Weighing device There has as function detect a small loss of agent's load fire-extinguisher inside the cylinder, good is due to a small escape of the gas or a complete discharge of the above mentioned cylinder. Every unit of weighing device will control one cylinder, which hangs without touching the soil, moving vertically when any loss of mass takes place in the cylinder. The weighing device, model SIEX-WD for fixed extinguishing systems, are used to detect a loss of load in the gas bottles. When the content falls down below a predetermined limit (between 0 and 5 %), the weight are going down. When the weighing device is operative, the force that exercises the cylinder loaded with halocarbonated gas is major than the exercised by the weight placed in the threaded rod of regulation. Therefore the system will remain in the position ON. In this context it is necessary to indicate that the weight of the loaded bottle is predetermined and that the weight gets calibrated from factory in order that it works correctly. Nevertheless it is possible to regulate displacing the weight across his rod of regulation. When the weight of the bottle diminishes (between 0 and 5 %) due to a possible escape or unload, the force exercised by the cylinder will be minor than the exercised by the weight, with which the system will go on to the position OFF. This system allows incorporate electrical detection, done with the installation of an end of line (SIEX-WD) (system listed by UL). These electrical devices will send an alarm sign to the head office of fires when it weights is situated in OFF's position. “ON” POSITION = FILLED CYLINDER “OFF” POSITION = EMPTY CYLINDER Technical Information Weighing device SIEX-WD Answer to a loss of load Between 0% and 5% of the net load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) 1252 lb (567,9 Kg) Min. permisible net weight (estinguishing agent) Max. permisible net weight (extinguishing agent) 914 lb (415 Kg) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 881 lb (4 Kg) “UF-MC-HC” - 27-01-2016 102/239 29.1. SIEX-WD Limit switch for weighing device Limit switch 3SE5 242-OHE10 Location Weighing device Box Plastic Tensión 24V (DC) Intensity 3A Minimum torque of activation 10 N Protection range IP66 / IP67 Connection for cables 2 threaded inlet M20x1.5 Instalation Non corrosive; inside Contacts 1NO/ 1 NC Approvals UL-EX15547 FM-3053302 29.2. SIEX-WD Limit switch for weighing device Limit switch XCK-T2121P16 Location Weighing device Box Plastic Tensión 24V (DC) Intensity 3A Maximum operating force 12 N Protection range IP66 Connection for cables 2 threaded inlet M20x1.5 Instalation Non corrosive; inside Contacts 1NO/ 1 NC UL-EX15547 FM-3053302 Approvals 29.3. SIEX-WD Limit switch for weighing device* Limit switch GLE Location Case Tensión Weighing device Metallic 24V (AC) Current 3. A Protection grade IP67 Connection for cables Contacts Approvals 2 threaded inlet ½” Normally closed / normally opened CE, UL, CSA and CCC * This is not part of the FM Approval. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 103/239 30. Hazardous locations weighing device This system allows incorporate electrical detection, well with the installation of an end of line (SIEX-WD). These electrical devices will send a sign of alarm to the head office of fires when it weighs him situe in OFF's position. When the weight of the bottle diminishes (between 0 and 5 %) due to a possible escape or unload, the force exercised by the cylinder will be minor to the exercised one for the weight, with which the system will go on to the position OFF. It has special design features which make this device suitable for being used in areas with atmospheres with explosion risk. It is said that an atmosphere has risk of explosion when in normal conditions it would have not this danger, but due to foreseeable events, the composition of this atmosphere could change in a such way that an explosion could happen. 30.1. SIEX-WD-BX Weighing device* Technical Information Characteristic Parameter Circuitry 1NC 1NO SPDT snap action, double break Electrical 10 A thermal Housing material Aluminium 1/2 in – 14NPT conduit Termination types Sealing NEMA 1, 3, 4, 6, 13; IP67 Vdc 24 Amps Inductive 10 Amps Resistive 10 Protection range ATEX (CE)² NEMA 7 Div 1&2, Class I, Groups B,C, & D; NEMA 9 Div 1&2, Class II, Groups E,F, & G NEMA 1, 2, 4, 6, 13; IP 67 II 2 G; Exd IIC T6 II 2 D; Ex d tD A21 Agency Certifications CSA, UL, or cULus IEC Ex² KOSHA¹ 4 International Korea Canada, USA NEPSI EX³ China 1 BXA3K, BXA4L, and BXB4L catalog listings are KOSHA certified. 2 ATEX & IEC Ex: [(Gas) II 2 G; Exd IIC T6: (Dust) II 2 D; Ex d tD A21 T85°C] 3 NEPSI Ex: GYJ111016 4 CSA, cUL, UL: NEMA 7 (Gas) Div 1&2, Class I, Groups B, C, & D; NEMA 9 (Dust) Div 1&2, Class II, Groups E, F, & * This is not part of the FM Approval. Weighing device SIEX-WD-BX Answer to a loss of load Between 0% and 5% of the net load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) 1252 lb (567,9 Kg) Min. permisible net weight (estinguishing agent) 881 lb (4 Kg) Max. permisible net weight (extinguishing agent) 914 lb (415 Kg) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 104/239 30.2. SIEX-WD-LX Weighing device* Technical Information Characteristic Parameter MICRO SWITCH™ hazardous area limit switches Product type Actuators Side rotary Circuitry 1NC 1NO SPDT snap action Housing material Aluminium 1/2 – 14NPT conduit Termination types Sealing NEMA 7 Div 1, clas 1 BCD; NEMA 9 Div 1, Class II, EFG. Agency Certifications Protection range CSA, UL, or cULus 4 Canada, USA Div.I, Class 1 Groups B,C, D Div.I, Class II, Groups E,F, G NEMA 7,9 * This is not part of the FM Approval. Weighing device SIEX-WD-LX Answer to a loss of load Between 0% and 5% of the net load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) 1252 lb (567,9 Kg) Min. permisible net weight (estinguishing agent) 881 lb (4 Kg) Max. permisible net weight (extinguishing agent) 914 lb (415 Kg) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 105/239 30.3. SIEX-WD-9007 Weighing device* Technical Information Characteristic Parameter Circuitry 1NC 1NO SPDT snap action Electrical 10 A thermal Housing material Aluminium Termination types 1/2 – 14NPT conduit Sealing NEMA 250, EN 60947-1, EN 60947-5-1, IEC 60947, UL 508, CE conformity documentation IP 67 Electrical Durability 1 million operating cycles Agency Certifications ATEX (CE)² Protection range CSA, UL, or cULus 4 Canada, USA Class I, Div.II, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 1, 2, 4, 6, 6P, 12, 13 IP 67 * This is not part of the FM Approval. Weighing device SIEX-WD-9007 Answer to a loss of load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) Min. permisible net weight (estinguishing agent) Max. permisible net weight (extinguishing agent) UL-EX15547 FM-3053302 Between 0% and 5% of the net load 1252 lb “UF-MC-HC” - 27-01-2016 (567,9 Kg) 881 lb (4 Kg) 914 lb (415 Kg) 106/239 30.4. SIEX-WD-802X Weighing device* Technical Information Characteristic Parameter Circuitry 1NC 1NO Housing material Aluminium Termination types Conduit pipe opening ½ in.Npt Sealing NEMA 7 and 9 Ambient operating temperature (-18º to 121ºC ) CSA, UL, or cULus 4 Canada, USA Agency Certifications Protection range Class 1,Groups B,C and D or Class II,Groups E,F and G or Class III;NEMA 4/nonharzardous locations * This is not part of the FM Approval. Weighing device SIEX-WD-802X Answer to a loss of load Between 0% and 5% of the net load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) 1252 lb (567,9 Kg) Min. permisible net weight (estinguishing agent) 881 lb (4 Kg) Max. permisible net weight (extinguishing agent) 914 lb (415 Kg) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 107/239 30.5. SIEX-WD-ATEX Weighing device* Technical Information Characteristic Parameter 1NC 1NO SPDT snap action, double break Aluminium Circuitry Housing material Termination types 1/2 in – 14NPT conduit NEMA 13, Class 1, division 2, Groups A, B, C, D. -29º+121º(-20!+250 ) Exception: Wobble stick and cat whisker devices are rated from 18º+54º(0º+130º) Sealing Ambient Temperature C (F) ATEX (CE)² Agency Certifications IEC Ex² International IP66 II 2 D; Ex tb IIIC T85ºc Protection range * This is not part of the UL Listed & FM Approval. Weighing device SIEX-WD-ATEX Answer to a loss of load Between 0% and 5% of the net load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) UL-EX15547 FM-3053302 1252 lb (567,9 Kg) Min. permisible net weight (estinguishing agent) 881 lb (4 Kg) Max. permisible net weight (extinguishing agent) 914 lb (415 Kg) “UF-MC-HC” - 27-01-2016 108/239 30.6. SIEX-WD-871 Weighing device* Technical Information Characteristic Parameter Material Plastic Contact type N.O. Operating voltage 20-250 V AC/DC Switching Frequency 10 Hz Conduit entrance 1/2 in – NPT Protection range Class I, Division II, Groups A, B,C & D NEMA 1, 2, 4, 6, 6P, 12, 13; IP 67, IP 69K Agency Certifications Protection range ATEX (CE)² UL, or cULus 4 Canada, USA Class I, Division II, Groups A, B,C & D NEMA 1, 2, 4, 6, 6P, 12, 13; IP 67, IP 69K * This is not part of the FM Approval. Weighing device SIEX-WD-871 Answer to a loss of load Between 0% and 5% of the net load Max. permisible gross weight (cylinder+valve+actuator+extinguishing agent) Min. permisible net weight (estinguishing agent) Max. permisible net weight (extinguishing agent) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 1252 lb (567,9 Kg) 881 lb (4 Kg) 914 lb (415 Kg) 109/239 30.7. SIEX-WD-E51 Weighing device* Technical Information Characteristic Parameter Material Plastic Contact type N.O. or NC Operating voltage 20-264 V AC/DC Sensing range Reflex 18 ft (5,5m) Conduit entrance 0.79 in (20mm) Protection range Class I, Division II, Groups A, B,C & D Class II, Division II, Groups F & G Class III, Division II NEMA 3, 3S, 4, 6, 6P, 12, 13; IP 67 Agency Certifications ATEX (CE)² CSA, UL, or cULus 4 Canada, USA * This is not part of the FM Approval. Max. 18 ft (5.5m) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 110/239 30.8. SIEX-WD-E52 Weighing device* Technical Information Characteristic Parameter Material Plastic Contact type N.O. or NC Operating voltage 20-264 V AC/DC Sensing range Thru-Beam 295ft (90m) Conduit entrance 0.79 in (20mm) Protection range Class I, Division II, Groups A, B,C & D Class II, Division II, Groups F & G Class III, Division II NEMA 3, 3S, 4, 6, 6P, 12, 13; IP 67 Agency Certifications ATEX (CE)² CSA, UL, or cULus 4 Canada, USA * This is not part of the FM Approval. Max. 295 ft (90m) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 111/239 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Certifications Atex (CE) UL, CSA Protection range Atex (CE) UL, CSA IEC EX KOSHA NEPSI EX Class I, Div.II, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 1, 2, 4, 6, 6P, 12, 13 IP 67 NEMA 7 (gas) Div 1&2, Class I, Groups B,C, & D; NEMA 9 (dust) Div 1&2, Class II, Groups E,F, & G NEMA 1, 2, 4, 6, 13; IP 67 II 2 G; Exd IIC T6 II 2 D; Ex d tD A21 UL, CSA UL, CSA Class 1,Groups B,C and D or Class II,Groups E,F and G or Class III;NEMA 4/nonharzardous locations NEMA 7 and 9 1/2 in – NPT 1/2 in – 14 NPT 1/2 in – 14 NPT 1/2 in – 14 NPT Conduit entrance Div.I, Class 1 Groups B,C, D Div.I, Class II, Groups E,F, G NEMA 7,9 24 Vdc Tension 24 Vdc 1 N.O.- 1 N.C. Aluminium 24 Vdc 1 N.O.- 1 N.C. Aluminium SIEX-WD -802X 24 Vdc Aluminium SIEX-WD -LX 1 N.O.- 1 N.C. Aluminium SIEX-WD -9007 1 N.O.- 1 N.C. Contact type Material SIEX-WD -BX Atex (CE) UL, CSA Class I, Division II, Groups A, B,C & D NEMA 1, 2, 4, 6, 6P, 12, 13; IP 67, IP 69K 1/2 in – NPT - 1 N.O. Plastic SIEX-WD -871 Atex (CE) IEC EX IP66 II 2 D; Ex tb IIIC T85ºc M20x1.5 24 Vdc 1 N.O.- 1 N.C. Aluminium SIEX-WD -ATEX UL, CSA Atex (CE) Class I, Division II, Groups A, B,C & D Class II, Division II, Groups F & G Class III, Division II NEMA 3, 3S, 4, 6, 6P, 12, 13; IP 67 UL, CSA Atex (CE) Class I, Division II, Groups A, B,C & D Class II, Division II, Groups F & G Class III, Division II NEMA 3, 3S, 4, 6, 6P, 12, 13; IP 67 20mm 20-264 V AC/DC 20-264 V AC/DC 20mm 1 N.O.- 1 N.C. Plastic SIEX-WD -E52 1 N.O.- 1 N.C. Plastic SIEX-WD -E51 30.9. Table of Hazardous location limit switches for SIEXWD-XX 112/239 31. Fixing brackets (modular, single and double row) The function of the fixing brackets is to fix the cylinders firmly to a solid surface, either a wall or a floor or both, in order to prevent slippage during discharge. Each strap has a slot for insertion in the rear channel, to allow the cylinder to be correctly aligned. The fixing bracket is designed to be installed on a rigid surface with sufficient structural resistance, with the cylinder resting on the floor. 31.1. Modular cylinder They consist of a nut and bolt, two straps and a rear channel. To ensure the container or cylinder is securely attached, it is recommended that two fixing brackets per bottle be used for all 40.2 litre cylinders and above. 31.2. Manifold system in simple line It´s composed of screws with nuts, clamps (as many as cylinders up the manifold), two rear horizontal rails and fixing bracket for mounting the manifold. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 113/239 31.3. Manifold system in double line It´s composed of screws with nuts, clamps (as many as cylinders up the manifold), four subsequent horizontal rails (two behind the first line of manifold and two behind second), rod threaded between the cylinders of the first line and fitting to hold the manifold. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 114/239 32. Fixing brackets anchored to the floor without weighing device This fixing bracket system varies in the previous one of the two vertical and horizontal rails perpendicular to the previous ones, which have has the purpose of anchoring to a wall, the floor or both simultaneously. 32.1. Modular cylinder It´s composed of nuts bolts, clamps with two rear horizontal rails, 2 rear vertical rails and two perpendicular to these last to the base. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 115/239 32.2. Manifold system in simple line It´s composed of screws with nuts, clamps (as many as cylinders up the manifold), two rear horizontal rails, 2 rear vertical racks, perpendicular to these two most recent at the base and finally two lanes perpendicular to the vertical frame to hold the manifold . UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 116/239 32.3. Manifold system in double line Type 1 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 117/239 Type 2 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 118/239 33. Fixing brackets with weighing device This fixing system has a horizontal frame in the upper part, designed to anchor the individual weighing systems on which the charged cylinders rest. This type of fixing is like a cage enclosing the cylinders, anchored either to the wall or the floor, or both. 33.1. Modular cylinder It´s composed of nuts screws, window fittings, horizontal rails (front and rear) and an upper horizontal frame, supported between the window hardware. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 119/239 33.2. Manifold cylinders in simple line Type 1 for cylinders up to 2.80 ft³ (80 liters) It´s composed of nuts screws, window fittings, horizontal rails (front and rear) and an upper horizontal frame, supported between the window hardware. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 120/239 Type 2 for cylinders from 2.80 ft³ (80 liters) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 121/239 33.3. Manifold cylinders in double line Type 1 for cylinders up to 2.80 ft³ (80 liters) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 122/239 Type 2 for cylinders from 2.80 ft³ (80 liters) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 123/239 34. Manifold fixing bracket in manifold cylinders Their function is to anchor the discharge manifold firmly to a wall or partition which is sufficiently firm and rigid to avoid possible movement during the halocarbonated gas discharge. They consist of two types of channel (wall channel and manifold channel) that form a 90º angle and are mounted vertically on the wall. One of the channels is fitted on the wall with screws and the other is used to fix the manifold using straps. The joint between the two channels can be made using a 90º solid bracket bolted to both channels, to allow the manifold support channel to be moved vertically to its correct position. The manifold fixing straps can slide along the manifold fixing channel. This ensures the manifold has plenty of room to slide along the channel until the most suitable position is reached. Once it is in the right position the straps are tightened and the manifold is correctly fixed. 34.1. Simple line Clamps to fixing manifold Manifold Manifold Manifold fixing channel to manifold 34.2. Double line Clamps to fixing manifold Manifold Manifold Manifold fixing channel to manifold UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 124/239 35. Manifold fixing bracket in manifold cylinders for weighing device in manifold cylinders. Their function is to anchor the discharge manifold firmly to a wall or partition which is sufficiently firm and rigid to avoid possible movement during the halocarbonated gas discharge. In this case the manifold is anchored directly to the fixing bracket manifold cylinders type cage, as shown in Fig. For this manifold is fastened by clamps to each of the windows there. The clamps can be moved linearly through the window rail. Thus the manifold has ample room for deslizase by rail to find the most suitable position. Having found that braces clench position, leaving the manifold set correctly. 35.1. Simple line Manifold fixing cannel to manifold cylinders Manifold fixing cannel to manifold Manifold Clamps to fixing manifold 35.2. Double line Manifold Manifold fixing cannel to manifold cylinders Clamps to fixing manifold Manifold fixing cannel to manifold UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 125/239 36. Flexible discharge hose The gas cylinders are connected to the manifold (in the case of manifold cylinders systems) or directly to the discharge pipe (in the case of modular cylinder) via hoses. This allows for quick and convenient connection of the cylinders on both the time of the assembly and in maintenance or recharging without disassembling the entire network of pipes and bottles. One end is connected to the outlet of the cylinder valve and the other end to the check valve mounted to the manifold in the manifold cylinders and of modular cylinder discharge pipe connection. Your connection at both ends is performed by rotating nuts that allow quick and efficient threading. This allows containers off for maintenance or recharge without dismantling other system elements such as joints, pipes, etc... There are various sizes depending on the size of valve are used: - Flexible hose 1/2” -- cylinder valve RGS-MAM-11-4 y 12-4. Flexible hose 3/4” -- cylinder valve RGS-MAM-20. Flexible hose 1” -- cylinder valve RGS-MAM-40. Rigid hose 1 1/2" -- cylinder valve RGS-MAM-40. Rigid hose 2” -- cylinder valve RGS-MAM-50. Rigid hose 3” -- cylinder valve RGS-MAM-80. 36.1. FH-15CO Flexible hose Technical Information: Flexible hose FH-15CO Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-15CO) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber W21.7x1/14” F revolving 1/2" BSP F revolving 7.09 In (180 mm) 90º 15.75/ 25.59 In (400/650 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 126/239 36.2. DH-15 Flexible hose Technical Information: Flexible hose DH-15 Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-15CO) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber W21.7x1/14” F revolving 1/2" BSP F revolving 3.15 In (80 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals 36.3. DH-15 I Flexible hose Technical Information: Flexible hose DH-15 I Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-15CO) Min. Curvature radius Max. Inclination angle Length Stainless steel AISI 316 Synthetic rubber W21.7x1/14” F revolving 1/2" BSP F revolving 3.15 In (80 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 127/239 36.4. DH-16 Flexible hose Technical Information: Flexible hose DH-16 Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-15CO) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber W21.7x1/14” F revolving 1/2" BSP F revolving 3.15 In (80 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals 36.5. DH-16 I Flexible hose Technical Information: Flexible hose DH-16 I Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-15CO) Min. Curvature radius Max. Inclination angle Length Stainless steel AISI 316 Synthetic rubber W21.7x1/14” F revolving 1/2" BSP F revolving 3.15 In (80 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 128/239 36.6. DH 20 Flexible hose Technical Information: Flexible hose DH 20 Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-20A / 21A) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 3/4" BSP F revolving 3/4" BSP F revolving 3.94 In (100 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals 36.7. DH 20 I Flexible hose Technical Information: Flexible hose DH 20 I Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-20A / 21A) Min. Curvature radius Max. Inclination angle Length Stainless steel AISI 316 Synthetic rubber 3/4" BSP F revolving 3/4" BSP F revolving 3.94 In (100 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 129/239 36.8. DH 21 Flexible hose Technical Information: Flexible hose DH 21 Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-20A / 21A) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 3/4" BSP F revolving 3/4" BSP F revolving 4.72 in (120 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals 36.9. DH 21 I Flexible hose Technical Information: Flexible hose DH 21 I Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-20A / 21A) Min. Curvature radius Max. Inclination angle Length Stainless steel AISI 316 Synthetic rubber 3/4" BSP F revolving 3/4" BSP F revolving 4.72 in (120 mm) 90º 9.84/ 11.81/ 15.75/ 19.69/ 27.56/ 33.46/ 39.47/ 49.21/ 59.06/ 78.74 In (250 / 300 / 400 / 500 / 700 / 850 / 1000 / 1250 / 1500 / 2000 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 130/239 36.10. FH-20HC Flexible hose Technical Information: Flexible hose FH-20HC Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-20A / 21A) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 3/4" BSP F revolving 3/4" BSP F revolving 9.45 In (240 mm) 90º 15.75/ 21.65/ 25.59/ 29.53/ 39.37 In (400 / 550 / 650 / 750 / 1000 mm) UL-EX15547 FM-3053302 Approvals 36.11. FH-25HC Flexible hose Technical Information: Flexible hose FH-25HC Connections Fexible conduct Connection thread to the container valve Connection thread to the check valve (VALAN-20A / 21A) Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 1" BSP F revolving 1" BSP F revolving 6.3 In (160 mm) 90º 15.75/ 21.26 In (400 and 540 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 131/239 36.12. FH-40HC Rigid hose Technical Information: Rigid hose FH-40HC Rigid conduct Connection thread to the container valve (RGS-MAM-40) Connection thread to the check valve (VALAN-40-23) Inclination angle Approvals Steel 1 1/2" BSP F revolving 1 1/2" BSP F revolving 90º UL-EX15547 FM-3053302 36.13. FH-50HC Rigid hose Technical Information: Rigid hose FH-50HC Rigid conduct Connection thread to the container valve (RGS-MAM-50) Connection thread to the check valve (VALAN-50-125) Inclination angle Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Steel 2" BSP F revolving 2" BSP F revolving 90º UL-EX15547 FM-3053302 132/239 36.14. FH-80HC Rigid-grooved hose Connection to the check valve 3” G Technical Information: Rígid grooved hose FH-80HC Material rigid elbow Connection thread to the container valve Connection thread to the check valve (VALAN-80) Inclination angle Length Working pressure Steel 3" Grooved 3" BSP Male 90º 10.9x5.2 In (276,8x132,2 mm) 363 Psi (25 bar) Approvals UL-EX15547 FM-3053302 Connection to the container valve 3” Grooved 36.15. FH-80HC34 Rigid-grooved hose Connection to the check valve 3” G Technical Information: Rígid grooved hose FH-80HC34 Material rigid elbow Connection thread to the container valve Connection thread to the check valve (VALAN-80) Inclination angle Length Working pressure Steel 3" Grooved 3" BSP Male 90º 10.9x5.2 In (276,8x132,2 mm) 363/ 464/ 493 Psi (25,32,34 bar) Approvals UL-EX15547 FM-3053302 Connection to the container valve 3” Grooved UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 133/239 36.16. FH-81HC Elbow rigid grooved Connection to discharge pipe 3” Grooved Technical Information: Rígid grooved hose FH-81HC Material rigid elbow Connection thread to the container valve Connecting to the discharge pipe Inclination angle Working pressure Steel 3" Grooved 3" Grooved 90º 363 Psi (25 bar) Approvals UL-EX15547 FM-3053302 Connection to the container valve 3” Grooved 36.17. FH-81HC34 Elbow rigid grooved Connection to discharge pipe 3” Grooved Technical Information: Rígid grooved hose FH-81HC34 Material rigid elbow Connection thread to the container valve Connecting to the discharge pipe Inclination angle Working pressure Steel 3" Grooved 3" Grooved 90º 363/ 464/ 493 Psi (25,32,34 bar) Approvals UL-EX15547 FM-3053302 Connection to the container valve 3” Grooved UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 134/239 37. Discharge hose adapters Its function is to facilitate the connection of the discharge valve to the modular cylinder. There are three types, the adapter binding "POADxxHH Loca", which links up the valve outlet to the discharge pipe, adapter binding "POADxxMH" that connect the discharge hose to the pipe, and the union adapter "POADxxHH" simple sleeve container valve to the pipe. 37.1. POADxxHH Loca Adapters Adapters POADxxHH Loca A Type POAD20HH Loca POAD25HH Loca POAD40HH Loca POAD50HH Loca Approvals A ¾” BSP 1” BSP 1 ½” BSP 2” BSP UL-EX15547 FM-3053302 37.2. POADxxMH Adapters Adapters POADxxMH Type POAD15MH POAD20MH POAD25MH POAD40MH POAD50MH A Approvals A ½” BSP ¾” BSP 1” BSP 1 ½” BSP 2” BSP UL-EX15547 FM-3053302 37.3. POADxxHH Adapters Adapters POADxxHH A Type POAD40HH POAD50HH Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 A 1 ½” BSP 2” BSP UL-EX15547 FM-3053302 135/239 POADxxHH Loca 38. POADxx POADPMxx Wall bypass Its function is to facilitate the connection between the hose and the discharge pipe in terms of passage through a wall or sheet metal wall. Connection to hose or discharge pipe Connection to hose or discharge pipe Wall bypass POADPMxx Connection thread to flexible hose and Connection thread to the discharge pipe Approvals UL-EX15547 FM-3053302 Type A POADPM10 3/8” BSP Male POADPM15 1/2" BSP Male POADPM20 3/4” BSP Male POADPM25 1” BSP Male UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 136/239 39. Activation flexible hoses It is used to connect the various auxiliary bottles to the pilot bottle or master cylinder. Its series connection allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various auxiliary or slave cylinder valves, by pressurising their respective pneumatic actuator heads. Activation flexible hoses FH-6PO / DH-10 / DH 10I FH-7PO / DH – 11 / DH 11I 39.1. FH-6PO Activation flexible hose Technical Information: Activation flexible hose FH-6PO Connections Fexible conduct Connecting thread at both ends Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Stainless steel mesh 1/4" BSP F revolving 2.99 In (76 mm) 90º 19.69/ 23.62/ 28.53/ 39.37 In (500 / 600 / 725 / 1000 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 137/239 39.2. DH 10 Activation flexible hose Technical Information: Activation flexible hose DH 10 Connections Fexible conduct Connecting thread at both ends Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 1/4" BSP F revolving 1.97 In (50 mm) 90º 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) UL-EX15547 FM-3053302 Approvals 39.3. DH 10 I Activation flexible hose Technical Information: Activation flexible hose DH 10 I Connections Fexible conduct Connecting thread at both ends Min. Curvature radius Max. Inclination angle Length Stainless steel AISI 316 Synthetic rubber 1/4" BSP F revolving 1.97 In (50 mm) 90º 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 138/239 39.4. FH-7PO Activation flexible hose Technical Information: Activation flexible hose FH-7PO Connections Fexible conduct Connecting thread at both ends Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 1/4" BSP F revolving 3.94 In (100 mm) 90º 19.69/ 23.62/ 28.53/ 39.37 In (500 / 600 / 725 / 1000 mm) UL-EX15547 FM-3053302 Approvals 39.5. DH 11 Activation flexible hose Technical Information: Activation flexible hose DH 11 Connections Fexible conduct Connecting thread at both ends Min. Curvature radius Max. Inclination angle Length Bi-chrome tempered steel Synthetic rubber 1/4" BSP F revolving 1.77 In (45 mm) 90º 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 139/239 39.6. DH 11 I Activation flexible hose Technical Information: Activation flexible hose DH 11 I Connections Fexible conduct Connecting thread at both ends Min. Curvature radius Max. Inclination angle Length Stainless steel AISI 316 Synthetic rubber 1/4" BSP F revolving 1.77 In (45 mm) 90º 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) Approvals UL-EX15547 FM-3053302 39.7. FH-2PO Activation flexible hose Technical Information: Activation flexible hose FH-2PO Connections Fexible conduct Connecting thread to the container valve Connecting thread to body Curvature radius Length Stainless steel AISI 316 Polyurethane 1/4” BSP revolving 1/8-27NFPT revolving 0.79 In (20 mm) 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) Approvals UL-EX15547 FM-3053302 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 140/239 39.8. FH-2POH Activation flexible hose Technical Information: Activation flexible hose FH-2POH Connections Fexible conduct Connecting thread to the container valve Connecting thread to body Curvature radius Length Stainless steel AISI 316 Polyurethane 1/4” BSP revolving 1/4” BSP revolving 0.79 In (20 mm) 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) Approvals 40. UL-EX15547 FM-3053302 POLATCU Copper pipe 0.24x0.16 in (6x4 mm) The copper actuator hose is used to actuate or discharge pneumatically the fire extinguishing gas container valves. The gas from the pilot cylinder flows through them and actuates the different pneumatic actuators of auxiliary or slave container valves. They are connected to the pneumatic actuators by tee (227TE), elbow (227CO) or adapter (POAD10MM). Regarding the total length, there are different measures depending on the use of pilot cylinder. Nut with bicone adaptor Variable Technical Information: Copper pipe POLATCU Material Type of cylinder valve Length Approvals UL-EX15547 FM-3053302 Copper RGS-MAM-20/40/50/80 RGS-MAM-11-4/12-4 RGS-MAM-03/03A POSX-NAU / POSX-NAUC 27CN / 227CNTK 227CNM Variable UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 141/239 41. Check Valves These valves are connected between the discharge hose and the manifold, allows the gas flow in one direction only, from the hose to the manifold, not in the other way. The valves prevent gas from escaping from the piping system during a discharge (except, of course, into the protected hazard area), should a cylinder not be connected to the manifold. They are supplied from the factory screwed onto the manifold. There are seven types of check valves: VALAN-80, VALAN-50-125, VALAN-40-23, VALAN-20A, VALAN21A, VALAN-15CO and VALAN-15CO VF. The models VALAN-50-125 and VALAN-40-23 are the same except for the size and fluid path diameter. They have a telescopic mechanism which slides up and down. This system prevents problems when screwing in the rigid discharge hoses, when the floor on which the cylinders rest is irregular or the cylinders are of different heights. The VALAN-20A, VALAN-21A, VALAN15CO and VALAN-15CO VF have a different, but just as effective, mechanism from the others. 41.1. VALAN-80 Check valve Connection to the discharge manifold Connection to the discharge hose Technical Information : Check valve VALAN-80 Body VALAN-80 Brass CuZn40Pb2 Piston VALAN-80 Brass CuZn39Pb3 Connection to the manifold 3" BSP (Female) Connection to the discharge hose 3" BSP (Female) Approvals UL-EX15547 FM-3053302 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 142/239 41.2. VALAN-50-125 Check valve Connection to the discharge manifold Technical Information: Check valve VALAN-50-125 Body VALAN-50-125 Connection to the manifold Brass CuZn40Pb2 2 1/2" BSP Connection to the discharge hose Connection to the discharge hose Approvals 2" BSP UL-EX15547 FM-3053302 Valan-50-125 41.3. VALAN-40-23 Check valve Connection to the discharge manifold Technical Information: Check valve VALAN-40-23 Body VALAN-40-23 Connection to the manifold Connection to the discharge hose Connection to the discharge hose Approvals Brass CuZn40Pb2 2" BSP 1 1/2" BSP UL-EX15547 FM-3053302 Valan-40-23 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 143/239 41.4. VALAN-21A Check valve Connection to the discharge manifold Technical Information: Check valve VALAN-21A Body VALAN-21A Brass CuZn40Pb2 Connection to the manifold 1" NPT Connection to the discharge hose Connection to the discharge hose Approvals 3/4" BSP UL-EX15547 FM-3053302 Valan-21A 41.5. VALAN-20A Check valve Connection to the discharge manifold Technical Information: Check valve VALAN-20A Body VALAN-20A Connection to the manifold Connection to the discharge hose Connection to the discharge hose Approvals Brass CuZn40Pb2 1" NPT 3/4" BSP UL-EX15547 FM-3053302 Valan-20A UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 144/239 41.6. VALAN-15CO Check valve Connection to the discharge manifold Technical Information: Check valve VALAN-15CO Body VALAN-15CO Connection to the discharge hose Brass CuZn40Pb2 Connection to the manifold 3/4" BSP Connection to the discharge hose 1/2" BSP Approvals UL-EX15547 FM-3053302 Valan-15CO 41.7. VALAN-15CO-VF Check valve This check valve is always installed with the diaphragm valve CVAD15. The diaphragm valve is installed between the discharge hose and the check valve of the master cylinder, ONLY in master-slave configurations. Connection to the discharge manifold Technical Information: Valan-15COVF + CVAD15 Check valve VALAN-15CO-VF Body VALAN-15CO-VF Connection to the discharge hose Connection to the manifold 3/4" BSP Connection to the discharge hose 1/2" BSP Minimum opening pressure Approvals UL-EX15547 FM-3053302 Brass CuZn40Pb2 “UF-MC-HC” - 27-01-2016 14.5 psi (1 bar) UL-EX15547 FM-3053302 145/239 42. CVAD15 Diaphragm valve* This device is used to deviate part of the discharge pressure of the master cylinder to the pilot line in order to activate the rest of the slave cylinders pneumatically with the pneumatic actuators. The diaphragm is always installed in a master-slave configuration between the discharge hose of the master cylinder and its check valve. Technical Information: Diaphragm valve CVAD15* Location Material Connection to the check valve Connection to the discharge hose Connection to the activation hose Approvals Discharge manifold Brass 1/2" BSP Female 1/2" BSP Male 1/4" BSP Female UL-EX15547 FM-3053302 * This is not part of the UL Approval. Check valve Valan-15CO-VF Diaphragm valve CVAD15 Discharge Hose Activation Hose UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 146/239 43. Main – Reserve Check valve These check valves in line, are connected in the main – reserve systems, in the outlet pipe of the manifold of the main battery and reserve battery. They do not allow that the gas come back during the discharge of the main or reserve battery to the manifold of the battery which are not in use, in case that any cylinder are not connected to the manifold or has been disassembled for their refilling. There are three types of main – reserve check valves: 227VALAN-50-125L, 227VALAN-40-23L and 227VALAN-80L. The three models are similar but with different size and fluid path diameter. 43.1. 227VALAN40-23L Check valve Female connection to the 1 ½” pipe Male connection to the 1 ½” pipe Technical Information: Check valve 227VALAN-40-23L Body 227VALAN-40-23L Brass Connection to the pipe Approvals UL-EX15547 FM-3053302 1 1/2” BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 147/239 43.2. 227VALAN50-125L Check valve Female connection to the 2” pipe Male connection to the 2” pipe Technical Information: Check valve 227VALAN-50-125L Body 227VALAN-50-125L Brass Connection to the pipe 2 " BSP UL-EX15547 FM-3053302 Approvals Check valve main - reserve 227VALAN-50-125L Reserve battery Main battery Location of the check valve main - reserve. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 148/239 43.3. 227VALAN-80L Check valve Connection to the pipe 3”G Connection to the pipe 3”G Technical Information: Check valve 227VALAN-80L Body 227VALAN-80L Brass CuZn40Pb2 Connection to the pipe 3" BSP (Female) Minimum opening Approvals 14.5 psi (1 bar) UL-EX15547 FM-3053302 Pipe Check valve 227valan-80L Pipe to cylinder battery UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 149/239 44. VALAN-WFR8 / WFR8-316 Non-return valve in line These valves are used in some pneumatically activated systems. They are normally fitted between the activation hoses of the pilot line. Their correct position is shown in the system installation drawings. In equipment with selector valves, their function is to direct the flow of pneumatic actuation pressure towards the points needed to actuate the appropriate number of cylinders. Technical Information Non-return valve in line VALAN-WFR-8 Material Inox AISI 303 and Brass Outlet and Inlet connection 1/4" BSP Female UL-EX15547 FM-3053302 Approvals Non-return valve in line VALAN-WFR-8-316 Material Outlet and Inlet connection Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Inox AISI 316 and Brass 1/4" BSP Female UL-EX15547 FM-3053302 150/239 4 1 1 3 1 Actuation hoses FH-6PO / FH-7PO / DH-10 / DH-10I / DH-11 / DH-11I 2 O-ring or metal-plastic washer 3 Tee of 1/4" BSP (227TE) 4 Non-return valve in line VALAN-WFR8 / WFR8-316 5 Pneumatic activation head 227CN / 227CNTK 5 3 2 Connection of non-return valve in line with discharge hose. 6 2 3 7 1 1 4 1 Actuation hose FH-6PO / FH-7PO / DH-10 / DH-10I / DH-11 / DH-11I 2 O-ring or metal-plastic washer 3 “Tee" of 1/4" BSP (227TE) 4 Non-return valve in line VALAN-WFR8 / WFR8-316 5 Pneumatic actuator head 227CN / CNTK 6 Copper tube POLATCU 7 Adapter copper tube to 1/4" G POA8CU 5 3 Connection of non-return valve in line with copper tube. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 151/239 45. VALAN-62 Shuttle valve The two ways check valve VALAN-62 for systems with INERT Gases Ig-01, has the function of the union of two cylinders or pilot bottles. It is used in systems, which because operation requirements, need 2 pilot bottles (One of them is usually opened only manually). 2 1 “Tee" of 1/4" BSP (227TE) 2 O-ring or metal-plastic washer 3 Non-return valve in line VALAN-WFR8 / WFR8-316 2 3 1 3 Shuttle valve VALAN-62 Components Approvals UL-EX15547 FM-3053302 2 non-return valve ¼ bsp female 1”tee” ¼” bsp male UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 152/239 46. Pilot bottle This bottle serves to actuate the cylinders in a bank of six or more cylinders or whenever selector valves are used. It consists of a 0.07, 0.24, 0.46 ft³ (2, 6.7 or 13.4 l) cylinder, a protective flange and a RGS-MAM-11-4 or 124 valve with pressure gauge. These in turn have a built-in re-assembled electrical actuator head (227SOL, 227SOLC or 227SOLC125) together with the manual actuator head (227DM, 227DMS, 227CMC, 227CMCC or 227CNM). Charged with dry nitrogen, it is actuated by an electric or manual signal and its purpose is to actuate the extinguishing agent cylinder bank. When the pilot bottle is actuated, the gas flows through the activation hoses and pneumatically actuates the various pneumatic discharge heads (227CN, 227CNTK or 227CNM), which, in turn, actuate the slave valves of the cylinders containing the extinguishing agent. 1 2 7 3 6 5 1. - Manual actuator head (227DM, 227DMS, 227CMC, 227CMCC or 227CNM). 2. - Re-assembled electrical actuator head (227SOL, 227SOLC or 227SOLC125). 3. - Container valve RGS-MAM-11-4 / 12-4. 4. - Pilot bottle 5. - Modular bracket. 6. - Security flange. 7. - Pressure switch. 4 Technical information Pilot bottle Cylinder capacity 100M2UFxx 100M6UFxx 100M13UFxx 0.07 ft³ 0.24 ft³ 0.47 ft³ (2L) (6,7L) (13,4L) Gas contained in the cylinder Valve type Actuation mechanism Inert Gases RGS MAM 11-4 / 12-4 Actuation port: Manual actuator head (227DM, 227DMS, 227CMC, 227CMCC or 227CNM). Electrical actuator head (227SOL, 227SOLC or 227SOLC125). Outlet valve thread W21.8 x 1/14” Filling port valve thread W21.8 x 1/14” Outside diameter See Annex 3 Lenght A Pressure gauge Filling pressure at 20º C UF40I-P150 UF40I-E150 UF40I-P200 UF40I-E200 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 153/239 Limitations in the use of the pilot bottle 19.69/ 23.62/ 27.56/ 31.5/ 39.37/ 49.21/ 59.06 In (500 / 600 / 700 / 800 / 1000 / 1250 / 1500 mm) 39.37 In (1000 mm) The following table shows the maximum number of pneumatic actuator heads that the pilot bottles with differents capacities and pressures are capable of activate: Pneumatic Actuator Head 227CN 227CN 227CN 227CNTK 227CNTK 227CNTK Capacity of Pilot bottle 0.07 ft³ (2 L) 0.24 ft³ (6,7 L) 0.47 ft³ (13,4 L) 0.07 ft³ (2 L) 0.24 ft³ (6,7 L) 0.47 ft³ (13,4 L) UL-EX15547 FM-3053302 Pressure 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) Pneumatic actuators with hoses FH-6PO, FH-7PO, DH 10, DH 10 I, DH 11, DH 11 I L: 19.69 in (500 mm) Pneumatic actuators with hoses FH-6PO, FH-7PO, DH 10, DH 10 I, DH 11, DH 11 I L: 23.62 In (600 mm) Pneumatic Actuators with hoses DH 10, DH 10 I, DH 11, DH 11 I L: 27.56 in (700 mm) Pneumatic Actuators with hoses FH-6PO, FH-7PO L: 28.54 in (725 mm) 35 29 26 25 40 34 29 28 50 42 37 35 60 51 44 43 55 46 40 39 55 46 40 39 55 46 40 39 60 51 44 43 55 46 40 39 60 51 44 43 60 51 44 43 65 55 48 46 50 43 38 37 55 47 42 40 55 47 42 40 55 47 42 40 55 47 42 40 55 47 42 40 55 47 42 40 60 51 45 44 55 47 42 40 55 47 42 40 60 51 45 44 60 51 45 44 “UF-MC-HC” - 27-01-2016 154/239 Pneumatic Actuator Head 227CN 227CN 227CN 227CNTK 227CNTK 227CNTK Pilot bottle 0.07 ft³ (2 L) 0.24 ft³ (6,7 L) 0.47 ft³ (13,4 L) 0.07 ft³ (2 L) 0.24 ft³ (6,7 L) 0.47 ft³ (13,4 L) Pressure 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) 1450 psi (100 bar) 1740 psi (120 bar) 2175 psi (150 bar) 2900 psi (200 bar) Pneumatic Actuators with hoses DH 10, DH 10 I, DH 11, DH 11 I L: 31.5 In (800 mm) Pneumatic Actuators with hoses FH-6PO, FH-7PO, DH 10, DH 10 I, DH 11, DH 11 I L: 39.37In (1000 mm) Pneumatic actuators with hoses DH 10, DH 10 I, DH 11, DH 11 I L:1250 mm Pneumatic Actuators with hoses DH 10, DH 10 I, DH 11, DH 11 I L: 1500 mm Copper tube POLATCU L: 1000 mm 23 18 15 13 42 26 21 17 14 48 32 26 21 18 60 39 32 22 22 72 36 29 24 20 66 36 29 24 20 66 36 29 24 20 66 39 32 26 22 72 36 29 24 20 66 39 32 26 22 72 39 32 26 22 72 42 34 28 23 78 34 28 23 20 58 37 31 25 21 64 37 31 25 21 64 37 31 25 21 64 37 31 25 21 64 37 31 25 21 64 37 31 25 21 64 41 34 28 23 70 37 31 25 21 64 37 31 25 21 64 41 34 28 23 70 41 34 28 23 70 IMPORTANT: Other configurations are available at the sole discretion of SIEX. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 155/239 46.1. Adapters for pilot bottles The functioning of these adapters are to make the connection between the outlet of the container valve of the pilot bottle and the flexible activation hose or copper tube. For this function four adapters will be used, one which reduce the outlet thread of the container valve (W21,7x1/14”) to thread of 1/4" BSP male, allowing that the flexible hose can be screwed. And another adapter which reduces the thread of 1/4" BSP to copper tube of 0.24x0.16 In (6x4mm). The third are compounded by the two previus adapters that joined between them, make possible their connection between the pilot bottle and the copper tube. The last adapter is a tee for copper tube. 46.1.1. POA8CU Adapter Adapter of 1/4" BSP f to copper tube POA8CU Material Connection to copper tube 0.24x0.16In (6x4 mm) Adapter of ¼” BSP to copper tube 46.1.2. Brass Bicone Connection to adapter (POA218) 1/4” BSP Female Approvals UL-EX15547 FM-3053302 POA218 Adapter Adapter of W21,7 to 1/4" BSP m POA218 Material Adapter of W 21,7 to ¼” BSP 46.1.3. Connection to flexible hose Approvals Brass 1/4” BSP UL-EX15547 FM-3053302 POA21CU Adapter Adapter of W21,7 to copper tube POA21CU Brass Connection to flexible hose 1/4” G Connection to copper tube Adapter of W21, 7 to copper tube 46.1.4. Material Approvals Bicone UL-EX15547 FM-3053302 POADT8CU Adapter Adapter copper tube to copper tube POADT8CU Material Connection to copper tube 0.24x0.16In (6x4 mm) Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Brass Bicone UL-EX15547 FM-3053302 156/239 Copper tube POLATCU Flrxible hose FH-6PO / FH-7PO / DH-10 / DN-10I / DH-11 / DH11I Teflon washer 0.24x0.16In (6x4 mm) Pilot bottle 47. Pilot Cartridge The pilot cartridge are compuonded by: valve RGS-MAM-03/03A, re-assembled electrical actuator head 227SOLR, 227SOLCR or 227SOLCR125, manual actuator head 227DM, 227DMR, 227DMS, 227CMC, 227CMCC or 227CNM, pilot cartridge of 0.003 or 0.006 ft³ (0.08 or 0.18 l) filled at 2175 psi (150 bar) and a pressure gauge (UF40I-P150,UF40I-P200, UF40I-E150 or UF40I-E200). Its function is pneumatically activates the container valves of systems of modular cylinders, batteries, and other mechanisms with pneumatic functionality where it can be mounted. Is enough with a manual or electrical activation of the corresponding actuator head that in turn, will give way to the N2 from the pilot cartridge to the pneumatic actuator head that makes the activation. This actuator can be installed in vertical or horizontal position. Re-assembled electrical actuator head 227SOLR, 227SOLCR, 227SOLCR125 Manual actuator head 227DMR Manual actuator head 227DM, 227DMR, 227DMS, 227CMC, 227CMCC, 227CNM Valve RGS-MAM-03/03A Pilot cartridge Presure gauge UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 157/239 Pilot Cartridge Cylinder capacity 100M008UFA 100M018UFA 0.003 ft³ (0,080 L) 0.006 ft³ (0,180 L) Gas contained in the cylinder Inert Gases RGS - MAM – 03/03A Valve type Re-assembled electrical actuator 227SOLR, 227SOLCR, 227SOLR125, 227SOLR220, 227SOLCR125, 227SOLCR220), or manual actuator 227DM, 227DMS, 227CMC, 227CMCC, 227DMR Mechanism of activation 1/4” BSP Female Threaded connection to the container valve Necessary energy 24V (DC) / 0,6 Amp / 10W UF40I-P150 UF40I-E150 UF40I-P200 UF40I-E200 Pressure gauge UL-EX15547 FM-3053302 Approvals Limitations in use of pilot cartridge 19.69 In (500 mm) 39.37 in (1000 mm) UL-EX15547 FM-3053302 Pneumatic Actuator Pilot cartridge capacity 227CN 0.003 ft³ (0,08 l) 227CNTK 0.003 ft³ (0,08 l) 227CN 0.006 ft³ (0,18 l) 227CNTK 0.006 ft³ (0,18 l) Pressure Actuator head with hoses FH-6PO, FH-7PO, DH 10, DH 10 I, DH 11, DH 11 I L: 19.69 In (500 mm) 2175 psi (150 bar) 2175 psi (150 bar) 2175 psi (150 bar) 2175 psi (150 bar) “UF-MC-HC” - 27-01-2016 10 20 19 29 158/239 48. FEDRxx Discharge nozzle Its function is to discharge extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. They are screwed onto the discharge piping in a vertical position, and can be 360º or 180º, with threads from 3/8” BSP to 2 1/2” BSP. The 360º nozzles have 8 outlet orifices at two levels and the 180º ones have 7, also at two levels. Each level has a different angle of inclination to improve gas distribution in the hazard area. The 360º radial nozzles discharge gas uniformly in a 360º circular section plane. 180º radial nozzles do so in half of this circle. The 180º nozzles are usually for installing along the walls of the hazard while the 360º ones are installed in the middle of the protected room. These discharge nozzles have a limitation of maximum heigh of 23.30 ft (7.1m) and a limitation of maximum coverage area of 43.30x43.30 ft (13.2 x 13.2m). Nozzle 360º Max. 43.30x43.30x23.30 ft (13,2m x13, 2m x7, 1m) Nozzle 180º Technical Information Discharge nozzle FEDRxx Material Carbonated steel / Inox Steel AISI 303 and 316 / Aluminum* / Brass Inlet and Outlet Finnish Thread connection to the pipe Zinc-niquel (Only the manufactured in carbonated steel) (Female thread) From 3/8” BSP to 2 1/2” BSP Nozzle 360º 8 orifices at 2 levels Nozzle 180º 7 orifices at 2 levels The threads connections comply with the International standards ISO 7-1 or ISO 228-1 YES UL-EX15547 FM-3053302 Approvals * This is not part of the FM Approval, only UL Listed. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 159/239 Thread (R) A e/c C B Nozzle 360º NOZZLES 360º - CARBONATED STEEL MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) FEDR10 3/8” BSP FEDR15 1/2” BSP 8 0.16 (4) 8 0.22 (5.5) FEDR20 FEDR25 3/4” BSP 8 1” BSP 8 FEDR32 1 1/4” BSP FEDR40 FEDR50 FEDR65 Length B In (mm) Length C In (mm) 0.94 (24) 1.4 (35.5) 0.55 (14) 1.18 (30) 1.66 (42.1) 0.63 (16) 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) 8 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) 1 1/2” BSP 8 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) 2” BSP 8 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) 2 1/2” BSP 8 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) NOZZLES 360º - ALUMINUM* MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10A 3/8” BSP 8 0.16 (4) 0.94 (24) 1.4 (35.5) 0.55 (14) FEDR15A 1/2” BSP 8 0.22 (5.5) 1.18 (30) 1.66 (42.1) 0.63 (16) FEDR20A 3/4” BSP 8 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) FEDR25A 1” BSP 8 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) FEDR32A 1 1/4” BSP 8 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) FEDR40A 1 1/2” BSP 8 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) FEDR50A 2” BSP 8 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) FEDR65A 2 1/2” BSP 8 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) * This is not part of the FM Approval, only UL Listed. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 160/239 NOZZLES 360º - BRASS MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10B 3/8” BSP 8 0.16 (4) 0.94 (24) 1.4 (35.5) 0.55 (14) FEDR15B 1/2” BSP 8 0.22 (5.5) 1.18 (30) 1.66 (42.1) 0.63 (16) FEDR20B 3/4” BSP 8 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) FEDR25B 1” BSP 8 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) FEDR32B 1 1/4” BSP 8 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) FEDR40B 1 1/2” BSP 8 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) FEDR50B 2” BSP 8 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) FEDR65B 2 1/2” BSP 8 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) NOZZLES 360º - INOX STEEL AISI 303 MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) FEDR10I 3/8” BSP FEDR15I 1/2” BSP 8 0.16 (4) 8 0.22 (5.5) FEDR20I FEDR25I 3/4” BSP 8 1” BSP 8 FEDR32I 1 1/4” BSP FEDR40I 1 1/2” BSP FEDR50I FEDR65I Length B In (mm) Length C In (mm) 0.94 (24) 1.4 (35.5) 0.55 (14) 1.18 (30) 1.66 (42.1) 0.63 (16) 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) 8 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) 8 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) 2” BSP 8 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) 2 1/2” BSP 8 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) NOZZLES 360º - INOX STEEL AISI 316 MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10I316 3/8” BSP 8 0.16 (4) 0.94 (24) 1.4 (35.5) 0.55 (14) FEDR15I316 1/2” BSP 8 0.22 (5.5) 1.18 (30) 1.66 (42.1) 0.63 (16) FEDR20I316 3/4” BSP 8 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) FEDR25I316 1” BSP 8 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) FEDR32I316 1 1/4” BSP 8 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) FEDR40I316 1 1/2” BSP 8 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) FEDR50I316 2” BSP 8 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) FEDR65I316 2 1/2” BSP 8 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 161/239 Thread (R) A e/c C B Nozzle 180º NOZZLES 180º - CARBONATED STEEL MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10180 3/8” BSP 7 0.16 (4) 0.94 (24) 1.4 (35.5) 0.55 (14) FEDR15180 1/2” BSP 7 0.22 (5.5) 1.18 (30) 1.66 (42.1) 0.63 (16) FEDR20180 ¾” BSP 7 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) FEDR25180 1” BSP 7 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) FEDR32180 1 ¼” BSP 7 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) FEDR40180 1 1/2” BSP 7 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) FEDR50180 2” BSP 7 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) FEDR65180 2 1/2” BSP 7 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) NOZZLES 180º - ALUMINUM* MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10180A 3/8” BSP FEDR15180A 1/2” BSP 7 0.16 (4) 7 0.22 (5.5) 0.94 (24) 1.4 (35.5) 0.55 (14) 1.18 (30) 1.66 (42.1) FEDR20180A ¾” BSP 7 0.63 (16) 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) FEDR25180A 1” BSP FEDR32180A 1 ¼” BSP 7 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) 7 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) FEDR40180A FEDR50180A 1 1/2” BSP 7 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) 2” BSP 7 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) FEDR65180A 2 1/2” BSP 7 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) * This is not part of the FM Approval, only UL Listed. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 162/239 NOZZLES 180º - BRASS MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10180B 3/8” BSP FEDR15180B 1/2” BSP 7 0.16 (4) 7 0.22 (5.5) 0.94 (24) 1.4 (35.5) 0.55 (14) 1.18 (30) 1.66 (42.1) FEDR20180B ¾” BSP 7 0.63 (16) 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) FEDR25180B 1” BSP FEDR32180B 1 ¼” BSP 7 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) 7 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) FEDR40180B FEDR50180B 1 1/2” BSP 7 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) 2” BSP 7 0.71 (18) 2.83 (72) 3.43(87) FEDR65180B 1.06 (27) 2 1/2” BSP 7 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) NOZZLES 180º - INOX STEEL AISI 303 MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) Length B In (mm) Length C In (mm) FEDR10180I 3/8” BSP FEDR15180I 1/2” BSP 7 0.16 (4) 7 0.22 (5.5) 0.94 (24) 1.4 (35.5) 0.55 (14) 1.18 (30) 1.66 (42.1) 0.63 (16) FEDR20180I FEDR25180I ¾” BSP 7 1” BSP 7 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) FEDR32180I 1 ¼” BSP FEDR40180I 1 1/2” BSP 7 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) 7 0.55 (14) 2.36 (60) 2.87(73) FEDR50180I 0.87 (22) 2” BSP 7 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) FEDR65180I 2 1/2” BSP 7 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) NOZZLES 180º - INOX STEEL AISI 316 MODEL Thread connection (R) No. of orifices Orifices Ø In (mm) Length Ex. A e/c In (mm) FEDR10180I316 3/8” BSP FEDR15180I316 1/2” BSP 7 0.16 (4) 7 0.22 (5.5) FEDR20180I316 ¾” BSP 7 FEDR25180I316 1” BSP FEDR32180I316 1 ¼” BSP FEDR40180I316 FEDR50180I316 FEDR65180I316 UL-EX15547 FM-3053302 Length B In (mm) Length C In (mm) 0.94 (24) 1.4 (35.5) 0.55 (14) 1.18 (30) 1.66 (42.1) 0.63 (16) 0.3 (7.5) 1.57 (40) 2.13 (54) 0.71 (18) 7 0.35 (9) 1.81 (46) 2.32 (59) 0.75 (19) 7 0.45 (11.5) 2.17 (55) 2.64 (67) 0.83 (21) 1 1/2” BSP 7 0.55 (14) 2.36 (60) 2.87(73) 0.87 (22) 2” BSP 7 0.71 (18) 2.83 (72) 3.43(87) 1.06 (27) 2 1/2” BSP 7 0.71 (18) 3.35 (85) 3.54(90) 1.18 (30) “UF-MC-HC” - 27-01-2016 163/239 48.1. POPCxxx Calibrated plate The calibrated plate is located inside the discharge nozzles in order to control the exact amount of gas to be discharged. As its name indicates, it is a circular plate with a central orifice calibrated according to the hydraulic calculations (calculation software). The diameter of the central calibrated orifice is stamped on the lower flat part of the nozzle. Its size is expressed in millimetres to two decimal places (e.g. 0.48 in (12.25 mm)). Calibrated plates must be fitted into every nozzle which is connected to cylinders or banks of cylinders with more than one nozzle to protect one or more hazard areas. In modular cylinders with a single nozzle, it is not necessary to use a calibrated orifice. Nor are they necessary in pre-engineered and balanced systems with 2 or 4 nozzles, provided that the distances and requirements of those systems are complied with. They are supplied from the factory assembled in the nozzles. Pipe Calibrate plate Nozzle Calibrated orifice according to hydraulic calculations Marked in the nozzle with the diameter of the calibrated orifice Calibrated plate Technical information Calibrated plates POPCxxx Material Types according to the nozzle Outlet diameter Calibrated orifice diameter Inox steel AISI 304 and Brass From 3/8” BSP to 2 1/2” BSP UL-EX15547 FM-3053302 BRASS INOX STEEL AISI 304 POPC10B 3/8” BSP POPC10I 3/8” BSP Adjusted to nozzle size POPC15B 1/2” BSP POPC15I 1/2” BSP POPC20B 3/4” BSP POPC20I 3/4” BSP According to the hidraulic calculations POPC25B 1” BSP POPC25I 1” BSP POPC32B 1 1/4” BSP POPC32I 1 1/4” BSP NO POPC40B 1 1/2” BSP POPC40I 1 1/2” BSP POPC50B 2” BSP POPC50I 2” BSP POPC65B 2 1/2” BSP POPC65I 2 1/2” BSP Exist restrictor in the instalation Approvals Calibrated plates POPCxxx UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 164/239 49. Selector valves They are used to protect several risks at once with a single cylinder bank or modular cylinder. In an HFC system two or more valves can be used to protect two or more hazard areas. When a fire starts in one of the hazard areas, the corresponding selector valve would open and discharge all or part of the extinguishing agent stored in the cylinders. When selector valves are opted for, at least one reserve cylinder bank should be installed in order not to leave the remaining hazards unprotected, in case a second discharge should be required in one of them. They are fitted directly to the discharge manifold or downstream on a separate manifold. They consist of a normally closed ball valve, a pneumatic cylinder, a re-assembled electrical and manual actuator. An electrical signal opens the electrical actuator corresponding to the selector valve of the hazard to be protected, so that when the nitrogen-filled pilot bottle is actuated, its pressure will be pushed on the piston of the appropriate valve, causing it to open. In the event of failure of the electrical actuator or the detection system, the system can be manually activated using the manual actuator. By turning the actuator lever 86º, pressure from the pilot bottle will move the pneumatic cylinder causing the selector valve to open. In the case of systems with selector valves, that is, a single cylinder or a cylinder bank which protects several hazards simultaneously, each hazard is required to be calculated independently with the software. The use of the selector valves has no effect on the hydraulic calculation in terms of equivalent length or pressure drop, but the effect related to the dead volume of the selector valve manifold in relation to the total volume of the pipe network must be considered. The limit of the ratio between the volume of the selector valves which are not opened in case of actuation of the system and the inner volume of the system piping shall be observed. Additional information of the limits can be found in this section. Selector valves (SVD) in “System components manual”. Due to the dead volume that we eventually have in the selector valves manifold, during agent discharge, we can not use a selector valves manifold bigger than the ratio 0.0833 of the volume of the pipe network. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 165/239 49.1. SVDxxx Selector valves Close Close Open Open Ball valve 21/2” to 4” Ball valve 3/4” to 2” Technical Information Selector valves SVDxxx 3/4” 1” 1 1/4” 1 1/2” 2” 2 1/2” 3” 4” Types or models of selector valves Actuator = SVD20 = SVD25 = SVD32 = SVD40 = SVD50 = SVD65 = SVD80 = SVD100 Pneumatic cylinder Type or model of pneumatic cylinder CILN35 Reset Manual Connection to the pipe to the inlet and outlet Maximum working pressure Thread NPT or BSP Male Or Welded SVD20-50 SVD65-100 UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 6240 psi (430 Bar) 5080 psi (350 Bar) “UF-MC-HC” - 27-01-2016 166/239 49.2. SVDxxxSH Selector valve Open Open Close Close Technical Information Selector valves SVDxxxSH 3/4” 1” 1 1/4” 1 1/2” 2” Types or models of selector valves Actuator = = = = = SVD20SH SVD25SH SVD32SH SVD40SH SVD50SH Pneumatic cylinder Type or model of pneumatic cylinder CILN35 Reset Manual Connection to the pipe to the inlet and outlet Maximum working pressure Thread BSP or NPT or Welded SVD20-50SH UL-EX15547 FM-3053302 5080 psi (350 Bar) UL-EX15547 FM-3053302 Approvals “UF-MC-HC” - 27-01-2016 167/239 49.3. Selector cabinet for selector valves The selector cabinet for selector valves has the function of activate the selector valve of the protected hazard area. The N2 pilot bottle and the electrical-manual actuator will be activated at the same time commanded by the fire Alarm Control Panel, so the nitrogen-filled in the pilot bottle pressurize and pushed on the piston of the appropriate valve, causing it to open and the subsequent activation of the battery system. 11 6 9 5 8 4 12 7 10 13 2 1 3 Nº 1 2 3 4 5 6 7 8 9 10 11 12 13 Denomination Selector cabinet Pilot cylinder bracket Pilot cylinder Pilot cylinder valve RGS-MAM-11-4 o 12-4 Re-assembled electrical actuator head 227SOL / 227SOLC / 227SOL125 / 227SOL220 / 227SOLC125 / 227SOLC220 Manual actuator head 227DM, 227DMS, 227CMC, 227CMCC Adapter POA21CU Re-assembled electrical actuator head 227SOLR / 227SOLCR / 227SOLR125 / 227SOLR220 / 227SOLCR125 / 227SOLCR220 Manual actuator head 227DM, 227DMS, 227CMC, 227DMR RGS-MAM-03/03A valve Outlet copper tube for selector valve connection Copper tube POLATCU Joint 1/8” NPT Technical Information Selector cabinet for selector valves Colour Black 26.38x23.62x7.48 In Size Approvals UL-EX15547 FM-3053302 (670 x600 x190mm) UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 168/239 49.4. SIEX-SVS valves Electrical-manual actuator for selector This electrical-manual actuator for selector valves has the function of gives way, electrically or manually, to the N2 how comes from the pilot bottle to pneumatically activate the selector valve. Normally it is supplied assembled inside the selector cabinet for selector valves. Technical Information Electrical-manual actuator SIEX-SVS 3 Material Brass CuZn40Pb2 Connection to the actuator port of the actuator heads Connection to the pipe to the inlet and outlet 2 Approvals 5 4 3/4” BSP Male 1/8” NPT Female UL-EX15547 FM-3053302 6 1 Nº 1 2 Denomination Actuator Re-assembled electrical actuator head 3 4 5 6 Manual actuator head Elbow 90º Cap Joint Type SIEX-SVS 227SOLR / 227SOLCR / 227SOLR125 / 227SOLR220 / 227SOLCR125 / 227SOLCR220 227DM, 227DMS, 227CMC, 227DMR 1/4" BSP – Ø0.24x0.16in (6x4mm) 1/8" NPT 1/8" NPT 49.5. Pilot cartridge for selector valves activation One of the function of the pilot cartridge 100M008UFA / 100M018UFA is the pneumatic activation of the selector valves. Pilot cartridge Selector valve UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 169/239 Limitations in use of Selector valves Activation hose or copper tube Length 3 Activation hose or copper tube Length 2 Activation hose or copper tube Length 1 V2= volume of the pipe network V1= volumen of the pipe network V3= volumen selector volves manifold As the volume V1 of the pipe network is larger than the pipe network V2: V1 > V2 V3 : V2 < 0.0833 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 170/239 Length 1 Connection between pilot bottle and selector valves Length 2 Connection between selector valves and battery system Length 3, Connection between the pneumatic actuators of the cylinders Pneumatic Actuator Type 227CN 0.07 (2) 227CN 0.24 (6.7) 227CN 78.74 In (2000 mm) 0.47 (13.4) 78.74 In (2000 mm) 227CNTK 0.07 (2) 227CNTK 0.24 (6.7) 227CNTK 0.47 (13.4) 227CN 0.07 (2) 227CN 0.24 (6.7) 227CN 118.11 In (3000 mm) Pilot Bottle Capacity ft³ (L) 0.47 (13.4) 118.11 In (3000mm) 227CNTK 0.07 (2) 227CNTK 0.24 (6.7) 227CNTK 0.47 (13.4) Maximum No. Of Pneumatic actuators and Hoses Filling Pressure psi (bar) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) 1450 (100) 1740 (120) 2175 (150) 2900 (200) Hoses :FH-6PO, FH-7PO, DH 10, DH 10 I, DH 11, DH 11 I Copper tube 19.69 In 32.62 In 27.56 In 28.54 In 31.5 In 39.37 In 49.21 In 59.06 In 39.37 In (500mm) (600mm) (700mm) (725mm) (800mm) (1000mm) (1250mm) (1500mm) (1000mm) 25 30 40 50 21 25 34 42 18 22 29 37 18 21 28 35 16 19 26 32 13 15 21 26 10 12 17 21 9 10 14 18 30 36 48 60 45 38 33 32 29 23 19 16 54 50 45 42 38 37 33 35 32 32 29 26 23 21 19 18 16 60 54 50 42 37 35 32 26 21 18 60 55 41 46 35 40 31 39 30 35 28 29 23 23 19 19 16 66 48 46 40 35 34 31 26 21 18 54 46 40 35 34 31 26 21 18 54 51 44 39 37 34 28 23 19 60 46 40 35 34 31 26 21 18 54 51 44 39 37 34 28 23 19 60 23 28 38 48 20 24 32 41 17 21 28 35 16 20 27 34 15 18 25 31 12 15 20 25 10 12 16 20 8 10 13 17 28 34 46 59 43 37 32 31 28 23 18 15 52 48 43 41 37 35 32 34 31 31 28 25 23 20 18 17 15 59 52 48 41 35 34 31 25 20 17 59 53 40 45 34 39 30 38 29 35 27 28 22 22 18 19 15 65 47 45 39 34 33 30 25 20 17 53 45 39 34 33 30 25 20 17 53 50 43 38 37 34 28 23 19 59 45 39 34 33 30 25 20 17 53 50 43 38 37 34 28 23 19 59 NOTE: Activation hoses are not available in all sizes. FH-6PO, FH-7PO in 19.69, 23.62, 28.54, 39.37 in (500, 600, 725 and 1000mm). DH 10, DH 10 I, DH 11, DH 11 I in 19.69, 23.62, 27.56, 31.5, 39.37, 49.21, 59.06 In (500, 600, 700, 800, 1000, 1250, 1500mm). IMPORTANT: Other configurations are available at the sole discretion of RG. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 171/239 50. Disable device valve The disable device valve for fixed gas extinguishing systems is used to prevent extinguishing gas discharging into the protected area when not required. The abort valve must remain in the closed position when the hazard area is occupied and open when the hazard area is not occupied. It is also useful for preventing accidental discharges during maintenance and inspection operations. It is screwed onto the discharge manifold, using a BSP or NPT thread using sealant or Teflon thread. A (SVAFC) 2-pole limit switch (NC / NO) may be fitted, set to change state when the valve is opened or closed, and to send an electrical signal to the fire Alarm control panel to warn that the system is isolated or operative. 2 12- Disable device valve Discharge manifold 1 Discharge nozzles UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 172/239 50.1. SVAxxx Disable device valve Close Close Open Open Discharge nozzles Discharge nozzles Manifold system Manifold system Technical information Disable device valve SVAxxx Types or models of disable device valves 1/4” = SVA6 3/4” = SVA20 1” = SVA25 1 1/4” = SVA32 1 1/2” = SVA40 2” = SVA50 2 1/2” = SVA65 3” = SVA80 4” = SVA100 Reset Manual Connection to the pipe to the inlet and outlet UL-EX15547 FM-3053302 Thread NPT or BSP or Welded UL-EX15547 FM-3053302 Approvals “UF-MC-HC” - 27-01-2016 173/239 50.2. SVAxxxSH Disable device valve Close Close Open Open Discharge nozzles Discharge nozzles Manifold system Manifold system Technical Information Disable device valve SVAxxxSH Types or models of disable device valves 3/4” 1” 1 1/4” 1 1/2” 2” = = = = = SVA20SH SVA25SH SVA32SH SVA40SH SVA50SH Reset Manual Connection to the pipe to the inlet and outlet Approvals UL-EX15547 FM-3053302 Thread BSP or NPT or Welded UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 174/239 50.3. End line for selector or disable device valves It has the function of detect at every moment the status of the selector or disable device valve (open or close). It is connected electrically to the control panel in order to send the corresponding signal with its status information. Inside, it has two contacts, one NC (normally closed) and another one NO (normally open) that changes the status when the switch is activated. Both can be used depending on the installation requeriments. 50.3.1. SVAFC End line for selector or disable device valves Technical Information End line SVAFC Location Disable device valve Box Plastic Tensión 24V (DC) Intensity 3A Velocity response in miliseconds >1,5 Mechanical durability in millons of operations 10 Minimum torque of activation 6N Minimum torque of positive openning 10 N Protection range IP65 Connection for cables 1 threaded inlet M20x1.5 Instalation Non corrosive; inside Approvals 50.3.2. UL-EX15547 FM-3053302 SVAGLC End line for selector or disable device valves Technical Information End line GLC Location Case Weighing device Metallic Tensión 24V (AC) Current 3. A Protection grade Connection for cables Contacts Approvals IP67 1 threaded inlet ½” Normally closed / normally opened CE, UL, CSA and CCC * This is not part of the FM Approval UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 175/239 51. Monitoring of selector and disable device valves for Hazardous locations It has the function of detect at every moment the status of the selector or disable device valve (open or close). It is connected electrically to the control panel in order to send the corresponding signal with its status information. Inside, it has two contacts, one NC (normally closed) and another one NO (normally open) that changes the status when the switch is activated. Both can be used depending on the installation requeriments. It has special design features which make this device suitable for being used in areas with atmospheres with explosion risk. It is said that an atmosphere has risk of explosion when in normal conditions it would have not this danger, but due to foreseeable events, the composition of this atmosphere could change in a such way that an explosion could happen. 51.1. SVAFC-BX Selector and Disable device valve* Technical Information Disable device valve SVAFC-BX Circuitry 1NC 1NO SPDT snap action, double break Electrical 10 A thermal Housing material Aluminium 1/2 in – 14NPT conduit Termination types Sealing NEMA 1, 3, 4, 6, 13; IP67 Vdc 24 Amps Inductive 10 Amps Resistive 10 Protection range NEMA 7 Div 1&2, Class I, Groups B,C, & D; NEMA 9 Div 1&2, Class II, Groups E,F, & G NEMA 1, 2, 4, 6, 13; IP 67 II 2 G; Exd IIC T6 II 2 D; Ex d tD A21 * This is not part of the FM Approval Agency Certifications ATEX (CE)² CSA, UL, or cULus 4 Canada, USA IEC Ex² International KOSHA¹ Korea NEPSI EX³ China 1 BXA3K, BXA4L, and BXB4L catalog listings are KOSHA certified. 2 ATEX & IEC Ex: [(Gas) II 2 G; Exd IIC T6: (Dust) II 2 D; Ex d tD A21 T85°C] 3 NEPSI Ex: GYJ111016 4 CSA, cUL, UL: NEMA 7 (Gas) Div 1&2, Class I, Groups B, C, & D; NEMA 9 (Dust) Div 1&2, Class II, Groups E, F, & UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 176/239 51.2. SVAFC-LX Disable device valve* Technical Information Disable device valve SVAFC-LX Housing material Aluminium 1/2 – 14NPT conduit Termination types Sealing NEMA 7 Div 1, clas 1 BCD; NEMA 9 Div 1, Class II, EFG. Agency Certifications CSA, UL, or cULus 4 Canada, USA Protection range Class I, Div.I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 7,9 * This is not part of the FM Approval 51.3. SVAFC-9007 Disable device valve* Technical Information Disable device valve SVAFC-9007 Electrical 10 A thermal Housing material Aluminium 1/2 – 14NPT conduit Termination types Sealing NEMA 250, EN 60947-1, EN 60947-5-1, IEC 60947, UL 508, IP 67 Electrical Durability Agency Certifications 1 million operating cycles ATEX (CE)² Protection range CSA, UL, or cULus 4 Canada, USA Class I, Div.I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 1, 2, 4, 6, 6P, 12, 13 IP 67 * This is not part of the FM Approval UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 177/239 51.4. SVAFC-802X Disable device valve* Technical Information Disable device valve SVAFC-802X Circuitry 1NC 1NO Housing material Aluminium Termination types Conduit pipe opening ½ in.Npt Sealing NEMA 7 and 9 Agency Certifications Protection range UL listed and CSA Certified Class 1,Groups B,C and D or Class II,Groups E,F and G or Class III;NEMA 4/nonharzardous locations * This is not part of the FM Approval 51.5. SVAFC-871 Disable device valve* Technical Information Disable device valve SVAFC-871 Material Plastic Contact type N.O. Operating voltage 20-250 V AC/DC Switching Frequency 10 Hz Conduit entrance 1/2 in – NPT Protection range Class I, Division II, Groups A, B,C & D NEMA 1, 2, 4, 6, 6P, 12, 13; IP 67, IP 69K Operating temperature Agency Certifications -25 °C to 70 °C [-13 °F to 158 °F] ATEX (CE)² Protection range UL, or cULus 4 Canada, USA Class I, Division II, Groups A, B,C & D NEMA 1, 2, 4, 6, 6P, 12, 13; IP 67, IP 69K * This is not part of the FM Approval UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 178/239 51.6. SVAFC-ATEX Disable device valve* Technical Information Disable device valve SVAFC-ATEX Circuitry 1NC 1NO SPDT snap action, double break Housing material Aluminium Termination types 1/2 in – 14NPT conduit Sealing NEMA 13, Class 1, division 2, Groups A, B, C, D. Agency Certifications Protection range ATEX (CE)² IEC Ex² International IP66 II 2 D; Ex tb IIIC T85ºc * This is not part of the FM Approval and UL Listed. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 179/239 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Certifications Atex (CE) UL, CSA Protection range Atex (CE) UL, CSA IEC EX KOSHA NEPSI EX Class I, Div.I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 1, 2, 4, 6, 6P, 12, 13 IP 67 NEMA 7 (gas) Div 1&2, Class I, Groups B,C, & D; NEMA 9 (dust) Div 1&2, Class II, Groups E,F, & G NEMA 1, 2, 4, 6, 13; IP 67 II 2 G; Exd IIC T6 II 2 D; Ex d tD A21 UL, CSA UL, CSA Class 1,Groups B,C and D or Class II,Groups E,F and G or Class III;NEMA 4/nonharzardous locations NEMA 7 and 9 1/2 in – NPT 1/2 in – 14 NPT 1/2 in – 14 NPT 1/2 in – 14 NPT Conduit entrance Class I, Div.I, Groups B,C, D Class II, Div.I, Groups E,F, G NEMA 7,9 24 Vdc Tension 24 Vdc 1 N.O.- 1 N.C. Aluminium 24 Vdc 1 N.O.- 1 N.C. Aluminium SVAFC-802X 24 Vdc Aluminium SVAFC-LX 1 N.O.- 1 N.C. Aluminium SVAFC-9007 1 N.O.- 1 N.C. Contact type Material SVAFC-BX Atex (CE) UL, CSA Class I, Division II, Groups A, B,C & D NEMA 1, 2, 4, 6, 6P, 12, 13; IP 67, IP 69K 1/2 in – NPT - 1 N.O. Plastic SVAFC-871 Atex (CE) IEC EX IP66 II 2 D; Ex tb IIIC T85ºc M20x1.5 24 Vdc 1 N.O.- 1 N.C. Aluminium SVAFC-ATEX 51.7. Table of Hazardous Locations limit switches for SVAXX 180/239 52. SVA6-3W Three ways isolated valve Their function is to isolate the pilot bottle release line in cylinder bank systems. This prevents accidental actuation of the system. The isolated valve is installed in the pilot release line, between the pilot bottle discharge hose and the line connected to the pneumatic head of the first cylinder. For this purpose a 1/4” BSP, 2 positions, 3-way ball valve is used, in order to vent to atmosphere in the closed position and thus avoid a build up of pressure due to possible leaks in the pilot bottle. This type of valve has three connections, an input from the pilot bottle, an output to the cylinder bank and another vented to atmosphere. This valve can be installed with the end line (see point 50.3 of this manual). Pilot cylinder ¼” G POSITION A Manifold system (Position A) Ventilation to the Atmosphere (Position B) Technical Information Isolated valve SVA6-3W Valve activation Manual Connection to the pipe Thread BSP UL-EX15547 FM-3053302 Approvals 1- ISOLATED VALVE 1/4" BSP 3 WAYS 2- LEVER 1/4" SVA 3- STOP WASHER 1/4" BSP 3 WAYS 1 Pilot bottle 3 2 Vented to atmosphere Cylinders battery UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 181/239 53. POVV8 Bleed valve The bleed valve's function is to depressurize the release line once the pneumatic heads are actuated. it allows a fast and safe depressurization only pushing the knob. When a small leakage appears and the gas flows through the release line, usually, it is accumulated and if the pressure is increased the discharge heads can be activated accidentally. With this valve we can avoid this problem, because it allows the outlet of the gas leakage avoiding the accidental actuation. It is installed in the last pneumatic actuator head, replacing the elbow by a tee and threading the remaining end to the bleed valve. Bleed valve POVV8 Material Activation knob Approvals Brass CuZn40Pb2 Plastic UL-EX15547 FM-3053302 ¼” G Bleed valve ¼” G Discharge hose FH-6PO /FH-7PO / DH 10 /DH 10I /DH 11 /DH 11I Tee ¼” BSP model 227TE O ring or metal-plastic joint UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 Pneumatic actuator 227CN 182/239 54. Discharge manifold for cylinders batteries It allows multiple cylinders to be connected to a common piping network. They are installed with check valves (VALAN-80, VALAN-50-125, VALAN-40-23, VALAN-20A, VALAN-21A and VALAN-15CO) to prevent gas from escaping to atmosphere should any of the bottles not be connected to the manifold. They are manufactured from standard piping (DIN 2440, Schedule 40 or 80 or 160) onto which paps have been welded for the check valves to be screwed on to. The check valves are supplied from the factory screwed onto the manifold. The manifold will have an external finish, coloured in red. Technical Information TYPE OF EXTINGUISHING AGENT TYPE OF PIPE WITHOUT WELDING HFC-227ea 363 psi 464 psi 493 psi 609 psi 725 psi 798 psi 25 bar 32 bar 34 bar 42 bar 50 bar 55 bar DIN 2440 SCHEDULE 40 SCHEDULE 80 SCHEDULE 160 DN20 (3/4") X X X X X X DN25 (1") X X X X X X DN32 (1 1/4") X X X X X X DN40 (1 1/2") X X X X X X DN50 (2") X X X X X X DN65 (2 1/2") X X X X DN80 (3") X X X X DN100 (4") X X X X DN125 (5") X X X DN150 (6") X X X DN20 (3/4") X X X X X X DN25 (1") X X X X X X DN32 (1 1/4") X X X X X X DN40 (1 1/2") X X X X X X DN50 (2") X X X X X X DN65 (2 1/2") X X X X X X DN80 (3") X X X X X X DN100 (4") X X X X X X DN125 (5") X X X X DN150 (6") X X X X DN20 (3/4") X X X X X X DN25 (1") X X X X X X DN32 (1 1/4") X X X X X X DN40 (1 1/2") X X X X X X DN50 (2") X X X X X X DN65 (2 1/2") X X X X X X DN80 (3") X X X X X X DN100 (4") X X X X X X DN20 (3/4") X X X X X X DN25 (1") X X X X X X DN32 (1 1/4") X X X X X X DN40 (1 1/2") X X X X X X DN50 (2") X X X X X X DN65 (2 1/2") X X X X X X DN80 (3") X X X X X X X X DN100 (4") APPROVALS UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 X X X X UL-EX15547 FM-3053302 183/239 55. 227CMSXXX Distributor for cylinders batteries The Distributor is used to collect all the gas from the cylinders and discharge it to the nozzle web pipe. It allows multiple bottles to be connected to a common piping network. They are installed with check valves (VALAN-40-23 / VALAN-50-125 / VALAN-80) to prevent gas from escaping to atmosphere should any of the bottles not be connected to the manifold. When the battery system is compounded by a number of cylinders that there is no handy manifold available, the manifold will be constructed by several handy manifolds to complete the collector needed. You can install the distributor with the combination of cylinders whith you want. The distributor will have an external finish, coloured in red. 55.1. 227CMSX2XX Distributor 227CMS2XX 227CMS4280 (Valan-40-23) 3” NPT 227CMS42100 (Valan-40-23) 4” NPT 227CMS52100 (Valan-50-125) 4” NPT 227CMS52150 (Valan-50-125) 6” NPT 227CMS82100 (Valan-80) 4” NPT 227CMS82150 (Valan-80) 6” NPT Quantity of check valves 2 UL-EX15547 FM-3053302 Approvals 55.2. 227CMSX3XX Distrubutor 227CMS3XX (Valan-40-23) 3” NPT 227CMS43100 (Valan-40-23) 4” NPT 227CMS53100 (Valan-50-125) 4” NPT 227CMS53150 (Valan-50-125) 6” NPT 227CMS83100 (Valan-80) 4” NPT 227CMS83150 (Valan-80) 6” NPT 227CMS4380 Quantity of check valves Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 3 UL-EX15547 FM-3053302 184/239 56. VREC / VREC-O Manifold pressure relief valve This device is used in cylinder systems that will be installed with selector valves or disable device valves only. In case of an accidental discharge of the extinguishing agent, this will be blocked in the manifold until the bursting disc of this valve detect an over-pressure and permits a controlled vent of the gas outside. The bursting disc is assembled in factory with the apropiate torque for its possible activation. Its recommendable that the pressure relief pipe discharge the gas to the atmosphere, far away from the protected area or the cylinder bank installation area. These are security mechanism to avoid that an over pressure in the manifold can occur when we have selector valves or disable device valves installed at the end of the manifold which does not permit the correct discharging of the extinguishing agent. Optional pipe for presure relief ¾” soket for presure relief piping Metal-plastic washer ¾” ¾” soket welded to the manifold Manifold pressure relief vale Technical Information Manifold pressure relief valve VREC / VREC-O Location Discharge manifold Material Brass Inlet connection 3/4" BSP Outlet connection 3/4" BSP UL-EX15547 FM-3053302 Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 185/239 56.1. VREC Manifold pressure relief valve Manifold pressure relief valve VREC Burst disc Pressure VREC60 870 psi (60 Bar) VREC110 1595 psi (110 Bar) VREC210 3050 psi (210 Bar) VREC310 4500 (310 Bar) VREC350 5080 (350 Bar) VREC430 6240 (430 Bar) 56.2. VREC-O Manifold pressure relief valve Manifold pressure relief valve VREC-O Burst disc Pressure UL-EX15547 FM-3053302 VREC-O60 870 psi (60 Bar) VREC-O110 1595 psi (110 Bar) VREC-O210 3050 psi (210 Bar) VREC-O310 4500 (310 Bar) VREC-O350 5080 (350 Bar) VREC-O430 6240 (430 Bar) “UF-MC-HC” - 27-01-2016 186/239 57. CSIRN Pneumatic siren This device connected, by means of a hose, to the manifold, to pilot bottle or directly to the discharge pipe. During the discharge of the extinguishing agent, the pressure exerted, activates the rotor of the siren, that will give out and audible alarm during the discharge. Discharge hose 49.2 ft (15m) Copper tube 49.2 ft (15m) Pneumatic siren CSIRN Flow rate (based on a nominal 1 minute discharge) 1450 Psi (100 Bar) 4.85 lb/min (2200 g/min) 1740 Psi (120 Bar) 5.73 lb/min (2600 g/min) 2180 Psi (150 Bar) 7.17 lb/min (3250 g/min) 2900 Psi (200 Bar) 9.26 lb/min (4200 g/min -4ºF to 122ºF (-20º to +50º C) 1/4” G H 90 dBC min 104 dBC max 1740 Psi (120 Bar) Zinc plated carbonated steel 98.4 ft (30 m) 98.4 ft (30 m) Copper tube 49.2 ft (15m) discharge hose + 49.2 ft (15m) Copper tube Working pressure Pilot bottle Working temperature Threat conexion Sound level Body material Maximum distance to be covered Conduit options ( Max.) UL-EX15547 FM-3053302 Approvals ATTENTION : Flow rate shall be calculated when discharging outside of the protected zone to ensure that the oxygen concentration is maintained above the intended limits as specified in NFPA 2001, Sec. 1.5.1.3. Flow rate should be calculated when discharging inside the protected zone to ensure that the oxygen concentration is maintained within the intended limits. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 187/239 58. D20 / D15 Odorizer NO T LIQ EF L UID ON O Discharge direction Discharge pipe This device has the objective of alert the presence of the agent, pervading of a strong smell of lemon or similar, the area where the discharge is happenning, with the purpose of avoid possible accidents. Those are made by the breaking of the bursting disc who retain the odor liquid, who are produced because of the pressure unleashed by the extinguishing agent discharge. In this way, the liquid are loosen and mixed with the gas and provides it a strong odor. YES Manifold Sentido de la descarga T LIQ EF L UID ON O YES NO Discharge direction 4 6 3 1 2 3 4 5 6 Cylinder Container valve Discharge hose Check valve Discharge manifold Odorizer MANIFOLD 5 CONNECTION PIPE 1 TEFL LIQU ON IDO 2 ELBOW OF 45 º TEFL LIQU ON IDO ODORIZER Discharge direction Socket welded to the the manifold Odorizer D15 / D20 Ebow at 45º UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 188/239 58.1. D20 Odorizer Technical Information Odorizer D20 Location Connection Approvals Discharge manifold or pipe 3/4" BSP UL-EX15547 FM-3053302 58.2. D15 Odorizer Technical Information Odorizer D15 Location Discharge manifold or pipe Connection Approvals UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 1/2" BSP UL-EX15547 FM-3053302 189/239 59. POSEÑALES Warnning sign A warning note is required on all the entrance doors to the protected hazard area to advise personnel that they are entering an area protected by an automatic gas extinguishing system. ¡ ATENCIÓN ! ZONA PROTEGIDA POR SISTEMA AUTOMATICO DE EXTINCION HFC-227ea. NO ENTRAR SI SE ESTA PRODUCIENDO LA DESCARGA DE HFC-227ea. CUANDO SUENE LA ALARMA, EVACUAR INMEDIATAMENTE LA ZONA DE PELIGRO. HFC 227ea DESPUES DE CADA DESCARGA DE HFC-227ea, NO VOLVER A ENTRAR HASTA QUE SE HAYA VENTILADO COMPLETAMENTE LA ZONA. --------------------------------------------------------------------------------------- ¡CAUTION! PROTECTED ZONE BY AUTOMATHIC HFC-227ea EXTINGUISH SYSTEM. DESCARGA DE HFC-227ea PULSADOR DE CONTROL MANUAL ----------HCF-227ea DISCHARGE MANUAL CONTROL ACTUATOR HFC 227ea ¡ATENCIÓN! ASEGURESE DE QUE TODO EL PERSONAL ES EVACUADO ANTES DE QUE SE PRODUZCA LA DESCARGA DE HFC-227ea ---------------- DO NOT TO ENTER IF THE HFC-227ea DISCHARGE IS TAKING PLACE. WHEN THE ALARM SOUNDS, EVACUATE INMEDIATELY THE HAZARD. ¡CAUTION! AFTER EACH HFC-227ea DISCHARGE, DO NOT RETURN INSIDE TILL THE ZONE HAS BEEN VENTILATED COMPLETELY. TEL.: (34) 947 28 11 08 MAKE SURE THAT ALL STAFF IS EVACUATED BEFORE THE HFC-227ea DISCHARGE TAKES PLACE TEL.: (34) 947 28 11 08 Alert signal, right: Sign for the door Alert signal, left: Signal which indicates the possibility of a manual activation Note that indicates the manual release A warning note to indicate that the system may be actuated manually must be placed at each point where this is the case. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 190/239 60. Combinations to container valves 60.1. RGS-MAM-11-4 / 12-4 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 191/239 60.2. RGS-MAM-20 / 40 / 50 / 80 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 192/239 60.3. RGS-MAM-03/03A UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 193/239 61. ANNEX 1: HFC-227ea Cylinders fill densities U.S.Units Max. pressure allowed Min. filling weight (lb) Max. filling weight (lb) Minimun fill density (lb/ft³) RGS-MAM-11-4 798 psi 1.98 5.07 RGS-MAM-11-4 798 psi 2.64 6.83 0.10 RGS-MAM-11-4 798 psi 2.64 0.10 RGS-MAM-11-4 798 psi 2.64 227M4UFJ-1 0.17 RGS-MAM-11-4 798 psi 227M4UFJ-2 0.17 RGS-MAM-11-4 Nominal Capacity (ft³) Valve Type 227M2UFV-1 0.07 227M2UFJ-1 0.10 227M2UFV-1 227M2UFV-2 Part Number Maximum fill density recommended (lb/ft³) 363 psi 464 psi 493 psi 609 psi 725 psi 798 psi 27.47 71.76 71.76 71.76 71.76 68.64 62.40 27.47 71.76 71.76 71.76 71.76 68.64 62.40 6.83 27.47 71.76 71.76 71.76 71.76 68.64 62.40 6.83 27.47 71.76 71.76 71.76 71.76 68.64 62.40 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFJ-3 0.17 RGS-MAM-11-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFV-1 0.17 RGS-MAM-11-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFV-2 0.17 RGS-MAM-11-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 68.64 62.40 227M4UFV-3 0.17 RGS-MAM-11-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 227M6UFM-1 0.21 RGS-MAM-11-4 493 psi 5.95 15.21 27.47 71.76 71.76 71.76 227M6UFJ-1 0.24 RGS-MAM-11-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M6UFJ-3 0.24 RGS-MAM-11-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M6UFV-1 0.24 RGS-MAM-11-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M6UFV-3 0.24 RGS-MAM-11-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M9UFM-3 0.32 RGS-MAM-11-4 493 psi 8.82 22.70 27.47 71.76 71.76 71.76 227M9UFM-4 0.32 RGS-MAM-11-4 493 psi 8.82 22.70 27.47 71.76 71.76 71.76 227M12UFM-1 0.42 RGS-MAM-11-4 363 psi 11.68 23.80 27.47 56.16 227M13UFAA-1 0.46 RGS-MAM-11-4 363 psi 12.78 25.79 27.47 56.16 227M13UFV-1 0.47 RGS-MAM-11-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFV-3 0.47 RGS-MAM-11-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFV-5 0.47 RGS-MAM-11-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFB-2 0.47 RGS-MAM-11-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFJ-1 0.47 RGS-MAM-11-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M16UFM-4 0.56 RGS-MAM-11-4 493 psi 15.65 35.26 27.47 56.16 56.16 62.40 227M2UFV-2 0.07 RGS-MAM-12-4 798 psi 1.98 5.07 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M2UFJ-2 0.10 RGS-MAM-12-4 798 psi 2.64 6.83 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M2UFV-3 0.10 RGS-MAM-12-4 798 psi 2.64 6.83 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M2UFV-4 0.10 RGS-MAM-12-4 798 psi 2.64 6.83 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFJ-4 0.17 RGS-MAM-12-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFJ-5 0.17 RGS-MAM-12-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFJ-6 0.17 RGS-MAM-12-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFV-4 0.17 RGS-MAM-12-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M4UFV-5 0.17 RGS-MAM-12-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 68.64 62.40 227M4UFV-6 0.17 RGS-MAM-12-4 798 psi 4.63 11.90 27.47 71.76 71.76 71.76 227M6UFM-2 0.21 RGS-MAM-12-4 493 psi 5.95 15.21 27.47 71.76 71.76 71.76 227M6UFJ-2 0.24 RGS-MAM-12-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M6UFJ-4 0.24 RGS-MAM-12-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M6UFV-2 0.24 RGS-MAM-12-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M6UFV-4 0.24 RGS-MAM-12-4 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M9UFM-5 0.32 RGS-MAM-12-4 493 psi 8.82 22.70 27.47 71.76 71.76 71.76 71.76 71.76 227M9UFM-6 0.32 RGS-MAM-12-4 493 psi 8.82 22.70 27.47 71.76 227M12UFM-2 0.42 RGS-MAM-12-4 363 psi 11.68 23.80 27.47 56.16 227M13UFAA-2 0.46 RGS-MAM-12-4 363 psi 12.78 25.79 27.47 56.16 227M13UFV-2 0.47 RGS-MAM-12-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFV-4 0.47 RGS-MAM-12-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFV-6 0.47 RGS-MAM-12-4 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 194/239 Part Number Nominal Capacity (ft³) Valve Type Max. pressure allowed Min. filling weight (lb) Max. filling weight (lb) Minimun fill density (lb/ft³) 227M13UFB-4 0.47 RGS-MAM-12-4 798 psi 13.00 33.94 227M13UFJ-2 0.47 RGS-MAM-12-4 798 psi 13.00 33.94 227M16UFM-6 0.56 RGS-MAM-12-4 493 psi 15.65 227M6UFM-3 0.21 RGS-MAM-20 493 psi 227M6UFJ-5 0.24 RGS-MAM-20 798 psi 227M6UFJ-6 0.24 RGS-MAM-20 227M6UFV-5 0.24 Maximum fill density recommended (lb/ft³) 363 psi 464 psi 493 psi 609 psi 725 psi 798 psi 27.47 71.76 71.76 71.76 71.76 68.64 62.40 27.47 71.76 71.76 71.76 71.76 68.64 62.40 35.26 27.47 56.16 56.16 62.40 5.95 15.21 27.47 71.76 71.76 71.76 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 RGS-MAM-20 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 68.64 62.40 227M6UFV-6 0.24 RGS-MAM-20 798 psi 6.61 16.97 27.47 71.76 71.76 71.76 227M9UFM-1 0.32 RGS-MAM-20 493 psi 8.82 22.70 27.47 71.76 71.76 71.76 227M9UFM-2 0.32 RGS-MAM-20 493 psi 8.82 22.70 27.47 71.76 71.76 71.76 227M12UFM-3 0.42 RGS-MAM-20 363 psi 11.68 30.42 27.47 71.76 227M13UFAA-3 0.46 RGS-MAM-20 363 psi 12.78 28.65 27.47 62.40 227M13UFV-7 0.47 RGS-MAM-20 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFV-8 0.47 RGS-MAM-20 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFV-9 0.47 RGS-MAM-20 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M13UFB-6 0.47 RGS-MAM-20 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 68.64 62.40 227M13UFJ-3 0.47 RGS-MAM-20 798 psi 13.00 33.94 27.47 71.76 71.76 71.76 227M16UFM-2 0.56 RGS-MAM-20 493 psi 15.65 35.26 27.47 71.76 71.76 71.76 227M21UFM 0.74 RGS-MAM-20 363 psi 20.50 46.28 27.47 62.40 227M25UFAA 0.88 RGS-MAM-20 363 psi 24.24 55.10 27.47 62.40 227M26UFB 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFJ-1 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFV-1 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFJ-2 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFV-2 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFJ-3 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFV-3 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFV-4 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M26UFV-5 0.95 RGS-MAM-20 798 psi 26.01 67.88 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M28UFM-1 1.00 RGS-MAM-20 493 psi 27.55 71.63 27.47 71.76 71.76 71.76 227M28UFM-2 1.00 RGS-MAM-20 493 psi 27.55 71.63 27.47 71.76 71.76 71.76 227M38UFAA 1.34 RGS-MAM-20 363 psi 37.03 83.75 27.47 62.40 227M40UFJ-1 1.41 RGS-MAM-20 798 psi 38.79 101.38 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFV-1 1.42 RGS-MAM-20 798 psi 39.01 101.82 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFB-2 1.41 RGS-MAM-20 798 psi 38.79 101.38 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFJ-2 1.41 RGS-MAM-20 798 psi 38.79 101.38 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFV-2 1.42 RGS-MAM-20 798 psi 39.01 101.82 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFJ-3 1.41 RGS-MAM-20 798 psi 38.79 101.38 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFN-1 1.41 RGS-MAM-20 798 psi 38.79 101.38 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFV-3 1.42 RGS-MAM-20 798 psi 39.01 101.82 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFN-2 1.41 RGS-MAM-20 798 psi 38.79 101.38 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFV-4 1.42 RGS-MAM-20 798 psi 39.01 101.82 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M40UFV-5 1.42 RGS-MAM-20 798 psi 39.01 101.82 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M61UFAA 2.15 RGS-MAM-40 363 psi 59.29 134.44 27.47 62.40 227M67UFB-1 2.38 RGS-MAM-40 798 psi 65.46 171.03 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M67UFJ 2.38 RGS-MAM-40 798 psi 65.46 171.03 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M67UFV-1 2.38 RGS-MAM-40 798 psi 65.46 171.03 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M67UFC 2.38 RGS-MAM-40 798 psi 65.46 171.03 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M67UFR 2.38 RGS-MAM-40 798 psi 65.46 171.03 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M67UFV-2 2.40 RGS-MAM-40 798 psi 66.12 172.35 27.47 71.76 71.76 71.76 71.76 68.64 62.40 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 195/239 Part Number Nominal Capacity (ft³) Valve Type Max. pressure allowed Min. filling weight (lb) Max. filling weight (lb) Minimun fill density (lb/ft³) Maximum fill density recommended (lb/ft³) 363 psi 464 psi 493 psi 609 psi 725 psi 798 psi 227M80UFJ 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFB-1 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFV-1 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFV-2 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFV-3 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFC 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFR 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFW 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M80UFV-4 2.82 RGS-MAM-40 798 psi 77.58 202.77 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M81UFM-2 2.88 RGS-MAM-40 493 psi 79.12 206.51 27.47 71.76 71.76 71.76 227M84UFAA-1 2.97 RGS-MAM-40 363 psi 81.55 185.14 27.47 62.40 227M86UFM 3.04 RGS-MAM-40 493 psi 83.53 217.98 27.47 71.76 71.76 71.76 227M84UFAA-2 2.97 RGS-MAM-50 363 psi 81.55 185.14 27.47 62.40 227M84UFAA-3 2.97 RGS-MAM-50 363 psi 81.55 185.14 27.47 62.40 227M84UFM-1 2.97 RGS-MAM-50 493 psi 81.55 212.91 27.47 71.76 71.76 71.76 227M84UFM-2 2.97 RGS-MAM-50 493 psi 81.55 212.91 27.47 71.76 71.76 71.76 227M100UFV-1 3.53 RGS-MAM-40 798 psi 96.98 253.46 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M100UFC 3.53 RGS-MAM-40 798 psi 96.98 253.46 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M100UFR 3.53 RGS-MAM-40 798 psi 96.98 253.46 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 71.76 71.76 68.64 62.40 227M100UFR-2 3.53 RGS-MAM-40 798 psi 96.98 253.46 27.47 71.76 227M108UFAA-1 3.83 RGS-MAM-50 363 psi 105.13 238.91 27.47 62.40 227M108UFAA-2 3.83 RGS-MAM-50 363 psi 105.13 238.91 27.47 62.40 227M120UFB-1 4.24 RGS-MAM-50 493 psi 116.37 304.15 27.47 71.76 71.76 71.76 227M120UFB-2 4.24 RGS-MAM-50 493 psi 116.37 304.15 27.47 71.76 71.76 71.76 227M120UFV-1 4.24 RGS-MAM-40 798 psi 116.37 304.15 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M120UFC 4.24 RGS-MAM-40 798 psi 116.37 304.15 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M120UFR 4.24 RGS-MAM-40 798 psi 116.37 304.15 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M120UFV-2 4.24 RGS-MAM-40 798 psi 116.37 304.15 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M127UFAA-1 4.48 RGS-MAM-50 363 psi 123.20 279.91 27.47 62.40 227M127UFAA-2 4.48 RGS-MAM-50 363 psi 123.20 279.91 27.47 62.40 227M140UFV-1 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFV-2 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFV-3 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFV-4 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFC-1 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFC-2 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFR-1 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFR-2 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M140UFV-5 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 68.64 62.40 227M140UFV-6 4.94 RGS-MAM-50 798 psi 135.77 354.84 27.47 71.76 71.76 71.76 227M143UFM-1 5.05 RGS-MAM-50 493 psi 138.85 362.34 27.47 71.76 71.76 71.76 227M143UFM-2 5.05 RGS-MAM-50 493 psi 138.85 362.34 27.47 71.76 71.76 71.76 227M143UFM-3 5.05 RGS-MAM-50 493 psi 138.85 362.34 27.47 71.76 71.76 71.76 227M143UFM-4 5.05 RGS-MAM-50 493 psi 138.85 362.34 27.47 71.76 71.76 71.76 227M150UFB-1 5.30 RGS-MAM-50 493 psi 145.46 380.19 27.47 71.76 71.76 71.76 227M150UFB-2 5.30 RGS-MAM-50 493 psi 145.46 380.19 27.47 71.76 71.76 71.76 227M150UFC-1 5.30 RGS-MAM-50 798 psi 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M150UFC-2 5.30 RGS-MAM-50 798 psi 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M150UFV-1 5.30 RGS-MAM-50 798 psi 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M150UFV-2 5.30 RGS-MAM-50 798 psi 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 196/239 Part Number Nominal Capacity (ft³) Valve Type Max. pressure allowed Min. filling weight (lb) Max. filling weight (lb) Minimun fill density (lb/ft³) 227M150UFC-3 5.30 RGS-MAM-50 798 psi 145.46 380.19 227M150UFC-4 5.30 RGS-MAM-50 798 psi 145.46 380.19 227M150UFR-1 5.30 RGS-MAM-50 798 psi 145.46 227M150UFR-2 5.30 RGS-MAM-50 798 psi 227M150UFV-3 5.30 RGS-MAM-50 798 psi 227M150UFV-4 5.30 RGS-MAM-50 227M152UFM-1 5.37 227M152UFM-2 227M180UFC Maximum fill density recommended (lb/ft³) 363 psi 464 psi 493 psi 609 psi 725 psi 798 psi 27.47 71.76 71.76 71.76 71.76 68.64 62.40 27.47 71.76 71.76 71.76 71.76 68.64 62.40 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 798 psi 145.46 380.19 27.47 71.76 71.76 71.76 71.76 68.64 62.40 RGS-MAM-50 493 psi 147.45 385.26 27.47 71.76 71.76 71.76 5.37 RGS-MAM-50 493 psi 147.45 385.26 27.47 71.76 71.76 71.76 6.35 RGS-MAM-50 798 psi 174.56 456.23 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M180UFB-1 6.35 RGS-MAM-50 493 psi 174.56 396.72 27.47 62.40 62.40 62.40 227M180UFM-1 6.35 RGS-MAM-50 493 psi 174.56 396.72 27.47 62.40 62.40 62.40 227M180UFV-1 6.35 RGS-MAM-50 798 psi 174.56 456.23 27.47 71.76 71.76 71.76 71.76 68.64 62.40 227M180UFV-2 6.35 RGS-MAM-50 798 psi 174.56 456.23 27.47 71.76 71.76 71.76 71.76 68.64 62.40 71.76 68.64 62.40 227M180UFB-3 6.35 RGS-MAM-80 493 psi 174.56 456.23 27.47 71.76 71.76 71.76 227M180UFM-2 6.35 RGS-MAM-80 493 psi 174.56 456.23 27.47 71.76 71.76 71.76 227M180UFV-3 6.35 RGS-MAM-80 798 psi 174.56 456.23 27.47 71.76 71.76 71.76 227M229UFM 8.08 RGS-MAM-80 493 psi 222.16 580.31 27.47 71.76 71.76 71.76 227M240UFB 8.47 RGS-MAM-80 493 psi 232.74 608.30 27.47 71.76 71.76 71.76 227M246UFM-1 8.68 RGS-MAM-80 363 psi 238.69 623.51 27.47 62.40 227M246UFM-2 8.68 RGS-MAM-80 493 psi 238.69 623.51 27.47 71.76 71.76 71.76 227M365UFM 12.88 RGS-MAM-80 493 psi 353.96 925.02 27.47 71.76 71.76 71.76 227M368UFM 12.99 RGS-MAM-80 493 psi 357.05 932.73 27.47 71.76 71.76 71.76 227M454UFM 16.03 RGS-MAM-80 493 psi 440.36 1000.62 27.47 62.40 62.40 62.40 227M501UFM 17.69 RGS-MAM-80 493 psi 485.98 1104.20 27.47 56.16 56.16 62.40 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 197/239 62. ANNEX 1: HFC-227ea Cylinders fill densities S.I. Units Maximum fill density recommended (Kg/l) 25 32 34 42 50 55 bar bar bar bar bar bar Nominal Capacity (liters) Valve Type Max. pressure allowed Min. filling weight (Kg) Max. filling weight (Kg) Minimun fill density (Kg/l) 227M2UFV-1 2 RGS-MAM-11-4 55 bar 0.9 2.3 0.44 1.15 1.15 1.15 1.15 1.1 1 227M2UFJ-1 2.7 RGS-MAM-11-4 55 bar 1.2 3.1 0.44 1.15 1.15 1.15 1.15 1.1 1 227M2UFV-1 2.7 RGS-MAM-11-4 55 bar 1.2 3.1 0.44 1.15 1.15 1.15 1.15 1.1 1 227M2UFV-2 2.7 RGS-MAM-11-4 55 bar 1.2 3.1 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFJ-1 4.7 RGS-MAM-11-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFJ-2 4.7 RGS-MAM-11-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 Part Number 227M4UFJ-3 4.7 RGS-MAM-11-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFV-1 4.7 RGS-MAM-11-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFV-2 4.7 RGS-MAM-11-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 1.15 1.1 1 227M4UFV-3 4.7 RGS-MAM-11-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 227M6UFM-1 6 RGS-MAM-11-4 34 bar 2.7 6.9 0.44 1.15 1.15 1.15 227M6UFJ-1 6.7 RGS-MAM-11-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M6UFJ-3 6.7 RGS-MAM-11-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M6UFV-1 6.7 RGS-MAM-11-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M6UFV-3 6.7 RGS-MAM-11-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M9UFM-3 9 RGS-MAM-11-4 34 bar 4.0 10.3 0.44 1.15 1.15 1.15 227M9UFM-4 9 RGS-MAM-11-4 34 bar 4.0 10.3 0.44 1.15 1.15 1.15 227M12UFM-1 12 RGS-MAM-11-4 25 bar 5.3 10.8 0.44 0.9 227M13UFAA-1 13 RGS-MAM-11-4 25 bar 5.8 11.7 0.44 0.9 227M13UFV-1 13.4 RGS-MAM-11-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFV-3 13.4 RGS-MAM-11-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFV-5 13.4 RGS-MAM-11-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFB-2 13.4 RGS-MAM-11-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFJ-1 13.4 RGS-MAM-11-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M16UFM-4 16 RGS-MAM-11-4 34 bar 7.1 16.0 0.44 0.90 0.90 1.00 227M2UFV-2 2 RGS-MAM-12-4 55 bar 0.9 2.3 0.44 1.15 1.15 1.15 1.15 1.1 1 227M2UFJ-2 2.7 RGS-MAM-12-4 55 bar 1.2 3.1 0.44 1.15 1.15 1.15 1.15 1.1 1 227M2UFV-3 2.7 RGS-MAM-12-4 55 bar 1.2 3.1 0.44 1.15 1.15 1.15 1.15 1.1 1 227M2UFV-4 2.7 RGS-MAM-12-4 55 bar 1.2 3.1 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFJ-4 4.7 RGS-MAM-12-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFJ-5 4.7 RGS-MAM-12-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFJ-6 4.7 RGS-MAM-12-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFV-4 4.7 RGS-MAM-12-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M4UFV-5 4.7 RGS-MAM-12-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 1.15 1.1 1 1.15 1.1 1 227M4UFV-6 4.7 RGS-MAM-12-4 55 bar 2.1 5.4 0.44 1.15 1.15 1.15 227M6UFM-2 6 RGS-MAM-12-4 34 bar 2.7 6.9 0.44 1.15 1.15 1.15 227M6UFJ-2 6.7 RGS-MAM-12-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M6UFJ-4 6.7 RGS-MAM-12-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M6UFV-2 6.7 RGS-MAM-12-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M6UFV-4 6.7 RGS-MAM-12-4 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 227M9UFM-5 9 RGS-MAM-12-4 34 bar 4.0 10.3 0.44 1.15 1.15 1.15 1.15 1.15 227M9UFM-6 9 RGS-MAM-12-4 34 bar 4.0 10.3 0.44 1.15 227M12UFM-2 12 RGS-MAM-12-4 25 bar 5.3 10.8 0.44 0.9 227M13UFAA-2 13 RGS-MAM-12-4 25 bar 5.8 11.7 0.44 0.9 227M13UFV-2 13.4 RGS-MAM-12-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFV-4 13.4 RGS-MAM-12-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFV-6 13.4 RGS-MAM-12-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFB-4 13.4 RGS-MAM-12-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 198/239 Part Number Nominal Capacity (liters) Valve Type Max. pressure allowed Min. filling weight (Kg) Max. filling weight (Kg) Minimun fill density (Kg/l) Maximum fill density recommended (Kg/l) 25 32 34 42 50 55 bar bar bar bar bar bar 227M13UFJ-2 13.4 RGS-MAM-12-4 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 227M16UFM-6 16 RGS-MAM-12-4 34 bar 7.1 16.0 0.44 0.90 0.90 1.00 1.15 1.1 1 227M6UFM-3 6 RGS-MAM-20 34 bar 2.7 6.9 0.44 1.15 1.15 1.15 227M6UFJ-5 6.7 RGS-MAM-20 55 bar 3.0 7.7 0.44 1.15 1.15 227M6UFJ-6 6.7 RGS-MAM-20 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 1.15 1.1 1 1.15 1.15 1.1 227M6UFV-5 6.7 RGS-MAM-20 55 bar 3.0 7.7 0.44 1.15 1 1.15 1.15 1.15 1.1 1 1.15 1.1 1 227M6UFV-6 6.7 RGS-MAM-20 55 bar 3.0 7.7 0.44 1.15 1.15 1.15 227M9UFM-1 9 RGS-MAM-20 34 bar 4.0 10.3 0.44 1.15 1.15 1.15 227M9UFM-2 9 RGS-MAM-20 34 bar 4.0 10.3 0.44 1.15 1.15 1.15 1.15 227M12UFM-3 12 RGS-MAM-20 25 bar 5.3 13.8 0.44 227M13UFAA-3 13 RGS-MAM-20 25 bar 5.8 13.0 0.44 1 227M13UFV-7 13.4 RGS-MAM-20 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFV-8 13.4 RGS-MAM-20 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFV-9 13.4 RGS-MAM-20 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFB-6 13.4 RGS-MAM-20 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M13UFJ-3 13.4 RGS-MAM-20 55 bar 5.9 15.4 0.44 1.15 1.15 1.15 1.15 1.1 1 227M16UFM-2 16 RGS-MAM-20 34 bar 7.1 16.0 0.44 0.90 0.90 1.00 227M21UFM 21 RGS-MAM-20 25 bar 9.3 21.0 0.44 1 227M25UFAA 25 RGS-MAM-20 25 bar 11.0 25.0 0.44 1 227M26UFB 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFJ-1 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFV-1 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFJ-2 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFV-2 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFJ-3 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFV-3 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFV-4 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M26UFV-5 26.8 RGS-MAM-20 55 bar 11.8 30.8 0.44 1.15 1.15 1.15 1.15 1.1 1 227M28UFM-1 28.3 RGS-MAM-20 34 bar 12.5 32.5 0.44 1.15 1.15 1.15 227M28UFM-2 28.3 RGS-MAM-20 34 bar 12.5 32.5 0.44 1.15 1.15 1.15 227M38UFAA 38 RGS-MAM-20 25 bar 16.8 38.0 0.44 1 227M40UFJ-1 40 RGS-MAM-20 55 bar 17.6 46.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFV-1 40.2 RGS-MAM-20 55 bar 17.7 46.2 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFB-2 40 RGS-MAM-20 55 bar 17.6 46.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFJ-2 40 RGS-MAM-20 55 bar 17.6 46.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFV-2 40.2 RGS-MAM-20 55 bar 17.7 46.2 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFJ-3 40 RGS-MAM-20 55 bar 17.6 46.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFN-1 40 RGS-MAM-20 55 bar 17.6 46.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFV-3 40.2 RGS-MAM-20 55 bar 17.7 46.2 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFN-2 40 RGS-MAM-20 55 bar 17.6 46.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFV-4 40.2 RGS-MAM-20 55 bar 17.7 46.2 0.44 1.15 1.15 1.15 1.15 1.1 1 227M40UFV-5 40.2 RGS-MAM-20 55 bar 17.7 46.2 0.44 1.15 1.15 1.15 1.15 1.1 1 227M61UFAA 61 RGS-MAM-40 25 bar 26.9 61.0 0.44 1 227M67UFB-1 67.5 RGS-MAM-40 55 bar 29.7 77.6 0.44 1.15 1.15 1.15 1.15 1.1 1 227M67UFJ 67.5 RGS-MAM-40 55 bar 29.7 77.6 0.44 1.15 1.15 1.15 1.15 1.1 1 227M67UFV-1 67.5 RGS-MAM-40 55 bar 29.7 77.6 0.44 1.15 1.15 1.15 1.15 1.1 1 227M67UFC 67.5 RGS-MAM-40 55 bar 29.7 77.6 0.44 1.15 1.15 1.15 1.15 1.1 1 227M67UFR 67.5 RGS-MAM-40 55 bar 29.7 77.6 0.44 1.15 1.15 1.15 1.15 1.1 1 227M67UFV-2 68 RGS-MAM-40 55 bar 30.0 78.2 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFJ 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 199/239 Maximum fill density recommended (Kg/l) 25 32 34 42 50 55 bar bar bar bar bar bar Part Number Nominal Capacity (liters) Valve Type Max. pressure allowed Min. filling weight (Kg) Max. filling weight (Kg) Minimun fill density (Kg/l) 227M80UFB-1 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFV-1 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFV-2 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFV-3 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFC 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFR 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFW 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M80UFV-4 80 RGS-MAM-40 55 bar 35.2 92.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M81UFM-2 81.5 RGS-MAM-40 34 bar 35.9 93.7 0.44 1.15 1.15 1.15 227M84UFAA-1 84 RGS-MAM-40 25 bar 37.0 84.0 0.44 1 227M86UFM 86 RGS-MAM-40 34 bar 37.9 98.9 0.44 1.15 1.15 1.15 227M84UFAA-2 84 RGS-MAM-50 25 bar 37.0 84.0 0.44 1 227M84UFAA-3 84 RGS-MAM-50 25 bar 37.0 84.0 0.44 1 227M84UFM-1 84 RGS-MAM-50 34 bar 37.0 96.6 0.44 1.15 1.15 1.15 227M84UFM-2 84 RGS-MAM-50 34 bar 37.0 96.6 0.44 1.15 1.15 1.15 227M100UFV-1 100 RGS-MAM-40 55 bar 44.0 115.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M100UFC 100 RGS-MAM-40 55 bar 44.0 115.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M100UFR 100 RGS-MAM-40 55 bar 44.0 115.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M100UFR-2 100 RGS-MAM-40 55 bar 44.0 115.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M108UFAA-1 108.4 RGS-MAM-50 25 bar 47.7 108.4 0.44 1 227M108UFAA-2 108.4 RGS-MAM-50 25 bar 47.7 108.4 0.44 1 227M120UFB-1 120 RGS-MAM-50 34 bar 52.8 138.0 0.44 1.15 1.15 1.15 227M120UFB-2 120 RGS-MAM-50 34 bar 52.8 138.0 0.44 1.15 1.15 1.15 227M120UFV-1 120 RGS-MAM-40 55 bar 52.8 138.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M120UFC 120 RGS-MAM-40 55 bar 52.8 138.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M120UFR 120 RGS-MAM-40 55 bar 52.8 138.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M120UFV-2 120 RGS-MAM-40 55 bar 52.8 138.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M127UFAA-1 127 RGS-MAM-50 25 bar 55.9 127.0 0.44 1 227M127UFAA-2 127 RGS-MAM-50 25 bar 55.9 127.0 0.44 1 227M140UFV-1 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFV-2 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFV-3 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFV-4 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFC-1 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFC-2 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFR-1 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFR-2 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M140UFV-5 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 1.15 1.1 1 1.15 1.1 1 227M140UFV-6 140 RGS-MAM-50 55 bar 61.6 161.0 0.44 1.15 1.15 1.15 227M143UFM-1 143 RGS-MAM-50 34 bar 63.0 164.4 0.44 1.15 1.15 1.15 227M143UFM-2 143 RGS-MAM-50 34 bar 63.0 164.4 0.44 1.15 1.15 1.15 227M143UFM-3 143 RGS-MAM-50 34 bar 63.0 164.4 0.44 1.15 1.15 1.15 227M143UFM-4 143 RGS-MAM-50 34 bar 63.0 164.4 0.44 1.15 1.15 1.15 227M150UFB-1 150 RGS-MAM-50 34 bar 66.0 172.5 0.44 1.15 1.15 1.15 227M150UFB-2 150 RGS-MAM-50 34 bar 66.0 172.5 0.44 1.15 1.15 1.15 227M150UFC-1 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFC-2 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFV-1 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFV-2 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFC-3 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 200/239 Maximum fill density recommended (Kg/l) 25 32 34 42 50 55 bar bar bar bar bar bar Part Number Nominal Capacity (liters) Valve Type Max. pressure allowed Min. filling weight (Kg) Max. filling weight (Kg) Minimun fill density (Kg/l) 227M150UFC-4 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFR-1 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFR-2 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFV-3 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M150UFV-4 150 RGS-MAM-50 55 bar 66.0 172.5 0.44 1.15 1.15 1.15 1.15 1.1 1 227M152UFM-1 152 RGS-MAM-50 34 bar 66.9 174.8 0.44 1.15 1.15 1.15 227M152UFM-2 152 RGS-MAM-50 34 bar 66.9 174.8 0.44 1.15 1.15 1.15 227M180UFC 180 RGS-MAM-50 55 bar 79.2 207.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M180UFB-1 180 RGS-MAM-50 34 bar 79.2 180.0 0.44 1.00 1.00 1.00 227M180UFM-1 180 RGS-MAM-50 34 bar 79.2 180.0 0.44 1.00 1.00 1.00 227M180UFV-1 180 RGS-MAM-50 55 bar 79.2 207.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M180UFV-2 180 RGS-MAM-50 55 bar 79.2 207.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M180UFB-3 180 RGS-MAM-80 34 bar 79.2 207.0 0.44 1.15 1.15 1.15 227M180UFM-2 180 RGS-MAM-80 34 bar 79.2 207.0 0.44 1.15 1.15 1.15 227M180UFV-3 180 RGS-MAM-80 55 bar 79.2 207.0 0.44 1.15 1.15 1.15 1.15 1.1 1 227M229UFM 229 RGS-MAM-80 34 bar 100.8 263.3 0.44 1.15 1.15 1.15 1.15 1.15 227M240UFB 240 RGS-MAM-80 34 bar 105.6 276.0 0.44 1.15 227M246UFM-1 246 RGS-MAM-80 25 bar 108.3 282.9 0.44 1 227M246UFM-2 246 RGS-MAM-80 34 bar 108.3 282.9 0.44 1.15 1.15 1.15 227M365UFM 365 RGS-MAM-80 34 bar 160.6 419.7 0.44 1.15 1.15 1.15 227M368UFM 368 RGS-MAM-80 34 bar 162.0 423.2 0.44 1.15 1.15 1.15 227M454UFM 454 RGS-MAM-80 34 bar 199.8 454.0 0.44 1.00 1.00 1.00 227M501UFM 501 RGS-MAM-80 34 bar 220.5 501.0 0.44 0.95 0.95 1.00 NOTE: This lengths are approximately due to the differences made in the manufacturing process. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 201/239 63. ANNEX 2: HFC-227ea Cylinders lengths U.S. Units Part Number Nominal Capacity (ft³) Nominal Diameter (in) Height Outlet (in) Valve Type Outlet thread valve 227M2UFV-1 0.07 3.94 14.97 RGS-MAM-11-4 W21.8x1/14" 227M2UFJ-1 0.10 4.26 17.73 RGS-MAM-11-4 W21.8x1/14" 227M2UFV-1 0.10 3.94 18.72 RGS-MAM-11-4 W21.8x1/14" 227M2UFV-2 0.10 3.94 18.72 RGS-MAM-11-4 W21.8x1/14" 227M4UFJ-1 0.17 4.26 28.17 RGS-MAM-11-4 W21.8x1/14" 227M4UFJ-2 0.17 5.52 18.72 RGS-MAM-11-4 W21.8x1/14" 227M4UFJ-3 0.17 5.52 18.52 RGS-MAM-11-4 W21.8x1/14" 227M4UFV-1 0.17 4.53 23.97 RGS-MAM-11-4 W21.8x1/14" 227M4UFV-2 0.17 5.52 17.57 RGS-MAM-11-4 W21.8x1/14" 227M4UFV-3 0.17 5.52 17.57 RGS-MAM-11-4 W21.8x1/14" 227M6UFM-1 0.21 6.00 RGS-MAM-11-4 W21.8x1/14" 227M6UFJ-1 0.24 5.52 23.64 RGS-MAM-11-4 W21.8x1/14" 227M6UFJ-3 0.24 5.52 23.64 RGS-MAM-11-4 W21.8x1/14" 227M6UFV-1 0.24 5.52 23.60 RGS-MAM-11-4 W21.8x1/14" 227M6UFV-3 0.24 5.52 23.60 RGS-MAM-11-4 W21.8x1/14" 227M9UFM-3 0.32 7.01 RGS-MAM-11-4 W21.8x1/14" 227M9UFM-4 0.32 7.01 RGS-MAM-11-4 W21.8x1/14" 227M12UFM-1 0.42 10.01 RGS-MAM-11-4 W21.8x1/14" 227M13UFAA-1 0.47 9.65 15.76 RGS-MAM-11-4 W21.8x1/14" 227M13UFV-1 0.47 5.52 42.95 RGS-MAM-11-4 W21.8x1/14" 227M13UFV-3 0.47 8.04 22.66 RGS-MAM-11-4 W21.8x1/14" 227M13UFV-5 0.47 8.04 23.44 RGS-MAM-11-4 W21.8x1/14" 227M13UFB-2 0.47 8.00 24.03 RGS-MAM-11-4 W21.8x1/14" 227M13UFJ-1 0.47 8.04 23.84 RGS-MAM-11-4 W21.8x1/14" 227M16UFM-4 0.56 10.01 19.06 RGS-MAM-11-4 W21.8x1/14" 227M2UFV-2 0.07 3.94 15.13 RGS-MAM-12-4 W21.8x1/14" 227M2UFJ-2 0.10 4.26 17.89 RGS-MAM-12-4 W21.8x1/14" 227M2UFV-3 0.10 3.94 18.87 RGS-MAM-12-4 W21.8x1/14" 227M2UFV-4 0.10 3.94 18.87 RGS-MAM-12-4 W21.8x1/14" 227M4UFJ-4 0.17 4.26 28.33 RGS-MAM-12-4 W21.8x1/14" 227M4UFJ-5 0.17 5.52 18.87 RGS-MAM-12-4 W21.8x1/14" 227M4UFJ-6 0.17 5.52 18.68 RGS-MAM-12-4 W21.8x1/14" 227M4UFV-4 0.17 4.53 24.13 RGS-MAM-12-4 W21.8x1/14" 227M4UFV-5 0.17 5.52 17.73 RGS-MAM-12-4 W21.8x1/14" 227M4UFV-6 0.17 5.52 17.73 RGS-MAM-12-4 W21.8x1/14" 227M6UFM-2 0.21 6.00 RGS-MAM-12-4 W21.8x1/14" 227M6UFJ-2 0.24 5.52 23.80 RGS-MAM-12-4 W21.8x1/14" 227M6UFJ-4 0.24 5.52 23.80 RGS-MAM-12-4 W21.8x1/14" 227M6UFV-2 0.24 5.52 23.76 RGS-MAM-12-4 W21.8x1/14" 23.76 227M6UFV-4 0.24 5.52 RGS-MAM-12-4 W21.8x1/14" 227M9UFM-5 0.32 7.01 RGS-MAM-12-4 W21.8x1/14" 227M9UFM-6 0.32 7.01 RGS-MAM-12-4 W21.8x1/14" 227M12UFM-2 0.42 10.01 RGS-MAM-12-4 W21.8x1/14" 227M13UFAA-2 0.47 9.65 15.92 RGS-MAM-12-4 W21.8x1/14" 227M13UFV-2 0.47 5.52 43.10 RGS-MAM-12-4 W21.8x1/14" 227M13UFV-4 0.47 8.04 22.81 RGS-MAM-12-4 W21.8x1/14" 227M13UFV-6 0.47 8.04 23.60 RGS-MAM-12-4 W21.8x1/14" UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 202/239 227M13UFB-4 Nominal Capacity (ft³) 0.47 Part Number Nominal Diameter (in) 8.00 Height Outlet (in) 24.03 RGS-MAM-12-4 Outlet thread valve W21.8x1/14" Valve Type 227M13UFJ-2 0.47 8.04 23.84 RGS-MAM-12-4 W21.8x1/14" 227M16UFM-6 0.56 10.01 19.22 RGS-MAM-12-4 W21.8x1/14" 227M6UFM-3 0.21 6.00 RGS-MAM-20 3/4" BSP 227M6UFJ-5 0.24 5.52 24.31 RGS-MAM-20 3/4" BSP 227M6UFJ-6 0.24 5.52 24.31 RGS-MAM-20 3/4" BSP 227M6UFV-5 0.24 5.52 24.27 RGS-MAM-20 3/4" BSP 24.27 227M6UFV-6 0.24 5.52 RGS-MAM-20 3/4" BSP 227M9UFM-1 0.32 7.01 RGS-MAM-20 3/4" BSP 227M9UFM-2 0.32 7.01 RGS-MAM-20 3/4" BSP 227M12UFM-3 0.42 10.01 RGS-MAM-20 3/4" BSP 227M13UFAA-3 0.47 9.65 16.43 RGS-MAM-20 3/4" BSP 227M13UFV-7 0.47 5.52 43.62 RGS-MAM-20 3/4" BSP 227M13UFV-8 0.47 8.04 23.32 RGS-MAM-20 3/4" BSP 227M13UFV-9 0.47 8.04 24.11 RGS-MAM-20 3/4" BSP 227M13UFB-6 0.47 8.00 24.70 RGS-MAM-20 3/4" BSP 227M13UFJ-3 0.47 8.04 24.51 RGS-MAM-20 3/4" BSP 227M16UFM-2 0.56 10.01 19.73 RGS-MAM-20 3/4" BSP 227M21UFM 0.74 12.02 RGS-MAM-20 3/4" BSP 227M25UFAA 0.88 11.82 19.82 RGS-MAM-20 3/4" BSP 227M26UFB 0.95 8.00 42.83 RGS-MAM-20 3/4" BSP 227M26UFJ-1 0.95 8.04 42.24 RGS-MAM-20 3/4" BSP 227M26UFV-1 0.95 8.04 42.04 RGS-MAM-20 3/4" BSP 227M26UFJ-2 0.95 9.02 35.14 RGS-MAM-20 3/4" BSP 227M26UFV-2 0.95 9.02 35.29 RGS-MAM-20 3/4" BSP 227M26UFJ-3 0.95 9.02 35.14 RGS-MAM-20 3/4" BSP 227M26UFV-3 0.95 9.02 35.29 RGS-MAM-20 3/4" BSP 227M26UFV-4 0.95 9.02 36.33 RGS-MAM-20 3/4" BSP 227M26UFV-5 0.95 9.02 35.29 RGS-MAM-20 3/4" BSP 227M28UFM-1 1.00 9.01 33.43 RGS-MAM-20 3/4" BSP 227M28UFM-2 1.00 9.01 34.37 RGS-MAM-20 3/4" BSP 227M38UFAA 1.34 11.82 27.82 RGS-MAM-20 3/4" BSP 227M40UFJ-1 1.41 8.04 60.75 RGS-MAM-20 3/4" BSP 227M40UFV-1 1.42 8.04 59.77 RGS-MAM-20 3/4" BSP 227M40UFB-2 1.41 9.02 49.53 RGS-MAM-20 3/4" BSP 227M40UFJ-2 1.41 9.02 50.51 RGS-MAM-20 3/4" BSP 227M40UFV-2 1.42 9.02 49.54 RGS-MAM-20 3/4" BSP 227M40UFJ-3 1.41 9.02 50.51 RGS-MAM-20 3/4" BSP 227M40UFN-1 1.41 9.02 49.41 RGS-MAM-20 3/4" BSP 227M40UFV-3 1.42 9.02 49.54 RGS-MAM-20 3/4" BSP 227M40UFN-2 1.41 9.02 51.69 RGS-MAM-20 3/4" BSP 227M40UFV-4 1.42 9.02 50.71 RGS-MAM-20 3/4" BSP 227M40UFV-5 1.42 9.02 49.54 RGS-MAM-20 3/4" BSP 227M61UFAA 2.15 11.82 41.96 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFB-1 2.38 10.52 60.95 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFJ 2.38 10.52 60.95 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFV-1 2.38 10.52 59.77 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFC 2.38 10.52 58.59 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFR 2.38 10.52 60.95 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFV-2 2.40 14.18 37.31 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFJ 2.82 10.52 70.01 RGS-MAM-40 1" or 1 1/2" BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 203/239 227M80UFB-1 Nominal Capacity (ft³) 2.82 Nominal Diameter (in) 10.52 Height Outlet (in) 70.41 RGS-MAM-40 Outlet thread valve 1" or 1 1/2" BSP 227M80UFV-1 2.82 10.52 69.23 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFV-2 2.82 10.52 69.23 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFV-3 2.82 10.52 71.98 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFC 2.82 10.52 67.85 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFR 2.82 10.52 69.82 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFW 2.82 10.52 67.85 RGS-MAM-40 1" or 1 1/2" BSP Part Number Valve Type 227M80UFV-4 2.82 14.18 42.43 RGS-MAM-40 1" or 1 1/2" BSP 227M81UFM-2 2.88 12.76 47.26 RGS-MAM-40 1" or 1 1/2" BSP 227M84UFAA-1 2.97 11.82 54.84 RGS-MAM-40 1" or 1 1/2" BSP 227M86UFM 3.04 12.76 RGS-MAM-40 1" or 1 1/2" BSP 227M84UFAA-2 2.97 11.82 54.96 RGS-MAM-50 2" BSP 227M84UFAA-3 2.97 11.82 54.96 RGS-MAM-50 2" BSP 227M84UFM-1 2.97 16.00 33.79 RGS-MAM-50 2" BSP 227M84UFM-2 2.97 16.00 33.79 RGS-MAM-50 2" BSP 227M100UFV-1 3.53 14.18 50.71 RGS-MAM-40 1" or 1 1/2" BSP 227M100UFC 3.53 14.03 49.92 RGS-MAM-40 1" or 1 1/2" BSP 227M100UFR 3.53 14.03 53.47 RGS-MAM-40 1" or 1 1/2" BSP 227M100UFR-2 3.53 14.18 50.71 RGS-MAM-40 1" or 1 1/2" BSP 227M108UFAA-1 3.83 14.74 47.28 RGS-MAM-50 2" BSP 227M108UFAA-2 3.83 14.74 47.28 RGS-MAM-50 2" BSP 227M120UFB-1 4.24 16.00 55.24 RGS-MAM-50 2" BSP 227M120UFB-2 4.24 16.00 55.24 RGS-MAM-50 2" BSP 227M120UFV-1 4.24 14.18 59.38 RGS-MAM-40 1" or 1 1/2" BSP 227M120UFC 4.24 14.03 58.59 RGS-MAM-40 1" or 1 1/2" BSP 227M120UFR 4.24 14.03 62.13 RGS-MAM-40 1" or 1 1/2" BSP 227M120UFV-2 4.24 14.18 60.56 RGS-MAM-40 1" or 1 1/2" BSP 227M127UFAA-1 4.48 14.74 54.02 RGS-MAM-50 2" BSP 227M127UFAA-2 4.48 14.74 54.02 RGS-MAM-50 2" BSP 227M140UFV-1 4.94 14.18 68.63 RGS-MAM-50 2" BSP 227M140UFV-2 4.94 14.18 68.63 RGS-MAM-50 2" BSP 227M140UFV-3 4.94 14.18 70.80 RGS-MAM-50 2" BSP 227M140UFV-4 4.94 14.18 70.80 RGS-MAM-50 2" BSP 227M140UFC-1 4.94 14.03 67.45 RGS-MAM-50 2" BSP 227M140UFC-2 4.94 14.03 67.45 RGS-MAM-50 2" BSP 227M140UFR-1 4.94 14.03 71.00 RGS-MAM-50 2" BSP 227M140UFR-2 4.94 14.03 71.00 RGS-MAM-50 2" BSP 227M140UFV-5 4.94 14.18 69.62 RGS-MAM-50 2" BSP 227M140UFV-6 4.94 14.18 69.62 RGS-MAM-50 2" BSP 227M143UFM-1 5.05 16.01 53.47 RGS-MAM-50 2" BSP 227M143UFM-2 5.05 16.01 53.47 RGS-MAM-50 2" BSP 227M143UFM-3 5.05 16.00 53.47 RGS-MAM-50 2" BSP 227M143UFM-4 5.05 16.00 53.47 RGS-MAM-50 2" BSP 227M150UFB-1 5.30 16.00 64.93 RGS-MAM-50 2" BSP 227M150UFB-2 5.30 16.00 64.93 RGS-MAM-50 2" BSP 227M150UFC-1 5.30 16.00 56.42 RGS-MAM-50 2" BSP 227M150UFC-2 5.30 16.00 56.42 RGS-MAM-50 2" BSP 227M150UFV-1 5.30 14.18 72.57 RGS-MAM-50 2" BSP 227M150UFV-2 5.30 14.18 72.57 RGS-MAM-50 2" BSP 227M150UFC-3 5.30 14.03 71.79 RGS-MAM-50 2" BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 204/239 227M150UFC-4 Nominal Capacity (ft³) 5.30 Nominal Diameter (in) 14.03 Height Outlet (in) 71.79 RGS-MAM-50 Outlet thread valve 2" BSP 227M150UFR-1 5.30 14.03 75.14 RGS-MAM-50 2" BSP 227M150UFR-2 5.30 14.03 75.14 RGS-MAM-50 2" BSP 227M150UFV-3 5.30 14.18 74.35 RGS-MAM-50 2" BSP 227M150UFV-4 5.30 14.18 74.35 RGS-MAM-50 2" BSP 227M152UFM-1 5.37 16.00 56.46 RGS-MAM-50 2" BSP 227M152UFM-2 5.37 16.00 56.46 RGS-MAM-50 2" BSP 227M180UFC 6.35 16.00 67.06 RGS-MAM-50 2" BSP 227M180UFB-1 6.35 18.20 51.93 RGS-MAM-50 2" BSP 227M180UFM-1 6.35 16.00 65.53 RGS-MAM-50 2" BSP 227M180UFV-1 3.35 16.00 68.63 RGS-MAM-50 2" BSP 227M180UFV-2 3.35 16.00 68.63 RGS-MAM-50 2" BSP Part Number Valve Type 227M180UFB-3 6.35 18.20 52.56 RGS-MAM-80 3" Grooved 227M180UFM-2 6.35 16.00 66.16 RGS-MAM-80 3" Grooved 227M180UFV-3 3.35 16.00 68.63 RGS-MAM-80 3" Grooved 227M229UFM 8.08 20.02 RGS-MAM-80 3" Grooved 227M240UFB 8.47 18.20 67.89 RGS-MAM-80 3" Grooved 227M246UFM-1 8.68 22.02 50.09 RGS-MAM-80 3" Grooved 227M246UFM-2 8.68 22.02 50.16 RGS-MAM-80 3" Grooved 227M365UFM 12.88 24.03 RGS-MAM-80 3" Grooved 227M368UFM 12.99 24.03 61.85 RGS-MAM-80 3" Grooved 227M454UFM 16.03 30.02 51.87 RGS-MAM-80 3" Grooved 227M501UFM 17.69 30.02 56.13 RGS-MAM-80 3" Grooved UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 205/239 64. ANNEX 2: HFC-227ea Cylinders lengths S.I. Units Nominal Capacity (liters) Nominal Diameter (mm) Height Outlet (mm) Valve Type Outlet thread valve 227M2UFV-1 2 100 380 RGS-MAM-11-4 W21.8x1/14" 227M2UFJ-1 2.7 108 450 RGS-MAM-11-4 W21.8x1/14" 227M2UFV-1 2.7 100 475 RGS-MAM-11-4 W21.8x1/14" 227M2UFV-2 2.7 100 475 RGS-MAM-11-4 W21.8x1/14" 227M4UFJ-1 4.7 108 715 RGS-MAM-11-4 W21.8x1/14" 227M4UFJ-2 4.7 140 475 RGS-MAM-11-4 W21.8x1/14" 227M4UFJ-3 4.7 140 470 RGS-MAM-11-4 W21.8x1/14" 227M4UFV-1 4.7 115 608.5 RGS-MAM-11-4 W21.8x1/14" 227M4UFV-2 4.7 140 446 RGS-MAM-11-4 W21.8x1/14" 227M4UFV-3 4.7 140 446 RGS-MAM-11-4 W21.8x1/14" 227M6UFM-1 6 152.4 RGS-MAM-11-4 W21.8x1/14" 227M6UFJ-1 6.7 140 600 RGS-MAM-11-4 W21.8x1/14" 227M6UFJ-3 6.7 140 600 RGS-MAM-11-4 W21.8x1/14" 227M6UFV-1 6.7 140 599 RGS-MAM-11-4 W21.8x1/14" 227M6UFV-3 6.7 140 599 RGS-MAM-11-4 W21.8x1/14" 227M9UFM-3 9 177.8 RGS-MAM-11-4 W21.8x1/14" Part Number 227M9UFM-4 9 177.8 RGS-MAM-11-4 W21.8x1/14" 227M12UFM-1 12 254 RGS-MAM-11-4 W21.8x1/14" 227M13UFAA-1 13 245 400 RGS-MAM-11-4 W21.8x1/14" 227M13UFV-1 13.4 140 1090 RGS-MAM-11-4 W21.8x1/14" 227M13UFV-3 13.4 204 575 RGS-MAM-11-4 W21.8x1/14" 227M13UFV-5 13.4 204 595 RGS-MAM-11-4 W21.8x1/14" 227M13UFB-2 13.4 203 610 RGS-MAM-11-4 W21.8x1/14" 227M13UFJ-1 13.4 204 605 RGS-MAM-11-4 W21.8x1/14" 227M16UFM-4 16 254 483.8 RGS-MAM-11-4 W21.8x1/14" 227M2UFV-2 2 100 384 RGS-MAM-12-4 W21.8x1/14" 227M2UFJ-2 2.7 108 454 RGS-MAM-12-4 W21.8x1/14" 227M2UFV-3 2.7 100 479 RGS-MAM-12-4 W21.8x1/14" 227M2UFV-4 2.7 100 479 RGS-MAM-12-4 W21.8x1/14" 227M4UFJ-4 4.7 108 719 RGS-MAM-12-4 W21.8x1/14" 227M4UFJ-5 4.7 140 479 RGS-MAM-12-4 W21.8x1/14" 227M4UFJ-6 4.7 140 474 RGS-MAM-12-4 W21.8x1/14" 227M4UFV-4 4.7 115 612.5 RGS-MAM-12-4 W21.8x1/14" 227M4UFV-5 4.7 140 450 RGS-MAM-12-4 W21.8x1/14" 227M4UFV-6 4.7 140 450 RGS-MAM-12-4 W21.8x1/14" 227M6UFM-2 6 152.4 RGS-MAM-12-4 W21.8x1/14" 227M6UFJ-2 6.7 140 604 RGS-MAM-12-4 W21.8x1/14" 227M6UFJ-4 6.7 140 604 RGS-MAM-12-4 W21.8x1/14" 227M6UFV-2 6.7 140 603 RGS-MAM-12-4 W21.8x1/14" 603 227M6UFV-4 6.7 140 RGS-MAM-12-4 W21.8x1/14" 227M9UFM-5 9 177.8 RGS-MAM-12-4 W21.8x1/14" 227M9UFM-6 9 177.8 RGS-MAM-12-4 W21.8x1/14" 227M12UFM-2 12 254 RGS-MAM-12-4 W21.8x1/14" 227M13UFAA-2 13 245 404 RGS-MAM-12-4 W21.8x1/14" 227M13UFV-2 13.4 140 1094 RGS-MAM-12-4 W21.8x1/14" 227M13UFV-4 13.4 204 579 RGS-MAM-12-4 W21.8x1/14" 227M13UFV-6 13.4 204 599 RGS-MAM-12-4 W21.8x1/14" 227M13UFB-4 13.4 203 610 RGS-MAM-12-4 W21.8x1/14" UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 206/239 227M13UFJ-2 Nominal Capacity (liters) 13.4 227M16UFM-6 16 254 227M6UFM-3 6 152.4 227M6UFJ-5 6.7 140 617 RGS-MAM-20 3/4" BSP Part Number Nominal Diameter (mm) 204 Height Outlet (mm) 605 RGS-MAM-12-4 Outlet thread valve W21.8x1/14" 487.8 RGS-MAM-12-4 W21.8x1/14" RGS-MAM-20 3/4" BSP Valve Type 227M6UFJ-6 6.7 140 617 RGS-MAM-20 3/4" BSP 227M6UFV-5 6.7 140 616 RGS-MAM-20 3/4" BSP 227M6UFV-6 6.7 140 616 RGS-MAM-20 3/4" BSP 227M9UFM-1 9 177.8 RGS-MAM-20 3/4" BSP 227M9UFM-2 9 177.8 RGS-MAM-20 3/4" BSP 227M12UFM-3 12 254 RGS-MAM-20 3/4" BSP 227M13UFAA-3 13 245 417 RGS-MAM-20 3/4" BSP 227M13UFV-7 13.4 140 1107 RGS-MAM-20 3/4" BSP 227M13UFV-8 13.4 204 592 RGS-MAM-20 3/4" BSP 227M13UFV-9 13.4 204 612 RGS-MAM-20 3/4" BSP 227M13UFB-6 13.4 203 627 RGS-MAM-20 3/4" BSP 227M13UFJ-3 13.4 204 622 RGS-MAM-20 3/4" BSP 227M16UFM-2 16 254 500.8 RGS-MAM-20 3/4" BSP 227M21UFM 21 305 RGS-MAM-20 3/4" BSP 227M25UFAA 25 300 503 RGS-MAM-20 3/4" BSP 227M26UFB 26.8 203 1087 RGS-MAM-20 3/4" BSP 227M26UFJ-1 26.8 204 1072 RGS-MAM-20 3/4" BSP 227M26UFV-1 26.8 204 1067 RGS-MAM-20 3/4" BSP 227M26UFJ-2 26.8 229 892 RGS-MAM-20 3/4" BSP 227M26UFV-2 26.8 229 895.6 RGS-MAM-20 3/4" BSP 227M26UFJ-3 26.8 229 892 RGS-MAM-20 3/4" BSP 227M26UFV-3 26.8 229 895.6 RGS-MAM-20 3/4" BSP 227M26UFV-4 26.8 229 922 RGS-MAM-20 3/4" BSP 227M26UFV-5 26.8 229 895.6 RGS-MAM-20 3/4" BSP 227M28UFM-1 28.3 228,6 848.5 RGS-MAM-20 3/4" BSP 227M28UFM-2 28.3 228.6 872.25 RGS-MAM-20 3/4" BSP 227M38UFAA 38 300 706 RGS-MAM-20 3/4" BSP 227M40UFJ-1 40 204 1542 RGS-MAM-20 3/4" BSP 227M40UFV-1 40.2 204 1517 RGS-MAM-20 3/4" BSP 227M40UFB-2 40 229 1257 RGS-MAM-20 3/4" BSP 227M40UFJ-2 40 229 1282 RGS-MAM-20 3/4" BSP 227M40UFV-2 40.2 229 1257.4 RGS-MAM-20 3/4" BSP 227M40UFJ-3 40 229 1282 RGS-MAM-20 3/4" BSP 227M40UFN-1 40 229 1254 RGS-MAM-20 3/4" BSP 227M40UFV-3 40.2 229 1257.4 RGS-MAM-20 3/4" BSP 227M40UFN-2 40 229 1312 RGS-MAM-20 3/4" BSP 227M40UFV-4 40.2 229 1287 RGS-MAM-20 3/4" BSP 227M40UFV-5 40.2 229 1257.4 RGS-MAM-20 3/4" BSP 227M61UFAA 61 300 1065 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFB-1 67.5 267 1547 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFJ 67.5 267 1547 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFV-1 67.5 267 1517 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFC 67.5 267 1487 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFR 67.5 267 1547 RGS-MAM-40 1" or 1 1/2" BSP 227M67UFV-2 68 360 947 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFJ 80 267 1777 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFB-1 80 267 1787 RGS-MAM-40 1" or 1 1/2" BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 207/239 227M80UFV-1 Nominal Capacity (liters) 80 Nominal Diameter (mm) 267 Height Outlet (mm) 1757 RGS-MAM-40 Outlet thread valve 1" or 1 1/2" BSP 227M80UFV-2 80 267 1757 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFV-3 80 267 1827 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFC 80 267 1722 RGS-MAM-40 1" or 1 1/2" BSP Part Number Valve Type 227M80UFR 80 267 1772 RGS-MAM-40 1" or 1 1/2" BSP 227M80UFV-4 80 360 1077 RGS-MAM-40 1" or 1 1/2" BSP 227M81UFM-2 81.5 323.8 1199.5 RGS-MAM-40 1" or 1 1/2" BSP 227M84UFAA-1 84 300 1392 RGS-MAM-40 1" or 1 1/2" BSP 227M86UFM 86 323.8 RGS-MAM-40 1" or 1 1/2" BSP 227M84UFAA-2 84 300 1395 RGS-MAM-50 2" BSP 227M84UFAA-3 84 300 1395 RGS-MAM-50 2" BSP 227M84UFM-1 84 406 857.6 RGS-MAM-50 2" BSP 227M84UFM-2 84 406 857.6 RGS-MAM-50 2" BSP 227M100UFV-1 100 360 1287 RGS-MAM-40 1" or 1 1/2" BSP 227M100UFC 100 356 1267 RGS-MAM-40 1" or 1 1/2" BSP 227M100UFR 100 356 1357 RGS-MAM-40 1" or 1 1/2" BSP 227M100UFR-2 100 360 1287 RGS-MAM-40 1" or 1 1/2" BSP 227M108UFAA-1 108.4 374 1200 RGS-MAM-50 2" BSP 227M108UFAA-2 108.4 374 1200 RGS-MAM-50 2" BSP 227M120UFB-1 120 406 1402 RGS-MAM-50 2" BSP 227M120UFB-2 120 406 1402 RGS-MAM-50 2" BSP 227M120UFV-1 120 360 1507 RGS-MAM-40 1" or 1 1/2" BSP 227M120UFC 120 356 1487 RGS-MAM-40 1" or 1 1/2" BSP 227M120UFR 120 356 1577 RGS-MAM-40 1" or 1 1/2" BSP 227M120UFV-2 120 360 1537 RGS-MAM-40 1" or 1 1/2" BSP 227M127UFAA-1 127 374 1371 RGS-MAM-50 2" BSP 227M127UFAA-2 127 374 1371 RGS-MAM-50 2" BSP 227M140UFV-1 140 360 1742 RGS-MAM-50 2" BSP 227M140UFV-2 140 360 1742 RGS-MAM-50 2" BSP 227M140UFV-3 140 360 1797 RGS-MAM-50 2" BSP 227M140UFV-4 140 360 1797 RGS-MAM-50 2" BSP 227M140UFC-1 140 356 1712 RGS-MAM-50 2" BSP 227M140UFC-2 140 356 1712 RGS-MAM-50 2" BSP 227M140UFR-1 140 356 1802 RGS-MAM-50 2" BSP 227M140UFR-2 140 356 1802 RGS-MAM-50 2" BSP 227M140UFV-5 140 360 1767 RGS-MAM-50 2" BSP 227M140UFV-6 140 360 1767 RGS-MAM-50 2" BSP 227M143UFM-1 143 406.4 1357 RGS-MAM-50 2" BSP 227M143UFM-2 143 406.4 1357 RGS-MAM-50 2" BSP 227M143UFM-3 143 406 1357 RGS-MAM-50 2" BSP 227M143UFM-4 143 406 1357 RGS-MAM-50 2" BSP 227M150UFB-1 150 406 1648 RGS-MAM-50 2" BSP 227M150UFB-2 150 406 1648 RGS-MAM-50 2" BSP 227M150UFC-1 150 406 1432 RGS-MAM-50 2" BSP 227M150UFC-2 150 406 1432 RGS-MAM-50 2" BSP 227M150UFV-1 150 360 1842 RGS-MAM-50 2" BSP 227M150UFV-2 150 360 1842 RGS-MAM-50 2" BSP 227M150UFC-3 150 356 1822 RGS-MAM-50 2" BSP UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 208/239 227M150UFC-4 Nominal Capacity (liters) 150 Nominal Diameter (mm) 356 Height Outlet (mm) 1822 RGS-MAM-50 Outlet thread valve 2" BSP 227M150UFR-1 150 356 1907 RGS-MAM-50 2" BSP 227M150UFR-2 150 356 1907 RGS-MAM-50 2" BSP 227M150UFV-3 150 360 1887 RGS-MAM-50 2" BSP 227M150UFV-4 150 360 1887 RGS-MAM-50 2" BSP 227M152UFM-1 152 406 1433.1 RGS-MAM-50 2" BSP 227M152UFM-2 152 406 1433.1 RGS-MAM-50 2" BSP 227M180UFC 180 406 1702 RGS-MAM-50 2" BSP 227M180UFB-1 180 462 1318 RGS-MAM-50 2" BSP 227M180UFM-1 180 406 1663.3 RGS-MAM-50 2" BSP 227M180UFV-1 180 406 1742 RGS-MAM-50 2" BSP 227M180UFV-2 180 406 1742 RGS-MAM-50 2" BSP Part Number Valve Type 227M180UFB-3 180 462 1334 RGS-MAM-80 3" Grooved 227M180UFM-2 180 406 1679.3 RGS-MAM-80 3" Grooved 227M180UFV-3 180 406 1742 RGS-MAM-80 3" Grooved 227M229UFM 229 508 RGS-MAM-80 3" Grooved 227M240UFB 240 462 1723.1 RGS-MAM-80 3" Grooved 227M246UFM-1 246 558.8 1271.3 RGS-MAM-80 3" Grooved 227M246UFM-2 246 558.8 1273 RGS-MAM-80 3" Grooved 227M365UFM 365 610 RGS-MAM-80 3" Grooved 227M368UFM 368 610 1569.7 RGS-MAM-80 3" Grooved 227M454UFM 454 762 1316.5 RGS-MAM-80 3" Grooved 227M501UFM 501 762 1424.5 RGS-MAM-80 3" Grooved NOTE: These lengths are approximately due to the differences made in the manufacturing process. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 209/239 65. ANNEX 3: Pilot cylinders lengths U.S. Units Part Number Nominal Capacity (ft³) Nominal Diameter (in) Height Outlet (in) 100M008UFA 0.003 1.38 7.88 100M018UFA 0.006 1.50 11.82 100M2UFV-1 0.07 3.94 100M2UFV-2 0.07 3.94 100M6UFJ-1 0.24 100M6UFJ-2 0.24 100M6UFV-1 Valve Type Outlet thread valve Filling Pressure 1450 psi 1740 psi 2175 psi 1/4" BSP X X X 2900 psi 1/4" BSP X X X 14.972 RGS-MAM-03 RGS-MAM-03A RGS-MAM-03 RGS-MAM-03A RGS-MAM-11-4 W21.7x1/14" X X X X 14.972 RGS-MAM-12-4 W21.7x1/14" X X X X 5.52 23.64 RGS-MAM-11-4 W21.7x1/14" X X X 5.52 23.64 RGS-MAM-12-4 W21.7x1/14" X X X 0.24 5.52 23.64 RGS-MAM-11-4 W21.7x1/14" X X X 100M6UFV-2 0.24 5.52 23.64 RGS-MAM-12-4 W21.7x1/14" X X X 100M6UFJ-3 0.24 5.52 23.64 RGS-MAM-11-4 W21.7x1/14" X X X X 100M6UFJ-4 0.24 5.52 23.64 RGS-MAM-12-4 W21.7x1/14" X X X X 100M6UFV-3 0.24 5.52 23.601 RGS-MAM-11-4 W21.7x1/14" X X X X 100M6UFV-4 0.24 5.52 23.601 RGS-MAM-12-4 W21.7x1/14" X X X X 100M13UFV-1 0.47 5.52 42.946 RGS-MAM-11-4 W21.7x1/14" X X X X 100M13UFV-2 0.47 5.52 42.946 RGS-MAM-12-4 W21.7x1/14" X X X X 100M13UFB-3 0.47 8.04 24.034 RGS-MAM-11-4 W21.7x1/14" X X X 100M13UFB-4 0.47 8.04 24.034 RGS-MAM-12-4 W21.7x1/14" X X X 100M13UFJ-1 0.47 8.04 23.837 RGS-MAM-11-4 W21.7x1/14" X X X X 100M13UFJ-2 0.47 8.04 23.837 RGS-MAM-12-4 W21.7x1/14" X X X X 100M13UFV-3 0.47 8.04 22.655 RGS-MAM-11-4 W21.7x1/14" X X X 100M13UFV-4 0.47 8.04 22.655 RGS-MAM-12-4 W21.7x1/14" X X X 100M13UFV-5 0.47 8.04 23.443 RGS-MAM-11-4 W21.7x1/14" X X X X 100M13UFV-6 0.47 8.04 23.443 RGS-MAM-12-4 W21.7x1/14" X X X X NOTE: This lengths are approximately due to the differences made in the manufacturing process. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 210/239 66. ANNEX 3: Pilot cylinders lengths S.I. Units Part Number Nominal Capacity (liters) Nominal Diameter (mm) Height Outlet (mm) Valve Type Outlet thread valve 100M008UFA 0.08 35 200 RGS-MAM-03 RGS-MAM-03A 100M018UFA 0.18 38 300 100M2UFV-1 2 100 100M2UFV-2 2 100 100M6UFJ-1 6.7 100M6UFJ-2 6.7 100M6UFV-1 Filling Pressure 100 bar 120 bar 150 bar 200 bar 1/4" BSP X X X RGS-MAM-03 RGS-MAM-03A 1/4" BSP X X X 380 RGS-MAM-11-4 W21.7x1/14" X X X X 380 RGS-MAM-12-4 W21.7x1/14" X X X X 140 600 RGS-MAM-11-4 W21.7x1/14" X X X 140 600 RGS-MAM-12-4 W21.7x1/14" X X X 6.7 140 600 RGS-MAM-11-4 W21.7x1/14" X X X 100M6UFV-2 6.7 140 600 RGS-MAM-12-4 W21.7x1/14" X X X 100M6UFJ-3 6.7 140 600 RGS-MAM-11-4 W21.7x1/14" X X X X 100M6UFJ-4 6.7 140 600 RGS-MAM-12-4 W21.7x1/14" X X X X 100M6UFV-3 6.7 140 599 RGS-MAM-11-4 W21.7x1/14" X X X X 100M6UFV-4 6.7 140 599 RGS-MAM-12-4 W21.7x1/14" X X X X 100M13UFV-1 13.4 140 1090 RGS-MAM-11-4 W21.7x1/14" X X X X 100M13UFV-2 13.4 140 1090 RGS-MAM-12-4 W21.7x1/14" X X X X 100M13UFB-3 13.4 204 610 RGS-MAM-11-4 W21.7x1/14" X X X 100M13UFB-4 13.4 204 610 RGS-MAM-12-4 W21.7x1/14" X X X 100M13UFJ-1 13.4 204 605 RGS-MAM-11-4 W21.7x1/14" X X X X 100M13UFJ-2 13.4 204 605 RGS-MAM-12-4 W21.7x1/14" X X X X 100M13UFV-3 13.4 204 575 RGS-MAM-11-4 W21.7x1/14" X X X 100M13UFV-4 13.4 204 575 RGS-MAM-12-4 W21.7x1/14" X X X 100M13UFV-5 13.4 204 595 RGS-MAM-11-4 W21.7x1/14" X X X X 100M13UFV-6 13.4 204 595 RGS-MAM-12-4 W21.7x1/14" X X X X NOTE: These lengths are approximately due to the differences made in the manufacturing process. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 211/239 67. ANNEX 4: PART NUMBERS LIST PART NUMBER FAMILY ANNEX 1 & 2 Cylinders n/a n/a n/a n/a n/a n/a Bridles Protective caps Stickers RGS-MAM-11-4 RGS-MAM-12-4 RGS-MAM-20 RGS-MAM-40 Container valves RGS-MAM-50 RGS-MAM-80 RGS-MAM-04 UFBD-06X40-8749 UFBD-06X50-8777 UFBD-06X60-8563 UL-EX15547 FM-3053302 Bursting discs DESRIPTION LIMITATIONS Seamless or welded steel container with siphon tube, container valve and bursting disc, with the corresponding agent quantity. Each cylinder has a bridle to fix the protective cap during transport and storage Used to allow install the protective caps They protect the valves during transport and/or storage UL – FM sticker Company stiker Cylinder sticker Cartridge sticker High flow, quick opening container valve. Outlet W21,8 and 3/4" BSP. Used in SIEX-SMS & Pilot cylinders. High flow, quick opening container valve. Outlet W21,8 and 3/4" BSP. Used in SIEX-SMS & Pilot cylinders. High flow, quick opening container valve. Outlet 3/4" BSP. Used in SIEX-HC 227. High flow, quick opening container valve. Outlet 1” and 1 1/2" BSP. Used in SIEX-HC 227. High flow, quick opening container valve. Outlet 2" BSP. Used in SIEX-HC 227. High flow, quick opening container valve. Outlet 3" Grooved. Used in SIEX-HC 227. Pneumatic time delayer Protect the system against the overpressure. Burst at 580 psi (40 bar). Protect the system against the overpressure. Burst at 725 psi (50 bar). Protect the system against the overpressure. Burst at 870 psi “UF-MC-HC” - 27-01-2016 Volumes from 0.07 to 17.69 ft³ (2 to 501 Liters) n/a n/a n/a n/a n/a n/a Cylinders from 0.07 to 0.57 ft³ (2 to 16 liters.) Cylinders from 0.07 to 0.57 ft³ (2 to 16 liters.) Cylinders from 0.21 to 1.42 ft³ (6 to 40.2 liters.) Cylinders from 2.15 to 4.24 ft³ (61 to 120 liters). Cylinders from 2.97 to 6.35 ft³ (84 to 180 liters). Cylinders from 6.35 to 17.69 (180 to 501 liters). Cylinders from 0.07 to 0.57 ft³ (2 to 16 liters.) PAGE in UF-MC-HC See Annex 1 and 2 11 11 12, 13 & 14 12, 13 & 14 12, 13 & 14 12, 13 & 14 15, 16, 17 & 18 15, 16, 17 & 18 15, 16, 17 & 18 15, 16, 17 & 18 15, 16, 17 & 18 15, 16, 17 & 18 27 & 28 RGS-MAM-11-4/12-4/20 19 & 20 RGS-MAM-11-4/12-4/20 19 & 20 RGS-MAM-11-4/12-4/20 19 & 20 212/239 PART NUMBER FAMILY UFBD-06X110-7971 UFBD-08X40-8770 UFBD-08X50-8780 UFBD-08X60-8502 UFBD-08X110-7973 UFBD-11X40-8771 UFBD-11X50-8781 UFBD-11X60-8564 UFBD-11X110-8073 UFBD-18X50-8782 UFBD-18X60-8503 UFBD-arand-23X17X1 ufbd-08x060-8502 ufbd-08x110-7973 UFBD-08X210-8610 UFBD-08X310-8611 UFBD-08X350-8613 UL-EX15547 FM-3053302 Bursting discs DESRIPTION (60 bar). Protect the system against the overpressure. Burst at 1595 psi (110 bar). Protect the system against the overpressure. Burst at 580 psi (40 bar). Protect the system against the overpressure. Burst at 725 psi (50 bar). Protect the system against the overpressure. Burst at 870 psi (60 bar). Protect the system against the overpressure. Burst at 1595 psi (110 bar). Protect the system against the overpressure. Burst at 580 psi (40 bar). Protect the system against the overpressure. Burst at 725 psi (50 bar). Protect the system against the overpressure. Burst at 870 psi (60 bar). Protect the system against the overpressure. Burst at 1595 psi (110 bar). Protect the system against the overpressure. Burst at 725 psi (50 bar). Protect the system against the overpressure. Burst at 870 psi (60 bar). Protect the system against the overpressure. Washer. Protect the system against the overpressure. Burst at 870 psi (60 bar). Protect the system against the overpressure. Burst at 1595 psi (110 bar). Protect the system against the overpressure. Burst at 3050 psi (210 bar). Protect the system against the overpressure. Burst at 4500 psi (310 bar). Protect the system against the overpressure. Burst at 5080 psi “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC RGS-MAM-11-4/12-4/20 19 & 20 RGS-MAM-40/50/80 19 & 20 RGS-MAM-40/50/80 RGS-MAM-40/50/80 RGS-MAM-40/50/80 RGS-MAM-50 RGS-MAM-50 RGS-MAM-50 RGS-MAM-50 RGS-MAM-80 RGS-MAM-80 RGS-MAM-80 VREC & VREC-O VREC & VREC-O VREC & VREC-O 19 & 20 19 & 20 19 & 20 19 & 20 19 & 20 19 & 20 19 & 20 19 & 20 19 & 20 19 & 20 185 & 186 185 & 186 185 & 186 VREC & VREC-O 185 & 186 VREC & VREC-O 185 & 186 213/239 PART NUMBER FAMILY UFBD-08X430-8612 UF40H-P25 UF40H-P32 UF40H-P34 UF40H-P42 UF40H-P50 UF40H-P55 UF40I-P150 UF40I-P200 UF40I-P0 UF40H-E25 UF40H-E32 UF40H-E34 UF40H-E42 UF40H-E50 UF40H-E55 UF40I-E150 UF40I-E200 UF40I-E0 Pressure gauges Pressure gauge with electrical contacts POPRENA20 POPRENC20 DESRIPTION (350 bar). Protect the system against the overpressure. Burst at 6240 psi (430 bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Indicates the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Monitoring the pressure of the cylinder (in psi and bar). Warn against a partial or total discharge. Normally Open. Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. POPRENA50 Pressure switches POPRENC50 POPRENA80 POPRENC80 UL-EX15547 FM-3053302 Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. Warn against a partial or total discharge. Normally Closed. “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC VREC & VREC-O 185 & 186 Cylinders filled at 362 psi (25 bar) Cylinders filled at 464 psi (32 bar) Cylinders filled at 493 psi (34 bar) Cylinders filled at 609 psi (42 bar) Cylinders filled at 725 psi (50 bar) Cylinders filled at 798 psi (55 bar) Cylinders filled at 2170 psi (150 bar) Cylinders filled at 2900 psi (200 bar) From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 From 21 to 26 Cylinders filled at 362 psi (25 bar) Cylinders filled at 464 psi (32 bar) Cylinders filled at 493 psi (34 bar) Cylinders filled at 609 psi (42 bar) Cylinders filled at 725 psi (50 bar) Cylinders filled at 798 psi (55 bar) Cylinders filled at 2170 psi (150 bar) Cylinders filled at 2900 psi (200 bar) Regulation field: 145-290 psi (10-20 bar) Regulation field: 145-290 psi (10-20 bar) Regulation field: 290-725 psi (20-50 bar) Regulation field: 290-725 psi (20-50 bar) Regulation field: 725-1160 psi (50-80 bar) Regulation field: 725-1160 psi (50-80 bar) 29 29 29 29 29 29 214/239 PART NUMBER FAMILY POPRENA150 POPRENC150 Warn against a partial or total discharge. Normally Open. POPRENC300 Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. APRESA20 APRESC20 Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. APRESA50 APRESC50 Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. APRESA80 APRESA250 Regulation field: 725-2175 psi (50-150 bar) Regulation field: 725-2175 psi (50-150 bar) Regulation field: 1450-3625 psi (100-250 bar) Regulation field: 1450-3625 psi (100-250 bar) Regulation field: 725-4350 psi (50-300 bar) Regulation field: 725-4350 psi (50-300 bar) Regulation field: 145-290 psi (10-20 bar) Regulation field: 145-290 psi (10-20 bar) Regulation field: 290-725 psi (20-50 bar) Regulation field: 290-725 psi (20-50 bar) Regulation field: 725-1160 psi (50-80 bar) Regulation field: 725-1160 psi (50-80 bar) Regulation field: 725-2175 psi (50-150 bar) Regulation field: 725-2175 psi (50-150 bar) Regulation field: 1450-3625 psi (100-250 bar) Regulation field: 1450-3625 psi (100-250 bar) Regulation field: 725-4350 psi Warn against a partial or total discharge. Normally Closed. POPRENA300 APRESC150 Warn against a partial or total discharge. Normally Open. Warn against a partial or total discharge. Normally Open. POPRENC250 APRESA150 LIMITATIONS Warn against a partial or total discharge. Normally Closed. POPRENA250 APRESC80 DESRIPTION Pressure switches Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. Warn against a partial or total discharge. Normally Closed. Warn against a partial or total discharge. Normally Open. APRESC250 Warn against a partial or total discharge. Normally Closed. APRESA300 Warn against a partial or total discharge. Normally Open. UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 29 29 29 29 29 29 30 30 30 30 30 30 30 30 30 30 30 215/239 PART NUMBER FAMILY APRESC300 POPRECO-AD 24,1 Pressure switches for hazardous locations POPRECO-AD 103,4 POPRECO-AD 413.7 227DM 227DMR 227DMS Manual actuators 227CMC Cable operated manual actuators 227CMCC 227CN 227CNTK 227TE 227CO POAD10MM UL-EX15547 FM-3053302 LIMITATIONS Warn against a partial or total discharge. Normally Closed. Popreco AD PSX POPRECO-AD 48,3 DESRIPTION Pneumatic actuators Warn against a partial or total discharge. Used in hazardous locations. Two contacts (Normally Open & Normally Closed). Warn against a partial or total discharge. Used in hazardous locations. Two contacts (Normally Open & Normally Closed). Warn against a partial or total discharge. Used in hazardous locations. Two contacts (Normally Open & Normally Closed). Warn against a partial or total discharge. Used in hazardous locations. Two contacts (Normally Open & Normally Closed). Warn against a partial or total discharge. Used in hazardous locations. Two contacts (Normally Open & Normally Closed). Used to manually activate the container valves and the electrical actuators. Used to manually activate the container valves. Used to manually activate the electrical actuators. Allows have a remote manual activation of the system with the help of a cable. Used together with a manual pull station TK-DMS/TK-DMS2. Is a 227CMC with protective box. Allows have a remote activation of the system with the help of a cable. Used together with a remote manual pull station TK-DMS/TK-DMS2 Used to pneumatically activate the container valves and the electrical actuators. Used to pneumatically activate the container valves and the electrical actuators. Is a 1/4" tee which connect the hoses and the pneumatic actuators of the pilot line Is a 1/4" elbow which connect the hoses and the last pneumatic actuator of the pilot line Is a 1/4" adapter which connect the hoses and the pneumatic actuator of the pilot line “UF-MC-HC” - 27-01-2016 (50-300 bar) Regulation field: 725-4350 psi (50-300 bar) Regulation field: 725-4350 psi (10-300 bar) Regulation field: 100 – 349 psi (6.9 – 24.1 Bar) Regulation field: 246 – 700 psi (17.2 – 48.3 Bar) Regulation field: 387 – 1500 psi (27.6 – 103.4 Bar) Regulation field: 2000- 6000 psi (137.9 – 413.7 Bar) RGS-MAM-11-4/12-4/20/40/50/80 227SOL/R/C/CR/C125/CR125 RGS-MAM-03/03A 227SOL/R/C/CR/C125/CR125 PAGE in UF-MC-HC 30 31 32 32 32 32 33 34 35 RGS-MAM-11-4/12-4/20/40/50/80 227SOL/R/C/CR/C125/CR125 63 RGS-MAM-11-4/12-4/20/40/50/80 227SOL/R/C/CR/C125/CR125 62 RGS-MAM-11-4/12-4/20/40/50/80 227SOL/R/C/CR/C125/CR125 RGS-MAM-11-4/12-4/20/40/50/80 227SOL/R/C/CR/C125/CR125 37 38 227CN - 227CNTK - 227CNM 39 227CN - 227CNTK - 227CNM 39 227CN - 227CNTK - 227CNM 40 216/239 PART NUMBER FAMILY DESRIPTION LIMITATIONS 227CNM Pneumatic manual actuators Used to manually or pneumatically activate the container valves and the electrical actuators. Detects at every moment the status of the electrical actuator (connect or isconnect). It has two contacts, NO and NC Detects at every moment the status of the electrical actuator (connect or isconnect). It has two contacts, NO and NC RGS-MAM-11-4/12-4/20/40/50/80 227SOL/R/C/CR/C125/CR125 RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A 227SOLFC 227SOLGLC USTS Security seal to solenoids. Supervision Safety Systems PAGE in UF-MC-HC 36 42 & 43 42 & 43 43 RCDS-1 It uses to disconnect the system during the maintenance 10A 250VAC, 15A 125-250 VAC, the rating is 15A up to 30VDC. 10A 250VAC, 15A 125-250 VAC, the rating is 15A up to 30VDC. MRS-2 It uses to select Main /reserve battery. 1 AMP 40 VDC 45 RCDS-2 It uses to disconnect the system during the maintenance 24 VDC, 10mA 45 RGS-MAM-11-4/12-4/20/40/50/80 46 & 47 RGS-MAM-03/03A 46 & 48 RGS-MAM-11-4/12-4/20/40/50/80 49 & 50 RGS-MAM-03/03A 49 & 51 RGS-MAM-11-4/12-4/20/40/50/80 52 & 53 RGS-MAM-03/03A 52 & 54 RGS-MAM-124/20/40/50/80/03/03A 55 RGS-MAM-124/20/40/50/80/03/03A 56 MRS-1 227SOL 227SOLR 227SOLC 227SOLCR 227SOLC125 Re-assembled electrical actuators Electrical actuator head 227SOLCR125 POSOLUFO POSOLUFX UL-EX15547 FM-3053302 Explosion proof electrical actuator head It uses to select Main /reserve battery. Used to electrically activate the container valve where it is mounted. It can be reseted manually by a reassembled screw. Used to electrically activate the container valve where it is mounted. It can be reseted manually by a reassembled screw. Used to electrically activate the container valve where it is mounted. It can be reseted manually by a reassembled screw. Used to electrically activate the container valve where it is mounted. It can be reseted manually by a reassembled screw. Used to electrically activate the container valve where it is mounted. It can be reseted manually by a reassembled screw. Used to electrically activate the container valve where it is mounted. It can be reseted manually by a reassembled screw. Used to electrically activate the container valve where it is mounted. Used to electrically activate the container valve where it is mounted. “UF-MC-HC” - 27-01-2016 44 44 217/239 PART NUMBER FAMILY 227DEFLAG 227DEFLAG1 227SOLC-AD HAZLOC Explosion proof electrical actuator head Pneumatic trip POSX-NAU POSX-NAUP POSX-NAUC Pneumatic trip Remote manual pull stations POSX-NAUCP TK-DMS TK-DMC2 TK-SIMPLEX UL-EX15547 FM-3053302 LIMITATIONS Used to electrically activate the container valve where it is mounted. Used to electrically activate the container valve where it is mounted. Used to electrically activate the container valve where it is mounted. Its activated manually or pneumatically to close doors, duct dampers, gas shut-off valves, etc. when the system activates. The activation knob is aluminium Its activated manually or pneumatically to close doors, duct dampers, gas shut-off valves, etc. when the system activates. The activation knob is plastic It is activated manually or pneumatically to close doors, duct dampers, gas shut-off valves, etc. when the system activates. It has a metallic box to be protected. The activation knob is aluminium It is activated manually or pneumatically to close doors, duct dampers, gas shut-off valves, etc. when the system activates. It has a metallic box to be protected. The activation knob is plastic It is used to remotely activate the extinguishing system. Used together with the cable operated manual actuator or the mechanical control unit. RGS-MAM-124/20/40/50/80/03/03A RGS-MAM-124/20/40/50/80/03/03A RGS-MAM-124/20/40/50/80/03/03A It is the same than the TK-DMS but allowed to be installed in the plasterboard or dry wall. TK-DMS2 TK-DMC DESRIPTION Remote manual pull stations Mechanical control unit It is used to have a manual activation of the mechanical control unit distantly. Installed in the middle of the detection line. It is used to have a manual activation of the mechanical control unit distantly. Installed at the end of the detection line. It has one mechanical detection network which releases the “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 57 58 59 & 60 132 lb (60 kg) 61 132 lb (60 kg) 62 132 lb (60 kg) 62 & 63 132 lb (60 kg) 62 & 63 Max. Length of cable: 124.5 ft 38m. Max. No of pulley elbows: 36 units Max. No of pulley tee: 1 unit Max. Length of cable: 124.5 ft 38m. Max. No of pulley elbows: 36 units Max. No of pulley tee: 1 unit Max. Length of cable: 205.9 ft 62.7m. Max. No of pulley elbows: 42 units Max. No of pulley tee: 1 unit Max. Length of cable: 205.9 ft 62.7m. Max. No of pulley elbows: 42 units Max. No of pulley tee: 1 unit RGS-MAM-11-4/12-4/20/40/50/80 66, 67 & 68 66, 67 & 68 69 & 70 69 & 70 71, 72 & 73 218/239 PART NUMBER FAMILY DESRIPTION LIMITATIONS PAGE in UF-MC-HC system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. TK-SIMPLEX-B It has one mechanical detection network which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. TK-SIMPLEX-C It has one mechanical detection network which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. TK-COMPLEX It has two mechanical detection networks which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. It only needs one fusible from one detection line. TK-COMPLEX-B TK-COMPLEX-C TK-COMPLEX Cross TK-COMPLEX-B Cross TK-COMPLEX-C Cross UL-EX15547 FM-3053302 Mechanical control unit Mechanical detection It has two mechanical detection networks which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. It only needs one fusible from one detection line. It has two mechanical detection networks which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. It only needs one fusible from one detection line. It has two mechanical detection networks which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. It needs at least one fusible from each detection line. It has two mechanical detection networks which releases the system when a fusible link or a thermo bulb is activated due to a rising of heat caused by a fire. It needs at least one fusible from each detection line. It has two mechanical detection networks which releases the system when a fusible link or a thermo bulb is activated due “UF-MC-HC” - 27-01-2016 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 RGS-MAM-03/03A 71, 72 & 73 71, 72 & 73 74, 75 & 76 74, 75 & 76 74, 75 & 76 74, 75 & 76 74, 75 & 76 74, 75 & 76 219/239 PART NUMBER FAMILY TK-KIT-T-F TK-KIT-T-B TK-KIT-C-F TK-KIT-C-B TK-KIT-A-F Mechanical detection Fusible And Thermo Bulbs TK-KIT-A-B KFT57 KFT74 KFT100 KFT138 KFT182 KFT232 KBT57S KBT68S KBT74S KBT79S UL-EX15547 FM-3053302 Fusible And Thermo Bulbs Fusible And Thermo Bulbs DESRIPTION LIMITATIONS to a rising of heat caused by a fire. It needs at least one fusible from each detection line. Detects the fire through the temperature by means of a fusible link for different temperatures which are joined by means of a steel cable. Scissors are used to fix the fusible. Detects the fire through the temperature by means of a thermo bulb for different temperatures which are joined by means of a steel cable. Scissors are used to fix the bulb. Detects the fire through the temperature by means of a fusible link for different temperatures which are joined by means of a steel cable. End of line are used to fix the fusible. Detects the fire through the temperature by means of a thermo bulb for different temperatures which are joined by means of a steel cable. End of line are used to fix the bulb. Detects the fire through the temperature by means of a fusible link for different temperatures which are joined by means of a steel cable. Hooks are used to fix the fusible. Detects the fire through the temperature by means of a thermo bulb for different temperatures which are joined by means of a steel cable. Hooks are used to fix the bulb. Fusible link: welded union that breaks at certain temperature. Fusible link: welded union that breaks at certain temperature. Fusible link: welded union that breaks at certain temperature. Fusible link: welded union that breaks at certain temperature. Fusible link: welded union that breaks at certain temperature. Fusible link: welded union that breaks at certain temperature. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 77 77 77 77 77 77 135º F or 57º C 165º F or 74º C 212º F or 100º C 280º F or 138º C 360º F or 182º C 450º F or 232º C 78 78 78 78 78 78 135º F or 57º C 79 155º F or 68º C 79 165º F or 74º C 79 175º F or 79º C 79 220/239 PART NUMBER FAMILY KBT93S KBT100S KBT141S KBT182S KBT232S KBT260S KBT57Q KBT68Q KBT74Q KBT79Q KBT93Q KBT100Q KBT141Q KBT182Q KBT232Q KBT260Q UL-EX15547 FM-3053302 Fusible And Thermo Bulbs Cable accessories Cable accessories DESRIPTION temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Standard response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. Thermo bulb: union device that breaks at certain temperature. Quick response. “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC 200º F or 93º C 79 212º F or 100º C 79 286º F or 141º C 79 360º F or 182º C 79 450º F or 232º C 79 500º F or 260º C 79 135º F or 57º C 79 155º F or 68º C 165º F or 74º C 175º F or 79º C 200º F or 93º C 212º F or 100º C 286º F or 141º C 360º F or 182º C 450º F or 232º C 500º F or 260º C 79 79 79 79 79 79 79 79 79 221/239 PART NUMBER FAMILY KFTTL KWR-50 TK-FL TK-FL2 TK-CP Cable accessories Cable accessories Thermal manual actuators TK-CP2 TK-CP3 TK-TE TK-TEC KCTM KCTM-R KCTM-C SIEX-NTD-C008 UL-EX15547 FM-3053302 LIMITATIONS Test link Cable used in mechanical detection line, remote manual activation line, pneumatic trip line, mechanical gas shut-off valve, etc. Normally protected by tube of Ø18mm. Used for testing Cable used in mechanical detection line, remote manual activation line, pneumatic trip line, mechanical gas shut-off valve, etc. It is protected by a plastic case. KWR-100 TK-DPDT DESRIPTION Thermal manual actuators Thermal pneumatic manual actuators Is used to fix the cable in their ends in order to block the cable. It is fixed by screws. It can be used several times. Is used to fix the cable in their ends in order to block the cable. It is fixed by manual force. It can be used only one time. Double micro-switch used to provide an electrical signal to the fire control panel in case the system is activated. It is installed in the mechanical control unit. Drives the inox steel cable to avoid obstacles and changes of direction to connect the elements of the cable lines. Drives the inox steel cable to avoid obstacles and changes of direction to connect the elements of the cable lines. Drives the inox steel cable to avoid obstacles and changes of direction to connect the elements of the cable lines. Used to take two remote manual actuators from the mechanical control unit or cable operated manual actuator. Allows connect several remote manual pull stations from the mechanical detection line. Used to thermically or manually activate the container valves where is mounted. Used to thermically or manually activate the container valves where is mounted. Used to thermically or manually activate the container valves where is mounted. Is a combination of a thermal actuator and the 0.003 ft³ 0,080 liters pilot cartridge, all installed in a protective cabinet. “UF-MC-HC” - 27-01-2016 Inox steel cable of Ø 0.06 in ( 1.5 mm) PAGE in UF-MC-HC 79 80 80 Inox steel cable of Ø 0.06 in ( 1.5 mm) with protective case For cable of Ø 0.06 in ( 1.5 mm) 80 For cable of Ø 0.06 in ( 1.5 mm) 81 0.1 A - 125 VAC 0.25 A - 30 VDC 81 Bending angle of 90º 82 Bending angle of 90º 82 Bending angle of 90º 82 TK-DMS / TK-DMS2 83 & 84 TK-DMC 85 RGS-MAM-11-4/12-4/20/40/50/80 86 & 89 RGS-MAM-03/03A 86 & 89 RGS-MAM-03/03A RGS-MAM-11-4/12-4/20/40/50/80 Max. Distance between detector and the extinguishing system: 49.21 ft 86 & 89 90, 91 & 92 222/239 PART NUMBER SIEX-NTD-C018 FH-6PO FAMILY Thermal pneumatic manual actuators Activation hoses FH-7PO DH 10 DH 10 I DH 11 DH 11 I Activation hoses Discharge hoses FH-2PO FH-2POH POLATCU FH-15CO DH 15 DH 15 I DH 16 DH 16 I FH-20HC UL-EX15547 FM-3053302 Discharge hoses Check valves DESRIPTION LIMITATIONS Is a combination of a thermal actuator and the 0.006 ft³ 0,180 liters pilot cartridge, all installed in a protective cabinet. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the electrical actuator. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the electrical actuator. Allows the gas from the master cylinder or pilot bottle to flow through them and actuate the various slave cylinder valves. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the “UF-MC-HC” - 27-01-2016 15m. Max. Distance between detector and the extinguishing system: 49.21 ft 30m. PAGE in UF-MC-HC 90, 91 & 92 Thread connection: 1/4" BSP 137 Thread connection: 1/4" BSP 139 Thread connection: 1/4" BSP 138 Thread connection: 1/4" BSP 138 Thread connection: 1/4" BSP 138 Thread connection: 1/4" BSP 140 Container valve: 1/4 BSP body: 1/8-27NFPT 140 Thread connection: 1/4" BSP 140 Thread connection: 1/4" BSP 140 Container valve: W21,7x1/14” Check valve: 1/2" BSP Container valve: W21,7x1/14” Check valve: 1/2" BSP Container valve: W21,7x1/14” Check valve: 1/2" BSP Container valve: W21,7x1/14” Check valve: 1/2" BSP Container valve: W21,7x1/14” Check valve: 1/2" BSP Container valve: 3/4” BSP 126 127 127 127 128 130 223/239 PART NUMBER FAMILY DH 20 DH 20 I DH 21 DH 21 I FH-25HC FH-40HC FH-50HC FH-80HC FH-80HC34 FH-81HC FH-81HC34 VALAN-15CO VALAN-15CO VF VALAN-20A VALAN-21A VALAN-40-23 UL-EX15547 FM-3053302 Check valves Diaphram valve DESRIPTION LIMITATIONS nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Discharge hose which connects the container valve with the nozzle pipe web or with the check valve of the manifold. Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Check valve: 3/4" BSP Container valve: 3/4” BSP Check valve: 3/4" BSP Container valve: 3/4” BSP Check valve: 3/4" BSP Container valve: 3/4” BSP Check valve: 3/4" BSP Container valve: 3/4” BSP Check valve: 3/4" BSP Container valve: 1” BSP Check valve: 1" BSP Container valve: 1 1/2” BSP Check valve: 1 1/2" BSP Container valve: 2” BSP Check valve: 2" BSP Container valve: 3” Grooved Check valve: 3" Grooved Container valve: 3” Grooved Check valve: 3" Grooved Container valve: 3” Grooved Check valve: 3" Grooved Container valve: 3” Grooved Check valve: 3" Grooved “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 129 129 130 130 131 132 132 133 133 134 134 Hose connection: 1/2" BSP 145 Hose connection: 1/2” BSP 145 Hose connection: 3/4” BSP 144 Hose connection: 3/4” BSP 144 Hose connection: 1 1/2” BSP 143 224/239 PART NUMBER FAMILY VALAN-50-125 VALAN-80 CVAD15 VALAN-WFR8 Non return valves VALAN-WFR8-316 Non return valves Shuttle valve VALAN-62 227VALAN-40-23L 227VALAN-50-125L In line check valves 227VALAN-80L In line check valves In line check valves POAD20HH Loca Adapters POAD25HH Loca POAD40HH Loca POAD50HH Loca UL-EX15547 FM-3053302 Adapters Adapters DESRIPTION Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Connected between the discharge hose and the manifold, allows the gas flow from the hose to the manifold. Connected between the discharge hose and the VALAN-15COVF, allows the gas flow from the hose to the manifold and the eslave cylinders. Used in some pneumatically activated systems. Normally fitted between the discharge hoses and the cylinder bank. Made in inox steel AISI 303. Used in some pneumatically activated systems. Normally fitted between the discharge hoses and the cylinder bank. Made in inox steel AISI 316. It has the function of the union of two cylinders or pilot bottles. Used in systems, which because operation requirements, need 2 pilot bottles. They do not allow that the gas come back during the discharge of the main or reserve battery to the manifold of the battery which are not in use. They do not allow that the gas come back during the discharge of the main or reserve battery to the manifold of the battery which are not in use. They do not allow that the gas come back during the discharge of the main or reserve battery to the manifold of the battery which are not in use. Facilitates the connection between container valve and discharge pipe. Facilitates the connection between container valve and discharge pipe. Facilitates the connection between container valve and discharge pipe. Facilitates the connection between container valve and “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC Hose connection: 2” BSP 143 Hose connection: 3” Grooved 142 Hose connection: 1/2” BSP 146 Connections: 1/4" BSP 150 & 151 Connections: 1/4" BSP 150 & 151 Connections: 1/4" BSP 152 Pipe connection: 1 1/2" BSP 147 Pipe connection: 2" BSP 148 Pipe connection: 3" Grooved 149 3/4" BSP 135 1" BSP 135 1 1/2" BSP 135 2" BSP 135 225/239 PART NUMBER FAMILY discharge pipe. Facilitates the connection between discharge hose and discharge pipe. Facilitates the connection between discharge hose and discharge pipe. Facilitates the connection between discharge hose and discharge pipe. Facilitates the connection between discharge hose and discharge pipe. Facilitates the connection between discharge hose and discharge pipe. Facilitates the connection between container valve and discharge pipe. Facilitates the connection between container valve and discharge pipe. Facilitates the connection between the hose and the nozzle in terms of passage through a wall or sheet metal wall. Facilitates the connection between the hose and the nozzle in terms of passage through a wall or sheet metal wall. Facilitates the connection between the hose and the nozzle in terms of passage through a wall or sheet metal wall. Facilitates the connection between the hose and the nozzle in terms of passage through a wall or sheet metal wall. POAD15MH POAD20MH POAD25MH POAD40MH POAD50MH POAD40HH POAD50HH POADPM10 POADPM15 POADPM20 POADPM25 Makes the connection between the outlet of the container valve and the flexible activation hose or copper tube. POA8CU POA218 POA21CU POADT8CU 100M008UFA UL-EX15547 FM-3053302 DESRIPTION Adapters Pilot cartridge & pilot cylinders Makes the connection between the outlet of the container valve and the flexible activation hose or copper tube. Makes the connection between the outlet of the container valve and the flexible activation hose or copper tube. Makes the connection between the outlet of the container valve and the flexible activation hose or copper tube. Pilot cartridge filled up to 2175 psi (150 bar) “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC 1/2" BSP 135 3/4" BSP 135 1" BSP 135 1 1/2" BSP 135 2" BSP 135 1 1/2" BSP 135 2" BSP 135 1/4" BSP 136 1/2" BSP 136 3/4" BSP 136 1" BSP 136 1/4" BSP to Cupper pipe 156 W21,7x1/14” to 1/4" BSP 156 W21,7x1/14” to Cupper pipe 156 Bicone 156 0.003 ft³ (0.080 liters) See annex 3 226/239 PART NUMBER FAMILY DESRIPTION LIMITATIONS 0.006 ft³ ( 0.180 liters) 0.07 ft³ (2 liters) See annex 3 0.07 ft³ (2 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 Pilot cartridge & pilot cylinders Weighing device Pilot cartridge filled up to 2175 psi (150 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) PAGE in UF-MC-HC See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.24 ft³ (6.7 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 100M018UFA 100M2UFV-1 100M2UFV-2 100M6UFJ-1 100M6UFJ-2 100M6UFV-1 100M6UFV-2 100M6UFJ-3 100M6UFJ-4 100M6UFV-3 100M6UFV-4 100M13UFV-1 100M13UFV-2 100M13UFB-3 100M13UFB-4 100M13UFJ-1 100M13UFJ-2 UL-EX15547 FM-3053302 “UF-MC-HC” - 27-01-2016 227/239 PART NUMBER FAMILY Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175 psi (100 / 120 / 150 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) Pilot cylinder filled at 1450, 1740, 2175, 2900 psi (100 / 120 / 150 / 200 bar) 100M13UFV-3 100M13UFV-4 100M13UFV-5 100M13UFV-6 Detects a small loss of agent's load extinguisher inside the cylinder (when loss between 0 and 5% of the agent). One weighing device controls one cylinder. SIEX-WD 3SE5 242-0HE10 XCK-T2121P16 GLE Weighing device Hazardous locations weighing device SIEX-WD-BX SIEX-WD-LX SIEX-WD-9007 SIEX-WD-802X SIEX-WD-ATEX SIEX-WD-871 SIEX-WD-E51 SIEX-WD-E52 UL-EX15547 FM-3053302 DESRIPTION Hazardous locations weighing device Brackets Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing device detects. Limit switch that send an electrical signal when the weighing “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 0.47 ft³ (13.4 liters) See annex 3 Max. permisible gross weight: 1252 lb (568 kg) Max. permisible net weight: 914 lb (415 kg) 100 & 101 103 103 103 104 105 106 107 108 109 110 111 228/239 PART NUMBER FAMILY n/a n/a 227CMS4280 227CMS42100 227CMS52100 227CMS52150 227CMS82100 227CMS82150 227CMS4380 227CMS43100 227CMS53100 227CMS53150 227CMS83100 227CMS83150 Manifolds Distributor for cylinder batteries. Distributor for cylinder batteries. Discharge indicator POID66L POID156L POID66I Discharge indicator Pressure switch POID156I POINPRE 6-6L POINPRE 15-6L UL-EX15547 FM-3053302 Pressure switch DESRIPTION LIMITATIONS PAGE in UF-MC-HC device detects. Fix the cylinders firmly to a solid surface, either a wall or a floor or both, in order to prevent slippage during discharge. Allows multiple bottles to be connected to a piping network. n/a From 113 to 125 n/a 183 Allows multiple bottles to be connected to a piping network. 3” NPT 184 Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Allows multiple bottles to be connected to a piping network. Detects the discharge of the extinguishing agent when this one takes place and give a visual signal. Manual reset. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and give a visual signal. Manual reset. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and give a visual signal. Manual reset. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and give a visual signal. Manual reset. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this 4” NPT 4” NPT 6” NPT 4” NPT 6”NPT 3” NPT 4” NPT 4” NPT 6” NPT 4” NPT 6”NPT Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP “UF-MC-HC” - 27-01-2016 184 184 184 184 184 184 184 184 184 184 184 101 101 101 101 101 101 229/239 PART NUMBER POINPRE 6-40L POINPRE 15-40L POINPRE 6-6I POINPRE 15-6I POINPRE 6-40I POINPRE 15-40I POINPRE-GLE 6-6L POINPRE-GLE 15-6L POINPRE-GLE 6-40L POINPRE-GLE 15-40L POINPRE-GLE 6-6I UL-EX15547 FM-3053302 FAMILY DESRIPTION LIMITATIONS Hazardous locations pressure switch one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 101 101 101 101 101 101 101 94 94 94 94 230/239 PART NUMBER FAMILY POINPRE-GLE 15-6I POINPRE-GLE 6-40I POINPRE-GLE 15-40I POINPRE-BX 6-6L POINPRE-BX 15-6L POINPRE-BX 6-40L POINPRE-BX 15-40L POINPRE-BX 6-6I POINPRE-BX 15-6I POINPRE-BX 6-40I POINPRE-BX 15-40I UL-EX15547 FM-3053302 Hazardous locations pressure switch Hazardous locations pressure switch DESRIPTION LIMITATIONS one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 94 94 94 95 95 95 95 95 95 95 95 231/239 PART NUMBER FAMILY POINPRE-LX 6-6L POINPRE-LX 15-6L POINPRE-LX 6-40L POINPRE-LX 15-40L POINPRE-LX 6-6I POINPRE-LX 15-6I Hazardous locations pressure switch Hazardous locations pressure switch POINPRE-LX 6-40I POINPRE-LX 15-40I POINPRE-9007 6-6L POINPRE-9007 15-6L POINPRE-9007 6-40L UL-EX15547 FM-3053302 Hazardous locations pressure switch Hazardous DESRIPTION LIMITATIONS one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 95 95 96 96 96 96 96 96 97 97 97 232/239 PART NUMBER FAMILY DESRIPTION locations pressure switch one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this POINPRE-9007 15-40L POINPRE-9007 6-6I POINPRE-9007 15-6I POINPRE-9007 6-40I POINPRE-9007 15-40I POINPRE-802X 6-6L POINPRE-802X 15-6L POINPRE-802X 6-40L POINPRE-802X 15-40L POINPRE-802X 6-6I POINPRE-802X 15-6I UL-EX15547 FM-3053302 Hazardous locations pressure switch Hazardous locations pressure switch LIMITATIONS Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 97 97 97 97 97 98 98 98 98 98 98 233/239 PART NUMBER FAMILY POINPRE-802X 6-40I POINPRE-ATEX 15-40I POINPRE-ATEX 6-6L POINPRE-ATEX 15-6L POINPRE-ATEX 6-40L POINPRE-ATEX 15-40L POINPRE-ATEX 6-6I POINPRE-ATEX 15-6I POINPRE-ATEX 6-40I POINPRE-ATEX 15-40I POVV8 UL-EX15547 FM-3053302 Hazardous locations pressure switch Bleed valve DESRIPTION LIMITATIONS one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Brass. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Detects the discharge of the extinguishing agent when this one takes place and send an electrical signal. Manual reset. Two contacts, NO/NC. Made in Inox steel. Depressurizes manually the release line once the pneumatic Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/4" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/2" BSP Activation pressure: 90±30 psi (6 ± 2 Bar) Connection thread: 1/4" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) Connection thread: 1/2" BSP Activation pressure: 580 ± 120 psi (40 ± 8 Bar) n/a “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 98 98 99 99 99 99 99 99 99 99 182 234/239 PART NUMBER D15 FAMILY Odorizers D20 VREC Odorizers Pressure relief valves VREC-O Pressure relief valves Pneuatic siren CSIRN Isolated valve SVD20 Selector valves SVD25 SVD32 SVD50 SVD65 SVD80 SVD100 UL-EX15547 FM-3053302 heads are actuated. Avoids the small leakages in the pilot line. Alerts the presence of the agent, pervading of a strong smell the area where the discharge is happening. Alerts the presence of the agent, pervading of a strong smell the area where the discharge is happening. Avoids an over pressure in the manifold can occur when we have selector valves or disable device valves installed in the manifold that can blocks the discharge. Avoids an over pressure in the manifold can occur when we have selector valves or disable device valves installed in the manifold that can blocks the discharge. It will give out and audible alarm during the discharge. SVA6-3W SVD40 DESRIPTION Selector valves Disable device valves Isolate the pilot bottle release line in cylinder bank systems. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC Thread connection: 1/2" BSP 188-189 Thread connection: 3/4" BSP 188-189 Burst pressures: 870 – 1595 – 3050 – 4500 – 5080 – 6240 psi 185 & 186 (60 – 110 – 210 – 310 – 350 – 430 bar) Burst pressures: 870 – 1595 – 3050 – 4500 – 5080 – 6240 psi 185 & 186 (60 – 110 – 210 – 310 – 350 – 430 bar) 1450 Psi (100 Bar) 1740 Psi (120 Bar) 2180 Psi (150 Bar) 2900 Psi (200 Bar) 1/4" BSP 187 181 3/4” BSP or NPT or welded From 165 to 171 1” BSP or NPT or welded From 165 to 171 1 1/4” BSP or NPT or welded From 165 to 171 1 1/2” BSP or NPT or welded From 165 to 171 2” BSP or NPT or welded From 165 to 171 2 1/2” BSP or NPT or welded From 165 to 171 3” BSP or NPT or welded From 165 to 171 4” BSP or NPT or welded From 165 to 171 235/239 PART NUMBER FAMILY SVD20SH SVD25SH SVD32SH SVD40SH SVD50SH SIEX-SVS SVA6 SVA20 SVA25 SVA32 SVA40 SVA50 SVA65 SVA80 SVA100 SVA20SH UL-EX15547 FM-3053302 Disable device valves Disable device valves DESRIPTION cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Used to protect several risks at the same time with a single cylinder bank or modular cylinder. Electrical-manual actuator for selector valves that gives way to the N2 who comes from the pilot bottle to activate the selector valve. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC 3/4” BSP or NPT or welded From 165 to 171 1” BSP or NPT or welded From 165 to 171 1 1/4” BSP or NPT or welded From 165 to 171 1 1/2” BSP or NPT or welded From 165 to 171 2” BSP or NPT or welded From 165 to 171 From 169 to 171 1/4” BSP or NPT From 172 to 180 3/4” BSP or NPT From 172 to 180 1” BSP or NPT From 172 to 180 1 1/4” BSP or NPT From 172 to 180 1 1/2” BSP or NPT From 172 to 180 2” BSP or NPT From 172 to 180 2 1/2” BSP or NPT From 172 to 180 3” BSP or NPT From 172 to 180 4” BSP or NPT From 172 to 180 3/4” BSP or NPT From 172 to 180 236/239 PART NUMBER FAMILY protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. SVA25SH Used to prevent extinguishing gas discharging into the protected area when not required. SVA32SH SVA40SH SVA50SH SVAFC SVAGLC SVAFC-BX Disable device valves Monitoring of selector and disable device valves for Hazardous locations SVAFC-LX SVAFC-9007 SVAFC-802X SVAFC-871 SVAFC-ATEX Monitoring of selector and disable device valves for Hazardous locations Discharge nozzles FEDRXX FEDRXXA FEDRXXB FEDRXXI UL-EX15547 FM-3053302 DESRIPTION Discharge nozzles Calibrated plate Used to prevent extinguishing gas discharging into the protected area when not required. Used to prevent extinguishing gas discharging into the protected area when not required. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. Detects at every moment the status of the selector or disable device valve (open or close). It has two contacts, NO and NC. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as “UF-MC-HC” - 27-01-2016 LIMITATIONS PAGE in UF-MC-HC 1” BSP or NPT From 172 to 180 1 1/4” BSP or NPT From 174 to 179 1 1/2” BSP or NPT From 174 to 179 2” BSP or NPT From 174 to 179 3A – 24 VDC – IP65 175 3A -IP65 175 176 177 177 178 178 179 Made in Carbonated steel. 360º From 3/8” to 2 1/2" BSP Made in Aluminum. 360º From 3/8” to 2 1/2" BSP Made in Brass. 360º From 3/8” to 2 1/2" BSP Made in Inox steel AISI 303. 360º 159 & 163 159 & 163 159 & 163 159 & 163 237/239 PART NUMBER FAMILY FEDRXXI360 FEDRXX180 FEDRXX180A FEDRXX180B FEDRXX180I FEDRXX180I360 POPCXXB POPCXXI POSEÑALES CGAC21 CGAC20 CGAC25 CGAC40 CGAC50 CGAC80 UFPA-11-4 UFPA-20 UFPA-40 UL-EX15547 FM-3053302 Calibrated plate Signals Adapters for filling cylinders Adapters for filling cylinders Replacement parts Adapters for filling cylinders Adapters for filling cylinders Replacement parts Replacement DESRIPTION LIMITATIONS homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. It discharges the extinguishing agent inside the hazard area as homogeneously as possible to achieve efficient extinguishing. Located inside the discharge nozzles in order to control the exact amount of gas to be discharged. Orifice calibrated. Located inside the discharge nozzles in order to control the exact amount of gas to be discharged. Orifice calibrated. From 3/8” to 2 1/2" BSP Made in Inox steel AISI 316. 360º From 3/8” to 2 1/2" BSP Made in Carbonated steel. 180º From 3/8” to 2 1/2" BSP Made in Aluminum. 180º From 3/8” to 2 1/2" BSP Made in Brass. 180º From 3/8” to 2 1/2" BSP Made in Inox steel AISI 303. 180º From 3/8” to 2 1/2" BSP Made in Inox steel AISI 316. 180º From 3/8” to 2 1/2" BSP Made in Brass From 3/8” to 2 1/2" Made in Inox steel From 3/8” to 2 1/2" Advises the personnel that they are entering an area protected by an automatic extinguishing system. Device which make easier the filling of the cylinder. Device which make easier the filling of the cylinder. Device which make easier the filling of the cylinder. Device which make easier the filling of the cylinder. Device which make easier the filling of the cylinder. Device which make easier the filling of the cylinder. Replacement of the piston assembly of the container valve. Replacement of the piston assembly of the container valve. Replacement of the piston assembly of the container valve. “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC 159 & 163 159 & 163 159 & 163 159 & 163 159 & 163 159 & 163 164 164 n/a 190 RGS-MAM-11-4/12-4 RGS-MAM-20 UF-MM-HC (34) UF-MM-HC (34) RGS-MAM-40 UF-MM-HC (34) RGS-MAM-40 UF-MM-HC (34) RGS-MAM-50 RGS-MAM-80 RGS-MAM-11-4/12-4 RGS-MAM-20 RGS-MAM-40 UF-MM-HC (34) UF-MM-HC (34) UF-MM-HC (38) UF-MM-HC (38) UF-MM-HC (38) 238/239 PART NUMBER FAMILY DESRIPTION LIMITATIONS UFPA-50 UFPA-80 UFOB-T1-41071-06D UFOB-T1-TOOL parts Replacement of the piston assembly of the container valve. Replacement of the piston assembly of the container valve. Replacement of the valve core of the container valve. Tool to be able to replace the valve core. RGS-MAM-50 RGS-MAM-80 n/a n/a UL-EX15547 FM-3053302 Replacement parts “UF-MC-HC” - 27-01-2016 PAGE in UF-MC-HC UF-MM-HC (38) UF-MM-HC (38) UF-MM-HC (38) UF-MM-HC (38) 239/239 ACTUATOR MONITORING DEVICE uf-amd-siex RV.01 (12-06-2017) SIEX-HCTM 227 at 360 & 610 psi (25 & 42 bar) HFC-227ea SIEX-HCTM S-FLOW at 464, 493, 725 & 798 psi (32, 34, 50 & 55 bar) HFC-227ea SIEX-CO2TM INERT-SIEXTM 01 (Ar) at 2900 & 4350 psi (200 & 300 bar) IG-01 INERT-SIEXTM 55 (Ar+N2) at 2900 & 4350 psi (200 & 300 bar) IG-55 INERT-SIEXTM 100 (N2) at 2900 & 4350 psi (200 & 300 bar) IG-100 INERT-SIEXTM 541 (Ar+N2+CO2) at 2900 & 4350 psi (200 & 300 bar) IG-541 SIEX-NCTM 1230 at 360 & 610 psi (25 & 42 bar) FK-5-1-12 SIEX-NCTM 1230 S-FLOW at 464, 493, 725 & 798 psi (32, 34, 50 & 55 bar) FK-5-1-12 INERT-SIEXTM CFT–01 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-01 INERT-SIEXTM CFT–55 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-55 INERT-SIEXTM CFT–100 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-100 INERT-SIEXTM CFT–541 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-541 2 “uf-AMD-SIEX” 12/06/17 INDEX ACTUATOR MONITORING DEVICE........................................................................................................................4 1. ACTUATOR MONITORING DEVICE ...................................................................................................................7 1.1. DESCRIPTION.....................................................................................................................................................................7 1.2. OPERATION ........................................................................................................................................................................8 1.3.INSTALLATION INSTRUCTIONS....................................................................................................................................... 9 1.4.ENGINERING SPECIFICATIONS....................................................................................................................................... 10 2. END OF LINE DIODE RESISTOR (EOLR)............................................................................................................11 2.1. SELECTION OF THE EOLR DIODE................................................................................................................................... 11 2.2. INSTALLATION OF THE EOLR DIODE WITH THE 227AMD........................................................................................ 11 3. MAINTENANCE................................................................................................................................................11 NOTICE: Operation of Actutation Monitoring Device shall cause the annunciation of a supervisory signal at a required operator interface for the releasing service fire alarm control panel. “uf-AMD-SIEX” 12/06/17 3 ACTUATOR MONITORING DEVICE This Bulletin describes the components which monitor any actuator head of an SIEX Extinguishing System. These components are shown as such. The use of an Actuator Monitoring Device in combined operation with an electrical actuator are required to meet requirements in NFPA 2001. The Actuator Monitoring Device will monitor the extinguishing system when it is being serviced or under maintenance. Electrically operated actuator head(s) are never to be removed when the extinguishing system is armed. If the actuator head is removed from a system component during service or maintenance, it must be placed back in its original condition when maintenance is completed. This Bulletin is a supplement of the SIEX fixed fire extinguishing systems indicated below. INERT-SIEXTM 01 (Ar) at 2900 & 4350 psi (200 & 300 bar) IG-01 SIEX-CO2 SIEX-HCTM S-FLOW at SIEX-HCTM 227 at 360 464, 493, 725 & 798 psi & 610 psi (25 & 42 bar) (32, 34, 50 & 55 bar) HFC-227ea HFC-227ea This Bulletin serves as a supplement to the following SIEX Design Installation, Operation and Maintenance Manuals. It is not intended to replace the requirements and limitations therein. The information contained in this Bulletin will be added to the Manual at the next revision. 4 MANUAL REV UL LISTED FM APROVED INSTALLATION MANUALP/N UF_MI_HC 08/02/2016 EX15547 3053302 DESIGN MANUALP/N UF_MD_HC 05/02/2016 EX15547 3053302 COMPONENTS MANUALP/N UF_MC_HC 27/01/2016 EX15547 3053302 MAINTENACE MANUALP/N UF_MM_HC 08/02/2016 EX15547 3053302 INSTALLATION MANUALP/N UF_MI_HC 08/02/2016 EX15547 3053302 DESIGN MANUALP/N UF_MD_HC 05/02/2016 EX15547 3053302 COMPONENTS MANUALP/N UF_MC_HC 27/01/2016 EX15547 3053302 MAINTENACE MANUALP/N UF_MM_HC 08/02/2016 EX15547 3053302 INSTALLATION MANUALP/N UF_MI_CO2 - EX16320 3054767 DESIGN MANUALP/N UF_MD_CO2 - EX16320 3054767 COMPONENTS MANUALP/N UF_MC_CO2 - EX16320 3054767 MAINTENACE MANUALP/N UF_MM_CO2 - EX16320 3054767 INSTALLATION MANUALP/N UF_MI_IG01 10/03/2016 EX26702 3055596 DESIGN MANUALP/N UF_MD_IG01 10/03/2016 EX26702 3055596 COMPONENTS MANUALP/N UF_MC_IG01 10/03/2016 EX26702 3055596 MAINTENACE MANUALP/N UF_MM_IG01 10/03/2016 EX26702 3055596 “uf-AMD-SIEX” 12/06/17 INERT-SIEXTM CFT–01 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-01 SIEX-NCTM 1230 S-FLOW at 464, 493, 725 & 798 psi (32, 34, 50 & 55 bar) FK-5-1-12 SIEX-NCTM 1230 at 360 & 610 psi (25 & 42 bar) FK-5-1-12 INERT-SIEXTM 541 INERT-SIEXTM 100 (N2) (Ar+N2+CO2) at 2900 & 4350 psi at 2900 & 4350 psi (200 & 300 bar) IG-100 (200 & 300 bar) IG-541 INERT-SIEXTM 55 (Ar+N2) at 2900 & 4350 psi (200 & 300 bar) IG-55 MANUAL REV UL LISTED FM APROVED INSTALLATION MANUALP/N UF_MI_IG55 10/03/2016 EX26702 3055596 DESIGN MANUALP/N UF_MD_IG55 10/03/2016 EX26702 3055596 COMPONENTS MANUALP/N UF_MC_IG55 10/03/2016 EX26702 3055596 MAINTENACE MANUALP/N UF_MM_IG55 10/03/2016 EX26702 3055596 INSTALLATION MANUALP/N UF_MI_IG100 10/03/2016 EX26702 3055596 DESIGN MANUALP/N UF_MD_IG100 10/03/2016 EX26702 3055596 COMPONENTS MANUALP/N UF_MC_IG100 10/03/2016 EX26702 3055596 MAINTENACE MANUALP/N UF_MM_IG100 10/03/2016 EX26702 3055596 INSTALLATION MANUALP/N UF_MI_IG541 10/03/2016 EX26702 3055596 DESIGN MANUALP/N UF_MD_IG541 10/03/2016 EX26702 3055596 COMPONENTS MANUALP/N UF_MC_IG541 10/03/2016 EX26702 3055596 MAINTENACE MANUALP/N UF_MM_IG541 10/03/2016 EX26702 3055596 INSTALLATION MANUALP/N UF_MI_NC - EX15547 XXXXXX DESIGN MANUALP/N UF_MD_NC - EX15547 XXXXXX COMPONENTS MANUALP/N UF_MC_NC - EX15547 XXXXXX MAINTENACE MANUALP/N UF_MM_NC - EX15547 XXXXXX INSTALLATION MANUALP/N UF_MI_NC - EX15547 XXXXXX DESIGN MANUALP/N UF_MD_NC - EX15547 XXXXXX COMPONENTS MANUALP/N UF_MC_NC - EX15547 XXXXXX MAINTENACE MANUALP/N UF_MM_NC - EX15547 XXXXXX INSTALLATION MANUALP/N UF_MI_CFT-01 Rev.00 EX27097 - DESIGN MANUALP/N UF_MD_CFT-01 Rev.00 EX27097 - COMPONENTS MANUALP/N UF_MC_CFT-01 Rev.00 EX27097 - MAINTENACE MANUALP/N UF_MM_CFT-01 Rev.00 EX27097 - SOLENOID MONITORING DEVICE MANUAL SUPPLEMENT P/N UF-SIEX-CFT_Solenoid Monitoring Device Rev.00 11/03/2016 EX27097 - “uf-AMD-SIEX” 12/06/17 5 INERT-SIEXTM CFT–541 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-541 INERT-SIEXTM CFT–100 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-100 INERT-SIEXTM CFT–55 (CONSTANT FLOW TECHNOLOGY) AT 2900 & 4350 PSI (200 & 300 BAR) – IG-55 MANUAL REV UL LISTED FM APROVED INSTALLATION MANUALP/N UF_MI_CFT-55 Rev.00 EX27097 - DESIGN MANUALP/N UF_MD_CFT-55 Rev.00 EX27097 - COMPONENTS MANUALP/N UF_MC_CFT-55 Rev.00 EX27097 - MAINTENACE MANUALP/N UF_MM_CFT-55 Rev.00 EX27097 - SOLENOID MONITORING DEVICE MANUAL SUPPLEMENT P/N UF-SIEX-CFT_Solenoid Monitoring Device Rev.00 11/03/2016 EX27097 - INSTALLATION MANUALP/N UF_MI_CFT-100 Rev.00 EX27097 - DESIGN MANUALP/N UF_MD_CFT-100 Rev.00 EX27097 - COMPONENTS MANUALP/N UF_MC_CFT-100 Rev.00 EX27097 - MAINTENACE MANUALP/N UF_MM_CFT-100 Rev.00 EX27097 - SOLENOID MONITORING DEVICE MANUAL SUPPLEMENT P/N UF-SIEX-CFT_Solenoid Monitoring Device Rev.00 11/03/2016 EX27097 - INSTALLATION MANUALP/N UF_MI_CFT-541 Rev.00 EX27097 - DESIGN MANUALP/N UF_MD_CFT-541 Rev.00 EX27097 - COMPONENTS MANUALP/N UF_MC_CFT-541 Rev.00 EX27097 - MAINTENACE MANUALP/N UF_MM_CFT-541 Rev.00 EX27097 - SOLENOID MONITORING DEVICE MANUAL SUPPLEMENT P/N UF-SIEX-CFT_Solenoid Monitoring Device Rev.00 11/03/2016 EX27097 - NOTE: It is the responsibility of your company to verify that this information has been received by the employees who currently hold valid certification credentials for design and or service of the system(s) referenced in this Bulletin. All fixed extinguishing systems manufactured by SIEX, are custom designed for a specific application. If the components described here are assembled with any other manufacturer’s components, or are used for another application not described in this manual, the component operation will not be correct. In this case, SIEX does not guarantee nor will be responsible for the improper use or application of the product. Any non-approved use or application and/or any non-approved modification of the product or its operation may result in serious accidents and/or personal injury. SIEX is not responsible for any non-approved use or application. 6 “uf-AMD-SIEX” 12/06/17 1. ACTUATOR MONITORING DEVICE 1.1. DESCRIPTION The AMD has an integral micro pointer switch that operates when the AMD is secured to the electrical activated head or any type of electrically actuated device. It is used to detect, at every moment, the status of the electrical actuator or any other activation head if it is in contact or disconnected from the actuation device. When the electrical actuator is disconnected the micro switch sends an electrical signal to the control panel displaying extinguishing systems status information. The AMD can be install in all types of cylinders for the extinguishing system. Because the AMD is designed to be mounted in any activation head (pneumatic, manual, electrical…) or only in a cylinder with electrical actuator, it can monitor all of the cylinders in the systems. The AMD for electric actuator on discharge valve control head is in compliance with the requirements of NFPA 2001-2012, UL 2166, UL 2127 and FM5600. ACTUACTOR MONITORING DEVICE Box Normally Open (N.O.) Normally Closed (N.C.) Brass 227AMD 227AMDC Aluminum* 227AMDA 227AMDAC Location 227SOL/ 227SOLR/ 227SOLC/ 227SOLCR/ 227SOLC125/ 227SOLCR125 / 227CN / 227DM /227DMR / 227CNM TK-Simplex / TK-Simplex-B / TK-Simplex-C / TK-complex / TKcomplex-B / TK-complex-C KCTM / KCTM-R / KCTM-C Tension 24V (DC) 0.3A Certifications UL/FM * This is not part of th UL Listed. Electrical actuator Pneumatic actuator Manual actuator or Pneumatic and manual actuator “uf-AMD-SIEX” 12/06/17 7 1.2. OPERATION The AMD is designed to monitor all types of valves:: ∆∆ RGS-MAM-11-4/12-4 (Pilot bottles) ∆∆ RGS-MAM-03B/03C (pilot cartridges & selector valves) ∆∆ RGS-MAM-20/40/50/80 (HFC-227ea & FK-5-1-12) ∆∆ RGS-MAM-11-1/12-1/12-1C (Co₂) ∆∆ RGS-MAM-11-2/12-2/12-2C (IG-01/55/100/541 at 200bar) ∆∆ RGS-MAM-11-3/12-3/12-3C (IG-01/55/100/541 at 300bar) The AMD is installed on the head actuation in its correct position until it stops, it must be threaded by hand, It is not necessary to tighten with a tool. The AMD is designed for monitoring the position of the electrical actuator in a pilot bottle, pilot cartridge (see Image 1) or master cylinder (this is mandatory for complying the UL, FM and NFPA requirements), or for monitoring all the valves of the cylinder battery assembled in all pneumatic actuator head (See Image 2). This is only one option. SIEX, as experts in extinguishing equipment, recommends it as a safety measure. It allows the operator to monitored. EEDactivation of all the cylinders and confirm the cylinders are always monitored. Optional Optional Optional Optional Required Image 2 227CO/TE 227DMS 227CN 227SOL 227AMD 227AMD RGS-MAM-11/12 RGS-MAM-11/12 RGS-MAM-03B/C Image 1 Pilot Cartridge 8 “uf-AMD-SIEX” 12/06/17 Pilot Bottle In case of batteries with directional valves, it is necessary monitor all electrical actuators, the pilot bottle and in each electrical actuator in the Selector cabinet for the selector valves (see image 3), as it is necessary to monitor the activation of the selector valve(s). 1.3.INSTALLATION INSTRUCTIONS The process to install the AMD in the valves is the same as the installation of the electrical actuator with which it is mounted; see Installation Manual of the relevant extinguishing agent. The AMD must be threaded by hand, it is not necessary to tighten with a tool. Once the installation and manual tightening of the electrical actuator on the valve is finished the top steel security ring can be removed, breaking the security seal. After that the AMD device can be rotated to the desired position, It can be installed in any position (See Image 4), loosen the AMD with a block screw and turn the valve around, It is only necessary to unscrew the block screw a few turns, no need to remove this screw, when the AMD is placed in the desired position, tighten the screw again (See Image 5). It is advisable to store the security ring for disassembly when necessary. X X Y Y Required X X Y Electrical activation circuit Y Image 3 Image 4 Security ring Supervision 227AMD circuit Image 5 Required AMD + 227SOL/SOLR Block srew “uf-AMD-SIEX” 12/06/17 9 1.4. ENGINERING SPECIFICATIONS To install the wiring of AMD, the next instructions must be followed: 1. Connect one of the brown leads to the supervision zone on the Fire Alarm Control Panel. The remaining brow and blue leads can be connected to the AMD or at the End Of Line Resistor (EOLR) (See Point 2 to EOLR information) 2. Connect one of the blue leads to the supervision zone on the Fire Alarm Control Panel. It can be connected to the next 227AMD or at the End Of Line Resistor (EOLR) (See Point 2 to EOLR information). It´s necessary differentiate between the electrical activation circuit and the AMD circuit. The AMD is only for supervision. They don´t share the same circuit in the Fire Alarm Control Panel. Image 6 10 “uf-AMD-SIEX” 12/06/17 The Actuator Monitoring Device AMD, shall be capable of switching the release output of a release panel to, either an armed system (under service system) or inactive system (disabled system). The unit works automatically if the activation head is correctly threaded into the valve, the system is armed. When you unscrew the activation head with the AMD, a signal must be appear in the control panel, to indicate the system is disabled. NOTICE: The connection for the supervisory circuit has 4 wires: 2 brown and 2 blue. ATTETION: It is necessary install the leads according Image 6, and install in a junction box the terminal block, after it install the leads in flex conduit/conduit. 2. END OF LINE DIODE RESISTOR (EOLR) 2.1. SELECTION OF THE EOLR DIODE The EOLR diode is used to supervise the 227AMD. This resistor must be selected according to the Fire alarm Control Panel and should be suitable to be used with that FACP. Please, check the electrical characteristics of the End Of Line Diode Resistor (EOLR) and the Fire Alarm Control Panel in order to be sure that the EOLR diode is suitable for use with that FACP. 2.2. INSTALLATION OF THE EOLR DIODE WITH THE 227AMD The EOLR must be installed in a Terminal Block with notched clamping plate, which is installed in Junction Box. For installation of the EOLR diode, follow the diagram in the respective chapter of the AMD Images in this document.. Some Fire Alarm Control Panels has the End Of Line Diode resistor integrated on them. In this case, the EOLR diode meets the electrical characteristics required by the Fire Alarm Control Panel. 3. MAINTENANCE This chapter describes the necessary maintenance working for the components described in this document. For general maintenance of the system, please, follow the instructions given in the relevant maintenance manual of each system. The following procedure is given for maintenance of these components: MONTHLY Check the status of the Actuator Monitoring Device: Inspect the AMD for damage, corrosion, and dirt. Check the Electrical Actuator for loose coupling and tighten if necessary. Replace the AMD if damaged. It is necessary to replace the entire actuator if the AMD have been damage. This test must be performed without discharging the extinguishing system. All actuators must be removed from the cylinders and pilot bottles prior to testing to prevent accidental cylinder discharge. “uf-AMD-SIEX” 12/06/17 11