RELAY SETTING CALCULATION DOCUMENT: RIC S/S#2 380/115/33KV BSP STATION: [ Multiples 1.8.1 Applicable for - 33kV CAPACITOR BANK Relay Type = ALSTOM P142 PT Ratio Overvoltage setting- Alarm Time settings fault current P142 91ND6M0500J = 33KV/SQRT(3)/115V/SQRT(3)) = 105% of nominal voltage = (1.05*66.4) = 5 Sec VOLT PROTECTION GROUP 1: OVER VOLTAGE SETTING MENU TEXT SETTING V> Measur't Mode Phase to Neutral V> Operate Mode Any Phase V> 1 Function DT V> 1 Voltage Set 70.0 V V> 1 Time Delay 5 Sec V> 1 TMS 1 V> 2 Status Disabled V> 2 Voltage Set N/A V> 2 Time Delay N/A 30 A Rev. No.: of 33KV CAPACITOR BANK OVER VOLTAGE STAGE-1 PROTECTION RELAY SETTING (59-1) Relay Ordering Data EE-269253 Doc. No.: 70.0 V 0.02 − 1 ] RELAY SETTING CALCULATION DOCUMENT: RIC S/S#2 380/115/33KV BSP STATION: [ Multiples 1.8.2 - fault current 33kV CAPACITOR BANK Relay Type = ALSTOM P142 Relay Ordering Data = P142 91ND6M0500J PT Ratio = 33KV/SQRT(3)/115V/SQRT(3)) Circuit Breaker = B409, B422, B434 Overvoltage setting- Alarm Time settings = 110% of nominal voltage = (1.1*66.4) = 3 Sec VOLT PROTECTION GROUP 1: OVER VOLTAGE SETTING MENU TEXT SETTING V> Measur't Mode Phase to Neutral V> Operate Mode Any Phase V> 1 Function Disabled V> 1 Voltage Set N/A V> 1 Time Delay N/A V> 1 TMS N/A V> 2 Status Enabled V> 2 Voltage Set 73 V V> 2 Time Delay 3.00S 31 A Rev. No.: of 33KV CAPACITOR BANK OVER VOLTAGE STAGE-1 PROTECTION RELAY SETTING (59-2) Applicable for EE-269253 Doc. No.: 73.0 V 0.02 − 1 ] RELAY SETTING CALCULATION DOCUMENT: RIC S/S#2 380/115/33KV BSP STATION: [ Multiples 1.8.3 - fault current 33kV CAPACITOR BANK Relay Type = ALSTOM P142 Relay Ordering Data = P142 91ND6M0500J PT Ratio = 33KV/SQRT(3)/115V/SQRT(3)) Circuit Breaker = B409, B422, B434 Undervoltage setting- Trip Time settings = 30% of nominal voltage = (0.3*66.4) = 5 Sec VOLT PROTECTION GROUP 1: OVER VOLTAGE SETTING MENU TEXT SETTING V< Measur't Mode Phase to Neutral V< Operate Mode Any Phase V< 1 Function Disabled V< 1 Voltage Set N/A V< 1 Time Delay N/A V< 1 TMS N/A V< 1 Poledead Inh Disabled V< 2 Status Enabled V< 2 Voltage Set 20 V V< 2 Time Delay 5 Sec V< 2 Poledead Inh Enabled 32 A Rev. No.: of 33KV CAPACITOR BANK UNDER VOLTAGE PROTECTION RELAY SETTING (27-2/27) Applicable for EE-269253 Doc. No.: 20.0 V 0.02 − 1 ] RELAY SETTING CALCULATION DOCUMENT: RIC S/S#2 380/115/33KV BSP STATION: [ Multiples 1.8.4 - fault 33kV CAPACITOR BANK Relay Type = ALSTOM P142 Relay Ordering Data = P142 316D6M0440J CT Ratio = 5/5 A Circuit Breaker = B409, B422, B434 As Per Vendor Recommendation ALARM STAGE CURRENT SETTING = 0.7 A ALARM STAGE TIME SETTING = 5 Sec TRIP STAGE CURRENT SETTING = 1.0 A TRIP STAGE TIME SETTING = 0.1 Sec GROUP 1: OVER CURRENT SETTING MENU TEXT SETTING I>1 Input Measured I>1 Function DT I>1 Direction Non-Dir I>1 Current Set 0.7A I>1 Time Delay 5 Sec I>1 tRESET 0 Sec I>2 Function DT I>2 Direction Non-Dir I>2 Current Set 1.0A I>2 Time Delay 0.1 Sec I>2 tRESET 0 Sec I>3 Status Disabled I>4 Status Disabled 33 A Rev. No.: of current 0.02 33KV CAPACITOR BANK NEUTRAL UNBALANCE OC PROTECTION RELAY SETTING (46-1 & 46-2) Applicable for EE-269253 Doc. No.: − 1 ] DOCUMENT: STATION: RELAY SETTING CALCULATION RIC S/S#2 380/115/33KV BSP [ Multiples 1.8.5 EE-269253 Doc. No.: A Rev. No.: of fault current 0.02 − 1 ] 33KV CAPACITOR BANK INST PH OC PROTECTION RELAY SETTING (50PA, 50PB & 50PC) Applicable for - 33kV CAPACITOR BANK Relay Type = ABB - RXIG22 Relay Ordering Data = RK 411 008-DG Circuit Breaker = B409, B422, B434 System voltage: = 33.0 KV CT Ratio = 1200-800-600/1A Adopted Tap 600 /1 A Maximum peak inrush current = 1180.0A (AS PER Manufacture Data) Maximum peak outrush current = 1210.0A (AS PER Manufacture Data) Relay setting = 1.2 X outrush Current / (SQRT(2) X CTR) =1.2 x 1210/( sqrt(2) x600) Relay setting = 1.71 A = 1.80 A 34 DOCUMENT: STATION: RELAY SETTING CALCULATION RIC S/S#2 380/115/33KV BSP [ Multiples EE-269253 Doc. No.: A Rev. No.: of fault current 0.02 − 1 ] 1.8.6 33KV CAPACITOR BANK INST GROUND OC PROTECTION RELAY SETTING (50PN) Applicable for - 33kV CAPACITOR BANK Relay Type = ABB - RXIG22 Relay Ordering Data = RK 411 008-DG Circuit Breaker = B409, B422, B434 System voltage: = 33.0 KV CT Ratio = 1200-800-600/1A Adopted Tap 600 /1 A Maximum peak inresh current 1180A @ 250 HZ (AS PER Manufacture Data) Maximum peak outresh current 1210A @ 278 HZ (AS PER Manufacture Data) RELAY SETTING = 1.00A 35 DOCUMENT: STATION: RELAY SETTING CALCULATION Doc. No.: EE-269253 RIC S/S#2 380/115/33KV BSP Rev. No.: A 1.8.7 33KV CAPCAITOR BANK NON DIRECTIONAL O/C PROTECTION Applicable for - 33kV CAPACITOR BANK Relay Type = ALSTOM - P142 Relay Ordering Data = P142 91ND6M0500J Circuit Breaker = B409, B422, B434 System voltage: = 33.0 KV CT Ratio = 1200-800-600/1A Adopted Tap 600 /1 A Capacitor rating = 10.0 MVar Capacitor current = = 10x10^3/(sqrt(3) x 33) Relay setting = (1.35 x capacitor current/CT ratio) = (1.35 x 175/600) Relay IDMTL curve = VERY INVERSE Fault current considered = 5000A Assumed Operating time required = 0.5 s Assumed Fault current in multiples of relay setting = (5000/(0.39X600) 21.37 times Relay operating time at TMS 1 = (13.5/21.37-1) 0.66 S Required relay operating time = 0.50 s Assumed Required TMS setting = (0.5/0.66) TMS SETTING = 0.76 175.00 A 0.39 In 0.76 GROUP 1: OVER CURRENT SETTING MENU TEXT SETTING I>1 Function IEC v Inverse I>1 Direction Non-Directional I>1 Current Set 0.39 A I>1 TMS 0.76 I>1 tRESET 0 Sec I>2 Function Disabled I>3 Status Disabled I>4 Status Disabled [ Multiples 36 of fault current 0.02 − 1 ] DOCUMENT: STATION: RELAY SETTING CALCULATION Doc. No.: EE-269253 RIC S/S#2 380/115/33KV BSP Rev. No.: A [ Multiples of fault current 0.02 − 1 ] 1.8.8 33KV CAPCAITOR BANK NON DIRECTIONAL E/F PROTECTION Applicable for - 33kV CAPACITOR BANK Relay Type = ALSTOM - P142 Relay Ordering Data = P142 91ND6M0500J Circuit Breaker = B409, B422, B434 System voltage: = 33.0 KV CT Ratio = 1200-800-600/1A Adopted Tap 600 /1 A Capacitor rating = 10000.0 KVar Capacitor current = Relay setting = 20% of CT current = 0.2 Relay IDMTL curve = Normal Inverse Fault current considered = 5000 A Assumed Operating time required = 0.25 s Assumed Fault current in multiples of relay setting = (5000/(0.2X600) 41.67 times Relay operating = (0.14/41.67^0.02-1) 1.81 S Required relay operating time = 0.25 s Required TMS setting = (0.25/1.81) TMS SETTING = 0.14 10000/(sqrt(3) x 33) GROUP 1: EARTH FAULT SETTING MENU TEXT SETTING I>1 Function IEC S Inverse I>1 Direction Non-Directional I>1 Current Set 0.20 A I>1 TMS 0.14 I>1 tRESET 0 Sec I>2 Function Disabled I>3 Status Disabled I>4 Status Disabled 37 175.00 A 0.2 A 0.14 RELAY SETTING CALCULATION DOCUMENT: Doc. No.: EE-269253 RIC S/S#2 380/115/33KV BSP STATION: A Rev. No.: 1.8.9 33KV CAPACITOR BANK AUTOMATIC CAPACITOR CONTROL (ACCS) SETTING FOR 3 TRANSFORMERS SYSETM Relay Type ( MVAR Reading Should be from 33KV) REC670 (CU-ACCS) Relay Ordering Circuit Breaker 1MRK 002 814-AC B409, B422, B434 CASE 1 CONDITION BC1 OPEN BC2 OPEN SET VALUES FOR CLOSING Mvar SET VALUES FOR OPENING TIME Mvar TIME QC1 CLOSE 11 Mvar-1 5 Min. t1 OPEN 1 Mvar-2 5 Min. t2 QC2 CLOSE 11 Mvar-1 5 Min. t1 OPEN 1 Mvar-2 5 Min. t2 QC3 CLOSE 11 Mvar-1 5 Min. t1 OPEN 1 Mvar-2 5 Min. t2 CASE 2 CONDITION BC1 OPEN BC2 CLOSED SET VALUES FOR CLOSING Mvar SET VALUES FOR OPENING TIME Mvar TIME QC1 CLOSE 11 Mvar-1 5 Min. t1 OPEN 1 Mvar-2 5 Min. QC2 CLOSE 12 Mvar-3 5 Min. t3 OPEN 2 Mvar-4 10 Min. t2 t4 QC3 CLOSE 13 Mvar-5 10 Min. t5 OPEN 3 Mvar-6 5 Min. t6 CONDITION BC1 CLOSED BC2 OPEN CASE 3 SET VALUES FOR OPENING SET VALUES FOR CLOSING Mvar TIME Mvar TIME QC1 CLOSE 12 Mvar-3 5 Min. t3 OPEN 2 Mvar-4 10 Min. t4 QC2 CLOSE 13 Mvar-5 10 Min. t5 OPEN 3 Mvar-6 5 Min. t6 QC3 CLOSE 11 Mvar-1 5 Min. t1 OPEN 1 Mvar-2 5 Min. t2 CONDITION BC1 CLOSED BC2 CLOSED Volts TIME 0-120 sec 104.0% 120Sec t9 Volts TIME 0-5 sec 98.0% 5Sec t10 TIME 0-30 sec 30 Sec t13 CASE 4- NOT APPLICABLE FOR 33 kV SYSTEM T1,T2,T3 CLOSED DISABLE CASE # 4 CASE 5 OVER VOLTAGE SET VALUES FOR OPENING V1 34.32 kV OPEN CASE 6 SET VALUES FOR CLOSING UNDER VOLTAGE V2 32.34 kV OPEN CASE 7 LEADING POWER FACTOR SET VALUES FOR OPENING pf OPEN 0.95 PF CASE 8 CONDITION BC1 CLOSED BC2 CLOSE T3-OPEN SET VALUES FOR CLOSING Mvar SET VALUES FOR OPENING TIME Mvar TIME QC1 CLOSE 12 Mvar-3 5 Min. t3 OPEN 2 Mvar-4 10 Min. t4 QC2 CLOSE 13 Mvar-5 10 Min. t5 OPEN 3 Mvar-6 5 Min. t6 DISCHARGE TIME FOR RECLOSING SET VALUES FOR RECLOSING 11 Min. t11 5-20 min Time delay to close QCx after QTx closed 11 Min. t12 5-20 min Capacitor Discharging time 2 Sec. t14 9,999 ms t15 Time delay to implement settings changes 0 - 9999 ms Time delay to avoid simultaneous closing of QCx 38