Uploaded by Khánh Phạm

VWE & VWVE Recloser Maintenance Manual

advertisement
Reclosers
Cooper Power Systems
Service Information
Types VWE and VWVE
Maintenance Instructions
S280-40-6
CAUTION
Do not energize this equipment out of
oil.
N
RADIATION
WARNING
Before performing electrical tests on
types VWE and VWVE Reclosers, refer
to Service Information S280-90-1.
Figure 1.
Type VWVE vacuum interrupting, three-phase, electronically controlled,
automatic circuit recloser.
CONTENTS
Introduction ..........................................2
Description and Operation .................2
General ...............................................2
Ratings ...............................................3
Electrical Ratings .............................3
Interrupting Ratings .........................3
Duty Cycle ........................................3
Mechanism Operation .........................4
Maintenance ..........................................5
Frequency of Maintenance ..................5
Periodic Maintenance Inspection ........5
Manual Operation of
the Recloser .....................................6
Mechanism in Oil .............................6
Mechanism Out of Oil ......................6
Insulation Withstand Tests ...................7
Oil Condition .........................................8
Current Transformers ....................18
Shop Maintenance Procedures ......... 8
Continuity Check .........................18
Bushings ........................................... 8
Ratio Test for Sensing CT’s .........18
Type VWE Bushings ....................... 8
Polarity Test for
Type VWVE Bushings .................... 10
Sensing CT’s ...........................18
Vacuum Interrupters ........................... 10
Output Test of Battery
Closing Solenoid Contactor................ 11
Charging CT ...........................18
Closing Solenoid ................................ 12
Closing Solenoid Fuse ....................... 13 Service Parts List ...............................20
Bushing Parts (Figure 30)..................21
Removing Mechanism From Head . 13
Head and Tank Assemblies
Re-lnstalling Mechanism
(Figure 31) .....................................23
Into Head ...................................... 14
Closing Coil Mechanism
Operation Checks.............................. 14
(Figure 32) .....................................25
Control Cable ................................ 14
Interrupter Mechanism
Circuit Components........................ 14
(Figure 33) ......................................27
Trip Solenoid................................ 18
Rotary Solenoid and
Closing Contactor .................... 18
Switches (SW1, SW2, SW3) . ..... 18
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction
for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a
problem not covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer.
March, 1983 • New Issue
1
INTRODUCTION
Service Information S280-40-6 provides
the maintenance instructions for Type
VWE and VWVE three-phase, electronically controlled, vacuum reclosers.
Included is a general description of the
recloser and its operation, instructions
for periodic inspection and routine maintenance, testing procedures, and instructions for shop repairs. A service parts
list, keyed to exploded-view drawings of
the recloser is included at the back of the
manual.
Procedures for testing the recloser
and control together are found in the
control installation manual S280-75-1.
DESCRIPTION
AND OPERATION
General
The Type VWE and VWVE reclosers, are
self-controlled devices that protect distribution lines and equipment. A complete
unit consists of the recloser, a Type ME
electronic control, and an interconnecting cable. Fault current sensing is provided by the control which actuates the
recloser. Circuit interruption is provided
by the recloser.
Figure 2.
Untanked Type VWE vaccum recloser.
2
The Type VWE and VWVE reclosers
trip open on overcurrent (either phase or
ground faults) and then reclose automatically. If the overcurrent is temporary the
automatic reclose restores normal service. If the fault is permanent a preset
number of trip and reclose operations are
performed to lockout. All three phases of
the VWE and VWVE reclosers open,
reclose and lockout simultaneously
Opening sequences can all be fast, all
delayed, or any combination of fast operations followed by delayed operations up
to a total of four. Fast operations clear
temporary faults before branch-line fuses
can be damaged. Delayed operations
allow time fuses or other downline protective devices to clear so that permanent
faults can be confined to smaller sections
of line.
Arc interruption takes place within the
three sealed vacuum interrupters. Oil is
used as an insulating medium but is not
involved in arc interruption. The moving
contacts of the vacuum interrupters are
driven by the release of opening springs
that are loaded when the recloser is
closed.
Closing energy, as well as energy to
charge the opening springs, is supplied by
a high-voltage closing solenoid momentarily connected phase-to-phase through a
high-voltage contactor. The contactor is
mechanically closed by a rotary solenoid
actuated by a signal from the electronic
control.
NOTE: The closing coil of Type VWVE reclosers
below serial 1304 is connected phase to
ground. An instruction plate, mounted on the
head indicates the proper connections for the
closing coil of the particular recloser.
A trip-free, yellow operating handle located under the sleet hood will manually lock
open the recloser. It cannot manually close
the recloser but must be in the CLOSED
position for the rotary close solenoid to
operate. A red contact position indicator
linked to the recloser mechanism but independent of the operating handle is also
located under the sleed hood.
The location of the major operation components of the VWE recloser is shown in
Figure 2. They are the same for the VWVE
recloser except for the configuration of the
bushings and the rating of the vacuum
interrupter. Being aware of the location of
these components and their
S280-40-6
part in the operation of the recloser will
give a quicker and clearer understanding
of the recloser maintenance and repair
procedures that follow.
Ratings
ELECTRICAL RATINGS
Nominal system voltage, kv
Maximum rated voltage, kv
Rated impulse withstand voltage (BIL) kv crest
60-Hertz withstand voltage, kv
Dry, one minute
Wet, ten seconds
Rated maximum continuous current, amps
Type VWE
Type VWVE27
Type VWVE38
2.4-14.4
15.5
110
14.4-24.9
27.0
125
24.9-34.5
38.0
150
50
45
560
60
50
560
70
60
560
INTERRUPTING RATINGS
Interrupting Current (RMS Symmetrical Amps)
Minimum
Trip
Current
(Amps)
25
35
50
70
100
120
140
170
200
240
280
340
400
480
560
600
680
800
960
1120
Type VWE
Type VWVE 27
and Type VWVE38
Above Serial 2680
Type VWVE
Below Senal 2680
Phase
Ground
Phase
Ground
Phase
Ground
_
_
_
3000*
4200*
6000*
8400*
12000
12000
12000
12000
12000
12000
12000
12000
12000
12000
12000
_
_
_
3000*
4200*
6000*
8400*
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
_
_
_
3000*
4200*
6000*
8400*
12000
12000
12000
12000
12000
12000
12000
12000
12000
12000
12000
3000*
3600*
4200*
5100*
6000*
7200*
8400*
10200*
12000
12000
12000
12000
12000
12000
12000
12000
_
_
_
3000*
3600*
4200*
5100*
6000*
7200*
8400*
10000*
10000
10000
10000
10000
10000
10000
10000
10000
_
_
_
3000*
3600*
4200*
5100*
6000*
7200*
8400*
10200*
12000
12000
12000
12000
12000
12000
12000
12000
_
_
_
_
* A protective accessory on the type ME electronic control can extend the interrupting current to the
maximum rating.
DUTY CYCLE
No. of Unit Operations
% ot Interrupting
Rating
X/R
Ratio
15-20
45-55
90-100
4
8
15
Type VWE
Type VWVE27
Type VWVE38
88
112
32
232
88
112
32
232
88
112
32
232
3
MECHANISM OPERATION
The recloser mechanism performs the
actual opening and closing of the vacuum interrupter contacts in response to
signals from the electronic control.
Contact opening is initiated by an electrical signal to a trip solenoid which acts
upon the toggle latch to release charged
opening springs. Contact closing is initated by an electrical signal to a rotary
solenoid which mechanically closes the
closing coil contactor to energize the
high voltage closing coil which closes the
vacuum interrupters and charges the
opening springs.
With the contacts closed, Figure 3, the
opening springs are fully extended and
the mechanism is in the rest (closed)
position. When the trip solenoid is energized, its push rod acts upon the toggle
latch to open the toggle and allow the
opening springs to act upon the contact
bar (Figure 4). As soon as the toggle
breaks, the contact arm assemblies are
rotated on their fixed pivots to instanteously open the interrupter contacts. I
the same motion the trip lever is rotated
to snap the toggle closed. This motion of
the reset lever also pulls the plunger out
of the closing coil. At this point the
mechansim is in the open (tripped) position (Figure 5).
A signal to the rotary solenoid closes
the contactor and energizes the high
voltage closing coil solenoid. As the
plunger is drawn down into the coil, the
reset lever is pulled down and latched,
the interrupter contacts are closed and
the closing springs are extended
(charged) figure 6). The mechanism is
then ready for another opening operation.
4
S280-40-6
MAINTENANCE
Frequency of Maintenance
Because reclosers are applied under
widely varying operating and climatic
conditions, maintenance intervals are
best determined by the user based on
actual operating experience. To assure
proper operation, reclosers must be
maintained when they have operated the
equivalent of a complete duty cycle and
before the dielectric strength has deteriorated below prescribed levels. In the
absence of specific operating experience,
the following procedures are recommended.
• When Type VWE and VWVE reclosers
are operated under usual service conditions as defined in ANSI (American
National Standards Institute) C37.60,
“Standard
Requirements
for
Automatic Circuit Reclosers for
Alternating Current Systems,” it is recommended that the following maintenance procedures be performed at
the completion of an equivalent duty
cycle.
NOTE: ANSI C37.61, “Guide for the
Application, Operation and Maintenance of
Automatic Circuit Reclosers” gives a procedure for converting the standard duty
cycle, as shown on page 3 of these
instructions into an equivalent duty cycle
based on the actual operating duty of the
recloser.
• However, if the recloser has not completed an equivalent duty cycle within
three years, it is recommended that
an external inspection, oil-level check,
and a check of the dielectric strength
of the oil be made at that time. (See
steps 1, 2, and 8 of “Maintenance
Procedure” below.)
• Also it is strongly recommended that
the vacuum interrupters be replaced
after 7000 operations of the recloser.
Periodic
Maintenance Inspection
Each periodic maintenance inspection at
the completion of an equivalent duty
cycle should include at least the following:
1. Bypass and remove the recloser from
service.
A. Disconnect the control cable from
the recloser.
2. Inspect external components.
A. Check for broken or cracked bushings. Replace as necessary. (See
page 8 for procedure.)
B. Check for paint scratches and
other mechanical damage; paint
to inhibit corrosion.
C. Note counter reading and enter in
the record log in the control.
Figure 7.
Location of scribe mark on movalbe contact rod of vacuum
interrupter
3. Perform a dielectric withstand test to
check the insulation level of the recloser and the vacuum integrity of the
interrupters. (See page 7 for procedure. )
4. Lower the tank to expose the internal
components.
CAUTION
Be sure the recloser is open (yellow
operating handle inder the sleet hood
is down) before lowering the tank, so
that the mechanism will not be tripped
accidently while the mechanism is out
of oil.
A. Attach the sheaves of the tank hoisting windlass mechanism to the
recloser tank and take up the slack.
B. Remove the ten head bolts that
attach the tank to the head casting
and carefully lower the tank.
5. Clean all internal components.
A. Remove all traces of carbon by wiping with a clean, lint-free cloth.
NOTE: Although current interruption
takes place in a sealed vacuum chamber, the closing solenoid contactor operates in oil and will produce some carbon
deposits.
B. Flush the mechanism with clean
transformer oil.
CAUTION
Never use volatile solutions, detergents,
or water-soluble cleaners
6. Check the contact erosion of the
vacuum interrupters.
A. Locate the scribe mark on the moving contact rod at the top of the
interrupter, Figure 7.
B. If the scribe mark falls below the top
of the phenolic guide when the
interrupter is closed, the interrupter
has reached the end of its useful life
and must be replaced. (See page
10 for replacement procedure.)
NOTE: Procedure for manually operating
the recloser when the mechanism is out
of oil is described on page 6.
7. Check circuit components attached to
the recloser head, frame and operating
mechanism.
A. Check condition of the wiring to the
terminal strip and make sure all
connections are tight.
B. Make sure that the rotary solenoid
and the trip solenoid are fir mly
attached to the recloser frame.
C. Check that the two mercury switches are securely held in place by the
nylon mounting straps.
D. Check condition of microswitch
mounted above main shaft.
5
E. Check condition of the bushing current transformers and the associated wiring.
F. Check the control cable receptacle.
If circuit component malfunction is
suspected, see page 15 for an
operational check procedure.
8. Check the dielectric strength of the
insulating oil.
A. An oil sample taken near the bottom
of the tank should have a dielectric
strength of not less than 22 kv rms.
B. Low dielectric strength indicates the
presence of water or carbon
deposits. Replace the oil as necessary.
9. If oil must be replaced,
A. Drain the tank, and clean out all
sludge and carbon deposits.
B. Fill with new, clean insulating oil up
to 2-1/4 inches below the top of the
tank flange. Tank capacity is
approximately 53 U.S. gallons. See
Oil Condition on page 8.
10. Clean and examine the head gasket.
Replace if it is cracked, cut, or otherwise damaged, or if it has been permanently deformed.
11. Clean the head gasket seat and retank
the recloser.
A. Move the yellow operating handle
under the sleet hood to the up position to avoid any possible binding
while raising the tank.
B. Replace the head bolts and torque
to 35-55 ft-lbs. Apply clamping
force gradually and equally, in rotation, to each bolt to achieve an
evenly distributed gasket sealing
pressure.
13. Repeat the high voltage dielectric
withstand test (Step 3) to make sure
the dielectric clearances within the
tank have not been compromised.
Manual Operation
of the Recloser
The recloser may be closed and opened
manually while the mechanism is either in
or out of oil.
MECHANISM IN OIL
For a tanked recloser (mechanism
immersed in oil) use the following manual
operating procedure.
A. To close the recloser.
1. Remove the closing tool port cover
and gasket from the side of the
head casting. (See Figure 2 for
location.)
2. Insert the KA9OR T-handle closing
tool (furnished as an accessory)
into the closing tool port (Figure 8)
and engage the pin on the closing
shaft.
3. Lift up the yellow operating handle
under the sleet hood to reset the
mechanism.
4. Turn the closing tool one-quarter turn
clockwise to close the main contacts.
WARNING
Never use the KA90R closing tool to
close an energized reclsoer.
CAUTION
Forcing the closing too beyond the
mechanism stop may shear the pin on
the closing shaft.
B. To open the recloser.
1. Pull down the yellow operating handle to trip open the recloser.
MECHANISM OUT OF OIL
To operate the mechanism out of oil, proceed as follows:
A. To close the recloser.
1. If the mechanism is still mounted in
the head use the procedure for a
tanked recloser above (Mechanism
in Oil).
2. If the mechanism is removed from
the head turn the trip-reset shaft
(Figure 9) with a pair of
needlenose pliers to reset the
mechanism, then turn the closing
shaft clockwise with the closing
tool to close the main contacts.
NOTE: Type VWE reclosers below serial
1340 and VWVE reclosers below serial
1060 require the following special
thread-sealing procedure to keep moisture from entering the tank along the
threads of the head bolts.
1. Before reinstalling the head bolts,
apply a liberal amount of a nonhardening pliable sealant, Permatex FormA-Gasket No. 2, to the end of each
bolt. The four leading threads should
be completely coated.
2. When the bolt is installed, a slight
bead of material (resembling an
O-ring) should remain on the top of
the tank flange. Apply the sealant
each time the head bolts are
removed and reinstalled.
12. Check the oil level with the dipstick in
the head and adjust the level to the
upper line on the dipstick.
NOTE: If the recloser is equipped with an
oil-sight gage, the oil level should be above
the sight gage. If the oil surface line is visible in the window, add oil to raise the level
to the upper line on the dipstick.
6
Figure 8
Manually closing the recloser with KA90R closing tool.
S280-40-6
CAUTION
The mechanism may be damaged if it is
"quick-tripped" with the yellow operating
handle while out of oil.
B. To open the recloser.
To open the contacts while the mechanism is out of oil, proceed as
follows:
1. Using the T-handle closirig tool
turn the closing shaft clockwise and
hold against the stop.
2. Release the trip lever (Figure 10) by
moving it to the right.
3. Then slowly allow the closing tool to
rotate counterclockwise to open the
main contacts.
NOTE: This procedure requires two people; one to operate the closing tool, the
other to operate the trip lever.
Insulation Level
Withstands Tests
High-potential withstand tests provide
information on the dielectric condition of
the recloser and the vacuum integrity of
the interrupters. Testing is performed at
75% of the rated low-frequency withstand voltage (37.5 kv for the VWE and
45 kv for the VWVE).
N
RADIATION
WARNING
At voltages up to 45 KV the radiation
emitted by the vacuum interrupter is
negligible. However at higher test voltages radiation injurious to personnel
may be emitted. See Radiation
Warning Service Information Bulletin
S280-90-1 for further details
Figure 9
Location of trip-reset shaft.
TEST 1: Proceed as follows:
1. Manually close main contacts of
recloser (see page 6 for procedure).
2. Ground recloser tank and head.
3. Connect all three source-side
bushings (1, 3, 5) together.
4. Apply proper test voltage to
sourceside bushings.
5. The recloser should withstand
the test voltage for 60 seconds.
TEST 2: Proceed as follows:
1. Manually close main contacts of
the recloser (see page 6 for
procedure).
2. Ground recloser tank and head.
3. Ground Phase A (bushing 2) and
Phase C (bushing 6).
4. Apply proper test voltage to
Phase B (bushing 3).
5. The recloser should withstand
the test voltage for 60 seconds.
TEST 3: proceed as follows:
1. Open main contacts of recloser
(see page 6 for procedure).
2. Ground recloser tank and head.
3. Connect and ground all three
loadside bushings (2, 4, 6).
4. Connect all three source-side
bushings (1, 3, 5).
5. Apply proper test voltage to
sourceside bushings.
6. The recloser should withstand
the test voltage for 60 seconds.
7. Reverse the connections: ground
source-side bushings (1, 3, 5);
apply test voltage to load-side
bushings (2, 4, 6) for 60 seconds.
8. The recloser should withstand
the test voltage for 60 seconds.
Figure 10
Trip lever releases mechanism whe opening recloser out of oil.
7
TEST RESULTS: These high potential
withstand tests provide information on the
dielectric condition of the recloser and the
vacuum integrity of the interrupters.
A. If the recloser passes the closed-contacts tests (Tests 1 and 2) but fails the
open-contacts test (Test 3) a deteriorated vacuum in one or more of the
interrupters is most likely the cause.
Retest each vacuum interrupter individually to determine the failed phase
or phases, and replace the interrupter(s). Retest to confirm the repair.
B. If the recloser fails the closed-contacts
tests (Test 1 and 2) the cause is likely
to be a diminished electrical clearance
or a failed insulation. After correcting
the problem, retest to confirm the
repair.
Oil Condition
Oil provides the internal insulation barrier
between phases and from phase to
ground, and must be replaced before it
deteriorates below a safe dielectric level.
Replace the oil if its dielectric strength
falls below 22 kv.
New oil should always be filtered before
using even though it is obtained from an
approved source. Passing the oil through
a blotter press will remove free water and
solid contaminants such as rust, dirt, and
lint. Keep aeration to a minimum during filtering to prevent moisture in the air from
condensing in the oil and lowering its
dielectric strength.
Used oil must be treated before reusing.
Filtering may remove absorbed and free
water and other contaminants to raise the
dielectric strength to acceptable levels.
However, filtering does not always remove
water-absorbing contaminants and the
dielectric strength may fall rapidly after
being returned to service. Therefore the
recloser should be filled with new oil, or oil
that has been restored to like-new condition. Oil used in these reclosers conforms
to ASTM Standard D3487, Type l; its property limits are shown in Table 1.
SHOP MAINTENANCE
PROCEDURES
The operations described in this section
should be performed under the cleanest
conditions possible. The repair work,
except for bushing replacement, will be
simplified if the work bench is arranged so
the mechanism/head assembly can be
inverted (bushings down). No special tools
are required for any of the repair procedures.
8
Table 1
Specifications for Oil Used in Cooper Power System's Distribution Switchgear
Characteristic
Acceptable Value
Color
Reaction
Neutralization no.
Corrosive sulfur
Steam emulsion no.
Flash point
Fire point
Pour point
Viscosity, max
cST (SUS) at
100 C
40 C
0C
Specific gravity at 15 C
Coefficient of expansion
(from 25 to 100 C)
Interfacial tension
Dielectric constant
Dielectric strength
Water content
(by Karl Fischer test)
PCB content
Weight
0 . 5 max (ASTM colorimeter)
Neutral
0.03 mg KOH/g max
Noncorrosive
25 seconds max
145 C min
160 C min
-40 C max
ASTM Test
Standard*
D1500
D974
D1275
D1935
D92
D92
D97
D445, D88
3.0 (36)
12.0 (66)
76.0 (350)
0.91 g/cc max
D1298
0.0007 to 0.0008
40 dynes per cm min
2.2 - 2 3
30 kV min
D1903
D971
D924
D877, D1816
35 ppm
No detectable amount
0.9 kg/liter
7.5 Ib/gal
D1533
D3304
*Tests are described in latest revision of ASTM standards.
BUSHINGS
Bushing maintenance generally consists of a thorough cleaning and a
careful examination for chips, cracks,
or other mechanical damage during
the periodic maintenance inspection.
Bushings must be replaced whenever
damage is discovered.
TYPE VWE BUSHINGS
A damages bushing can be replaced
with the recloser either tanked or
untanked, depending upon the circumstance or the damage.
• If the bushing porcelain is accidentally chipped during installation of
the recloser, an it is obvious that no
other damage has occured, the
bushing porcelain only can be
replaced without untanking the
recloser.
• If the bushings has been damaged
while in service or storage, the
recloser must be untanked. Water
or other contaminants may have
entered the tank (test the oil) the
bushing lead may be damaged
(either mechanically or electrical
flashover), or pieces of porcelain
may have fallen into the tank.
Replacing the Bushing Porcelain
with the Recloser Tanked
Refer to Figure 11 and proceed as follows:
1. Unscrew the bushing terminal and discard the terminal gasket.
2. Remove the three hex head capscrews
and clamps that secure the bushing to
the head and lift out the porcelain.
3. Remove and discard the lower bushing
gasket.
4. Twist off the split aluminum clamping ring
from the old porcelain. If it is in good
condition install it on the new porcelain;
replace with new ring if damaged.
NOTE: The clamping ring cushions and distributes the pressure between the porcelain
and the clamps. DO NOT OMIT.
5. Using a new gasket, install the new
porcelain over the bushing rod and into
the head. Make sure the roll pin on the
end of the rod is seated into the locking
groove at the top of the porcelain.
6. Position the clamping ring with the split
centered between two clamping bolts.
7. Reassemble the bushing to the head
casting with the bushing clamps. Tighten
the clamping bolts evenly, a little at a
time, to a torque of 10-15 ft-lbs
S280-40-6
NOTE: Clamping forces must be applied
gradually and equally in rotation to each
bolt. This results in an evenly distributed
gasket sealing pressure.
8. Install a new ter minal gasket and
reassemble the terminal to the bushing
rod with 35 ft-lbs of torque.
NOTE: Apply a ver y small amount of
petroleum jelly to the knurled surface of the
inside face of the terminal before assembling
the terminal to the bushing rod.
Replacing the Bushing
with the Recloser Untanked.
Refer to Figure 12 and proceed as follows:
1. Disconnect the appropriate bushing
lead from the bottom end of the bushing rod.
2. Remove the three hex head capscrews
and clamps that secure the bushing to
the head and lift out the complete
bushing assembly.
3. Remove and discard the lower bushing
gasket.
4. The complete bushing assembly can
be replaced or new porcelain only can
be installed depending upon the
extent of damage. If new porcelain
only is to be installed, proceed as follows:
A. Unscrew the bushing terminal and
withdraw the rod from the bottom
of the procelain; discard the terminal gasket.
B. Insert the rod assembly all the way
into the new porcelain, making
sure the roll pin is seated in the
locking groove in the top of the
bushing.
C. Assemble the terminal to the bushing rod using a new terminal gasket; tighten to a torque of 35 ftlbs.
NOTE: Apply a very small amount of
petroleum jelly to the knurled surface of
the inside face of the terminal before
assembling the terminal to the bushing
rod.
5. Twist off the split aluminum clamping
ring from the old bushing and install on
the new bushing if it is in good condition; replace the ring if damaged.
NOTE: The clamping ring cushions and distributes the pressure between the procelain
and the clamps. DO NOT OMIT.
6 Install the bushing assembly (new or
reworked) into the head using a new
lower bushing gasket. Position the
bushing with the stud-end of the terminal pointing outward.
7. Position the clamping ring with the split
centered between two clamping bolts.
8. Reassemble the bushing to the head
casting. Tighten the clamping bolts
evenly, a little at a time, to a torque of
10-15 ft-lbs.
NOTE: Clamping forces must be applied
gradually and equally in rotation to each
bolt. This results,in an evenly distributed
gasket sealing pressure.
9. Reconnect the lead to the bushing rod.
Figure 11
Replacing bushing with
recloser tanked.
Figure 12
Bushing parts VWE recloser.
9
TYPE VWVE BUSHINGS
The bushings of the Type VWVE recloser
are oil-filled. The special fixtures and procedures required to assemble these
bushings is beyond the scope of normal
shop maintenance repair. Therefore if a
Type VWVE bushing is in any way damaged, the complete bushing assembly
must be replaced. Refer to Figure 13 and
proceed as follows:
1. Disconnect the appropriate bushing
lead from the bottom end of the bushing rod.
2. Remove the three hex head capscrews
and bushing clamps that secure the
bushing to the head casting and lift out
the complete bushing assembly.
3. Remove and discard the lower bushing
gasket.
4. Twist off the split, aluminum ring from
the old bushing and install on the new
bushing assembly if it is in good condition; replace ring if damaged.
NOTE: The clamping ring cushions and distributes the pressure between the porcelain
and the clamps. DO NOT OMIT.
Figure 13
Removing Type VWVE bushing.
10
5. Install the new bushing assembly into
the head using a new lower bushing
gasket. Position the bushing with the
stud-end of the terminal pointing outward.
6. Position the clamping ring with the split
centered between two clamping bolts.
7. Reassemble the bushing to the head
casting. Tighten the clamping bolts
evenly, a little at a time, to a torque of
10-15 ft-lbs.
NOTE: Clamping forces must be applied
gradually and equally, in rotation, to each
bolt. This results in an evenly distributed
gasket sealing pressure
8. Reconnect the lead to the bushing rod.
Vacuum Interrupters
Vacuum interrupters must be replaced
when:
• They lose their vacuum as evidenced by
a failure during the low frequency
dielectric withstand test across the
open contacts;
• The interrupter contacts have eroded
beyond their useful life as evidenced
by the position of the scribe mark on
the moving contact rod, or
• The interrupters have completed their
mechanical life of 7000 operations.
To replace an interrupter, refer to Figure
14 and proceed as follows:
Figure 14
Vacuum interrupter replacement.
1. Make sure the closer contacts are open,
the yellow manual operating handle
under the sleet hood is pulled down.
2. Cut the three nylon tie straps which
secure the vertical insulating barrier and
remove the barrier.
3. Loosen and remove the upper interrupter
clamp. As the clamp is loosened, atmospheric pressure on the bellows will
cause the contact rod to move down into
the interrupter. This action can be verified
by observing the scribe mark on the contact rod. It will move downward to just
above (or below) or just below the fiber
disk at the top of the interrupter.
NOTE: If the contact rod does not move, the
interrupter may have lost its vacuum or the contact rod may be sticking in the clamping fingers
of the contact operating rod assembly. Use a
screwdriver to gently spread the clamping fingers to free the rod.
4. Disconnect the bushing lead from the
lower contact plate assembly.
5. Loosen and remove the lower interrupter
clamp.
6. Remove the hardware attaching the lower
contact plate to the three ver tical
stringers and remove the contact plate
and the vacuum interrupter.
S280-40-6
7. Install a new vacuum interrupter into
the clamping fingers of the contact
operating rod and the lower contact
plate and attach the plate to the
stringers.
NOTE: On the side with the single stringer, a
spacer on the stringer stud provides a
1/16inch gap between contact plate and the
attaching flat washer and locknut when the
interrupter contacts are open. This gap is
intentional.
8. Manually close the recloser.
9. Coat the threads of the interrupter
clamps and attaching screws with a
film of transformer oil and install, but
do not tighten, the upper and lower
interrupter clamps.
10. Position the upper and lower interrupter clamps just below the shoulder
on the finger-type current exchange
connectors so that the clamping force
will be applied to the center of each as
shown in Figure 15.
11. Rotate the interrupter so that one of
the hex nuts at the top of the interrupter is centered directly beneath the
gap on one side of the upper clamp.
(See Figure 15.)
CAUTION
When rotating the interrupter avoid twisting the contact rod to prevent damaging
the bellows and destroying the interrupter.
Figure 15
Orientation of interrupter and clamp.
Closing Solenoid Contactor
Type VWE reclosers below serial 3901
and Type VWVE reclosers below serial
1304 are equipped with a double pole
contactor, KA430R3, which provides a
single break in each line (Figure 16). Type
VWE reclosers, serial 3901 and above,
and Type VWVE reclosers serial 1304
and above are equipped with a double
pole contactor, KA1143R, which provides
two breaks in series in each line (Figure
17). Maintenance procedures are the
same for both contactors.
If the contacts are badly burned or
eroded, the entire contactor must be
replaced. See Figure 18 and proceed
as follows:
1. Unhook the two toggle openings
from the pin that connects the operating shaft of the contactor to the
toggle arm.
2. Remove the three C-type retaining
rings indicated in Figure 18 and
withdraw the pin.
3. Disconnect the two coil leads from
the contactor.
12. Tighten the screws of each interrupter
clamp evenly to a torque of 75 in-lbs.
NOTE: Clamps must be tight to prevent
slippage of the interrupter contact rods in
their current-exchange connectors.
13. Reconnect the bushing lead to the
lower contact plate.
14. Re-install the vertical insulation barrier
plate between the long bushing lead
and the mechanism. Position the plate
and secure it with cotton coil-tying
cord, or similar cotton lacing. Wrap the
cord snuggly at each tie point three of
four turns, knot and cut the loose
ends about 1/4 inch from the knot. A
drop of Pliobond on the loose ends
and the knot will prevent raveling. The
two ties securing the barrier to the
vertical stringer should also encircle
and secure the bushing lead.
15. Manually trip and close the recloser
several times to check interrupter
operation.
NOTE: Contact movement can be verified
by observing the movement of the scribe
mark on the upper contact rod of the interrupter. When the recloser is open the
scribe mark will be about 5/8-inch above
the fibre disk; on closing the mark will travel
1/2-inch downward.
Figure 16
KA4304R3 single break contactor.
11
NOTE: On the KA430R3 (Figure 16) contactor configuration, reattach the lockwasher and hex nut to the contactor terminal
immediately after disconnecting the coil
lead to prevent loss of moving contact
parts which are attached to the support
plate with the same hardware.
4. Disconnect the two fuse leads from the
contactor.
5. Remove three hex head capscrews
and lockwasher that attach the contactor to the underside of the recloser
mechanism frame and remove the
contactor.
6. Install the new contactor by reversing
the disassembly procedure. Use new
C-rings to secure the toggle-link pin.
7. Connect the solenoid coil leads to the
lower terminals of the KA430R3 “singlebreak” contactor or the inside terminals of the KA1 143R “double-break”
contactor.
8. Connect the fuse leads to the upper terminals of the KA430R3 or the outside
terminals of the KA1143R contactor.
9. Check Figures 16 and 17 for properlead
connections. Be sure coil and fuse
leads are positioned for maximum
clearance to other grounded parts.
Closing Solenoid
The closing solenoid coil of Type VWVE/
VWVE27 recloser below serial 1304 is
connected phase-to-ground and is rated to
operate on the system’s phase-to-neutral
voltage. It is protected with a fuse on the
hot side. The other side of the coil is
grounded by a lead connected from the
contactor to the frame. The closing
solenoid coil of type VWVE/VWVE27
reclosers serial 1304 and above, and all
Type VWE and Type VWVE38 reclosers, is
connected phase-to-phase and is rated to
operate a full system voltage. It is protected with two fuses, one on either side. A
data plate attached to the recloser head
between source side bushings 3 and 5 provides the coil connection information.
If the solenoid coil must be replaced,
due to damage or change in operating voltage, refer to Figure 19 and proceed as follows:
1. Disconnect the two coil leads from the
closing solenoid contactor.
NOTE: On the KA430R3 (Figure 16) contactor configuration, reattach the lockwashers
and nut to the contactor terminal immediately after disconnecting the coil lead to prevent
loss of parts of the moving contact arm
assembly which is attached to the support
plate with the same hardware.
Figure 17
KA1143R double-break contactor.
2. Remove the four capscrews and lockwashers which attach the base plate to
the bottom of the solenoid frame posts
and lower the coil and base plate.
3. Remove the coil from the base plate and
discard the coil gasket.
4. Using a new coil gasket, install the new
closing coil on the base plate.
NOTE: A new coil gasket is included in the
closing coil replacement kit.
5. Reassemble the base plate to the
solenoid frame posts and connect the
coil leads to the contactor terminals.
Make sure the coil leads clear the
solenoid frame by at least 1/2-inch.
6. The closing coil replacement kit includes
two new coil fuses which should be
installed with the new coil. See Closing
Solenoid Fuses on page 13 for fuse
replacement procedure.
7. The closing coil replacement kit also
includes a new voltage date plate.
Replace the plate on the sleet hood of
the recloser head if the operating voltage of the recloser is being changed.
Figure 18
Changing closing solenoid contactor.
12
S280-40-6
Figure 19
Parts involved in solenoid coil replacement.
Closing Solenoid Fuses
Only one fuse (on the hot side) is used
with closing coils connected phase-toneutral. Two fuses are used with closing
coils connected phase-to-phase.
New fuses are provided with the closing
solenoid coil replacement kit and should
be installed with the replacement coil.
Fuses can also be ordered separately for
individual replacement if damaged.
A label, attached to the closing coil,
specifies the catalog number, and color
band coding of the properfuse required to
protect the coil. This information is also
listed in Table 2. Note the voltage rating is
either phase-to-phase, or phase-to-neutral
depending upon type of closing solenoid
coil connection.
To replace a closing solenoid fuse:
a. Disconnect the long fuse lead atthe
closing solenoid contactor.
b. Disconnect the lead wire from the
ter minal at the other end of
thefuse.
c. Loosen the mounting strap and slide
out the fuse.
d. Install the new fuse and reconnect
the fuse leads.
NOTE: Be sure the long fuse lead
clears and grounded parts and insulating supports by at least 1/2-inch.
TABLE 2.
Closing Solenoid Fuse Data
Closing Solenoid
Voltage*
2.4 - 3.3 kv
4.16 - 6.0 kv
7.2 - 11 kv
12 - 24.9 kv
Fuse
Catalog
Number
Color
Band
KA259R904
KA259R901
KA259R902
KA259R903
Two Red
Black
Yellow
Red
*Either phase-to-phase or phase-to-ground neutral depending upon coil connection.
Removing Mechanism
from Head
To gain access to components located in
or on the main frame, the following procedure may be used to remove the mechanism from the head.
NOTE: These procedures will be simplified if
the untanked head and mechanism assembly
can be inverted (bushings down). The unit can
be supported on its bushings.
1. Disconnect all six bushing leads from
the rods at the ends of the bushings.
2. Disconnect the lockout lever and contact position indicator shafts by disengaging the spring loaded couplers and
locking them in the disengaged position, Figure 20.
3. If the recloser is equipped with the
auxiliary switch accessory, remove
the C or E-ring and washer, Figure
21, and disconnect the operating
lever of the switch from the recloser
mechanism.
4. If the recloser is equipped with the
CTtype batter y charger power
source, remove the screws that
secure the 0.2 mfd bathtub capacitor
to the recloser frame, Figure 22.
NOTE: The CT-type batter y charger
power source is standard on Type VWE
reclosers below serial 2100 and Type
VWVE reclosers below serial 1500. It may
be provided as an accessory on later
units.
13
5. Disconnect the seven leads connected
to the bottom of the terminal block
attached to the recloser frame, Figure
23. Be sure all leads are labeled
before removing. With the unit inverted as shown in Figure 23, the leads
are labeled A, B, C, D, E, R and N
from left to right.
6. The lead bundle is secured with a
nylon strap attached to the mechanism frame, Figure 23. Remove the
attaching screw to free the strap from
the mechanism.
7. Remove the six socket head bolts and
lockwashers that secure the frame to
the head casting and carefully lift the
mechanism from the head. Six long
pipe spacers will be released when
the mechanism is lifted.
Table 20
Couplers locked in disconnection position.
NOTE: By temporarily substituting eyebolts for two of the hex head bolts in the
bottom of the closing solenoid frame, the
mechanism can be easily lifted and handled with a hoist (Figure 24).
8. Remove the two spring-loaded couplers disengaged in Step 2 for safekeeping.
The components remaining in the head
are shown in Figure 25.
Re-lnstalling
Mechanism
into Head
Table 21
Remove E-ring to disconnect auxiliary switch operating lever.
To re-install the recloser mechanism
assembly into the head, the following
procedure may be used.
1. Install the couplers on the lockout
lever and contact position indicator
shafts of the mechanism and lock
them in the disengaged position.
2. Carefully lower the mechanism
assembly onto the six pipe spacers
which have been positioned over the
attaching holes in the casting. (Figure
25)
3. Install the six attaching socket head
bolts and tighten evenly to avoid any
binding of the mechanism.
NOTE: Replace the hex head bolts in the
bottom of the closing solenoid frame if
eyebolts were used for handling the
recloser mechanism.
Table 22
Capacitor for CT-type battery charger.
14
4. Re-engage the lockout lever and contact position indicator shaft by releasing the shaft couplers.
5. Reconnect the operating lever of the
auxiliary switch (if used) to the mechanism and secure with the washer
and E-ring. (Figure 22)
6. Attach the 0.2 mfd bathtub capacitor
(if present) to the mechanism frame.
(Figure 22)
7. Reconnect the leads to the respective
terminals on the terminal block, and
reattach the nylon strap to the frame
to secure the lead bundle. (Figure 23)
8. Reconnect the bushing leads to their
respective bushings.
S280-40-6
Operational Checks
An internal connection diagram of the
recloser circuits is shown in Figure 26.
The operating sequence for the various
circuit components is diagrammed in
Figure 27. These components should
provide trouble-free operation with little or
no maintenance. However, if the recloser
does not operate properly, the following
checks can be made to trouble-shoot the
recloser circuits.
NOTE: Procedures for checking, testing and
trouble shooting the electronic control are provided in a separate manual (S280-75-1)
The recloser need not be untanked to
perform these checks.
Figure 23
Connections to terminal strip attached to reclose mechanism frame.
CONTROL CABLE
Using an ohmmeter, check the continuity
between like pins and pin sockets of the
connector plugs on either end of the
electronic control cable and for discontinuity between unlike pins and pin sockets
to determine the condition of the control
cable.
NOTE: Pins or pin sockets N and P on either
plug are not connected.
Repair or replace the control cable if
defective.
CIRCUIT COMPONENTS
Figure 24
Lifting mechanism inand out of the head.
All measurements are made at the pin
sockets of the control cable receptacle on
the recloser head. A reading within + 15
percent of the specified value indicates
components are operational. Any component failing to meet the specified checks
should be replaced. Figure 28 identifies
the various circuit components.
NOTE: If the electronic control battery is used
to supply the 25 vdc power, connect as directed for only as long as necessary to perform
the specified action to prevent excessive battery drain.
Figure 25
Head casting detached from operating mechanism. Hexsocket-head bolts have
been attached to head casting for illustrative purposes.
15
SW1 - MICROSWITCH ON MAINSHAFT—CLOSED WHEN CLOSING SOLENOID
PLUNGER IS DOWN*
SW2 - MERCURY SWITCH ON MANUAL OPERATING HANDLE—CLOSED WHEN
HANDLE IS UP ON “CLOSED” POSITION.
SW3 - MERCURY SWITCH *ON MAIN SHAFT—OPEN WHEN CLOSING SOLENOID
PLUNGER IS DOWN*
*PLUNGER IS DOWN WHEN RECLOSER IS CLOSED
NOTE 1: FOR VWVE BELOWSERIAL1304, CLOSING COIL IS CONNECTED PHASE
C TO GROUND AND PHASE B FUSE IS ELIMINATED.
NOTE 2: FOR VWE BELOW SERIAL 2000 AND VWVE BELOW SERIAL 1500
BATTERY CHARGING TRANSFORMER IS STANDARD. IT IS SUPPLIED
AS AN ACCESSORY ON LATER UNITS.
Figure 26
Internal connection diagram type VWE-VWVE recloser.
16
**FOR PHASES-TO-GROUND
NEUTRAL CONNECTED COIL
THIS FUSE IS ELIMINATED
S280-40-6
Figure 27
Sequential operation of contacts in VWE-VWVE reclosers.
17
2. Connect the ohmmeter to pin sockets K
and L to check the continuity of the battery charger CT winding if used.
• The meter should read approximately
1000 ohms. A zero ohms reading
indicates the 0.2 mfd capacitor may
be short-circuited. Readings deviating more than + 20% from 1000
ohms indicate a damaged resistor or
transformer winding.
Ratio Test for Sensing CT’s
1.Connect all three phases of the recloser
in series as shown in Figure 29 and close
the recloser contacts with the manual
closing tool.
2. Connect a 100 ampere a-c test current
to test points 1 and 2.
3. Energize the 100 ampere test source.
4. Using a 0-500 millimeter check the current output across socket pins K-G, K-H,
and K-J. (Figure 29A)
• The output of each CT should measure 100 ma + 10%.
Figure 28
Location of circuit components on mechanism frame.
Trip-Solenoid
1. Connect an ohmmeter between pin
sockets A and B.
• The meter should read approximately
9.5 ohms.
2. Lift up the yellow manual operating handle under the sleet hood and manually
close the recloser with the handle closing tool as described on page 6.
3. Momentarily apply 25 vdc to pin sockets
A (+) and B (-).
• The recloser should trip.
Rotary Solenoid and
Closing Solenoid Contactor
1. Connect an ohmmeter between pin
sockets E and F. The meter should read
approximately 19 ohms.
2. With the yellow manual operating handle
in the up position and the recloser contacts open, momentarily apply 25 vdc to
pin sockets F (+) and E
(-)
• The rotary solenoid should operate
producing an easily distinguishable
sound. Repeat two or three times.
3. Connect the ohmmeter across source
side B and C phase bushings, or from
source side C bushing to recloser
ground (depending upon the recloser
coil connection) and again energize the
rotary solenoid.
• The meter should indicate closing coil
continuity (read the effective dc
resistance of the closing coil) confirming that the closing solenoid contactor is closed.
4. With the rotary solenoid still energized,
manually close the recloser with the
closing tool.
18
• The ohmmeter should indicate loss
of continuity indicating that the
closing solenoid contactor has
opened.
Switches (SW1, SW2, SW3)
Table 3 shows switch for manual operating lever/recloser contact combinations.
An ohmmeter connected across the
designated pin sockets of the control
cable receptacle will indicate zero for a
closed contact and infinity for an open
contact.
CURRENT TRANSFORMERS
The current sensing transformers are
mounted on the source side bushings
underneath the head casting. The battery charger CT power source (if applicable) is mounted on the load side center bushing.
Continuity Check
1. Connect an ohmmeter, in turn, to pin
sockets K and G, K and H, and K
and J to check the continuity of the
three current sensing transformers.
• The meter should readapproximately 7 ohms, the d.c. resistance of
each winding.
NOTE: Be sure to allow for the tolerances
of meter being used. The resistance of
certain type of meters is not negligible.
Use as high a scale (lower resistance) as
is accurately readable.
5. A 100 ma reading verifies the 1000:1
ratio of the sensing CT’s. If the 100 ma
is not attained the CT winding is probably faulty.
6. De-energize the test source.
Polarity Test for Sensing CT’s
1. With the phases still connected in series
from the previous test, connect the secondaries of the CT’s in parallel by connecting pin socket G to H to J and measure the output between pin sockets K
and J as shown in Figure 29B.
2. Energize the 100 ampere a-c test
source.
A. All three transformers should have
the same polarity the output should
measure 300 ma.
B. If one transformer has its polarity
opposite of the remaining two the
output will measure 100 ma.
3. De-energize the test source and remove
the jumper wire from the receptacle.
TABLE 3.
Switch Status.
Recloser
Contacts
Manual
Operating
Lever
SW1
Pin Sockets
C&D
SW2
Pin Sockets
F&N
SW3
Pin Sockets
A&N
OPEN
DOWN
OPEN
OPEN
CLOSED
OPEN
UP
OPEN
CLOSED
CLOSED
CLOSED
UP
CLOSED
CLOSED
OPEN
S280-40-6
Output Test of Battery Charging CT
1. With the phases still connected in
series, energize 100 ampere a-c
source.
2. Measure the output between pin socket
K and L of the control cable receptacle.
• Output should measure 40-60 ma.
3. Readings within this range indicates
sufficient output to maintain control
battery charge.
Figure 29
Test circuit for checking bushing current transformers.
NOTE: Ratio and polarity test-circuits shown are the effective circuits that contribute to the testing. Components not having an effect on the current flow are not shown. Dotted lines in the polarity-test circuit are test leads.
19
SERVICE
PARTS LIST
The service parts and hardware listed and
illustrated include only those parts and
assemblies usually furnished for repair or
involved in the maintenance procedures
described in this manual. Further breakdown of listed assemblies is not recommended.
Dimensions of all common hardware
parts have been carefully checked so that
they may be locally acquired. The suffix letter of the 14 character catalog number for
common hardware parts codes the plating
of the part:
A - No plating; raw material
H - Silver
M -Black oxide
Q - Cadmium + zinc + chromate
Y - Zinc + chromate
Z - Electro zinc + bronze irridite
Figure 30
Bushing parts - exploded view.
20
A hardware kit, Catalog No.
KA849R1, contains an assortment of
roll pins, cotter pins, retaining rings,
stop nuts, etc.— common hardware
parts used in Cooper Power System
reclosers that may not be readily locally
available.
To assure correct receipt of any part
order, always include recloser type and
serial number. Because of Cooper
Power System's continuous improvement policy, there may be instances
where the parts furnished may not look
extactly the same as the parts ordered.
However, they will be completely interchangeable without any rework of the
recloser.
All parts carry the same warranty as
any whole item of switchgear, i.e.
against defects in material or workmanship within a period of one year from
date of shipment.
S280-40-6
Bushing Parts (Figure 30)
Qty.
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
Catalog
Description
Bushing assembly - Type VWE
Standard creepage
Standard creepage with
BCT accy
17-inch extra-creepage
17-inch extra-creepage
with BCT accy
Bushing assembly-Type VWVE
Standard creepage
Standard creepage with
BCT accy
26-1/2-inch extra-creepage
26-1/2-inch extra-creepage
with BCT accy
Hex jam nut, 1/2—20, brass
For Type VWE
For Type VWVE
Flat washer
Split lockwasher, med, 1/2,
bronze
Capscrew, hex hd,
3/8—16x2-1/4, stl
Bushing clamp
Clamping ring
Lower bushing gasket
Terminal
Upper bushing gasket
Bushing ceramic-Type VWE
Standard creepage
Standard creepage with
BCT accy
17-inch extra-creepage
17-inch extra-creepage
with BCT accy
Per
Number
Assy.
Item
No.
13
KA717R25
6
KA717R26
KA717R27
6
6
14
KA717R28
6
15
KA717R29
6
16
KA717R30
KA717R31
6
6
KA717R32
6
17
K880725320050H
K880725320050H
KP2028A3
6
12
12
K900830050000A
6
K730101137225Q
KP1109R
KP1111R
KP2090A66
KA17W901
KP2090A57
3
3
1
1
1
1
KP1110R
1
19
20
21
22
1
1
KP186W
1
Bushing rod assembly
Type VWE
Standard & 17-inch creepage
Standard & 17-inch creepage
with BCT accy
Roll pin, 1/8x15/16 (included
in Item 13)
Flat washer (included in
item 13)
Insulating tube (included in
item 13)
Standard & 17-inch creepage
Standard & 17-inch creepage
with BCT accy
Shock absorber (included in
item 13)
Qty.
Per
Assy.
KA716R20
1
KA716R21
1
K970801125093M
1
KP2028A39
1
KP3230A49
1
KP3230A46
1
KP2090A2
1
The following parts are applicable to the bushing current
transformer accessory only
18
KP171W
KP1578R
Description
Catalog
Number
23
24
25
26
Capscrew, hex hd, 3/8—16x2,
stl
Transformer clamping flange
Flange gasket
Replacement current transformer
600:5, multi-ratio
1200:5, multi-ratio
Capscrew, hex hed,
3/8—16x1-1/4, stl
Transformer clamping sleeve
Hex nut, 3/8—16, stl
Stud
Bushing spacer
K730101137200Q
KP170W
KP2090A73
3
1
2
KA159W
KA132W
1
1
K730101137125Q
KP169W
K880201116037Q
KP3149A40
KP275W
3
1
3
3
1
21
Figure 31
Head and tank assemblies - exploded view.
22
S280-40-6
Head and Tank Assemblies (Figure 31)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Description
Receptacle and wiring
bundle assembly
Gasket
Capscrew, hex hd, 1/4—20x3/4,
stl
Split lockwasher, med., 1/4, stl
Oil level dipstick
O-ring gasket
Closing oil instruction plate
All Type VWE and Type VWVE
serial 1304 and above
Type VWVE below serial 1304
Self-tapping screw,
Type Z, #2x3/16, sst
Capscrew, hex hd, 1/4—20x5/8
stl
Manual closing tool access
cover plate
Cover plate gasket
Capscrew, hex hd,
5/8—11x1-1/2, stl
Split lockwasher, med, 5/8, stl
Lifting lug
Capscrew, hex hd, 1/4—20x5/8,
stl
Split lockwasher, med, 1/4, stl
Auxiliary switch cover plate
Cover plate gasket
Ground connector
Head casting, includes control
shaft bushings
Head gasket
Cable clamp
Cable clamp
Machine screw, rd hd,
8—32x5/16, stl
Split lockwasher, med No. 8, stl
Current transformer support
Spacer
Current transformer
Flat washer, 14S, brass
Split lockwasher, med, 1/4, stl
Machine screw, rd hd,
1/4—30x2, stl
Hex nut, 10—24, stl
Split lockwasher, med,
No. 10, stl
Resistor, wirewound, 100 ohm,
25 watt
Bracket
Machine Screw, rd hd,
10—24x2-1/4, stl
Self-tapping screw, Type Z,
#4x3/16, sst
Voltage data plate
Nameplate
Type VWE
Type VWVE
Catalog
Number
Qty
Per
Assy.
Item
No.
40
KA33RE1
K P611R
1
1
K730101125075Q
K900801025000Z
KA363R
KP2000A9
4
4
1
1
43
44
KP2312R
KP1225R
1
1
K721515102031Z
2
45
46
47
48
49
50
51
K730101125062Q
2
KP246R1
KP2000A12
1
1
K730101162150Q
K900801062000Z
KP456H2
2
2
2
K730101125062Q
K900801025000Z
KP609R
KP611R
KA392R
4
4
1
1
1
KA840R
KP2103A8
KP2006A1
KP2006A2
1
1
2
4
K721501108031Z
K900801008000Z
KP145RE
KP3009A38
KA86RE1
K900525025056A
K900801025000Z
6
6
6
6
3
12
9
K721501125200Z
K881001124010Z
6
3
K900801010000Z
3
KP4022A31
KP238RE
3
3
K721501110225Z
3
K801515004018A
KP567R
4
1
KRW271V1
KRW307V1
1
1
41
42
52
53
54
55
56
57
58
59
60
61
62
63
64
Description
Self-tapping screw, rd hd.
No. 12x1/2, sst
Cover plate
Manual operating handle
assembly
Spacer
Retaining ring, Type C, 5/16 in,
sst (WA516)
Roll pin, 1/8x3/4, stl
Shaft and lever assembly
Spacer
Flat washer, 14S, brass
Cotter pin, 3/32x1/2, brass
Roll pin, 3/32x1/2, stl
Retaining ring, Type C, 3/16 in,
sst (WA510)
Groove pin
Spacer
Retaining ring, Type C, 3/8 in,
sst (WA518)
Indicator and support assembly
Spacer
Groove pin
Spacer
Capscrew, hex hd, 1/2—13x1/4,
stl
Flat washer
Pipe plug, 1 in, sq hd
Tank
Oil sampling and drain valve
Pipe plug, 1/2 in sq hd
Catalog
Number
Qty.
Per
Assy.
K801515012050A
KP283R
5
1
KA477R
KP3009A39
1
1
K970915302000A
K970801125075M
KA18RE
KP3007A8
K900525026056A
K970525093050A
K970801093050M
1
1
1
1
1
1
1
K970915188000A
KP3123A12
KP3006A9
2
1
1
K970915375000A
KA19RE
KP301 3A38
KP3126A4
KP301 3A11
2
1
3
1
1
K730101150325Q
KP2028A23
KP2007A4
KRW116FA
KA809R
KP2007A3
10
10
1
1
1
1
The following parts are applicable to the CT-type battery
charger power source. It is standard on the Type VWE below
serial 2100 and VWVE below serial 1500; it is an optional
accessory on later units.
65
66
67
68
69
70
71
72
73
74
75
76
77
78
Capacitor, 0.2 mfd, 2500 wvdc
Split lockwasher, med, No. 6, stl
Machine screw, rd hd,
6— 32x5/16, stl
Hex nut, 10—24, stl
Split lockwasher, med,
No. 10, stl
Flat washer, 14S, brass
Resistor, wirewound, 1000 ohms,
25 w
Bracket
Machine screw, rd hd
10—24x2-1 /4, stl
Current transformer support
Spacer
Current transformer
Split lockwasher, med, 1/4, stl
Machine screw, rd hd,
1/4—20x2, stl
KP4004A8
K900801006000Z
1
2
K721501106031Z
K881001124010Z
2
1
K900801010000Z
K900525026056A
3
2
KP4022A36
KP238E
1
1
K721501110225Z
KP145RE
KP3009A38
KA86RE1
K900801025000Z
1
2
2
1
2
K721501125200Z
2
23
Figure 32
Closing coil mechanism - exploded view.
24
S280-40-6
Closing Coil Mechanism (Figure 32)
Item
No.
1
2
3
4
5
6
7
8
9A
9B
10
11
12
13
14
15
Description
Capscrew, skt hd,
1/2—13x4-1/2, stl
Split lockwasher, med, 1/2, stl
Spacer
Operating lever coupler
Indicator shaft coupler
Contactor toggle spring
Groove pin
Retaining ring WA514, Type C,
1/4, stl
Closing solenoid contactor,
below 30 kv
Closing solenoid contactor,
above 30 kv
Capscrew with preassembled
split lockwasher, 1/4—20x1/2,
stl
Machine screw, rd hd,
1/4—30x1/2, brass
Split lockwasher, med, 1/4,
bronze
Hex nut, 1/4—20, brass
Fuse retainer clip
Closing coil fuse assembly
(also included in closing
coil replacement kit,
item 27)
2.4-3.3 kv (2 red color bands)
4.15-6 kv (black color band)
7.2 to 11 kv (yellow color
band)
12 to 24.9 kv (red color band)
Catalog
Number
Qt
Per
Assy.
21
22
23
24
25
26
Fuse mounting bracket
Lead assembly
Flat washer, 3/8 SAE, stl
Groove pin
Retaining ring WA518, Type C,
3/8, stl
Plunger and link assembly
Upper stringer assembly
Hex nut, 3/8—16, stl
Split lockwasher, med, 3/8, stl
Capscrew, hex hd,
3/8—16x1 -1/4, stl
Solenoid frame
Description
Catalog
Number
Closing coil replacement kit
(includes closing coil, lower
coil gasket, 28, two fuse
assemblies, 15, and voltage
data plate, 36 Figure 31)
60 Hertz
50 Hertz
2.4 kv
KA834R1
KA861R1
3.3 kv
KA834R10
KA861R10
4.16-4.8 kv
KA834R2
KA861R2
6.0 kv
KA834R6
KA861R6
7.2-8.32 kv
KA834R3
KA861R3
11.0 kv
KA834R9
KA861R9
12.0-13.2 kv
KA834R4
KA861R4
14,0 kv
KA834R5
KA861R5
17.0 kv
KA834R12
KA861R12
20.0 kv
KA834R11
KA861R11
23.0-24.9 kv
KA834R13
KA861R13
125 vdc*
KA834R7
250 vdc*
KA834R8
*No fuses required with low- voltage dc coils
Qty.
Per
Assy.
27
KP2036A3
K900801050000M
KP3182A1
KP1177R
KP1056R1
KP141R1
KP1306R
6
6
6
1
1
2
1
KP970901250000M
4
KA430R3
1
KA1143R
1
K830101125050A
3
K721525125050A
6
K900830025000A
K881025120025A
KP2006A16
6
8
2
28
29
30
31
2
32
33
34
35
36
KA259R904
KA259R901
37
38
39
40
41
KA259R902
KA259R903
NOTE: Only one fuse assembly is required on reclosers with closing coils connected phase to ground (type VWVE below serial
1304)
16
17
18
19
20
Item
No.
KP257L
KA28W1
K900201037000A
KP3126A2
2
2
2
1
K970901375000M
KA50R
KA62R
K880201116037A
K900801037000Z
2
1
4
4
12
K730101137125A
KP100R1
12
1
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Lower solenoid gasket
Solenoid bridge plate assembly
Solenoid frame post
Machine screw, rd hd,
8—32x3/4, stl
Cable clip
Split lockwasher, med, No. 8, stl
Hex nut, 8—32, stl
Trip solenoid assembly
Capscrew, hex hd, 1/4—30x1/2,
stl
Flat washer, 1/4 SAE, stl
Hex nut, 1/4—20, stl
Insulator
Terminal block
Machine screw, fil hd,
6—32x5/8, stl
Lead wire assembly
Hex nut, 6—32, brass
Machine screw, rd hd,
6—32x1/2, brass
Mercury switch (SW-3)
Mounting clip
Machine screw, rd hd,
8—32x7/16, stl
Machine screw, rd hd,
6—32x1, brass
Internal tooth lockwasher,
No. 6, brz
Hex nut, 6—32, brass
Microswitch (SW-1)
Rotary solenoid assembly
Type VWE below serial 3900
and Type VWVE below serial
2850
Type VWE above serial 3900
and Type VWVE above serial
2850
Hex nut, 1/4—28, stl
Flat washer, No. 14S, brass
Split lockwasher, med, 1/4, stl
Groove pin
Retaining ring WA510, Type C,
3/16, stl
Spring
Spacer
Cotter pin, 3/32x1, brass
1
KP389R
KA644R1
KP1669R
1
1
4
K721501108075Z
KP2006A8
K900801008000Z
K881001132008Z
KA11RVE
5
7
4
5
1
K730101125050Y
K900201025000Z
K880201120025Y
KP2101A209
KP2101A9
1
2
1
1
1
K721801106062Z
KA62RE
K881025132006A
2
1
1
K721525106050A
KP134RE1
KP2006A19
1
1
4
K721501108043Z
4
K721525106100A
2
K901032006000A
K881025132006A
K999904130008A
4
2
1
KA12RE1
1
KA61WE
K881001328025Z
K900525025056Z
K900801025000Z
KP3123A3
1
4
2
2
1
K970901188000M
KP98L
KP3007A30
K970525093100A
2
1
1
1
25
Figure 33
Interrupter mechanism - exploded view.
26
S280-40-6
Interrupter Mechanism (Figure 33)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Description
Insulating barrier
Wire tie
Contact rod assembly replacement kit
Groove pin
Retaining ring, Type C, 1/4” stl
Spring
Upper current exchange
assembly
Phases A and B
Phase C
Upper stringer assembly
Capscrew, hex hd, 3/8 16x1-3/4
brass
Flat washer, No. 24S, brass
Short bushing lead (6 per phase)
Phases A and B
Phase C
Short lead insulation
Phases A and B
Phase C
Spacer
Split lockwasher, mea, 3/8 si brz
Hex nut, 3/8 16, brass
Interrupter clamp
Qty
Per
Assy.
Item
No.
KRW125N1
K994904170004A
3
12
17
18
KRW706VA
KP3124A50
K970901250000M
KP1066VWS
3
3
6
6
KRW115FB
KRW115FA
KA62R
2
1
9
K730125137175A
K900525039087H
3
6
KP3250A13
KP3250A14
12
6
KP2106A72
KP2106A71
KP3013A63
K900833037000A
K881025116037A
KP1036VS
2
1
3
6
6
12
Catalog
Number
19
20
21
22
23
24
25
26
27
28
29
Description
Capscrew, skt hd, 1/4—20x1, stl
Vacuum interrupter
VWE below S/N 7305
VWVE below S/N 7295
Phases A and B
Phase C
VWE above S/N 7305
VWVE/VWVE27 above S/N
7295
VWVE38
Lower stringer assembly
Spacer
Flat washer, 3/8 AN, stl
Elastic stop nut, 3/8—16
Flat washer, 3/8 SAE, stl
Split lockwasher, med, 3/8, stl
Hex nut, 3/8—16, stl
Lower current exchange
assembly
Phases A and B
Phase C
Long bushing lead (6 per phase)
Long lead insulation (6 per
phase)
Capscrew, hex hd, 3/8—16x1,
brass
Catalog
Number
Qty.
Per
Assy.
KP2036A10
12
KRW710V1
KRW710V2
KA327VS2
2
1
3
KA327VS2
KA338VS1
KA107VS
KP3009A121
K900201039062Z
KP2020A21
K900201037000A
K900801037000A
K880201116037A
3
3
9
3
3
3
9
9
9
KA127VWS2
KA127VWS1
KP3250A15
2
1
18
KP2106A77
3
K730125137100A
3
27
Cooper Power Systems
Quality from
Cooper Industries
©1991
Cooper Power Systems, Inc.
Kyle® is a registered trademark of Cooper Industries, Inc.
P.O. Box 2850 • Pittsburgh, PA 15230
Printed on Recycled Paper
KBP
5/95
Download