Electrotechnics N5 Module 1: DC machines CONSTRUCTION The general construction of a four-pole dc generator or motor is shown below: www.futuremanagers.com Module 1: DC machines (continued) GENERATOR AND MOTOR PRINCIPLES There is no real difference between an electric generator and an electric motor. Consider a conductor lying in a magnetic field as shown in the figure. If the conductor is moved downwards, the emf is in such a direction that the current produced, sets up an upward force. In maintaining the motion against this force, work is done. Mechanical energy is converted into electrical energy and the apparatus is essentially an electric generator. www.futuremanagers.com Module 1: DC machines (continued) THE COMMUTATOR A commutator is a cylinder at one end of the armature formed by a large number of copper segments. The segments are insulated from each other and from the shaft by thin mica or micanite sheets and clamped together by insulated end rings. A sectioned view is illustrated. www.futuremanagers.com Module 1: DC machines (continued) ARMATURE WINDINGS Armature windings are distributed in slots over the circumference of the armature core. Armature windings can be divided into two groups depending on the manner in which the windings are connected to the commutator. The two groups are lap windings and wave windings. www.futuremanagers.com Module 1: DC machines (continued) FIELD COILS Direct current (dc) machines are named according to the method used to connect the field coils. A separately-excited machine is one in which the dc supply to the field coils is completely separate from the connections to the armature. www.futuremanagers.com Module 1: DC machines (continued) ARMATURE REACTION Armature reaction is the distortion of the main flux entering and leaving the armature, caused by the flux set up by armature conductors when they carry current. www.futuremanagers.com Module 1: DC machines (continued) CALCULATION OF DEMAGNITISING AND CROSS AMPERE-TURNS For every 360 electrical degrees there are 4π electrical degrees containing conductors that are responsible for the demagnetising of ampere-turns. ∴ Demagnetising ampere-turns per pole = (π‘ππ‘ππ ππππππ − π‘π’πππ /ππππ) × 1 = 2 www.futuremanagers.com 1 π × × π 2π × 4π 360 4π 360 Module 1: DC machines (continued) ARMATURE REACTION IN A DC MOTOR The direction of the armature current in a dc motor is opposite to that of the generated emf. It follows that in a dc motor, the flux is distorted backwards, and the brushes have to be shifted backwards if they are to be on the magnetic neutral axis when the machine is loaded. www.futuremanagers.com Module 1: DC machines (continued) COMPENSATING WINDING Ampere-turns per pole for compensating winding = 1 πΌ π πππ × × × ππππ 2 π 2π ππππ πππ‘πβ ππππππ ≈ 0,7 × πππππ‘π’ππ π‘π’πππ /ππππ www.futuremanagers.com Module 1: DC machines (continued) COMMUTATION Commutation is the reversal of the emf and current in the short-circuited coil during its transfer from one commutator segment to the next. Up to the instant of short-circuit, the coil has been carrying full-circuit current in one direction. The moment it leaves short-circuit, it must carry full-circuit current in the opposite direction. If the current has just reached its fully reversed value at the end of the short-circuit period, commutation is ideal. www.futuremanagers.com Module 1: DC machines (continued) TORQUE OF AN ELECTRIC MOTOR In a practical motor, the commutator and brushes ensure that the current through the armature conductor windings are always in such a direction, relative to the field set up by the field coils, that continuous, unidirectional forces are exerted on the armature conductors. The resulting unidirectional forces cause the armature to rotate. The magnitude of the resulting rotational force is referred to as the torque of the motor. www.futuremanagers.com Module 1: DC machines (continued) STARTING TORQUE AND ACCELERATION The value of the starting torque required, will depend largely on its duty. At the instant of starting there is no back emf as the rotor is at standstill and only the armature circuit resistance is there to limit the armature current. The current drawn at the instant of starting would be excessive. In order to limit the starting current, a reduced voltage must be supplied to the armature. www.futuremanagers.com Module 1: DC machines (continued) GRADING OF STARTING RESISTORS A common method of grading the resistance is based on a current-time diagram as in the figure below. Notching up is presumed to take place always when the current has fallen to a certain minimum value 12 , and the maximum current on each notch is taken to be 11 . www.futuremanagers.com Module 1: DC machines (continued) SPEED CHARACTERISTICS OF ELECTRIC MOTORS The speed characteristic of a motor represents the variation of speed with current. Its shape can be derived from: π − πΌπ π π π= π∅ www.futuremanagers.com Module 1: DC machines (continued) TORQUE CHARACTERISTICS OF ELECTRIC MOTORS The torque of a shunt motor is α armature current: Curves A, B and C in the figure show the relative shapes of torque curves for shunt series and compound motors which have the same full-load torque OQ with the same full-load armature current OP, the exact shape of curve C depending on the relative value of the shunt and series ampere-turns at full load. www.futuremanagers.com Module 1: DC machines (continued) SPEED CONTROL The speed of series motors may be controlled by varying the exciting current, but in this, the regulating resistance must be connected in parallel with the field winding. By these means, a varying amount of the total current can be diverted and the field winding can carry any desired fraction of the main current. www.futuremanagers.com Module 2: AC circuit theory ALTERNATING CURRENT In the case of alternating current the current reverses its direction at a constant rate. This occurs as a result of the constant reversal of polarity at the output terminals of the power supply. www.futuremanagers.com Module 2: AC circuit theory (continued) GENERATION OF A SINGLE-PHASE ALTERNATING EMF The emf can be represented by a sine wave, which represents a two pole generator with the armature rotating in an anticlockwise direction through a uniform magnetic field. www.futuremanagers.com Module 2: AC circuit theory (continued) AVERAGE AND EFFECTIVE OR RMS VALUE OF AN ALTERNATING QUANTITY The effective value of an alternating current is that value of alternating current, which produces the same amount of heat energy, at the same rate, as a direct current would, if passed through an identical resistance. www.futuremanagers.com Module 2: AC circuit theory (continued) NON-SINUSOIDAL WAVEFORM To find the average and/or effective value of a non-sinusoidal waveform, use is made of the midordinate rule. www.futuremanagers.com Module 2: AC circuit theory (continued) RESISTANCE IN AC CIRCUITS The current flowing through a pure resistor is governed by Ohm’s law for every instant of time, i.e. 1 = e/R for every point on the cycle. This means that the current waveform for a purely resistive circuit is exactly the same shape as the waveform of the applied pd and is in phase with it. www.futuremanagers.com Module 2: AC circuit theory (continued) INDUCTANCE IN AC CIRCUITS A self-induced emf is produced in an inductor whenever the current through it changes. When an alternating current flows through a pure inductor, the value of the current is continually changing and so produces a self-induced emf at every instant. www.futuremanagers.com Module 2: AC circuit theory (continued) CAPACITANCE IN AC CIRCUITS A capacitor is a device for storing electric charge. The charge on the plates is always proportional to the pd between them, thus, as this pd varies, current must flow either into or out of the capacitor in order to maintain the correct charge. The greater the rate of change of the pd, the greater will be the rate of change of current. www.futuremanagers.com Module 2: AC circuit theory (continued) THE SERIES CIRCUIT Consider a series circuit comprising a resistor R, an inductance L with an inductive reactance of XL , and a capacitor C with a capacitive reactance XC , connected across a supply voltage, V. The resulting current I will be common to all the components. www.futuremanagers.com Module 2: AC circuit theory (continued) SERIES PARALLEL CIRCUITS If circuits with impedances of Z1 , Z2 , etc, are connected in parallel: 1 1 1 = + π π1 π2 π1 π2 ∴π= π1 + π2 www.futuremanagers.com Module 2: AC circuit theory (continued) THREE-PHASE AC SYSTEMS When compared to single-phase systems, three-phase distribution has the following advantages: • Two voltage are available, and • For the same power rating, three-phase motors are smaller, cheaper, more efficient, operate at a better power factor, and are self-starting. • Only 87% of the amount of copper is required for the same output. www.futuremanagers.com Module 3: Transformers PRINCIPLES OF OPERATION OF A TRANSFORMER Transformers are used for raising or lowering the voltage in an ac circuit with a corresponding decrease or increase in the current. Essentially, a transformer is made up of a primary and secondary winding, electrically separate from each other, but magnetically coupled by means of an iron core. www.futuremanagers.com Module 3: Transformers (continued) CONSTRUCTION The construction of transformers is the simplest of all ac machines. The principal elements of a transformer are; • The magnetic circuit, • The windings, • the cooling system, and in larger transformers, • The oil tanks, and • Protection devices. www.futuremanagers.com Module 3: Transformers (continued) TRANSFORMER ON OPEN-CIRCUIT When connected to an ac supply with the secondary winding open-circuited, it acts simply as a highly inductive coil, and the current drawn is just sufficient to set up a flux which makes the emf of self inductance (neglecting the small resistance drop) equal and opposite to the supply pd. www.futuremanagers.com Module 3: Transformers (continued) USEFUL AND LEAKAGE FLUXES IN A TRANSFORMER The effect of leakage flux can be considered as being equivalent to two inductive reactances π1 and π2 in series with a transformer which has no leakage flux. www.futuremanagers.com Module 3: Transformers (continued) EQUIVALENT CIRCUIT OF A TRANSFORMER The behaviour of a transformer may be considered by assuming it to be equivalent to a transformer which has no losses and no magnetic leakage and an iron core, thus requiring no magnetising current, and then allowing for the imperfections of the transformer by means of additional impedances. www.futuremanagers.com Module 3: Transformers (continued) THREE-PHASE, CORE-TYPE TRANSFORMERS Modern large transformers are usually of the three-phase core-type shown below. Three similar limbs are connected by top and bottom yokes, each limb has the primary and secondary windings arranged concentrically. www.futuremanagers.com Module 3: Transformers (continued) PARALLEL OPERATION When operating two or more transformers in parallel, their satisfactory performance requires that they have: • The same voltage-ratio, • The same per-unit impedance, • The same polarity, and • The same phase-sequence and zero relative phase-displacement. www.futuremanagers.com Module 4: Measuring instruments CONSTRUCTION Essentially, most measuring instruments comprise: • A fixed field system, • A controlling system, • A damping system, and • A pointer attached to a moving system and pivoted in jewelled bearings. www.futuremanagers.com Module 4: Measuring instruments (continued) TYPES OF MEASURING INSTRUMENTS Ammeters and voltmeters are the most common and well-known of all measuring instruments. Power is measured by means of a wattmeter. A frequency meter is used to measure the frequency of ac cycles per second in an alternating current circuit. Power factor meters are used to measure the power factor of an alternating current circuit. www.futuremanagers.com Module 4: Measuring instruments (continued) MEASUREMENT OF POWER IN THREE-PHASE SYSTEMS Measuring power in three-phase systems is similar to measuring power in single-phase systems. Consider a star-connected, balanced load, with an accessible, neutral connection. The total power can be measured with a single wattmeter. www.futuremanagers.com Module 4: Measuring instruments (continued) RANGE EXTENSION Measuring instruments are mostly required to be connected to measure currents or voltages of values higher than their construction is able to allow them. In ac circuits, instrument transformers are invaluable in fulfilling this function. www.futuremanagers.com Module 5: AC machines INDUCTION MOTOR In an induction motor, there are no electrical connections between the stator and the rotor. The energy is transferred entirely magnetically, as in the case of a transformer, by means of the emf induced in the rotor conductors, by the rotating field set up by the stator windings. This principle of operation enables the motor to be manufactured as a simple, robust and efficient machine. www.futuremanagers.com Module 5: AC machines (continued) EXPRESSION FOR THE EMF OF AN ALTERNATOR Magnetic flux cutting a conductor in 1 revolution = Π€ × 2π Magnetic flux cutting a conductor in 1 second = 2ππΠ€ × π Average emf generated in 1 conductor = 2ππΠ€ volts www.futuremanagers.com Module 5: AC machines (continued) EFFECT OF DISTRIBUTING THE WINDING (DISTRIBUTOR FACTOR) By distributing the winding in two or more slots per pole per phase, the number of conductors per slot is reduced and the emf waveform is improved. emf with a distributed winding The ratio = emf with a concentrated winding is termed the distribution factor of the winding and may be represented by the symbol πΎπ . www.futuremanagers.com Module 5: AC machines (continued) SHORT-PITCH WINDING: PITCH FACTOR The waveform of the resultant emf generated in an alternator may be improved by making the coil pitch less than a pole pitch. With a full-pitch coil, the emf 's generated in the two sides are in phase with each other. When the coil is short-pitched by an angle ‘a’ electrical degrees, as shown below, the emf's generated in coil sides A and B differ in phase by an angle ‘a’. www.futuremanagers.com Module 5: AC machines (continued) GENERAL EXPRESSION FOR THE EMF OF AN ALTERNATOR If πΎπ = distribution factor of the winding, and πΎπ = pitch factor of the winding, then rms value of emf/phase = 2,22 πΎπ πΎπ ππΠ€. www.futuremanagers.com Module 5: AC machines (continued) SYNCHRONISING OF ALTERNATORS A represents an alternator connected to the bus-bars, and B is an alternator to be connected in parallel. To enable this to be done, the following conditions must be fulfilled: • The frequency of B must be the same as that of A. • The emf generated in B must be equal to the busbar voltage. • The emf of B must be in phase with the busbar voltage. www.futuremanagers.com Module 5: AC machines (continued) PARALLEL OPERATION OF ALTERNATORS Consider two similar single-phase alternators, A and B, connected in parallel to the busbars, and assume that there is no external load connected across the bus-bars: www.futuremanagers.com Module 5: AC machines (continued) THREE-PHASE MOTORS The operation of an induction motor is dependent on a rotating magnetic field which is established in the air gap of the motor by the stator currents. The manner in which the rotating magnetic field is established by a three-phase stator winding of a three-phase induction motor, may be illustrated by considering the direction of current flow through the three phases, at several successive instants. www.futuremanagers.com Module 5: AC machines (continued) PRINCIPLE OF OPERATION OF A THREE-PHASE INDUCTION MOTOR When the stator winding is energised from a three-phase supply, a rotating magnetic field is established, which rotates at synchronous speed. As the field sweeps across the rotor conductors, an emf is induced in them. Since the rotor circuit is completed, either through end rings, or slip-rings and external resistors, the induced emf causes a current to flow in the rotor conductors. The rotor conductors carrying current in the stator field thus have a force exerted upon them. www.futuremanagers.com Module 5: AC machines (continued) SPEED CONTROL BY POLE-CHANGING Two economical speeds can be obtained, one double the other, by arranging the stator windings so that the number of poles can be changed at will in some simple ratio, such as eight to four. www.futuremanagers.com Module 6: Generation and supply of AC power TRANSMISSION AND SUPPLY Power stations are often situated considerable distances from centres of power consumption. One of the main reasons that makes it practical and economically viable for power stations to be built far from consumers, is that it is relatively cheap and easy to transport the final product, in this case, electrical power. www.futuremanagers.com Module 6: Generation and supply of AC power (continued) RESISTANCE OF OVERHEAD LINES The resistance of a conductor is directly proportional to the length (β) of the conductor. Another factor which affects the resistance is the type of material (ρ) from which the conductor is manufactured. It can be said: π π = π www.futuremanagers.com Module 6: Generation and supply of AC power (continued) INDUCTANCE OF A SINGLE-PHASE OVERHEAD LINE An alternating current results in inductance in any conductor. Since transmission lines run for great distances, the inductance becomes problematic. L of conductor B only = 0,05 + 0,2 log π (π/π) ππ»/ππ The total inductance of the line = 0,1 + 0,4 log π (π/π) ππ»/πππ’π‘π ππ www.futuremanagers.com Module 6: Generation and supply of AC power (continued) INDUCTANCE OF A THREE-PHASE, THREE-WIRE OVERHEAD LINE The three conductors are said to be symmetrically spaced when their centres lie on the corners of an equilateral triangle. Let each side of the triangle be d metres long and the radius of each conductor, be r metres, then: πΏ πβ = 0,05 + 0,5log e (d/r)mH/km www.futuremanagers.com Module 6: Generation and supply of AC power (continued) CAPACITANCE OF A SINGLE-PHASE OVERHEAD LINE Capacitance is directly proportional to the area between two parallel conductors and inversely proportional to the distance between them. Because of the length of the conductors, the effective area is very large, which counteracts the large distance between the conductors. πΆ= 1 F/m, 36×109 ×logπ [(π−π)/π] www.futuremanagers.com line to line. Module 6: Generation and supply of AC power (continued) CAPACITANCE OF A SINGLE-PHASE, THREE-WIRE OVERHEAD LINE The total charging current between any conductor and the neutral plane is the phasor sum of two equal charging currents 120 degrees apart. The total equivalent capacitance between any conductor and the neutral plane is π πΆπ = 1/18. log π [( )/π]μF/km π www.futuremanagers.com