EARTHQUAKE RESISTANT DESIGN OF REINFORCED CONCRETE BUILDING BASED ON IS : 1893 (PART1)-2016 October, 2019 By Anil Kumar Sariar, Shamvwi Consultant 414, Jagat Trade Center, Fraser Road,Patna Email Id : shamvwi@gmail.com A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 1 Earthquake An earthquake is a sudden, rapid shaking of the Earth caused by the release of strain energy stored in rocks. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 2 The Elegant (but Unsafe) Central Library Building A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 3 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 4 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 5 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 6 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 7 Earthquake Design is special Earthquake Effects versus Wind Effects Droof Fw Movement under Building A. K. Sariar, Shamvwi Const. Pressure on Building Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 8 Earthquake Design is special Movement under the building Inertia forces at masses .. - mug (t) Mass m .. ug (t) Moving-base Structure A. K. Sariar, Shamvwi Const. Fixed-base Structure Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 9 Earthquake Design is special Movement under the building F Earthquake Behaviour :: Inelastic Droof Lateral Load F Wind Behaviour :: Elastic 0 A. K. Sariar, Shamvwi Const. Lateral Deformation D Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 10 Built Environment Inverted Pendulum A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 11 Built Environment Traditional design Under same earthquake shaking Max. response of structures different with T Earthquake Shaking A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 12 Built Environment Traditional design Design Earthquake Force Soil effect Flexible Wall Soil Original Building A. K. Sariar, Shamvwi Const. Flexible Soil Inverted Pendulum Model Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 13 Built Environment Behaviour Mass Stiffness Light Heavy Twist Swing with equal ropes A. K. Sariar, Shamvwi Const. Building with heavy mass on one side Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 14 Built Environment Behaviour Mass Stiffness Swing with unequal ropes A. K. Sariar, Shamvwi Const. Building Presentation on IS:1893:2016 / Oct. 2019 on slope Lecture 1 / slide 15 Buildings with Parking 230mm A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 16 Bullish India Sequence of Design Sequence of Construction Logical Sequence of Design & Construction A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 17 Bullish India Sequence of Design as practiced in many buildings in India Sequence of Construction Indian Practice of Design & Construction A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 18 Earthquake Resistance Structural Elements Structural Wall (Vertical Element) Floor Slab (Horizontal Diaphragm) Load Path Soil A. K. Sariar, Shamvwi Const. Foundation Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 19 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 20 Earthquake Design is special Earthquake Effects Damage expected in normal structures Earthquake-RESISTANT not Earthquake-PROOF A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 21 SECTION 1 This Section covers Foreword, Scope and References IS:1893-2016(Part I) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 22 Different Parts of IS:1893 Part 1: General Provisions and Buildings Part 2: Liquid Retaining Tanks – Elevated and Ground Supported Part 3: Bridges and Retaining Walls Part 4: Industrial Structures Including Stack Like Structures Part 5: Dams and Embankments A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 23 What does IS:1893 Cover? Specifies Seismic Design Force Other seismic requirements for design, detailing and construction are covered in other codes e.g., IS:4326, IS:13920, ... For an earthquake-resistant structure, one has to follow IS:1893 together with seismic design and detailing codes. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 24 Coverage of Part 1 General Provisions Applicable to all structures like building, parking structure and ancillary structures. Liquid retaining structure Bridges Embankments and retaining wall Industrial structures Concrete Masonry and earth dam A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 25 Major Changes Design Spectra are defined for natural period up to 6s; Same design response spectra are specified for all buildings, irrespective of material of construction. Dynamic analysis has been recommended for zone other than II. Effect of brick wall is included and expressions for the same has been provided. Consideration for soft storey is provided logically A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 26 Zone Map Zone II to Zone III have been defined. The Annex E of the code gives zone and Z for cities with population more than 3Lakh. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 27 Other Effects Earthquakes can cause damage in a number of ways. For instance: Vibration of the structure: this induces inertia force on the structure By inertia force, we mean mass times acceleration Landslide triggered by earthquake Liquefaction of the founding strata Fire caused due to earthquake Flood caused by earthquake The code generally addresses only the first & 3rd aspect A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 28 Seismic Hazard The criterion for seismic zones remains same as before Zone Area liable to shaking intensity II VI (and lower) III IV V VII VIII IX A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 29 Foundation and Soil Factor Soil has been classified as hard soil site, medium stiff soil sites and Soft soil site. Theses soil types has been classified on basis of soil type and N value and given in table 2 of the code. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 30 Response Spectrum During ground shaking, one can measure ground acceleration versus time (accelerogram) using an accelerograph Accelerograph is the instrument Accelerogram is the record obtained from it Accelerogram is the variation of ground acceleration with time (also called time history of ground motion) Unless otherwise mentioned, response spectrum is based on a linear elastic system A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 31 Typical Accelerograph This is a typical analog instrument. These days, digital instruments are becoming popular (photo from Earthquakes by Bolt) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 32 Typical Accelerograms From Dynamics of Structures by A K Chopra, Prentice Hall Time, sec A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 33 Response Spectrum (contd…) If the ground moves as per the given accelerogram, what is the maximum response of a single degree of freedom (SDOF) system (of given natural period and damping)? Response may mean any quantity of interest, e.g., deformation, acceleration T=2 sec, Damping =2% a(t)/g Ground motion time history A. K. Sariar, Shamvwi Const. Time, sec Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 34 Response Spectrum (contd…) By response we may mean any response quantity of interest to us, for example: Absolute acceleration of the mass Relative velocity of the mass with respect to base Termed as Velocity Response Spectrum Relative displacement of the mass with respect to base Termed as Acceleration Response Spectrum Termed as Displacement Response Spectrum Word Spectra is used to denote plural of Spectrum. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 35 Response Spectrum (contd…) Response spectrum is a very powerful tool. Uses of response spectrum: To obtain maximum response of a SDOF system (to the original accelerogram using which response spectrum was obtained) To obtain maximum response in a particular mode of vibration of a multi degree of freedom (MDOF) system It tells about the characteristics of the ground motion (accelerogram) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 36 Zone Factor (Z) The code uses a single parameter: Zone Factor (Z). Zone V Z 0.36 IV III II 0.24 0.16 0.10 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 37 Modal Mass It is that mass of the structure which is effective in one particular natural mode of vibration Can be obtained from the equation in Cl. 7.7.5.4 for simple lumped mass systems It requires one to know the mode shapes One must perform dynamic analysis to obtain mode shapes See example in next slides to appreciate the physical significance of Modal Mass A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 38 Seismic Weight (Cl.3.26) It is the total weight of the building plus that part of the service load which may reasonably be expected to be attached to the building at the time of earthquake shaking. It includes permanent and movable partitions, permanent equipment, etc. It includes a part of the live load Buildings designed for storage purposes are likely to have larger percent of service load present at the time of shaking. Notice the values in Table 10 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 39 Centre of Stiffness Cl. 4.5 defines Centre of Stiffness for single storey and multi Storey building separately as The point through which the resultant of the restoring forces of a system acts. For single Storey building it is one point while for multistory building, it is set of points on horizontal floor It is defined as: If the building undergoes pure translation in the horizontal direction (that is, no rotation or twist or torsion about vertical axis), the point through which the resultant of the restoring forces acts is A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 40 the Centre of Stiffness Centre of Rigidity Both Centre of Stiffness (CS) and Centre of Rigidity (CR) are the same terms for our purposes. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 41 Eccentricity Cl. 4.6 defines Static Eccentricity. This is the calculated distance between the Centre of Mass and the Centre of Stiffness. Under dynamic condition, the effect of eccentricity is higher than that under static eccentricity. Hence, a dynamic amplification is to be applied to the static eccentricity before it can be used in design. cl. 7.82 provides an amplification of 1.5 to the computed eccentricity (cl. 4.6). A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 42 Eccentricity (contd…) An accidental eccentricity is also considered because: The computation of eccentricity is only approximate. During the service life of the building, there could be changes in its use which may change centre of mass. Design eccentricity (cl.4.6) is obtained from static eccentricity by accounting for (cl.7.8.2) Dynamic amplification, and Accidental eccentricity A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 43 Dual System Consider buildings with shear walls and moment resisting frames. In 1984 version of the code, Table 5 (p. 24) implied that the frame should be designed to take at least 25% of the total design seismic loads. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 44 Dual System (contd…) In the new code several choices are available to the designer: When conditions of Cl. 4.9 are met: dual system. Example 1: Analysis indicates that frames are taking 30% of total seismic load while 70% loads go to shear walls. Frames and walls will be designed for these forces and the system will be termed as dual system. Example 2: Analysis indicates that frames are taking 10% and walls take 90% of the total seismic load. To qualify for dual system, design the walls for 90% of total load, but design the frames to resist 25% of total seismic load A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 45 Dual System (contd…) Conditions of Cl. 4.9 are not met. Here, two possibilities exist (see Footnote 4 in Table 7, p. 23): Frames are not designed to resist seismic loads. The entire load is assumed to be carried by the shear walls. In Example 2 above, the shear walls will be designed for 100% of total seismic loads, and the frames will be treated as gravity frames (i.e., it is assumed that frames carry no seismic loads) Frames and walls are designed for the forces obtained from analysis, and the frames happen to carry less than 25% of total load. In Example 2 above, the frames will be designed for 10% while walls will be designed for 90% of total seismic loads. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 46 Dual System (contd…) Clearly, the dual systems are better and are designed for lower value of design force. See Table 7 (p. 23) of the code. There is different value of response reduction factor (R) for the dual systems. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 47 Moment Resisting Frame Cl. 4.14 defines Ordinary and Special Moment Resisting Frames. Ductile structures perform much better during earthquakes. Hence, ductile structures are designed for lower seismic forces than non-ductile structures. For example, compare the R values in Table 9 IS:13920-2016 provides provisions on ductile detailing of RC structures for seismic performance. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 48 Number of Storeys (Cl.4.15) When basement walls are connected with the floor deck or fitted between the building columns, the basement storeys are not included in number of storeys. This is because in that event, the seismic loads from upper parts of the building get transferred to the basement walls and then to the foundation. That is, Columns in the basement storey will have insignificant seismic loads, and Basement walls act as part of the foundation. In new code, Cl. 7.6 requires height of building. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 49 Soft Story Cl. 4.20 defines Soft Storey It is defined as Storey having less lateral stiffness than that of upper Storey. It is calculated as storey shear divided Storey drift. Storey drift: It is relative displacement between floors of storey under consideration. Most Indian buildings will be soft storey as per this definition simply because the ground storey height is usually different from that in the upper storeys. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 50 Weak Storey (Cl 4.20.2) Note that the stiffness and strength are two different things. Stiffness: Force needed to cause a unit displacement. It is given by slope of the forcedisplacement relationship. Strength: Maximum force that the system can take Soft storey refers to stiffness Weak storey refers to strength Usually, a soft storey may also be a weak storey A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 51 Storey Drift Storey Drift defined in cl. 4.21 of the Code. Cl. 7.11.1 of the code provides: Storey drift not to exceed 0.004 times the storey height. Table 6 of the code provides: Storey drift not to exceed 0.002 times the storey height in case of soft storey. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 52 Earthquake Design Principle Large earthquakes are infrequent as compared to smaller earthquakes The criteria is: Minor (and frequent) earthquakes should not cause damage Moderate earthquakes should not cause significant structural damage (but could have some non-structural damage) Major (and infrequent) earthquakes should not cause collapse Read Earthquake Tip 8 (http://www.nicee.org/EQTips/EQTip08.pdf) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 53 Seismic Design Principle A well designed structure can withstand a horizontal force several times the design force due to: Overstrength Redundancy Ductility A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 54 Overstrength The structure yields at load higher than the design load due to: Partial Safety Factors Material Properties Partial safety factor on seismic loads Partial safety factor on gravity loads Partial safety factor on materials Member size or reinforcement larger than required Strain hardening in materials Confinement of concrete improves its strength Higher material strength under cyclic loads Strength contribution of non-structural elements Special ductile detailing adds to strength also A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 55 Redundancy Yielding at one location in the structure does not imply yielding of the structure as a whole. Load distribution in redundant structures provides additional safety margin. Sometimes, the additional margin due to redundancy is considered within the “overstrength” term. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 56 Ductility As the structure yields, two things happen: There is more energy dissipation in the structure due to hysteresis The structure becomes softer and its natural period increases: implies lower seismic force to be resisted by the structure Higher ductility implies that the structure can withstand stronger shaking without collapse A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 57 Response Reduction Factor Overstrength, redundancy, and ductility together lead to the fact that an earthquake resistant structure can be designed for much lower force than is implied by a strong shaking. The combined effect of overstrength, redundancy and ductility is expressed in terms of Response Reduction Factor (R) See Fig. on next slide. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 58 Δ Total Horizontal Load Total Horizontal Load Maximum force if structure remains elastic Fel Linear Elastic Response Maximum Load Capacity Fy Load at First Yield Fs Due to Ductility Non linear Response Due to Redundancy First Significant Yield Due to Overstrength Design force Fdes 0 Δw Δy Figure: Courtesy Dr. C V R Murty Δmax Roof Displacement (Δ) Response Reduction Factor A. K. Sariar, Shamvwi Const. Maximum Elastic Force (Fel) Design Force (Fdes) Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 59 Cl. 6.1.3 & Cl 6.1.4. Imply that the earthquake resistant structures should generally be ductile. IS:13920-2016 gives ductile detailing requirements for RC structures. IS:13920-2016 provides condition for stronger column and weaker beam. Sum of Ultimate flexural capacity of Columns and that of Beams >=1.4. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 60 Soil Structure Interaction (Cl. 6.1.5) If there is no structure, motion of the ground surface is termed as Free Field Ground Motion Normal practice is to apply the free field motion to the structure base assuming that the base is fixed. This is valid for structures located on rock sites. For soft soil sites, this may not always be a good assumption. Presence of structure modifies the free field motion since the soil and the structure interact. Hence, foundation of the structure experiences a motion different from the free field ground motion. The difference between the two motions is accounted for by Soil Structure Interaction (SSI) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 61 Direction of Ground Motion During earthquake shaking, ground shakes in all possible directions. Direction of resultant shaking changes from instant to instant. Basic requirement is that the structure should be able to withstand maximum ground motion occurring in any direction. We already discussed that for most structures, main concern is for horizontal vibrations rather than vertical vibrations. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 62 Direction of Ground Motion (contd…) One does not expect the peak ground acceleration to occur at the same instant in two perpendicular horizontal directions. Hence for design, maximum seismic force is not applied in the two horizontal directions simultaneously. If the walls or frames are oriented in two orthogonal (perpendicular) directions: It is sufficient to consider ground motion in the two directions one at a time. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 63 Liquefaction Cl.6.3.5.3 It points out that in case of loose or medium dense saturated soils, liquefaction may take place. Sites vulnerable to liquefaction require Liquefaction potential analysis. Remedial measures to prevent liquefaction. Else, deep piles are designed assuming that soil layers liable to liquefy will not provide lateral support to the pile during ground shaking. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 64 Liquefaction Potential Information given in cl.6.3.5.3 and Table 2 on Liquefaction Potential is very primitive: A simplified method is given in Annex F for determining liquefaction potential analysis. It is common these days to use SPT or CPT results for detailed calculations on liquefaction potential analysis. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 65 Vertical Acceleration Cl.6.4.6 It is estimated with S/g=2.5 Vertical acceleration has been taken two-third of horizontal acceleration A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 66 Regular and Irregular Configuration (Cl. 7.1) The statement of Cl. 7.1 is an attempt to emphasize the importance of structural configuration for ensuring good seismic performance. Good structural configuration has implications for both safety and economy of the building. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 67 Regular versus Irregular Configuration Tables 5 and 6 list out the irregularities in the building configuration Table 5 and Fig. 3 for Irregularities in Plan Table 6 and Fig. 4 for Irregularities in Elevation A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 68 Building Plans with Orthogonal Systems A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 69 walls Building Plans with Non-Orthogonal Systems A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 70 Torsional Irregularity Uneven Distribution of mass Heavy Mass Vertical Components of Seismic Resisting System A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 71 Torsional Irregularity (contd…) Geometrically building may appear to be regular and symmetrical, but may have irregularity due to distribution of mass and stiffness. It is better to distribute the lateral load resisting elements near the perimeter of the building rather than concentrate these near centre of the building. See fig. on next slide A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 72 (a) (b) Arrangement of shear walls and braced frames-not recommended. Note that the heavy lines indicate shear walls and/or braced frames Fig. From NEHRP Commentary (a) (b) Arrangement of shear walls and braced frames- recommended. Note that the heavy lines indicate shear walls and/or braced frames A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 73 Torsional Irregularity (contd…) Table 5 says that torsional irregularity exists if the drift (lateral displacement) at one end of the building is more than 1.5 times the minimum of the drift at the two ends. Δ1 Δ2 Torsional irregularity when Δ2> 1.5[(Δ1)] A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 74 Re-entrant Corner When an otherwise regular building has a large re-entrant corner, wings of the building tend to vibrate in a manner different from that of the entire building. Hence, building treated as irregular when offset dimension exceeds 15% of the total dimension. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 75 Re-entrant Corner (contd…) Fig 3 of code shows the plan irregularity as hereunder Note that upper parts of the figure show 15% to 20%. It will save confusion if the figure showed only 15%. Code has taken fig from NEHRP Commentary. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 76 Diaphragm Discontinuity Diaphragm discontinuity changes the lateral load distribution to different elements as compared to what it would be with rigid floor diaphragm. Also, it could induce torsional effects which may not be there if the floor diaphragm is rigid. Observe the top two figures of page 20. Again, these are from NEHRP Commentary and not traced correctly in our code. See next slide. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 77 Diaphragm Discontinuity (contd…) RIGID FLEXIBLE O DIAPHRAGM P E N DIAPHRAGM Vertical Components of Seismic Resisting System Discontinuity in Diaphragm Stiffness A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 78 Out-of-Plane Offsets This is a very serious irregularity wherein there is an out-of-plane offset of the vertical element that carries the lateral loads. Such an offset imposes vertical and lateral load effects on horizontal elements, which are difficult to design for adequately. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 79 Out-of-Plane Offsets (contd…) Shear Wall Out-of-Plane Offset in Shear Wall A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 80 Stiffness Irregularity It leads to soft storey condition. Analysis is done for both bare frame and infill frame. Drift is restricted to 0.2%. Structural wall density is kept to minimum 2% of plan area in both direction. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 81 Mass Irregularity Mass irregularity will be induced by the presence of a heavy mass on a floor, say a swimming pool. Note that the mass irregularity in IS1893 has been defined when weight of a floor exceeds 150% the weight of the adjacent floor. NEHRP defines it when the weight exceeds 150% of that of the adjacent floor. Dynamic analysis is performed. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 82 Stiffness & Mass Irregularity A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 83 Vertical Geometric Irregularity Buildings with vertical offsets will fall in this category. Also, a building may have no apparent offset, but its lateral load carrying elements may have irregularity. For instance, shear wall length may suddenly reduce. When building is such that larger dimension is above the smaller dimension, it acts as an inverted pyramid and is undesirable. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 84 Vertical Geometric Irregularity A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 85 Vertical Geometric Irregularity A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 86 Problems with Irregularities In buildings with vertical irregularity, load distribution with building height is different from that in Cl. 7.7.1. Dynamic analysis is required. In buildings with plan irregularity, load distribution to different vertical elements is complex. Floor diaphragm plays an important role and needs to be modelled carefully. A good 3-D analysis is needed. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 87 Problems with Irregularities (contd…) In irregular building, there may be concentration of ductility demand in a few locations. Special care needed in detailing. Just dynamic analysis may not solve the problem. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 88 Design Lateral Force (Cl. 7.6) two methods: Equivalent Static Method and response spectrum method. There have been instances of designer calculating seismic design force for each 2-D frame separately based on tributary mass shared by that frame. This is erroneous since only a fraction of the building mass is considered in the seismic load calculations. See fig next slide A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 89 Mass that causes Earthquake Force in X-Direction EQx Mass being considered for calculation of inertia force due to earthquake EQx Plan of building A. K. Sariar, Shamvwi Const. Calculation of design seismic force on the basis of tributary mass on 2-D frames leads to significant underdesign. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 90 Design Lateral Force (Cl. 7.6) (contd…) Now, Cl. 7.6.1 makes it clear that one has to evaluate seismic design force for the entire building first and then distribute it to different frames/ walls. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 91 Fundamental Natural Period (Cl. 7.6) Major changes in empirical equations for natural period. Now: For frame buildings without brick infills For all other buildings, including frame buildings with brick infill panels: T = 0.075 h0.75,for RC frame bldgs T = 0.085 h0.75,for steel frame bldgs T = 0.09h/(d) For RC structural wall: T = 0.075h^0.75/(Aw) > = 0.09h/(d) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 92 Vertical Distribution of Seismic Load (Cl. 7.6.3) Lateral load distribution with building height depends on In low and medium rise buildings, Natural periods and mode shapes of the building Shape of design spectrum Fundamental period dominates the response, and Fundamental mode shape is close to a straight line (with regular distribution of mass and stiffness) For tall buildings, contribution of higher modes can be significant even though the first mode may still contribute the maximum response. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 93 Vertical Distribution of Seismic Load (Cl. 7.6.3) (contd…) Hence, NEHRP provides the following expression for vertical distribution of seismic load Qi VB Wi hik n k W h j j j 1 Where k = 1 for T ≤ 0.5sec, and k = 2 for T ≥ 2.5 sec. Value of k varies linearly for T in the range 0.5 sec to 2.5 sec. In IS:1893 over the years, k = 2 has been taken regardless of natural period This is conservative value and has been retained in current edition of the code also. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 94 Horizontal Distribution... (Cl. 7.6.4) Floor diaphragm plays an important role in seismic load distribution in a building. Consider a RC slab (see figure next slide) For horizontal loads, it acts as a deep beam with depth equal to building width, and the beam width equal to slab thickness. Being a very deep beam, it does not deform in its own plane, and it forces the frames/walls to fulfil the deformation compatibility of no in-plane deformation of floor. This is rigid floor diaphragm action. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 95 Concept of Floor Diaphragm Action Fig. from Jain S K, “A Proposed Draft for IS:1893…Part II: Commentary and Examples,” J. of Struct Engg, Vol. 22, No. 2, July 1995, pp 73-90 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 96 Horizontal Distribution... (Cl. 7.7.2) (contd…) Implications of rigid floor diaphragm action: In case of symmetrical building and loading, the seismic forces are shared by different frames or walls in proportion to their own lateral stiffness. See figure next slide. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 97 Lateral Load Distribution Due to Rigid Floor Diaphragm: Symmetric Case – No Torsion Fig. from Jain S K, “A Proposed Draft for IS:1893…Part II: Commentary and Examples,” J. of Struct Engg, Vol. 22, No. 2, July 1995, pp 73-90 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 98 When building is not symmetrical, the floor undergoes rigid body translation and rotation. See figure next slide A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 99 Analysis of Forces Induced by Twisting Moment (Rigid Floor Diaphragm) Fig. from Jain S K, “A Proposed Draft for IS:1893…Part II: Commentary and Examples,” J. of Struct Engg, Vol. 22, No. 2, July 1995, pp 73-90 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 100 Rigid Diaphragm Action In-plane rigidity of floors is sometimes misunderstood to mean that The beams are infinitely rigid, and The columns are not free to rotate at their ends. Rotation of columns is governed by out-of-plane behaviour of slab and beams. (a) In-plane floor deformation, (b) Outof-plane floor deformation. Fig. from Jain S K, “A Proposed Draft for IS:1893…Part II: Commentary and Examples,” J. of Struct Engg, Vol. 22, No. 2, July 1995, pp 73-90 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 101 Buildings without Diaphragm Action When the floor diaphragm does not exist, or when the diaphragm is extremely flexible as compared to the vertical elements The load can be distributed to the vertical elements in proportion to the tributary mass A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 102 Flexible Floor Diaphragms There are instances where floor is not rigid. “Not rigid” does not mean it is completely flexible! Hence, buildings with flexible floors should be carefully analyzed considering in-plane floor flexibility. Note 1 of Cl. 7.7.2.2 gives the criterion on when the floor diaphragm is not to be treated as rigid. Definition of Flexible Floor Diaphragm (Cl. 7.7.2.2) Fig. from Jain S K, “A Proposed Draft for IS:1893…Part II: Commentary and Examples,” J. of Struct Engg, Vol. 22, No. 2, July 1995, pp 73-90 A. K. Sariar, Shamvwi Const. (Plan View of Floor) In-plane flexibility of diaphragm to be considered when Δ2>1.5{0.5(Δ1+ Δ2)} Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 103 Lateral Load Distribution Considering Floor Diaphragm Deformation: Vertical Analogy Method Fig. from Jain S K, “A Proposed Draft for IS:1893…Part II: Commentary and Examples,” J. of Struct Engg, Vol. 22, No. 2, July 1995, pp 73-90 A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 104 Analysis for Flexible Floor Diaphragm Buildings (contd…) Alternatively, one can take the design force as envelop of (that is, the higher of) the two extreme assumptions, i.e., Rigid diaphragm action No diaphragm action (load distribution in proportion to tributary mass) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 105 Requirement of Dynamic Anal. Cl. 7.8.1 Criteria for Dynamic Analysis Seismic Zone Regular Building Irregular Buildings II Ht < 15m For all Height III,IV and V For all building A. K. Sariar, Shamvwi Const. For all building Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 106 Why Dynamic Analysis? Expressions for design load calculation (cl. 7.6.3) and load distribution with height based on assumptions Fundamental mode dominates the response Mass and stiffness distribution are evenly distributed with building height Thus, giving regular mode shape A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 107 Why Dynamic Analysis? (contd…) In tall buildings, higher modes can be quite significant. In irregular buildings, mode shapes may be quite irregular Hence, for tall and irregular buildings, dynamic analysis is recommended. Note that industrial buildings may have large spans, large heights, and considerable irregularities: These too will require dynamic analysis. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 108 Dynamic Analysis as per Cl. 7.7.5.4 New code gives this method in a more systematic manner in Cl.7.7.5.4 The analysis procedure is valid when a building can be modeled as a lumped mass model with one degree of freedom per floor (see fig. next slide) If the building has significant plan irregularity, it requires three degrees of freedom per floor and the procedure of Cl. 7.7.5.4 is not valid. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 109 Lumped Mass Model for Cl. 7.7.5.4 X3(t) X2(t) X1(t) A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 110 At the end of this section Dynamic analysis requires considerable skills. Just because the computer programme can perform dynamic analysis: it is not sufficient. One needs to develop in-depth understanding of dynamic analysis. There are approximate methods (such as Rayleigh’s method, Dunkerley’s method) that one should use to evaluate if the computer results are right. It is not uncommon to confuse between the units of mass and weight when performing dynamic analysis. Leads to huge errors. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 111 Bldgs with Soft Storeys Cl. 7.10 Most of the time, soft storey building is also the weak storey building. In the code, distinction between soft storey and weak storey has not been made. Soft/weak storey buildings are well-known for poor performance during earthquakes. In Bhuj earthquake of 2001, most multistorey buildings that collapsed had soft ground storey. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 112 Bldgs with Soft Storeys Cl. 7.10 (contd…) Fig from Murty et al, 2002 Open ground story Bare frame Notice that the soft-storey is subject to severe deformation demands during seismic shaking. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 113 Buildings with Soft Storeys Cl. 7.10 (contd…) This clause gives two approaches for treatment of soft storey buildings. First approach is dynamic analysis considering B/W and inelstic deformation. It is a very sophisticated approach. Based on non-linear analysis. Code has no specifications for applying this approach. Cannot be applied in routine design applications with current state of the practice in India. Structural wall density >=2% in both direction. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 114 Deformations Cl. 7.11 For a good seismic performance, a building needs to have adequate lateral stiffness. Low lateral stiffness leads to: Large deformations and strains, and hence more damage in the event of strong shaking Significant P-D effect Damage to non-structural elements due to large deformations Discomfort to the occupants during vibrations. Large deformations may lead to pounding with adjacent structures. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 115 Deformations Cl. 7.11 (contd…) Stiff structures, even though attract more seismic loads, have generally performed better during past earthquakes. The current code also restricts inter-storey displacement to 0.004 times the storey height under design seismic loads. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 116 Deformations Cl. 7.11 (contd…) Note that real displacement in a strong shaking will be much larger than the displacement calculated for design seismic loads Because design seismic force is a reduced force. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 117 Computation of Drift Note that higher the stiffness, lower the drift but higher the lateral loads. Hence, For computation of T for seismic design load assessment, all sources of stiffness (even if unreliable) should be included. For computation of drift, all sources of flexibility (even if unreliable) should be incorporated. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 118 Computation of Drift (contd…) Thus, in computation of drift: Stiffness contribution of non-structural elements and non-seismic elements (i.e., elements not designed to share the seismic loads) should not be included. This is because such elements cannot be relied upon to provide lateral stiffness at large displacements All possible sources of flexibility should be incorporated, e.g., effect of joint rotation, bending and axial deformations of columns and shear walls, etc. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 119 Compatibility of Non-Seismic Elements (Cl. 7.11.2) Important when not all structural elements are expected to participate in lateral load resistance. Examples include flat-plate buildings or buildings with pre-fabricated elements where seismic load is resisted by shear walls, and columns carry only gravity loads. During 1994 Northridge (Calif.) earthquake, many collapses due to failure of gravity columns. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 120 Compatibility of Non-Seismic Elements (Cl. 7.11.2) (contd…) During shaking, gravity columns do not carry much lateral loads, but deform laterally with the shear walls due to compatibility imposed by floor diaphragm (see Fig. next slide) Moments and shears induced in gravity columns due to the lateral deformations may cause collapse if adequate provision not made. ACI Code for RC design has a separate section on detailing of gravity columns to safeguard against this kind of collapse. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 121 Compatibility of Non-Seismic Elements (Cl. 7.11.2) (contd…) Shear Wall Fig. V Agrawal Shear Wall Floor Slab A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 122 Compatibility of Non-Seismic Elements (Cl. 7.11.2) (contd…) Since deflections are calculated using design seismic force (which is a reduced force), the deflection is to be multiplied by R. Multiplier R could be debated since it will only ensure safety against Design Basis Earthquake. For safety against Maximum Considered Earthquake, multiplier should be (2R). A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 123 Separation Between Adjacent …Cl. 7.11.3 During seismic shaking, two adjacent units of the same building, or two adjacent buildings may hit each other due to lateral displacements (pounding or hammering). This clause is meant to safeguard against pounding. Multiplication with R is as explained earlier: since deflection is calculated using design seismic force which are reduced forces. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 124 Separation Between Adjacent …Cl. 7.11.3 (contd…) Pounding effect is much more serious if floors of one building hit at the mid height of columns in the other building. Hence, when two units have same floor elevations, the multiplier is reduced from R to R/2. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 125 Separation Between Adjacent …Cl. 7.11.3 (contd…) Potential pounding location Building 2 Building 1 a Potential pounding location Building 2 Building 1 b Pounding in situation (b) is far more damaging. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 126 Foundations Cl. 7.12.1 This is a preventive use of foundation types vulnerable to differential settlement. In zones III,IV and V, ties to be provided for isolated spread footings and for pile caps Except when footings directly supported on rock Cl 7.12.1 of the code which states: Isolated R.C.C. footing without tie beams, or unreinforced strip foundation shall not be permitted in soft soils with N<10. This note is applicable for all seismic zones. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 127 Cantilever Projections Cl. 7.12.2 All projections (vertical and horizontal) are most vulnerable to damage during earthquakes. Being cantilevers, there is no redundancy, and hardly any ductility. Design of projections for five times the seismic coefficient. A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 128 Compound Walls Cl. 7.12.3 To be designed for design horizontal coefficient Ah with I=1 and R=1,S/g=2.5 and Z=1.25Z A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 129 Moment Resisting Frame Cl. 4.14 defines Ordinary and Special Moment Resisting Frames. Ductile structures perform much better during earthquakes. Hence, ductile structures are designed for lower seismic forces than non-ductile structures. For example, compare the R values in Table 9 IS:13920-2016 provides provisions on ductile detailing of RC structures for seismic performance. A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 General Principles and Design Criteria (Section 6) Four main sub-sections Cl. 6.1: General Principles Cl. 6.2: Assumptions Cl. 6.3: Load Combination and Increase in Permissible Stresses Cl. 6.4: Design Spectrum This lecture covers sub-sections: Cl. 6.2 and Cl. 6.3 A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Cl.6.2 Assumptions Earthquake consists of a number of waves having different frequency. No Resonance occurs due to earthquake waves. There have been instances such as the Mexico earthquake of 1985 which have violated above assumption (a). A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Assumption b) A strong earthquake takes place infrequently. A strong wind also takes place infrequently. Hence, the possibility of strong wind and strong ground shaking taking place simultaneously is very very low. It is common to assume that strong earthquake shaking and strong wind will not occur simultaneously. Same with strong earthquake shaking and maximum flood. A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Assumption c) on Modulus of Elasticity Modulus of elasticity of materials such as concrete, masonry and soil is difficult to specify Its value depends on Stress level Loading condition (static versus dynamic) Material strength Age of material, etc A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Load Combination 0.9DL 1.5EL Horizontal loads are reversible in direction. In many situations, design is governed by effect of horizontal load minus effect of gravity loads. In such situations, a load factor higher than 1.0 on gravity loads will be unconservative. Hence, a load factor of 0.9 specified on gravity loads in the combination 4) Many designs of footings, columns, and positive steel in beams at the ends in frame structures are governed by this load combination Hence, this combination has been made very specific in IS:1893-2016. A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Liquefaction Potential Information given in cl.6.3.5.3 and Table 2 on Liquefaction Potential is very primitive: A simplified method is given in Annex F for determining liquefaction potential analysis. It is common these days to use SPT or CPT results for detailed calculations on liquefaction potential analysis. A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Moment of Inertia Cl.6.4.3.1 For structural analysis, moment of inertia is taken as 70% of Igross of Column 35% of Igross of Beam A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Vertical Acceleration Cl.6.4.6 It is estimated with S/g=2.5 Vertical acceleration has been taken two-third of horizontal acceleration A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Equations for Design Spectrum Equivalent Static Method A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Equations for Design Spectrum Dynamic Analysis Method A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Equations for Design Spectrum Equivalent Analysis Method A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Equations for Design Spectrum Dynamic Analysis Method A. K. Sariar,Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Thank you A. K. Sariar, Shamvwi Const. Presentation on IS:1893:2016 / Oct. 2019 Lecture 1 / slide 143