SF2 CB SPECS • Effective KVAR for the installed single tuned filter =2450KVAR • System voltage= 13.8 KV 1 Circuit breaker sizing as per IEC 62271-100 1.1Input data for selection of Circuit Breaker as per IEC 62271-100 Input data SN 1 2 3 4 5 6 7 8 9 10 11 Item Filter fundamental current (A) Filter total current (ungrounded) A System voltage (KV) SWGR rated short circuit (KA) Short circuit duty(I ‘‘K) Inrush current t(KA) For filter Inrush frequency (KHZ) For filter Inrush I×F(KAKHZ) For filter Outrush current (KA) For filter Outrush frequency (KHZ) For filter Outrush I×F (KAKHZ) For filter Value 102.62 1.25 × 102.62= 128.28 13.8 25 KA 23.627 KA 0.588 0.257 0.151 0.606 0.257 0.156 Referance As per design As per IEEE Std 1036-2010, 4.2.1 DWG: XB.0536-ABB DWG: XB.0536-ABB As per ETAP As per Calculation As per Calculation As per Calculation As per Calculation As per Calculation As per Calculation 1.2Rating Selection for Circuit Breaker of SF2 M-SG201 A & B Capacitor bank Rating Selection for MV CB as per IEC 62271-100, 2008 Parameter Value Reference for values SN 1 CB type As per SWGR, Indoor S1, C2 2 CB class 3 Rated Voltage, Ur (Kv, rms) 17.5 4 Rated Normal current (A, rms) 1250 5 5.a Rated Short Circuit Breaking current (Isc) r.m.s. value of its a.c. component As per IEC 62271-100, clause:4.107 and clause:3.4.119 As per IEC 62271-1 2007 Clause 4.1 Check As per IEEE Std C37.06-2009, , tabel 1 As per IEC 62271-1-2007, Clause 4.4.1 Check As per IEEE Std C37.06-2009, tabel 1 31.5 As per IEC 62271-100, clause 4.101.1 As per IEEE Std C37.06-2009, tabel 1 DC time constant of the rated short-circuit breaking current, in milli seconds 45 As per IEC 62271-100, clause 4.101.2 6 TRV, (Peak value uc in KV 30 7 First pole to Clear factor (Kpp) 1.5 8 Rated short-circuit making current, kA peak 9 10 11 Rated duration of short-circuit in Seconds Preferred Peak inrush current (KA, peak) Preferred Inrush frequency (KHZ) As per IEC 62271-100, Table-1 on Page 52 and Table-24 on Page 126. Check IEEE std C37.06-2009, table2 IEC 62271-100Page 172 and Table 24 on Page 126. Check IEEE std C37.06-2009, table2 As per IEC 62271-100,clause 8.103.4 Check IEEE C37.06-2009, table1 This is only option with 40kA rating CB (of ABB) As per IEC 62271-100-2008, Table 9, page 61 As per IEC 62271-100-2008, Table 9, page 61 in kA 5.b 31.5 x 2.6 = 81.9 3 20 4.250