CD00965 USERS’ Manual MATRIX UW-MTX2.5, 2.5G, 3.5, 3.5EC LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE UT Protection &Control Unit for U-POWER Omega system LARSEN &TOUBRO Copyright c 2010 Larsen & Toubro.All Right Reserved. REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 2 OF 86 CD00965 Congratulations... U are on the verge of being the proud user of U-POWER Omega Air Circuit Breaker equipped with one of the World’s most advanced Protection & Control Unit UW MTX 2.5, 2.5G, 3.5, 3.5EC While U-POWER redefines Safety and User-friendliness in ACBs, UW-MTX offers the State-of-the-art in Circuit Protection & Control. Feature-by-feature, designed with USERS in mind. Before proceeding further ... UW-MTX offers a host of integrated features and easy navigation. Please go through section 4-1- ‘Navigation Overview’ to get a quick view of the unit’s diverse functions. This USERS’ Manual is a generic guide to normal site installation, operation and maintenance. U-POWER Omega ACBs and their accessories should only be installed, operated and maintained by competent and properly authorized personnel. MATRIX units are pre-configured for factory settings with Group 1 activated. These are LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF generic settings and provide Overload & Short Circuit protections. REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY:HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 3 OF 86 CD00965 Contents: 1.Identification 2.Feature List 3.Protection Characteristics 4.Overview 4.1 Menu Navigation Overview 4.2 Family Overview 5.Configuration 5.1 Unit Settings 5.2 System Settings 5.3 Protection 6.Reading Data 6.1 6.2 6.3 6.4 Metering Values View Records IO Status Active Modules 7.Supplementary Modules 8.Control Connections 9.Add-On Modules 9.1 Metering Module 9.2 Communication Modules LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 10.Simulation kit 11.Fault Diagnosis 12.Self Diagnostic Test 13.List of CAT nos 14.Memory Map REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: HRA APPROVED BY: HRA 300202311 PROJECTION CD00965 SHEET 4 OF 86 CD00965 1. Identification UW-MTX 2.5 UW-MTX 2.5G Identification Label Power ON LED Fault Indication LEDs Navigation Keys Escape key Query key E/F Test key } OLED Display UW-MTX 3.5EC UW-MTX 3.5 LARSEN & TOUBRO LIMITED *Communication Module AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Test Kit Connector Configurator Metering Module *Modbus/ Zigbee/ Profi bus Module 1-1 REVISIONS LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. DATE SCALE MTX RELEASE USERS MANUAL - 08.02.2010 U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 5 OF 86 CD00965 2.Feature List Feature no. FEATURES/MODULE SUPPORTED Protections 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Current Metering Voltage Metering Trip records Event records Additional protections Power Metering Maximum Demand Reverse Power Trip Circuit Supervision Earth Leakage Restricted Earth Fault Digital Input Output Analog Output Relay Zone Selective Interlock Configurator (Smart Card) Temperature Module Modbus UW-MTX VERSIONS 2.5 2.5G 3.5 LSI √ LSIGN √ √ √ √ LSIGN √ * √ √ √ * * * * * * * * * * * * * 20 Profibus * 21 Zig-bee * 3.5EC LSIGN √ √ √ √ √ √ √ √ * * * * * * * * * √ * * Metering display UW-MTX2.5/2.5G/3.5/3.5EC P&C Unit Parameter Screen abbreviation Current # Voltage # Frequency Power Factor # # LARSEN & TOUBRO LIMITED Energy # AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Power Max Demand # ^ Temperature Details I1,I2,I3,IN,Ig Phase, Neutral and Earth IΔ, IREF Earth Leakage,Restricted EF Current Imax Maximum running current per phase % Load Percentage Loading per phase Avg.I Average phase current Phase-Neutral voltage V1,V2,V3 Max V Maximum voltage per phase V12,V23,V31 Ph-Ph Voltage Max V12,V23,V31 Maximum Ph-Ph Voltage Avg. Vp-p Average Ph-Ph Voltage Avg Vp-n Average Ph-N Voltage F System Frequency P.F System Power Factor W Active power per phase and total (kW) VAr Reactive Power per phase and total (kVAr) Apparent Power per phase and total (kVA) VA Active Energy per phase and total (kW) Wh Reactive Energy per phase and total (kVArh) VArh Apparent Energy per phase and total (kVAh) VAh Active Energy(kW) Wh Reactive Energy (kVArh) VArh Apparent Energy (kVAh) VAh Temperature per phase (˚C) ø * Features/Modules available as optional # Requires Metering module ^ Requires TM Module. 2-1 REVISIONS LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. DATE SCALE MTX RELEASE USERS MANUAL - 08.02.2010 U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 6 OF 86 CD00965 Protection Settings UW-MTX2.5 Parameter Overload (Phase) Overload (Neutral) Short Circuit Directional SC Instantaneous Earth Fault Restricted EF Earth Leakage LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Under Current Current Unbalance Under Voltage Protection: Enable/Disable Pick-Up (Ir)=In x …for I2T, I4T, SI, LI / VI Curves Delay (tr) in s Pre-alarm Thermal Memory ON/OFF Protection: Enable/Disable Pick-Up IN= Ir x … Pre-alarm Delay (tr) in s Protection: Enable/Disable Double S/C ON/OFF I2T ON/OFF Pick-Up Lo, Is= In x … Pick-Up Hi, Is= In x… Delay Hi (ts) Delay Lo (ts) Pre-alarm Cold Pick-Up: ON/OFF Cold Delay Protection: Enable/Disable Direction:Top / Bottom I2T: ON/OFF Pick - up (Is) : In x… Delay (ts) Pre-alarm Cold Pick - Up: ON/OFF Cold Delay Protection: Enable/Disable Pick - up (Ip)=In x… Protection: Enable/Disable I2T: ON/OFF Pick-Up (Ig) = In x… I2T OFF (tg) I2T ON (tg) Pre-alarm Cold Pick-Up: ON/OFF Cold Delay Mode: Trip/Alarm/Both Protection: Enable/Disable I2T:OFF/ON Pick-Up (Ig) = In x… forI2t ON, I2 t OFF I2T OFF (tg) I2T ON (tg) Pre-alarm Cold pick-Up:ON/OFF Mode: trip/Alarm/Both Protection: Enable/Disable Pick-Up (IΔ) Delay Mode: Trip/Alarm/Both Protection: Enable/Disable Pick-Up = Ir x… Delay Mode: Trip/Alarm/Both Protection: Enable/Disable Pick- Up = In x… Delay Mode: Trip/Alarm/Both Protection: Enable/Disable Pick up (Vs) =Vn x … Delay Vs reset Mode: Trip/Alarm/Both UW-MTX2.5G UW-MTX3.5 UW-MTX3.5EC Factory Settings ü ü ü ü .4 to 1 In in steps of .05 .5-1-2-4-6-12-18-24-30 .5 to .95 in steps of .05xIr ü x - ü ü ü ü ü ON ü Disable .5 to 2 in steps of .5 .5 to .95 in steps of .05xIr Same as Overload Phase ü ü ü ü ü ü ü ü ü ü ü ü 0.6 to 12 In in steps of 0.05 0.6 to 12 In in steps of 0.05 20-100-200-300-400 ms 20-100-200-300-400 ms 0.5 to 0.95 in steps of 0.05xIs ü ü ü ü 100 ms to 10s in steps of 100ms x - x - ü ü ü ü ü ü ü 0.6 to 12 In in steps of .05 20-100-200-300-400 ms 0.5 to 0.95 in steps of .05xIs ü ü 100 ms to 10s in steps of .05xIs ü ü ü 1.5 to 10 in steps of .1 ; 10 to 15 in steps of 1 x x x x x x - ü ü ü ü ü ü 0.2-0.3-0.4-0.5-0.6 100ms to 1 s in steps of 100 ms 100-200-300-400 ms .5 to .95 in steps of .05xIg ü ü ü 100ms to 5 s in steps of .1s ü x x x x x - ü ü ü ü ü ü .1 to .6 in steps of .1 100 ms to 5 s in steps of .1s 100-200-300-400 ms .5 to .95 in steps of .05xIg 60 ms to 10 s in steps of 20ms ü ü ü ü 0.3 to 30A in steps of 0.1 A 100-200-300-400-500 ms √ √ √ √ 0.2 to 0.8 in steps of 0.05 1 to 255 s in steps of 1 s √ √ √ √ 10 to 90%in steps of 5% 500 ms to 60s in steps of 0.5s √ √ √ √ 0.7 to 0.95 in steps of 0.01 100 ms to 5s in steps of 100 ms 1.01 to 1.04 xVs √ Enable 1 (I2T) 12 0.5Ir √ Disable Enable OFF OFF 6 In 6 In 400 ms 400 ms 0.5Is OFF 1s Disable Disable Enable OFF 0.6 400ms 400ms .8xIg OFF Both Disable Disable Disable Disable Disable - 2-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 7 OF 86 CD00965 Over Voltage Voltage Unbalance Residual Voltage Under Frequency Over Frequency Rev Power Leading PF Lagging PF MD Active MD Reactive MD Apparent Phase Sequence Bkr Failure LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPERTY OF Trip Records Display Communication Query Protection: Enable/Disable Pick-Up (Vs)= Vn x… Delay Vs reset Protection: Enable/Disable Pick- Up (Vs) = Vn x… Delay Vs reset Mode: Trip/Alarm/Both Protection: Enable/Disable Pick-Up(Vs)=Vn x… Delay Vs reset Mode: Trip/Alarm/Both Protection: Enable/Disable Pick-Up (Fn) Delay Reset Freq Mode: Trip/Alarm/Both Protection: Enable/Disable Pick-Up (Fn) Delay Reset Freq Mode: Trip/Alarm/Both Protection: Enable/Disable Pick - Up = Pn x… Delay Mode: trip/Alarm/Both Protection: Enable/Disable Pick- Up = Pf x… Delay Mode: trip/Alarm/Both Protection: Enable/Disable Pick - Up = Pf x… Delay Mode: trip/Alarm/Both Protection: Enable/Disable Type Pick-Up = En x… Mode: Trip/Alarm/Both Protection: Enable/Disable Type Pick - Up= En x… Mode: Trip/Alarm/Both Protection: Enable/Disable Type Pick-Up=En x… Mode: Trip/Alarm/Both Protection: Enable/Disable Delay Mode: Trip/Alarm/Both Protection: Enable/Disable Delay Last 5 Records x x - x - x x x x x x x x x x x x - x - x - √ √ x x x x x x x x x - √ √ 1.05 to 1.5 Vn in steps of .01 100ms to 5s in steps of 100ms .95 to .99 Vs in steps of 0.01 √ √ 5 to 20% in step of 1% 500ms to 60 s in steps of .5s .95 to 0.99 Vs in steps of 0.01 √ √ √ √ 0.15/0.2/0.25/0.3/0.4 100ms to 5s in steps of .1s 0.95 to 0.99 Vs in steps of 0.01 √ √ √ √ 45-50 Hz in steps of .1Hz 1-30 s in steps of 0.1s 1.01 to 1.05 Fn in steps of 0.01 √ √ √ √ 50-55 Hz in steps of 0.1 Hz 1-30 s in steps of 0.1s 0.95 to 0.99 Fn in step of 0.01 √ √ √ √ 0.05 to 0.4 in steps of 0.01 100ms-20s in steps of 0.1s √ √ √ √ 0.5 to 0.99 in a steps of 0.01 1/2/3/4/5 s √ √ √ √ 0.5 to 0.99 in a steps of 0.01 1/2/3/4/5 s √ √ √ √ Deliver/Receive 0.4 to 1 in steps of 0.01 √ √ √ √ Deliver/Receive 0.4 to 1 in steps of 0.01 √ √ √ √ Deliver/Receive 0.4 to 1 in steps of 0.01 √ √ √ √ 100ms 5s in steps of 100ms √ √ √ √ 50 ms to 2 s in steps of 0.05 s √ √ OLED display Mod-bus/Profi bus/Zig-bee Modules - - * √ √ √ √ √ Supplimentary Module Relay,DIO,Analog,ZSI,EL,REF,TM,TCS - - * * Time based set group Test kit connectivity AUX supply(24V DC) √ √ √ √ √ √ √ √ √ √ √ √ Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable Disable - 2-3 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 8 OF 86 CD00965 3. Protection Characteristics 2 Overload I T 10000 1000 Trip Time (s) 100 30 s 24 s 10 18 s Tolerance Trip Time: ±20% 12 s 6s 4s 1 2s LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 1s 0.5 s 0.1 1 2 1.2 3 4 5 6 7 8 9 10 Current Multiples (x Ir) 3-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 9 OF 86 CD00965 Protection Characteristics 4 Overload I T 100000 10000 1000 Trip Time (s) 100 10 30 s 24 s 18 s 12 s 1 6s 4s 2s 1s 0.1 Tolerance Trip Time: ±20% LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.5 s 0.01 1 2 1.2 3 4 5 6 7 8 9 10 Current Multiples (x Ir) 3-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 10 OF 86 CD00965 Protection Characteristics Overload SI 10000 1000 Trip Time (s) 100 30s 24s 18s 12s 10 6s 4s 2s Tolerance Trip Time: ±20% 1 1s LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.5s 0.1 1 2 1.2 3 4 5 6 7 8 9 10 Current Multiples (xIr) 3-3 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 11 OF 85 CD00965 Protection Characteristics Overload LI/VI 10000 1000 Trip Time (s) 100 30s 24s 18s 10 12s 6s 4s 2s 1 Tolerance Trip Time: ±20% LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 1s 0.5s 0.1 1 2 1.2 3 4 5 6 7 8 9 10 Current Multiples (x Ir) 3-4 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA 300202311 PROJECTION CD00965 CHECKED BY: AnS APPROVED BY: SSK SHEET 12 OF 86 CD00965 Protection Characteristics 2 Short Circuit I T ON 10000 1000 12 0.6 Trip Time (s) 100 10 1 0.4 0.3 0.2 0.1 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.1 0.02 0.01 0.01 0.1 1 50 10 Current Multiples (x In) 3-5 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 13 OF 86 CD00965 Protection Characteristics Short Circuit I2T OFF 10000 1000 Trip Time (s) 100 10 12 0.6 1 0.4 0.3 0.2 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.1 0.1 0.02 0.01 0.01 0.1 1 10 50 Current Multiples (x In) 3-6 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 14 OF 86 CD00965 Protection Characteristics Instantaneous 100 10 Trip Time (s) 1.5 15 1 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.1 0.01 0.01 0.1 1 10 Current Multiples (x In) 3-7 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY:HRA 300202311 PROJECTION CD00965 CHECKED BY: AnS APPROVED BY : SSK SHEET 15 OF 86 CD00965 Protection Characteristics 2 Earth FaultI T ON 10000 1000 0.2 0.3 100 0.4 0.5 0.6 0.8 2.4 Trip Time (s) 10 1 0.4 s LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.1 0.1 s 0.01 0.8 0.01 0.1 2.4 1 10 50 Current Multiples (x In) 3-8 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 16 OF 86 CD00965 Protection Characteristics 2 Earth Fault I T OFF 100 0.2 Trip Time (s) 10 0.6 1 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 0.1 0.1 0.01 0.1 1 10 50 Current Multiples (x In) 3-9 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA 300202311 PROJECTION CD00965 CHECKED BY: AnS APPROVED BY: SSK SHEET 17 OF 86 08.02.2010 DATE SCALE - DRAWN BY:HRA DEPT: APPROVED BY: SSK PROJECTION Frequency I-frame In Ue voltage Maint Period Maintenance Incoming Poles Ph seq System Settings MTX Unit Configurator Modbus Config. Mode Date & time Communication Event Recorder Sign Convention Max Demand Setting P/W Commands P/W Language Contrast Unit Settings (Password protected) AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF LARSEN & TOUBRO LIMITED, SHEET 18 OF Overload Short circuit Directional SC Instantaneous Earth Fault Ntrl Overload Restricted EF Earth Leakage Under Current Current Unbal Current Protection Set Group 1 Set Group 2 Protection View Mode Settings Under Voltage Over Voltage Voltage Unbal Residual Volt Voltage Protection Digital I/Os Relay Temperature Modbus Configurator Analog O/P ZSI TCS Earth Leakage ZIG-Bee Profibus Restricted EF Module Settings Trip Record Event Record Maintenance View Records Restore Settings Current Voltage Frequency Power Factor Power Energy Max Demand Temperature Metering : 0A : 0A : 0A Under Freq Over Freq Frequency Protection Maint OP Clear MD Change Set Group Factory Setting Clear Max. I Clear Max. V Clear Energies (Password protected) I1 I2 I3 Current Rev Power Leading PF Lagging PF MD Active MD Reactive MD Apparent Phase Sequence Bkr failure Other Protection Active Modules Power Protection Default Settings ACB status FSD status Digital I/O 1 Digital I/O 2 Digital I/O 3 Digital I/O 4 Relay 1 Relay 2 Relay 3 Relay 4 IO Status 4.Overview 4.1 Menu Navigation Overview REVISIONS 4-1 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER 300202311 CHECKED BY:AnS CD00965 86 CD00965 DATE 08.02.2010 SCALE - DRAWN BY: HRA DEPT: CHECKED BY: AnS APPROVED BY: SSK PROJECTION 300202311 Metering Module - Provides voltage inputs for metering & protections Relay - Configurable 4 Outputs per module - Max. 4 modules per UW-MTX - DIN rail / Base mountable module AO Analog Output - 4 Configurable Output - Analog output in range of 4-20 mA REF Restricted Earth Fault Protection - Detects zone of Earth fault - Needs specified external CTs - DIN rail / Base mountable module EL Earth Leakage Protection - Range 0.3A to 30A - Needs specified external CTs - DIN rail / Base mountable module ZSI Zone Selective Interlock -Provides time Discrimination for Short circuit & Earth fault CAN BUS ( Communication protocol for UW-MTX Family) PS Power Supply (24Vdc) - 2 outputs Available 200mA(for UW-MTX) & 650mA (for UW-MTX + modules) - Operating voltage 85-265 Vac - DIN rail / Base mountable module Digital I/O Configurator Module - 4 Inputs & 4 Outputs per module -for configuring the - Max. 4 modules per UW-MTX unit through - DIN rail / Base mountable module smart card Communication Module Modbus/Zigbee/Profibus Aux supply 4.2 Family Overview AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF REVISIONS LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. MATRIX USERS’ MANUAL U-POWER CD00906 SHEET 19 OF 86 TCS Trip Circuit Supervision - Monitors healthiness of Shunt Trip Circuit - DIN rail / Base mountable module TM Temperature Protection - Monitors terminal temperature - 2 selectable temperature modules - Mounted inside breaker CD00906 CD00965 5. Configuration - Incorrect / Inadequate Configuration can result in lack of protection and/or nuisance tripping / erroneous signaling. CAUTION - Restrict the knowledge of setting passwords within authorised personnel only. To configure UW-MTX P&C unit, the display needs to be ON. Display switches ON when, - the breaker is carrying 10% of rated current (In) in any one phase or - 24 Vdc supply is connected to terminals AS+ & AS-. Access the settings: Tools required: Screw Driver (Tip width 3 mm) To access the settings remove the P&C unit cover and do the changes after powering upthe P&C Unit. P&C Units type UW-MTX are pre-configured to default factory settings (ref. page 2-2,2-3). Default settings are common for both Set Groups 1 & 2. The settings can be changed using Navigational keys on the UW-MTX overlay .Function of different navigation keys are given below. É T ? Open the P&C cover Current PWR O/L S/C INST I1 I2 I3 :0A :0A :0A E/F UP button NTRL Back Key Left Select ALRM Right TRIP Down T For configuring the UW-MTX P&C unit, enter to the configuration Mode .Configuration of the unit can be done through the unit overlay, configurator module and smart card and also through modbus module. Menu LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Current I1 I2 I3 :0A :0A :0A Settings View Records Metering Settings Config Mode View Mode Password **** (Press “SEL” key to Select particular Menu.) Config Mode Password 0 1 2 3 4 5 6 7 8 9 MTX Unit Configurator Modbus MTX Unit Protection System Settings Unit Settings Default password: “0000” 5-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 20 OF 86 CD00965 5.1 Unit Settings Unit Settings Date & Time Date & Time Communication Event Recorder UP/DOWN Year Month Date Date & Time Communication Event Recorder LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING Communication Device ID Parity Baud Type Baud Rate Device ID Parity Pickup Trip Alarm :1 : None : Manual : 9.6 K :1 :None : Enable : Enable : Enable Event Recorder Module Rmve : Enable Relay I/P : Enable IO Input : Enable The Events which needs to be captured under Event Recorder shall be made Enable here. Unit Settings Max Demand Max Demand Settings P/W Commands P/W Integration : 30 min Interval : 5 min MD Integration period and interval can be programmed here New Password Unit Settings THIS DRAWING AND DESIGN IS THE PROPE RTY OF Communication Event Recorder Unit Settings UP/DOWN : 11 : 02 : 09 MOD/Profi bus communication parameters can be set in this menu. Date & Time Communication Event Recorder UP/DOWN Hour Minute Second (Press “SEL” key to Select particular Menu.) Date,Time can be programmed in Date & Time Menu . Unit Settings UP/DOWN : 09 : Oct : 12 Date & Time Max Demand Settings P/W Commands P/W **** New Password 0 1 2 3 4 5 6 7 8 9 Save Settings? Yes No Default Settings password is “0000”. Settings password can be changed to a new password with this option. Settings password is used to access the Unit ,System and Protection Settings of the P&C unit. 5-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 21 OF 85 CD00965 Unit Settings Unit Settings New Password Max Demand Settings P/W Commands P/W UP/DOWN **** Auto SET GRP MODE SG1-SG2 SG2-SG1 Contrast Auto SET GRP Maintenance Hour Minute : 15 : 10 Password Password **** 0 1 2 3 4 5 6 7 8 9 Maintenance Installation Date Breaker Installation Date shall be programmed here. Unit Settings LARSEN & TOUBRO LIMITED SG1-SG2 To Enable the auto Set Group option, configure “MODE” as “Enable” and set the time in SG1-SG2 at which Set Group 2 becomes the active Set Group and SG2-SG1 at which Set Group 1 becomes active Set group of the Unit. These Set Groups will be switched automatically in the specified timings. Unit Settings AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING No OLED Screen contrast can be adjusted in this screen. Contrast Auto SET GRP Maintenance THIS DRAWING AND DESIGN IS THE PROPE RTY OF Yes 30 % Unit Settings UP/DOWN 0 1 2 3 4 5 6 7 8 9 Contrast Contrast Auto SET GRP Maintenance UP/DOWN Save Settings? New Password Default commands password is “0000”. Commands password can be changed to a new password with this option. Command P/W shall be used for executing commands under “Restore Settings”. Same password can be used for Earth Fault test by the test button in the unit. Unit Settings UP/DOWN ...Contd. Day Light Saving Auto SET GRP Maintanence Day Light Saving DST Mode Start DST End DST Start DST Month Date Hour :3 :1 :2 Start and End date of Day light saving and DST hours can be programmed in this menu. CAUTION After changing Unit settings escape from the menu, save the settings and reset the power of the unit once to get it applied. 5-3 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 22 OF 86 CD00965 5.2 System Settings System Settings System Settings Frequency I-Frame In Frequency I-Frame In : 50Hz : 4000A : 4000A : 60Hz : 4000A : 4000A (Press “SEL” key to Select particular Menu.) Frequency can be set as per the system UP/DOWN System Settings System Settings I-Frame In Ue Voltage I-Frame In Ue Voltage : 1600A : 1600A : 415V : 1600A : 1000A : 415V I-frame and In values shall be programmed as per the below look-up table for different breaker and ratings . Breaker Frame Size Breaker rating(A) I-Frame In 1,2,3 400 630 800 800A 400 630 800 1,2,3 1000 1250 1600 1600 1000 1250 1600 1 2000 2500 3200 3200 2000 2500 3200 2,3 2000 2500 3200 4000 4000 2000 2500 3200 4000 3 5000 6300 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING 5000 6300 I-frame,In values shall be programmed correctly for proper metering and protection of the P&C unit UP/DOWN THIS DRAWING AND DESIGN IS THE PROPE RTY OF 6300 System Settings System Settings Ue Voltage : 415V Maint Period : 6mths Maintenence : Disable Ue Voltage : 415V Maint Period : 6mths Maintenence : Enable Maintenance feature and the period can be programmed here.When “Maintenance” is Enable, after the specified“Maint Period”, P&C unit will give the warning message“Maintenance Required” Similarly do all other settings in System settings CAUTION After changing System settings escape from the menu ,save the settings and reset the power of the unit once to get it applied. 5-4 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 23 OF 85 CD00965 5.3 Protection Protection settings include basic and advanced protections Basic protections: 1. Overload 2. Short circuit 3.Instantaneous 4.Earth fault 5.Neutral Overload Advanced protections:1. Under Current 5. Over Voltage 9. Over Frequency 13. Leading PF 17. MD Apparent 2. Current Unbalance 6. Voltage Unbalance 10. Reverse Power 14. Lagging PF 18. Earth Leakage 3. Directional Short Circuit 4. Under-voltage 7. Residual Voltage 8. Under-frequency 11. Breaker Failure 12. Phase sequence 15. MD Active 16. MD Reactive 19. Restricted Earth Fault Refer Section: 2 for the protection features available for various UW-MTX ranges Protection Settings are available in Set Group 1 and Set Group 2. By default Set Group 1 will be active.To manually change the Set Group use the command “Change Set Group” in Restore Settings. To enable the Set Group change automatically enable “Auto Set GRP” option in Unit Settings. Protection Settings Protection Set Group 1 Set Group 1 Set Group 2 I Protection V Protection Freq Protection I Protection Overload Short Circuit Directional SC Set Group 1 Power Protection Other Protection Overload Overload Protection : Enable O/L Char : I2T Pick-up(Ir) : 1 In Delay (tr) : 30s Pre-alarm : 0.95Ir Thm - mem : Off Thm-mem ‘On’ enables the P&C Unit to trip early if the fault reoccurs*. UP/DOWN I Protection Overload Short Circuit Directional SC LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Short Circuit Short Circuit Protection : Disable Double S/C : Off I2t : Off Pk-up Lo(Is) : 6In Pk-up Hi(Is) : 6In Delay Lo(ts) : 400ms Delay Hi(ts) : 400ms Pre-alarm : 0.50Is Cold Pk-up : Off Double S/C ‘ON’ ,activates two different time delays corresponding to high and low pick up values. With Double S/C off, system will follow high pick up and delay for the fault. Cold pick up can be enabled to avoid false tripping of the unit against high inrush current. While Cold pick up is ‘ON’, P&C unit will not issue trip when fault current is less than double the pick up value till the specified cold delay elapses. Short Circuit Cold Delay Short Circuit : 1s * For a finite time duration only. CAUTION It is safe to change the protection setting when the breaker is in service position. Commissioning & maintenance should be carried out by skilled technician only. Before touching the device, ensure the person operating is free of electrostatic charge Upstream protection equipment has to be set in a way, so that upstream faults are interrupted safely. 5-5 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 24 OF 85 CD00965 Protection ...Contd. I Protection I Protection Overload Short Circuit Directional SC Protection Direction I2t : Disable : Top : Off I Protection Pick-up (Is) : 6 In Delay (ts) : 100ms Pre-alarm : 0.50Is I Protection Cold Pk-up Cold Delay : Off : 1s Directional SC protects system from the short Circuit in the reverse direction. UP/DOWN I Protection Instantaneous Instantaneous Earth Fault Neutral Overload Protection : Enable Pick-up (Ip) : 8 In UP/DOWN I Protection Instantaneous Earth Fault Neutral Overload UP/DOWN Earth Fault Earth Fault Protection : Disable I2t : Off Pick-up (Ig) : 0.30In I2T Off (tg) : 300ms I2T On (tg) : 100ms Pre-alarm : 0.80Ig Earth Fault Cold Pk-up Cold Delay Mode : Off : 1s : Both Cold pick up ‘On’ in EF enables the P&C unit not to trip for double the pick up current for the specified time delay. I Protection Neutral Overload Instantaneous Earth Fault Neutral Overload Protection : Disable Pick-up (IN) : 1 Ir Pre-alarm : 0.80Ir UP/DOWN LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF I Protection Under Current Restricted EF Earth Leakage Under Current Protection Pick-up Delay : Disable : 0.8Ir : 1s Under Current Mode : Alarm UP/DOWN 5-6 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 25 OF 86 CD00965 Protection ...Contd. I Protection Current Unbal Current Unbal Protection Pick-up Delay : Disable : 90%In : 2s Current Unbal Mode : Alarm Saving the Settings in P&C Unit After configuring the protection settings, press É key to escape from menu and confirm the changes in “Save Settings” screen .After doing all the protection settings come back to the Set Group screen and press the escape key again. “Save in Progress” message confirms that Set Group has saved. Save Settings ? Yes No I Protection É Overload Short Circuit Directional SC Set Group 1 I Protection É V Protection Freq Protection SAVE In progress É LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Protection Settings will be applied immediately after confirming the changes. If any alarm or pick up is present in system 5 minutes prior to the changes “Settings not Applied” warning will be displayed, and all the settings will be applied after 5 min (if no pick up or alarm reoccurred). To apply the settings immediately , reset the unit power supply once . 5-7 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 26 OF 86 CD00965 Advanced Protection Settings V Protection V Protection Under Voltage Over Voltage Voltage Unbal Residual Volt Under Voltage,Over Voltage,Voltage Unbalance ,Residual Voltage are available under Voltage Protection UP/DOWN Under Voltage Under Voltage Protection : Disable Pick-up (Vs) : 0.75Vn Delay : 1s Vs reset Mode : 1.050Vs : Alarm UP/DOWN Over Voltage Over Voltage Protection : Disable Pick-up (Vs) : 1.25Vn Delay : 1s Vs reset Mode : 0.95Vs : Alarm UP/DOWN Voltage Unbal Voltage Unbal Protection : Disable Pick-up (Vs) : 10%Vn Delay : 2s Vs reset Mode : 0.95Vs : Alarm LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF UP/DOWN Residual Volt Residual Volt Protection : Disable Pick-up (Vs) : 0.20Vn Delay : 2s Vs reset Mode : 0.95Vs : Alarm 5-8 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY:HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 27 OF 86 CD00965 Advanced Protection ...Contd. Frequency Protection Freq Protection Under Freq Protection : Disable Pick-up (Fn) : 45Hz Delay : 10s Under Freq Over Freq Under Freq Reset Freq Mode : 1.05Fn : Alarm UP/DOWN Freq Protection Over Freq Under Freq Over Freq Protection : Disable Pick-up (Fn) : 55Hz Delay : 10s Over Freq Reset Freq Mode : 0.95Fn : Alarm Power Protection Rev Power Power Protection Protection Pick-up Delay Rev Power Leading PF Lagging PF : Disable : 0.20Pn : 2s Rev Power Mode : Alarm UP/DOWN Leading PF Power Protection Protection : Disable Pick-up (Fn) : 0.75 Delay : 3s Rev Power Leading PF Lagging PF Leading PF Mode : Alarm LARSEN & TOUBRO LIMITED Power Protection AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF UP/DOWN Lagging PF Protection Pick-up Delay Rev Power Leading PF Lagging PF : Disable : 0.75 : 2s Lagging PF Mode : Alarm 5-9 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 28 OF 86 CD00965 Advanced Protection ...Contd. Other Protection MD Active Other Protection Protection Type Pick-up MD Active MD Reactive MD Apparent : Disable : Deliver : 0.4En MD Active Mode : Alarm UP/DOWN Other Protection MD Reactive Protection Type Pick-up MD Active MD Reactive MD Apparent : Disable : Deliver : 0.4En MD Reactive Mode : Alarm UP/DOWN Other Protection MD Apparent Protection Type Pick-up MD Active MD Reactive MD Apparent : Disable : Deliver : 0.4En MD Apparent Mode : Alarm UP/DOWN Other Protection Phase Sequence Protection Delay Mode Phase Sequence Bkr Failure : Disable : 1s : Alram LARSEN & TOUBRO LIMITED Other Protection AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF UP/DOWN Bkr Failure Protection Delay Phase Sequence Bkr Failure : Disable : 2s After doing the settings press “ “key to confirm the settings in Save Settings 5-10 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 29 OF 86 CD00965 5.4 Module Settings Module Settings Digital I/Os Digital I/Os Relay Temperature Digital I/Os D I/O 1 D I/O 2 D I/O 3 Module 30 31 :Enable :Enable :Enable For Digital I/O, Relay Modules make the Module settings “Enable” to activate the connected Module. UP/DOWN Module Settings Relay Temperature Modbus Modbus Modbus Module :Enable Protl Type :RTU Parity : None Stop Bit :2 Baud Type :Manual Baud Type :2.4 k Make the Modbus settings in the menu Program rest of the module settings as explained above . 5.5 Restore Settings The following functions are available under “Restore Settings” 1.Maint. Operation 5.Clear Max I 2.Clear MD 6.Clear Max V 3.Change SetGroup 7.Clear Energies 4.Factory Setting 5.5.1.Maintenance Operation Display Restore Settings Unit Settings Module Settings Restore Settings Maint. Operation Clear MD Change Set Group Password Maint. Operation Maintenance: Yes **** LARSEN & TOUBRO LIMITED Enter the Command P/W here.(Default Password is “0000”) AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF After doing each maintenance, access maintenance in restore settings and give “Yes” command. This resets the “Maintenance Required” warning message which will be displayed the specified maintenance period. 5.5.2 Clear MD, Clear Max I, Clear Max V, Clear Energies These commands will clear the maximum values the P&C unit has captured during its operation. 5-11 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 30 OF 85 CD00965 Display MTX Unit Unit Settings Module Settings Restore Settings Restore Settings Password Maint.Operation Clear MD Change Set Group **** Claer MD Clear MD : Yes (Default Password is “0000”) Save Settings? Yes No Do the same for clearing Max I, Max V and Max Energies 5.5.3 Change Set Group There are 2 Set Groups available for the protection Settings. By default Set Group 1 will be active. To change the Set Group the below procedure should be followed. Restore Settings MTX Unit Unit Settings Module Settings Restore Settings Maint. Operations Clear MD Change Set Group Password **** Change Set Group Active SG : SG2 (Default Password is “0000”) Save Settings? Yes No After changing the Set Group Save the settings. 5.5.4 Factory Settings Factory Settings can be restored by this option. MTX Unit Restore Settings Unit Settings Module Settings Restore Settings Clear MD Change Set Group Factory Settings Password **** Factory Settings Restore Set : Yes LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF (Default Password is “0000”) Save Settings? Yes No 5-12 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 31 OF 86 CD00965 5.6 Default Settings Default display settings can be set in this menu. Select the Metering screen and set the screen duration as per the requirement. MTX Unit Default Settings LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Module Settings Restore Settings Default Settings I-SCR 1 I-SCR 2 Voltage Ph-N 03 s 03 s 03 s 5-13 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 32 OF 86 CD00965 6. Reading Data 6.1 Metering values The metering screen can be accessed as shown. Menu Current I1 I2 I3 Setting View Records Metering : 0A : 0A : 0A Metering Metering Metering Metering Metering Metering P Fower Factor Power Frequency Energy Current Voltage Frequency By Selecting each of these parameters, corresponding metering values will be displayed Max Demand Temperature Phase Sequence 6.2 View Records Menu Current I1 I2 I3 Settings Setting View Records Metering : 0A : 0A : 0A ViewMenu Records Trip Records Event Records Maintenance Trip record stores latest five trip information which includes Cause, Date, Time of the trip. It also records the pick up and delay values set for the particular protection. Current, Voltage, Frequency, PF values during the fault time is also recorded in the trip record. Event records store information of the latest events. Events records has three sub division viz. Protection, Module and Other. “Protection” stores latest 10 events related to protection based events viz. alarm, pick up, trip. “Module” stores latest 5 events related to modules. “Other” stores latest 5 records which includes set group change, maintenance. LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 6.3 IO Status Menu Current I1 I2 I3 Metering IO Status Active Modules : 0A : 0A : 0A IO Status indicates the status of ACB, FSD status (open/close) and Input / Output status of Relay and DIO module. 6-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 33 OF 86 CD00965 6.4 Active Modules Menu Current I1 I2 I3 Settings View Records Metering : 0A : 0A : 0A Menu Metering IO Status Active Module LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Active modules shows all the modules connected with the release. 6-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 34 OF 86 CD00906 7.Supplementary Modules Total 9 supplementary modules are available with UW-MTX3.5 series of P & C units. RELAY DIGITAL INPUT/OUTPUT (DI/O) POWER SUPPLY (PS) ZONE SELECTIVE INTERLOCKING(ZSI) ANALOG OUTPUT (AO) TRIP CIRCUIT SUPERVISION (TCS) TCS LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF EARTH LEAKAGE (EL) RESTRICTED EARTH FAULT (REF) TEMPERATURE (TM) 7-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 35 OF 86 CD00906 Supplementary Modules UW-MTX3.5 series is supported by supplementary modules, which enhance the functionality of the P&C unit and offer a complete system solution. I/P 1 I/P 4 I/P 3 I/P 2 PWR COMM 1 3 2 4 MNT NODE T O/P 1 O/P 2 O/P 3 O/P 4 DIGITAL I/O Installation,configuration and operation of these modules is explained below. Installation: 70.2 PS, AO, DI/O, RELAY, REF, EL, TCS & ZSI are suitable for base mounting and DIN rail (35mm) mounting. TM module is screw fixing. Self Diagnostic Test: All the modules (Except PS Module) are having self diagnostics test button provided on the front facia. Self test of the supplementary module can be performed by removing the CAN communication connection of the P&C unit with the PS module and 24V dc supply connected. (which is looped with the supplementary modules) After test RED led indicates module is not healthy and GREEN indicates module is healthy. 85 101.3 7.1 PS Module a. For basic protections, UW-MTX works independent of external power supply. b. For additional features like Communication and external Modules, 24 Vdc supply is required. c. CAN (Controlled area network) communication is provided through this module. It is the internal communication bus in UW- MTX unit and rest of the supplementary modules can be looped with it. LARSEN & TOUBRO LIMITED Output 1: 24V dc, 650 mA: for connecting matrix unit + supplementary modules Output 2: 24V dc, 200 mA: only for connecting matrix protection & control unit ,ZSI or TM module AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF PS provides 24Vdc auxiliary supply for Input voltage 85-265 Vac Refer Section 8-1 for connection details. One PS is adequate for one unit of UW-MTX and five supplementary modules connected to it. 7-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 36 OF 86 CD00906 7.2 DI/O (Digital I/O Module) Separate digital Input & Output contacts are provided through DI/O modules. Each DI/O offers 4 Digital Inputs and 4 Relay Outputs. UW-MTX3.5 series can accept up to 4 DI/O modules for cascading the Input/Outputs as per user requirements. To enable DI/O module ,access the Module settings in the P&C unit and set the corresponding parameters. The module ID can be set using the DIP switches provided on the front facia of the module . DIP switch position” UP” means corresponding module is enabled . Also enable the same module in the MATRIX unit in Module settings. The I/Ps & O/Ps are configurable to boolean logic equations. Total 16 combinations of these equation are possible to assign. Contact Ratings: Input contacts: 24 Vdc or 230 V ac Output contacts: 24 Vdc or 230 V ac, 6A (resistive load) For connection details, refer Section 8-1. Configuration I1 I2 I3 Settings Menu Current : 0A : 0A : 0A Settings View Records Metering Config Mode View Mode Config Mode 0 1 2 3 4 5 6 7 8 9 MTX Unit Configurator Modbus MTX Unit System Settings Unit Settings Module Settings Select “Module Settings” D I/O 1 Digital I/Os D I/O 1 D I/O 2 D I/O 3 **** Enter the password “0000”(default) Press “SEL” key in the overlay Password Password Module 30 31 : Enable : Enable : Enable Module Settings Digital I/Os Relay Temperature Select “Digital I/Os” D I/O 1 32 33 34 : Enable : Enable : Level D I/O 1 35 36 37 : Level : Level : Level UT AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF Digital I/Os 36 37 Input Type :Level :Level :24 V Input Type: 24Vdc / 230 VAC 30-33: digital Inputs with fixed boolean logics. These inputs can be enabled. 34-37: digital outputs with fixed boolean logics.These inputs can be set as level or pulse. 7-3 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 37 OF 86 CD00906 Digital Input/Output configuration: Digital I/O module D I/O 1 D I/O 2 D I/O 3 D I/O 4 Digital Input 30-33 40-43 50-53 60-63 Relay Output 34-37 44-47 54-57 64-67 Boolian logic for Digital Inputs/Output: DIGITAL I/P2 D2 OUTPUT 1 OUTPUT 3 OUTPUT 4 OUTPUT 2 DIGITAL I/P3 DIGITAL I/P4 OP4=D4 OP1=D1 NAND D2 OP2=D1 NOR D2 OP3=D3 XOR D4 D3 D4 UT AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF DIGITAL I/P1 D1 7-4 REVISIONS LARSEN & TOUBRO LIMITED, DATE UN-RS3 USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 38 OF 86 CD00906 7.3 Relay module Relay module has 4 potential free relay contacts (2 change over contacts and 2 NO) which are configurable. The ratings of the relay is 230V, 6A. With the help of this, user can manouevre interlocks in the distribution system. Configuration: Relay module can be configured through Menu section as detailed below. The module ID can be set using the DIP switches provided on the front facia of the module . DIP switch position” UP” means corresponding module is enabled . Enable the same module in the MATRIX unit in Module settings. . Also the output option can be set to Level or Pulse . Module settings Relay Settings Digital I/Os Relay Temperature Relay Settings O/P Config Bkr Operation Relay Relay 1 Relay 2 Relay 3 Relay Relay 3 Relay 4 Bkr. Operation Select “Relay” Relay 1 Relay 1 Module: Enable 70 : Level 71 : Level 71 72 73 : Level : Level : Level Similarly, change other parameters Here 70-73 are the relay outputs of Relay 1 Relay outputs: Relay module Relay Relay Relay Relay Relay Outputs (Assigned in P&C unit) 70-73 80-83 90-93 A0-A3 1 2 3 4 Relay module o/p configuration details: UT AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF Each relay module will have 4 configurable outputs. Under o/p configuration, individual relay module output can be configured in either alarm or trip mode for different protections detailed below. 1. Overload 2. Short circuit 3. Instantaneous 4. Earth fault 5. Neutral overload 6. Reverse power 7. Phase sequence 8. Under voltage 9. Over voltage 10. Under frequency 11. MD (active) 12. Breaker Operation Short form given in the P&C Unit :OL_AL, OL_TR :SC_AL, SC_TR :INST_TR :EF_AL, EF_TR :N OL_AL, N OL_TR :RP_AL, RP_TR :PhSeq_AL, PhSeq_TR :UV_AL, UV_TR :OV_AL, OV_TR :UF_AL, UF_TR :MDkw_AL, MDkw_TR :BKR_OP , BKR_CL 7-5 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 39 OF 86 CD00906 Breaker operations (open & close) can be performed using the relay contacts. Note: Once any of these listed configuration parameter is assigned to a relay output, that option will not be available for the remaining relay modules (output contacts). 7.4 TM (Temperature Module) TM (Temperature Module) converts inputs from thermistors and provides breaker terminal temperature data in UW-MTX3.5 series P&C unit. TM is located inside U-POWER ACB and senses temperature through thermistors connected in the breaker terminals. Hence, o o ‘Temperature Rise protection’ is a factory installed option. The temperature protection range is from 85 C to 115 C. Configuration: TM module can be configured through Menu section as detailed below. Module settings Temperature Digital I/Os Relay Temperature Module1 : Enable Module2 : Enable Protection : Enable Temperature Mode Prealm Pickup : Both : 0.5C : 85°C Similarly, change other parameters. Select “Temperature” 7.5 Analog output (AO) module: Analog output module is parallel metering option for panel display meters. It gives an output of 4-20mA to which analog ammeter and voltmeter can be connected. 4 mA corresponds to zero current or voltage metering . 20 mA output corresponds to 1.5 time set I-frame value of current or 1.5 times set Vn value in Protection and Control Unit. AO communicates with Matrix Protection & Control unit on internal CAN BUS protocol. Refer page 8-1 for connection details. Configuration: AO module can be configured for the following parameters through Menu section as detailed below. 2. Y-Phase I 5. Y-Phase V 3. B-Phase I 6. B-Phase V UT AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF 1. R-Phase I 4. R-Phase V Analog O/P Module Settings Module : Enable O/P Param 1: R-Ph I O/P Param 2: R-Ph V Modbus Configurator Analog O/P Analog O/P O/P Param 2: R-Ph V O/P Param 3: Y-Ph I O/P Param 4: Y-Ph V Select “Analog O/P” 7-6 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 40 OF 86 CD00906 7.6 ZSI (Zone Selective Interlocking) module ZSI module communicates with UW-MTX3.5 series on internal CAN BUS protocol. Total 20 downstream & 3 upstream breakers can be supported. It gives protection against Short circuit & Earth faults. Refer page 8-1 for connection details. Configuration: ZSI module can be configured through Menu section as detailed below, Module settings ZSI Smart Card Analog O/P ZSI Module : Enable Direction ZSI: On ZSI Config : Both Select “ZSI” ZSI configuration “Both” will enable ZSI for ground fault and short circuit Sout ZSI MODULE 1 For ZSI feature, P&C units are hardwired as shown and they communicate with each other through restraining signals. UT AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF In ZSI active mode , time delays in Short circuit and earth fault are set progressively higher towards the main incomer ACB. In the given diagram, ACB 1 has the highest delay of 400ms for Short Circuit. ACB 2,ACB 3 are having delays 200ms, 100ms respectively. ZSI MODULE 2 For fault at Y, ACB3 will send restraining signal to ACBs 1 & 2 and ACB 3 will trip in minimum ZSI time delay ie 50ms , and the fault will be cleared . ACB 2,ACB 3 will remain closed. If ACB 3 fails to trip ACB 2 will issue trip in another 50ms. For faults at intermediate locations like X, therewill be no restraining signal from down stream breakers ACB2, ACB 3 and hence ACB1 will trip in 50 ms instead of preset 400ms delay. ZSI MODULE 3 Sin Gout ACB 1 Gin S. C. Time Delay 400 ms X Sout ACB 2 Gout Sin Gin Sout Gout Sin Gin S. C. Time Delay 200 ms ACB 3 S. C. Time Delay 100 ms Y 7-7 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 41 OF 86 CD00906 ZSI Connection details In ZSI module Sout and Gout are the short circuit and Ground fault restraining signal outputs and Gin and Sin are the input signals to the modules. In a multilevel system all Sout signals in the lowest level shall be connected in parallel and fed to the Sin of next higher level module. Similarly the connections to be made for Gout and Gin . Matrix P&C unit with ZSI module can support maximum 20 down stream and 3 upstream breakers . Wire specifications: Description - PVC sheathed shielded twisted pair wire Size - 7/0.2 tinned Copper Shield - Braided tinned copper ID: 4.6 max Impedance - approx. 76 Ohm/km at 200 MHZ No. of twists - Approx. 11 twists / ft. 7.7 TCS (Trip Circuit Supervision) This module continuously monitors healthiness of Shunt Trip Circuit. User can set it in alarm, trip or both mode for malfunction indication as required. Separate NO relay contact is provided which can be used by user. This module supports entire range of shunt coils from 24V-415V. Refer pages 8-1, 8-5 & 8-6 for connection details. Module Settings TCS Analog O/P ZSI TCS Module : Enable Protection : Enable Mode : Both UT AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE RTY OF Select “TCS” 7-7 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 42 OF 86 CD00906 7.8 EL (Earth Leakage) module: EL (Earth leakage protection module) monitors Earth leakages, through special Current transformers recommended by L&T. EL communicates with UW-MTX3.5 series on internal CAN BUS protocol. For external indications, it offers change-over contact P1, P2, P3 (24Vdc /240Vac, 5A). This can be used in standalone mode. DIP Switches are provided on the front facia of the module to configure the pick-up & delay settings.Refer Section 7-10 for the settings when used as a stand alone module. Refer page 8-1 for connection details. Module Settings Earth Leakage Earth Leakage ZSI TCS Earth Leakage Module : Enable Protection : Enable Mode : Both Mode Pick-up Delay : Both : 0.5A : 500ms Select “Earth Leakage” 7.9 REF ( Restricted earth fault) module: REF (Restricted earth fault module) is used for Earth faults protection in restricted zone i.e. upstream of the breaker upto the transformer. It monitors the faults through a set of special CTs recommended by L&T. REF communicates with UW-MTX3.5 series on internal CAN bus protocol. For external indications, it offers a change-over contact OP1-OP2 (24Vdc/240Vac,5A). This module can be used as standalone module. DIP switches are provided on the front facia of module to configure the pick-up & delay settings. Module settings Restricted EF Profibus ZIG-Bee Restricted EF Module : Enable Protection : Enable Mode : Both Module settings Module settings Pick-up I2T Off I2T On I2T off I2T on REF char :0.40In :400ms :400ms : 400ms : 400ms : On Select “Restricted EF” LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE The following are dip switch settings (in the front facia) to be done for using EL,REF module as an add on module of Matrix P&C unit or a stand alone module. Also frequency of operation can be also set through the dip switch selection. MODE ADD ON ADD ON STAND ALONE STAND ALONE FREQUENCY DIP setting 50Hz 00 60Hz 01 50Hz 10 60Hz 11 7-8 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 43 OF 86 CD00906 While using EL,REF Modules in stand alone mode the following settings to be kept for the required protection. Current selection(mA) 16.6 33.3 100 166.6 233.3 300 366.6 433.3 500 566.6 633.3 700 766.6 833.3 900 966.6 EL DIP SWITCH SELECTION DIP setting Delay selection(ms) 0000 100 0001 200 0010 300 0011 400 0100 500 0101 600 0110 700 0111 800 1000 900 1001 1000 1010 2000 1011 2500 1100 3000 1101 3500 1110 4000 1111 5000 REF DIP SWITCH SELECTION LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE Current selection(mA) 200 300 400 500 600 200 200 200 200 200 200 200 200 200 200 200 DIP setting 0000 0001 0010 0011 0100 0101 0110 0111 1000 1001 1010 1011 1100 1101 1110 1111 Delay selection(ms) 100 200 300 400 500 600 700 800 900 1000 500 500 500 500 500 500 DIP setting 0000 0001 0010 0011 0100 0101 0110 0111 1000 1001 1010 1011 1100 1101 1110 1111 DIP setting 0000 0001 0010 0011 0100 0101 0110 0111 1000 1001 1010 1011 1100 1101 1110 1111 7-10 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 44 OF 86 SCALE DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK - DEPT: 300202311 PROJECTION AS- AS+ CAN-L CAN-H Z-H SIC INTER CONNECTION DATE T S-OUT LARSEN & TOUBRO LIMITED, SHEET 45 U-POWER CD00906 OF 86 S-IN G-IN MNT COMM ZSI AS+ ASCAN L CAN H AO2 + AO3 + AO4 + OP1 OP2 OP3 T1-T4 : THERMISTOR INPUTS Z-L : ZSI CAN LOW Z-H : ZSI CAN HIGH CAN- H : CAN HIGH CAN- L : CAN LOW OP1 OP2 OP3 OP4 AO1 + 4 RELAY O/PS OP4 AO1 AO2 AO3 AO4 OP3 OP2 OP4 * RELAY O/P CT input T1-T4 } connection to breaker terminals 4 ANALOG O/PS IP4 COM IP3 } OP1 OP2 OP3 OP4 IP2 IP3 IP4 COM GIN SIN SOUT GOUT 4 DIGITAL O/PS OP1 IP1 IP1 IP2 4 DIGITAL (24V dc/230V AC) Inputs AS+ : AUXILIARY 24VDC : GND : S/C OUTPUT : S/C INPUT : E/F OUTPUT : E/F INPUT G-OUT PWR AS- Note: One Power Supply module can be connected to maximum 5 modules AS+ ASSOUT SIN GOUT GIN RJ 45 CABLE 08.02.2010 CAN COMMUNICATION BUS Z-L 8.Control Connection UT RTY OF AND MUST NOT BE COPIED OR LENT WITHO THEIR PERMISSION IN WRITING LARSEN & TOUBRO LIMITED THIS DRAWING AND DESIGN IS THE PROPE REVISIONS 8-1 ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL RELAY O/P CT input STATUS T4 RELAY T3 T2 1 CAN Communication Bus T Coil TCS RELAY O/P MNT COMM PWR T1 Supply CD00906 300202311 EC1 Legend Control circuit equipment Ref. No. TCS X C1 A1 44 42 43 34 41 32 33 D2 31 D1 24 22 23 14 21 13 12 EC2 11 } 1m CFI, only 1 No. will be available C-L 134 Z-L 6m Z-H 131 X2 Shunt Rel. # & “NO” 6 C-H Aux. Contact “NO” 3 AL- Aux. Contact “NO” 3 AL+ Electrical Charging Device # 2 X1 } } C2 } } } } } } } } } } } A2 For RTC/URM/SRM only one can be used X = 101/111/121 X1 = 102/112/122 X2 = 104/114/124 M-G Aux. Aux. Closing Contact Contact Release “NC” “NC” # 3 3 5 Aux. Aux. Contact Contact “NO” “NO” 3 3 Protection& Control Unit 1 C-G Under Voltage Release # 4 D- Aux. Contact “NC” 3 D+ Aux. Contact “NC” 3 V2 For UW-MTX 2.5/2.5G/3.5/3.5EC V1 8.1 SIC Terminations V3 LARSEN & TOUBRO LIMITED V0 AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING AS- APPROVED BY: SSK PROJECTION AS+ CHECKED BY: AnS Electrical Position Indication 8e CMN } HRA N1 DEPT: CN N2 08.02.2010 TST DRAWN BY: SCALE } DATE DSN THIS DRAWING AND DESIGN IS THE PROPE RTY OF REVISIONS 8-2 LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL U-POWER CD00906 SHEET 46 OF 86 CD00906 UW-MTX 2.5 EC 11 .3 .4 12 2 Electric Charging Device 13 .1 .2 14 UR 31 .3 .4 32 AX 33 .1 .2 34 AX CR SR/SRW U-POWER CD00906 SHEET 47 OF 86 AS+ AS- AL+ AL- to 5V-30 V dc 150 mA Relay or any other indicating device which can give alarm for Short circuit and Earth Fault trip 3 4 3 5 6 U/V Auxiliary Auxiliary Closing Shunt Contacts Release Contacts Release Release 2NO + 2NC 2NO + 2NC AX 21 .3 .4 22 AX 23 .1 .2 24 : 24V DC Power Supply : TRIP ALARM +,TRIP ALARM- . This output can be connected 1 Ref. No. AS+, ASAL+,AL- Protection & Control Unit Main Circuit LOAD N R Y B 41 .3 .4 42 8.2 Connection Details (UW-MTX 2.5) 43 LARSEN & TOUBRO LIMITED 112 124 114 4m U/V Fault Signal/ Shunt Trip Signal/ Ready to Close (only one can be 111 AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING EC1 EC2 D1 D2 A1 A2 .1 .2 44 C1 TCS .1 .2 C2 ACB STATUS ACB STATUS 122 121 APPROVED BY: SSK 214 212 204 202 DSN TST CN 134 1m Common Fault Indication 8e Electrical Position Indication 9 Additional Electrical Position Indication CI2 302 CI1 304 CT2 312 CT1 314 CS2 402 CS1 404 PI 412 CFM 414 131 HRA 300202311 CMN CHECKED BY: AnS PROJECTION 201 DEPT: 211 301 08.02.2010 311 DRAWN BY: SCALE 401 DATE 411 THIS DRAWING AND DESIGN IS THE PROPE RTY OF REVISIONS 8-3 LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL CD00906 UW-MTX 2.5G U-POWER CD00906 SHEET 48 OF 86 N1, N2 AS+, ASAL+,AL- ASAS+ ALAL+ EC 13 .1 .2 14 11 .3 .4 12 2 :External Neutral CT to 5V-30 V dc 150 mA Relay or any other indicating device which can give alarm for Short circuit and Earth Fault trip . UR 31 .3 .4 32 AX AX 3 4 3 5 6 X X2 7 302 214 212 204 202 DSN CN 134 1m 8e 9 Additional Electrical Position Indication CI2 304 CI1 312 CT2 314 CT1 402 CS2 404 CS1 412 PI 414 CFM TST X1 U/V Fault Signal/ Common Electrical Shunt Trip Signal/ Fault Position Ready to Close Indication Indication (only one can be used) SR/SRW CR A1 U/V Auxiliary Auxiliary Closing Shunt Contacts Release Contacts Release Release 2NO + 2NC 2NO + 2NC AX 21 .3 .4 22 AX 23 .1 .2 24 Electric Charging Device :AUX 24V DC Power Supply :TRIP Alarm+, TRIP AlarmThis output can be connected 1 Ref. No. N1 Protection&Control Unit N2 Main Circuit LOAD N R Y B 33 .1 .2 34 8.3 Connection Details (UW-MTX 2.5G) 41 .3 .4 42 LARSEN & TOUBRO LIMITED 43 AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING ACB STATUS ACB STATUS EC1 EC2 D1 D2 TCS A2 .1 .2 44 C1 .1 .2 C2 APPROVED BY: SSK 131 CHECKED BY: AnS PROJECTION CMN HRA 300202311 201 DEPT: 211 301 08.02.2010 311 DRAWN BY: SCALE 401 DATE 411 THIS DRAWING AND DESIGN IS THE PROPE RTY OF REVISIONS 8-4 LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. MTX RELEASE USERS’ MANUAL CD00906 SHEET Z-H ACB STATUS D+ N1 49 USERS’ MANUAL OF OMEGA SYSTEM U-POWER CD00906 OF 86 V3 V2 V1 V0 EC 13 .1 .2 14 11 .3 .4 12 2 to 5V-30 V dc 150 mA Relay or any other indicating device which can give alarm for Short circuit and Earth Fault trip . UR 31 .3 .4 32 AX AX SR/SRW CR A1 D+ DN1 N2 Z-L Z-H 3 4 5 6 : DATA + : DATA : External Neutral CT : External Neutral CT : ZSI CAN-Low : ZSI CAN-High 3 U/V Auxiliary Auxiliary Closing Shunt Contacts Release Contacts Release Release 2NO + 2NC 2NO + 2NC AX 21 .3 .4 22 AX 23 .1 .2 24 Electric Charging Device :24V DC Power Supply :TRIP ALARM+,TRIP ALARMThis output can be connected C-L :CAN-Low C-H :CAN-High M-G :MOD-GND C-G :CAN-GND V0,V1,V2,V3 :N ,R,Y,B, VOLTAGE I/P AS+, ASAL+,AL- 1 N2 Ref. No. D- Protection&Control Unit ACB STATUS Main Circuit LOAD AS+ AS- Z-L UW-MTX 3.5 M-G C-G N R Y B 33 .1 .2 34 8.4 Connection Details (UW-MTX 3.5) 41 .3 .4 42 LARSEN & TOUBRO LIMITED AL+ AL- 43 AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING C-H C-L EC1 EC2 D1 D2 TCS A2 .1 .2 44 C1 .1 .2 C2 APPROVED BY: SSK DSN TST CN 134 X2 X1 1m 8e U/V Fault Signal/ Common Electrical Shunt Trip Signal/ Fault Position Ready to Close Indication Indication (only one can be used) X 7 214 212 204 202 9 Additional Electrical Position Indication CI2 302 CI1 304 CT2 312 CT1 314 CS2 402 CS1 404 PI 412 CFM 414 131 HRA 300202311 CMN CHECKED BY: AnS PROJECTION 201 DEPT: 211 301 08.02.2010 311 DRAWN BY: SCALE 401 DATE 411 THIS DRAWING AND DESIGN IS THE PROPE RTY OF REVISIONS 8-5 LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. CD00906 M-G AL+ D+ D- N2 N1 1 AL- Ref. No. C-G Protection&Control Unit V0 : 24V DC Power Supply : TRIP ALARM +,TRIP ALARM- . This output can be connected to 5V-30 V dc 150 mA Relay or any other indicating device which can give alarm for Short circuit and Earth Fault trip . C-L :CAN-Low C-H :CAN-High M-G :MOD-GND C-G :CAN-GND V0,V1,V2,V3 :N,R,Y,B VOLTAGE I/PS AS+, ASAL+,AL- V1 UW-MTX-3.5EC C-H C-L Main Circuit LOAD N R Y B EC 13 .1 .2 14 11 .3 .4 12 2 Electric Charging Device 21 .3 .4 22 UR 33 .1 .2 34 31 .3 .4 32 AX AX D+ DN1 N2 Z-L Z-H 3 4 5 6 : DATA + : DATA : External Natural CT : External Natural CT : ZSI CAN-Low : ZSI CAN-High 3 X2 7 302 214 212 204 202 DCD CN 134 1m 8e 9 Additional Electrical Position Indication CI2 304 CI1 312 CT2 314 CT1 402 CS2 404 CS1 412 PI 414 CFM TST For Ready to Close/ Common Electrical U/V Fault Signal/ Fault Position Shunt Trip Signal Indication Indication (only one can be used) SR/SRW CR A1 U/V Auxiliary Auxiliary Closing Shunt Contacts Release Contacts Release Release 2NO + 2NC 2NO + 2NC AX 23 .1 .2 24 AX 41 .3 .4 42 8.5 Connection Details (UW-MTX 3.5EC) AS+ AS- 43 LARSEN & TOUBRO LIMITED ACB STATUS ACB STATUS Z-H Z-L EC1 EC2 D1 D2 TCS A2 .1 .2 44 C1 .1 .2 C2 AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING X1 X V3 V2 APPROVED BY: SSK 131 HRA 300202311 CMN CHECKED BY: AnS PROJECTION 201 DEPT: 211 301 08.02.2010 311 DRAWN BY: SCALE 401 DATE 411 THIS DRAWING AND DESIGN IS THE PROPE RTY OF REVISIONS 8-6 LARSEN & TOUBRO LIMITED, ENGINEERS,MUMBAI. USERS’ MANUAL OF OMEGA SYSTEM U-POWER CD00906 SHEET 50 OF 86 CD00906 CD00906 9. Add-On Modules 9.1 Metering Module Metering Module Matrix P&C unit has 3 types of add-on modules. 1.Metering Module 2.Communication Module (Modbus/Zig bee/Profi bus) 3.Configurator Module Metering Module can provide the metering of below listed parameters in an electrical distribution system. They are Voltage, Frequency, Power, Power Factor, Energy and Maximum Demand. Also it offers various advanced protection features viz ; 1.Over Voltage 4.Voltage Unbalance 7.Lagging P.F 10.MD Active 13.Directional SC 2.Under Voltage 4.Over Frequency 8.Leading P.F 11.MD Reactive 14.Phase Sequence 3.Residual Voltage 5. Under frequency 9. Reverse Power 12.MD Apparent Metering Module will be available in UW-MTX 3.5,UW-MTX 3.5EC Protection and Control Unit versions. LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE Operating range of metering Module: Metering Module can be used for system voltage 220-440V (Ph-Ph). Maximum operating Ph-Ph voltage of this module is 440V. Minimum Voltage input for Voltage metering is 100 V ph-ph. . CAUTION Before removing Metering module from the P&C unit for maintenance , make sure to remove the Voltage connection from the rear end of the unit. 9-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 51 OF 86 CD00906 9.2 Communication Modules UW-MTX3.5 series provides 3 options for communication functionality. These modules are hot - plugable and derive the supply from the release. All these modules have 2 LEDs for power status and communication indication and a self test switch 1) MODBUS Module - Works on Modbus RTU protocol 2) PROFIBUS Module - Works on Profibus DP V0 protocol 3) ZIGBEE Module - Works on Wireless Zigbee protocol 9.2.1 MODBUS Module Modbus Module is used for the Configuration, Monitoring and Control of Matrix P&C unit and its supplementary modules. It offers Client / Server communication in RTU mode. Configuration function: Unit Settings System Settings Protection Settings Group 1 Protection Settings Group 2 Module Settings Monitoring function: Metering Data – Voltage, Current, Power, Energy, Power Factor, Online Module Status Status Data – Alarm & Trip Status, Digital Input Output Module & Relay Module Status Record Data – Trip Records, Event Records, Maintenance Records Control function: Commands for Set group Change, Restore Factory defaults, Clear Maximum Demand, Maximum Current value, Maximum Voltage value and Energy, Open and Close Circuit Breaker, Maintenance Acknowledgement and Earth Fault (EF) test. Settings: Settings Menu Settings View Records Metering Config Mode View Mode Password Password **** 0 1 2 3 4 5 6 7 8 9 Default password “0000” Config Mode MTX Unit MTX Unit Configurator Modbus System Settings Unit Settings Module Settings Unit Settings Communication Date & Time Communication Event Recorder Device ID : 1 Save the Unit settings and configure Module Setting as follows Module Settings LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE MTX Unit System Settings Unit Settings Module Settings Relay Temperature Modbus Module : Enable / Disable Node : 1 to 126 Parity : None, Even or Odd Modbus Module Parity Stop Bit Modbus : Enable : None :2 Baud Type Baud Rate : Manual : 9.6 k Stop Bit : 1 / 2 Baud Rate : 300bps, 1.2, 2.4, 4.8, 9.6, (kbps) 19.2, 38.4, 57.6, 115.2 * Power reset the device if Unit Settings is changed 9-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 52 OF 86 CD00906 SETUP: DATA+ DATA- RS232 to RS485 CONVERTER SERIAL CABLE VS + GND SHIELD PS MODULE M-G C-G D+ D- V1 V2 V3 V0 AS+ AS- SIC Termination PC HMI Pre-wired Connections inside breaker Shielded Co-axial 2 core Cable COMM STATUS TEST MODBUS SELF TEST SWITCH For factory use only STATUS LED Blinks AMBER for 5s when Module is connected indicating self test Blinks GREEN continuously to indicate healthy POWER ON GLOWS RED if unhealthy / self test fails. (Please reinsert the module or contact L&T office if problem persists) LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE COMMUNICATION LED Blinks RED during communication data transfer 9-3 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 53 OF 86 CD00906 9.2.2 PROFIBUS Module Profibus Module supports PROFIBUS DP V0 slave protocol. This module communicates with PROFIBUS Class 1 and/or Class 2 Master. GSD file should be used / loaded in PROFIBUS master for understanding the device functions. Network termination switch is provided at the rear end of the module. Thus this module can be used as end node in the network. It communicates on baud-rates 9.6Kbps, 19.2Kbps, 45.45Kbps, 93.75Kbps, 187.5Kbps, 500Kbps, 1.5Mbps, 3Mbps, 6Mbps, 12Mbps. It automatically detects the baud-rate selected by PROFIBUS master for communication. PROFIBUS module is used to monitor critical status parameters of Matrix P&C unit like Pick-up, Alarm and Trip status. Settings: Settings Menu Settings View Records Metering Config Mode View Mode Password Password **** 0 1 2 3 4 5 6 7 8 9 Default password “0000” Config Mode MTX Unit MTX Unit Configurator Modbus System Settings Unit Settings Module Settings Unit Settings Communication Date & Time Communication Event Recorder Device ID : 1 Save the Unit settings and configure Module Setting as follows Module Settings MTX Unit LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE System Settings Unit Settings Module Settings TCS Earth Leakage Profibus Profibus Module Module : Enable / Disable Node : 1 to 126 : Enable * Power reset the device if Unit Settings is changed 9-4 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 54 OF 86 CD00906 SETUP: DATA+ PROFIBUS CABLE DATA- SHIELD PS MODULE M-G C-G D+ D- V1 V2 V3 V0 AS+ AS- SIC Termination PROFIBUS MASTER OR PLC Pre-wired Connections inside breaker Shielded Co-axial 2 core Cable COMM STATUS TEST PROFIBUS SELF TEST SWITCH For factory use only STATUS LED Blinks AMBER for 5s when Module is connected indicating self test Blinks GREEN continuously to indicate healthy POWER ON GLOWS RED if unhealthy / self test fails. (Please reinsert the module or contact L&T office if problem persists) LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE COMMUNICATION LED Blinks RED during communication data transfer 9-5 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 55 OF 86 CD00906 9.2.3 ZIGBEE Module UW-MTX3.5 series provides Wireless Communication using ZigBee protocol formulated under IEEE 802.15.4 standard for Wireless Personal Area Network (WPANs). Zigbee operates in ISM radio bands of 2.4GHz The Communication range is 200m Line of sight (LOS) with over the air data rates upto 250 Kbps Zigbee module is used for Monitoring parameters of Matrix P&C unit and its supplementary modules. Monitoring function: Metering Data – Voltage, Current, Power, Energy, Power Factor, Online Module Status Status Data – Alarm & Trip Status, Digital Input Output Module & Relay Module Status Record Data – Trip Records, Event Records, Maintenance Records Settings: Menu Current I1 I2 I3 :0A :0A :0A Settings View Records Metering Settings Config Mode View Mode Password **** Default password “0000” Config Mode Password 0 1 2 3 4 5 6 7 8 9 MTX Unit Configurator Modbus LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE Module Settings Earth Leakage Profibus ZIG-Bee Module : Enable / Disable Freq Sel : 11 to 26 Pan ID : 0 to 65.53k Zig - Bee Module Freq Sel Pan ID MTX Unit System Settings Unit Settings Module Settings : Enable : 11 :1 9-6 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 56 OF 86 CD00906 SETUP: ZIGBEE CORDINATOR POWER LED USB CABLE (OPTIONAL) NETWORK LED PS MODULE M-G C-G D+ D- V1 V2 V3 V0 AS+ AS- SIC Termination PC HMI COMM STATUS TEST ZIGBEE SELF TEST SWITCH For factory use only STATUS LED Blinks AMBER for 5s when Module is connected indicating self test Blinks GREEN continuously to indicate healthy POWER ON GLOWS RED if unhealthy / self test fails. (Please reinsert the module or contact L&T office if problem persists) COMMUNICATION LED GLOW RED when not in network Blinks RED during communication data transfer Note: LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE 1) It is necessary to first switch on the Coordinator module and form a network. Coordinator Module can be directly plugged in the PC USB port or USB cable can be used 2) Power LED on Coordinator Module will glow GREEN when connected to the port. Network LED on Coordinator module will glow GREEN when it forms a network 3) Zigbee Module should be now inserted in the Matrix P&C unit. 9-7 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 57 OF 86 CD00906 9.3. SMART CONFIGURATOR UW-MTX3.5 series has an optional Smart Configurator Module which is used for easy Parameterisation of the P&C unit. Smart Configurator works on the principle of RF interface at 106kbps between the module and the Smart Card. The following operations can be performed on the Smart Card 1) Write File - Copy files from the P&C unit to the card 2) Read File - Copy files from the card to the P&C unit 3) Delete File - Delete selected file from the card 4) Format Card - Delete all the files from the card and format it At a time maximum 2 files can be stored on the Smart Card. The files that can be written on the card are as follows 1) REQ.CFG 2) DEQ.CFG 3) SG1.CFG 4) SG2.CFG 5) SST.CFG 6) UST.CFG 7) IO1.CFG 8) IO2.CFG 9) IO3.CFG 10) IO4.CFG 11) RL1.CFG 12) RL2.CFG - Relay Equations - DIO Equations - Set Group 1 - Set Group 2 - System Settings - Unit Settings - IO Module 1 - IO Module 2 - IO Module 3 - IO Module 4 - Relay Module 1 - Relay Module 2 13) RL3.CFG 14) RL4.CFG 15) AOP.CFG 16) TM1.CFG 17) ZSI.CFG 18) MOD.CFG 19) PBM.CFG 20) ZIG.CFG 21) EL.CFG 22) REF.CFG 23) TCS.CFG - Relay Module 3 - Relay Module 4 - Analog Output - Temperature Module - Zone Selective Interlocking - Modbus Module - Profibus Module - Zigbee Module - Earth Leakage Module - Restricted Earth Fault Module - Trip Circuit Supervision Module Settings: Menu Current I1 I2 I3 :0A :0A :0A Settings View Records Metering Settings Config Mode View Mode Password **** Default password “0000” Config Mode Password 0 1 2 3 4 5 6 7 8 9 MTX Unit Configurator Modbus LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE Module Settings Temperature Modbus Configurator Module : Enable / Disable Configurator Module MTX Unit System Settings Unit Settings Module Settings : Enable 9-8 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 58 OF 86 CD00906 SETUP PS MODULE M-G C-G D+ D- V1 V2 V3 V0 AS+ AS- SIC Termination INSERT CARD HERE (Card goes inside the module partially. Check the Comm LED to see whether the card is detected.) COMM STATUS TEST CONFIGURATOR SELF TEST SWITCH For factory use only STATUS LED Blinks AMBER for 5s when Module is connected indicating self test Blinks GREEN continuously to indicate healthy POWER ON GLOWS RED if unhealthy / self test fails. (Please reinsert the module or contact L&T office if problem persists) COMMUNICATION LED GLOWS RED when card is detected. Blinks RED during communication data transfer OPERATION Menu Current I1 I2 I3 :0A :0A :0A Settings View Records Metering Settings Config Mode View Mode Password **** Default password “0000” Config Mode LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE Password 0 1 2 3 4 5 6 7 8 9 MTX Unit Configurator Modbus Configurator Read Card Write Card Delete Files Configurator Write Card Delete Files Format Card Select the card function “Command Success”or “Command Fail” message is displayed on Matrix P&C unit after completion of operation. 9-9 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 59 OF 86 CD00906 10. SIMULATION KIT Matrix Simulation kit is a battery operated Hand Held device used to simulate various test conditions for verifying different protections. Key Features: 1) Simulation of 3 phase current and voltage test signals with adjustable phase angles (0 degree to 359 degree) 2) Provides sensor / CT continuity check 3) Manual and Automated test modes with test scripts generation 4) Stores test records on SD card with trip time stampings 5) Provides PC interface with USB and MODBUS IDENTIFICATION: TEST CABLE CONNECTOR POWER ADAPTOR IN POWER ON OLED (Display) SOFT RIGHT SOFT LEFT UP SELECT RIGHT LEFT DOWN RUN / STOP LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE USB SLOT SD CARD SLOT 10-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 60 OF 86 CD00906 OPERATION: Insert Connector here TEST CABLE Insert Connector here Power On the Simulation Kit and press “SEL” key / SOFT Right key to go to MENU MENU SYSTEM SETTINGS TEST OPTIONS SYSTEM SETTINGS DEVICE CONFIG DEVICE STATUS BACK FRAME RATED NOMINAL VOLT MOD SELECT MENU BACK LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING SELECT RELEASE TEST RELEASE TEST CT CNTY TEST SELECT NEW SCRIPT RTY OF THIS DRAWING AND DESIGN IS THE PROPE BACK Set as per Matrix release TEST OPTIONS TEST OPTIONS SYSTEM SETTINGS DEVICE CONFIG DEVICE STATUS V2 V3 I1Ø I2Ø 16 00 A 10 00 A 4 15 V Absent BACK SELECT NEW SCRIPT 00.10 Vn 00.10 Vn 00 00 ° 00 00 ° BACK ü ü RUN I3Ø V1Ø V2Ø V3Ø BACK I1 I2 I3 V1 SELECT 00.10 In 00.10 In 00.10 In 00.10 Vn BACK ü ü ü ü RUN NEW SCRIPT 00 00 ° 00 00 ° 00 00 ° 00 00 ° BACK NEW SCRIPT NEW SCRIPT OPEN SCRIPT REL/BRK ID OPERATOR NAME V1Ø V2Ø V3Ø FREQ RUN BACK 00 00 ° 00 00 ° 00 00 ° 50.00 Hz Press RUN after setting the Test Values RUN * Please refer the Simulation Kit Manual for details 10-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: ABL CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 61 OF 86 CD00906 11. Fault Diagnosis Fault identification: When P&C unit trips the breaker, a mechanical indication is provided through popping-out of the red pointer at the upper end of the unit. With Auto reset feature, the pointer will reset automatically. To identify the type of fault, open the P&C unit cover and press “?” (Query) button continuously to read the latest “Trip Info”which includes cause of trip ,Date &Time. This local fault indication is independent of auxiliary supply or batteries and is available for repeat usage* after the fault. If AUX supply is present the P&C unit will indicate the fault through the fault indicating LED. For example in case of Overload trip both Overload and trip LED will glow as the fault indication. T Trip and events Records: Trip data can be obtained by accessing “Trip Records”.It stores last 5 “Trip Records” which records the trip cause, date and time of the trip. Trip records also contains current, frequency, Voltage and System power factor values of the system while the trip has occurred. Events records captures the events like alarm, pick up and trip. Matrix P&C unit can store last 10 events in the event record. 12. Self Diagnostic Test Earth fault test can be done by pressing the “T” button. For this unit needs to be poweredup in AUX mode. Enter the current command password (Default Password “0000”) after pressing the “T” button in the unit . Current Password : 0A : 0A : 0A **** I1 I2 I3 Command Success LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE (Enter command P/W Default p/w is “0000”) Once the password is entered, unit will issue E/F trip. E/F and Trip LED glows. To reset the LEDs ,press “T” again, enter the same password and reset the ACB status (Open to Close) * For a definite time period only and depends on the usage 11-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 62 OF 86 CD00906 12.List of Cat Nos LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED UTOR LENT WITHO THEIR PERMISSION IN WRITING RTY OF THIS DRAWING AND DESIGN IS THE PROPE Sl.No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Cat No CL90700 CL90610 CL90611 CL90112 CL90113 CL90704 CL90705 CL90709 CL90732 CL90732 CL90733 CL90737 CL90712 CL90715 CL90716 CL90717 CL90718 CL90719 CL90720 CL90721 CL90722 Component Description UW-MTX 3.5 EC RELEASE ASSEMBY UW-MTX2.5G RELEASE ASSEMBY UW-MTX4.5 RELEASE ASSEMBY UW-MTX2.5 RELEASE ASSEMBY UW-MTX 3.5 RELEASE ASSEMBY MATRIX VL MODULE ASSY MATRIX SMART CARD MODULE ASSY MATRIX COMM MOD MODULE ASSY MATRIX PROFIBUS MODULE ASSLY MATRIX PROFIBUS MODULE ASSLY MATRIX ZIGBEE MODULE ASSLY MATRIX ZIGBEE USB MODULE ASSLY TM MODULE ASSY, MATRIX; U-POWER DIGITAL I/O MODULE-MATRIX;U-POWER RELAY MODULE-MATRIX;U-POWER ANALOG OUTPUT MODULE-MATRIX;U-POWER ZSI MODULE-MATRIX;U-POWER TCS MODULEMATRIX;U-POWER EL MODULE-MATRIX;U-POWER REF MODULE-MATRIX;U-POWER POWER SUPPLY MODULE-MARTRIX;U-POWER 11-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS’ MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00906 SHEET 63 OF 86 CD00965 14.Memory Map Address Parameter Size(in words) UNITS Divisor/ Multiplier 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 A A A A A A A A A A A A A A A % % % 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1/10 1/10 1/10 Interpretation Metering Parameters Current 30001 30003 30005 30007 30009 30011 30013 30015 30017 30019 30021 30023 30025 30027 30029 30031 30033 30035 R Phase Current Y Phase Current B Phase Current N Phase Current G Phase Current Earth Leakage Current Restricted Earth Fault Current R Phase Maximum Current Y Phase Maximum Current B Phase Maximum Current N Phase Maximum Current G Phase Maximum Current Earth Leakage MaximumCurrent Restricted Earth Fault Maximum Current Average Current R Phase % Load Current Y Phase % Load Current B Phase % Load Current Voltage 30037 30039 30041 30043 30045 30047 30049 30051 30053 30055 30057 30059 30061 30063 R Phase Voltage Y Phase Voltage B Phase Voltage R - N Phase Maximum Voltage Y - N Phase Maximum Voltage B - N Phase Maximum Voltage P - N Average Voltage R - Y Phase - Phase Voltage Y - B Phase - Phase Voltage B - R Phase - Phase Voltage R - Y Phase - Phase Maximum Voltage Y - B Phase - Phase Maximum Voltage B - R Phase - Phase Maximum Voltage Phase - Phase Average Voltage 2 2 2 2 2 2 2 2 2 2 2 2 2 2 V V V V V V V V V V V V V V 1 1 1 1 1 1 1 1 1 1 1 1 1 1 30065 System Frequency 2 Hz 1/100 Power Factor 30067 30069 30071 30073 R Phase Power Factor Y Phase Power Factor B Phase Power Factor System Power Factor 2 2 2 2 1/100 1/100 1/100 1/100 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPERTY OF Power 30075 30077 30079 30081 30083 30085 30087 30089 30091 30093 30095 30097 R Phase Active Power Y Phase Active Power B Phase Active Power Total Active Power R Phase Reactive Power Y Phase Reactive Power B Phase Reactive Power Total Reactive Power R Phase Apparent Power Y Phase Apparent Power B Phase Apparent Power Total Apparent Power 2 2 2 2 2 2 2 2 2 2 2 2 KW KW KW KW KW KW KW KW KW KW KW KW 1 1 1 1 1 1 1 1 1 1 1 1 14-1 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 64 OF 86 CD00965 Address Size(in words) Parameter UNITS Interpretation Divisor/ Multiplier Energy 30099 30101 30103 Active Energy Reactive Energy Apparent Energy 2 2 2 1 1 1 Maximum Demand 30105 30107 30109 Active Maximum Demand Reactive Maximum Demand Apparent Maximum Demand 2 2 2 Total Harmonic Distorsion 30111 30113 30115 30117 30119 30121 30123 30125 30127 30129 30131 30133 30135 30137 30139 30141 30143 30145 Total Harmonic R Phase Current Fundamental Harmoinc R Phase Current THD_R Phase Current Total Harmonic Y Phase Current Fundamental Harmoinc Y Phase Currentent Energy THD_Y Phase Current Total Harmonic B Phase Current Fundamental Harmoinc B Phase Current THD_B Phase Current Total Harmonic R Phase Voltage Fundamental Harmoinc R Phase Voltage THD_R Phase Voltage Total Harmonic Y Phase Voltage Fundamental Harmoinc Y Phase Voltage THD_Y Phase Voltage Total Harmonic B Phase Voltage Fundamental Harmoinc B Phase Voltage THD_B Phase Voltage 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Temperature 30147 30149 30151 30153 R - Phase Terminal Temperature Y - Phase Terminal Temperature B - Phase Terminal Temperature N - Phase Terminal Temperature 2 2 2 2 30155 Phase sequence 2 1 - RBY , 0 - RYB 1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off -Alarm Off 0 -Alarm Off - Alarm 0 -AlarmOn Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off °C °C °C °C 1/10 1/10 1/10 1/10 Status(Broadcast) Parameters Alarm,Pickup ,Trip and Misc Status Alarm Status LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 30167 Alarm Status0 Instantaneous Alarm Status Earth Fault Alarm Status ShortCircuit Alarm Status Directional ShortCircuit Alarm Status OverLoad Alarm Status OverLoad Neutral Alarm Status ZSI EF Alarm Status ZSI SC Alarm Status Phase Sequence Alarm Status REF Alarm Status Earth Leakage Alarm Status Current Unbalance Alarm Status Under Current Alarm Status Under Voltage Alarm Status Over Voltage Alarm Status Voltage Unbalance Alarm Status 0 1 14-2 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 65 OF 86 CD00965 Address 30168 Size(in words) Parameter Alarm Status1 Residual Voltage Alarm Status Under Frequency Alarm Status Over Frequency Alarm Status Reverse Power Alarm Status TCS Alarm Status Leading PF Alarm Status Lagging PF Alarm Status Peak Factor Alarm Status Form Factor Alarm Status MD Active Alarm Status MD Reactive Alarm Status MD Apparent Alarm Status THD Alarm Status Terminal Temperature Alarm Status Reserved Bkr Failure Alarm Status UNITS Interpretation Divisor/ Multiplier 1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm OffOff 0 -Alarm 1 - 0Alarm OnOff -Alarm 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off 0 -Alarm Off PickupStatus0 Instantaneous Pickup Status Earth Fault Pickup Status ShortCircuit Pickup Status Directional ShortCircuit Pickup Status OverLoad Pickup Status OverLoad Neutral Pickup Status ZSI EF Pickup Status ZSI SC Pickup Status Phase Sequence Pickup Status REF Pickup Status Earth Leakage Pickup Status Current Unbalance Pickup Status Under Current Pickup Status Under Voltage Pickup Status Over Voltage Pickup Status Voltage Unbalance Pickup Status 1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - 0Pickup Off - Pickup Off 1 -Pickup OnOff 0 - Pickup 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off PickupStatus1 Residual Voltage Pickup Status Under Frequency Pickup Status Over Frequency Pickup Status Reverse Power Pickup Status TCS Pickup Status Leading PF Pickup Status Lagging PF Pickup Status Peak Factor Pickup Status Form Factor Pickup Status MD Active Pickup Status MD Reactive Pickup Status MD Apparent Pickup Status THD Pickup Status Terminal Temperature Pickup Status Reserved Reserved1 1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup 0 - Pickup OffOff 0 - Pickup 1 -Pickup OnOff 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off 0 - Pickup Off Pickup Status 30169 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 30170 Trip Status 30171 TripStatus0 Instantaneous Trip Status Earth Fault Trip Status ShortCircuit Trip Status Directional ShortCircuit Trip Status OverLoad Trip Status 1 :1 :1 :1 :1 :1 0 - Release Not Tripped Release Not 0 0- -Release NotTripped Tripped Release Tripped Not Tripped 1 0- -Release Not Tripped Tripped 01-- Release Release Not 0 - Release Not Tripped 14-3 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 66 OF 86 CD00965 Address 30172 Size(in words) Parameter UNITS Interpretation Divisor/ Multiplier OverLoad Neutral Trip Status ZSI EF Trip Status ZSI SC Trip Status Phase Sequence Trip Status REF Trip Status Earth Leakage Trip Status Current Unbalance Trip Status Under Current Trip Status Under Voltage Trip Status Over Voltage Trip Status Voltage Unbalance Trip Status :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - 0Release - ReleaseNot NotTripped Tripped 1 - 0Release - ReleaseTripped Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped TripStatus1 Residual Voltage Trip Status Under Frequency Trip Status Over Frequency Trip Status Reverse Power Trip Status TCS Trip Status Leading PF Trip Status Lagging PF Trip Status Peak Factor Trip Status Form Factor Trip Status MD Active Trip Status MD Reactive Trip Status MD Apparent Trip Status THD Trip Status Terminal Temperature Trip Status EF Test Button Trip Status Reserved 1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped - Release Not Not Tripped Tripped 0 -0Release - ReleaseTripped Not Tripped 1 -0Release 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped 0 - Release Not Tripped Status Data 30173 Misc Status Maintenance Require status(Display a pop up if bit is Set) Online file edited in RAM ACB Status(Display status continuously) FSD Status (Display status continuously) Flag for default setting applied(Display a pop up if bit is Set) LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved Reserved 30250 30251 30252 30253 30254 30255 30256 30257 1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 :1 0 - Maintenance Not Required 0 - File not edited in RAM 0 - Breaker Close,1 - Breaker Open 0 - FSD Open,1 - FSD Close 0 - Default settings not applied 0 0 0 0 0 0 0 0 0 0 0 DIO Module Status (Each module to be accessed separably) DIO Module 1 (All the registers within this module has to be accessed together) DIO Module 1 - Input 1 Status DIO Module 1 - Input 2 Status DIO Module 1 - Input 3 Status DIO Module 1 - Input 4 Status DIO Module 1 - Output 1 Status DIO Module 1 - Output 2 Status DIO Module 1 - Output 3 Status DIO Module 1 - Output 4 Status 1 1 1 1 1 1 1 1 Disabled - 0 Disabled - 0 Disabled Disabled - 0- 0 Inactive -1 -0 Disabled Active -3 -0 Disabled Invalid Value- -0 2 Disabled Disabled - 0 Disabled - 0 14-4 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 67 OF 86 CD00965 Address Size(in words) Parameter DIO Module 2 30258 30259 30260 30261 30262 30263 30264 30265 DIO Module 2 - Input 1 Status DIO Module 2 - Input 2 Status DIO Module 2 - Input 3 Status DIO Module 2 - Input 4 Status DIO Module 2 - Output 1 Status DIO Module 2 - Output 2 Status DIO Module 2 - Output 3 Status DIO Module 2 - Output 4 Status DIO Module 3 - Input 1 Status DIO Module 3 - Input 2 Status DIO Module 3 - Input 3 Status DIO Module 3 - Input 4 Status DIO Module 3 - Output 1 Status DIO Module 3 - Output 2 Status DIO Module 3 - Output 3 Status DIO Module 3 - Output 4 Status 1 1 1 1 1 1 1 1 DIO Module 4 - Input 1 Status DIO Module 4 - Input 2 Status DIO Module 4 - Input 3 Status DIO Module 4 - Input 4 Status DIO Module 4 - Output 1 Status DIO Module 4 - Output 2 Status DIO Module 4 - Output 3 Status DIO Module 4 - Output 4 Status 1 1 1 1 1 1 1 1 (All the registers within this module has to be accessed together) Relay Module 1 Relay Module 1 - Output 1 Status Relay Module 1 - Output 2 Status Relay Module 1 - Output 3 Status Relay Module 1 - Output 4 Status Relay Module 2 - Output 1 Status Relay Module 2 - Output 2 Status Relay Module 2 - Output 3 Status Relay Module 2 - Output 4 Status LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Relay Module 3 30290 30291 30292 30293 Disabled Disabled -0 -0 Disabled Inactive -1 -0 Disabled -0 Active -3 Disabled Invalid Value - 02 1 1 1 1 Disabled Disabled - 0- 0 Disabled Inactive -1 -0 Disabled Active -3 -0 Disabled Invalid Value- -0 2 (All the registers within this module has to be accessed together) Relay Module 3 - Output 1 Status Relay Module 3 - Output 2 Status Relay Module 3 - Output 3 Status Relay Module 3 - Output 4 Status 1 1 1 1 Disabled Disabled - 0-0 Disabled Inactive -1 -0 Disabled Active -3 -0 Invalid Value- -0 2 Disabled (All the registers within this module has to be accessed together) Relay Module 4 30294 30295 30296 30297 1 1 1 1 (All the registers within this module has to be accessed together) Relay Module 2 30286 30287 30288 30289 Disabled - 0 Disabled - 0 Disabled Disabled -0 -0 Disabled Inactive -1 -0 Disabled -0 Active -3 Disabled Invalid Value - 02 Disabled - 0 Disabled - 0 (Each module to be accessed separably) Relay Module Status 30282 30283 30284 30285 Disabled - 0 Disabled - 0 Disabled Disabled -0 -0 Disabled Inactive -1 -0 -0 ActiveDisabled -3 InvalidDisabled Value --20 Disabled - 0 Disabled - 0 (All the registers within this module has to be accessed together) DIO Module 4 30274 30275 30276 30277 30278 30279 30280 30281 Interpretation Divisor/ Multiplier (All the registers within this module has to be accessed together) DIO Module 3 30266 30267 30268 30269 30270 30271 30272 30273 UNITS (All the registers within this module has to be accessed together) 1 Disabled - 0 1 Disabled - 0 Disabled - 0 1 Disabled - 0 Inactive - 1 1 -0 Active Disabled -3 1 InvalidDisabled Value - 2- 0 1 Disabled - 0 1 Disabled - 0 1 Disabled - 0 Relay Module 4 - Output 1 Status Relay Module 4 - Output 2 Status Relay Module 4 - Output 3 Status Relay Module 4 - Output 4 Status 1 1 1 1 Disabled Disabled -0-0 Disabled Inactive -1 -0 Active -3 -0 Disabled Invalid Value--02 Disabled 14-5 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 68 OF 86 CD00965 Address Size(in UNITS Divisor/ Multiplier Interpretation words) Active Set Group and Total Trip both has to be accessed together. Parameter Misc. Data 30298 30299 Active Set Group Total Trip 30300 30301 30302 30303 30304 30305 30306 30307 30308 30309 30310 30311 30312 30313 30314 Module 1 Module 2 Module 3 Module 4 Module 5 Module 6 Module 7 Module 8 Module 9 Module 10 Module 11 Module 12 Module 13 Module 14 Module 15 MSB LSB 1 1 1 - Active Set Group 2 1 1 Module Online Status 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 :NA :Module ID Records Each Record should be accessed separately(one at a time). 1 1 1 1 1 1 1 1 1 1 Trip Record ( 44Words ) Trip Cause Trip Time - Year Trip Time - Month Trip Time - Date Trip Time - Hour Trip Time - Min Trip Time - Sec Trip Time - mSec # Pickup Setting String Pickup Setting Multiplication Factor LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING ZIGBEE: 0xB4 DEVICE NET: 0xB5 GSM: 0xB6 PROFIBUS: 0xB7 DATA LOGGER: 0xC0 This location indicates Status of ZSI module.ZSI Module ID = 1C (Only one record can be accessed at a time.) * THIS DRAWING AND DESIGN IS THE PROPE RTY OF EL Module: 0x10 EL Module: Module:0x11 0x10 REF REF Module: 0x11 TCS Module: 0x12 TCS Module: 0x12 DISPLAY_MODULEID : 0X1A DISPLAY_MODULEID : 0X1A ANALOGIO_MODULEID: 0x20 ANALOGIO_MODULEID: 0x20 THERMISTER1_MODULEID: 0x2A THERMISTER1_MODULEID: 0x2A THERMISTER2_MODULEID: 0x2B0x2B THERMISTER2_MODULEID: DIO1_MODULEID: 0x30 DIO1_MODULEID: 0x30 DIO2_MODULEID: 0x40 DIO2_MODULEID: 0x40 DIO3_MODULEID: 0x50 DIO3_MODULEID: 0x50 DIO4_MODULEID: 0x60 DIO4_MODULEID: 0x60 RELAY1_MODULEID: 0x70 RELAY1_MODULEID: 0x70 RELAY2_MODULEID: 0x80 RELAY2_MODULEID: 0x80 RELAY3_MODULEID: 0x90 RELAY3_MODULEID: 0x90 RELAY4_MODULEID: 0xA0 RELAY4_MODULEID: 0xA00xB0 MODBUS_MODULEID: CONFIGURATOR_MODULEID: 0xB1 MODBUS_MODULEID: 0xB0 ETHERNET/TCP IP: 0xB2 0xB1 CONFIGURATOR_MODULEID: Pickup Setting 2 Delay Setting 2 mSec 1.25 R Phase Mean Current 2 A 1 Y Phase Mean Current 2 A 1 B Phase Mean Current 2 A 1 Neutral Mean Current 2 A 1 Earth Fault Mean Current 2 A 1 Restricted Earth Fault Mean Current 2 A 1 Earth Leakage Mean Current 2 A 1 R Phase Mean Voltage 2 V 1 YPhase Mean Voltage 2 V 1 B Phase Mean Voltage 2 V Frequency System Power Factor 1 1 1 1/100 1/100 14-6 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 69 OF 86 CD00965 Address Parameter Mainrenance Period Incoming(0 -Top,1 - Bottom) Poles(0 - 3 Poles,1 - 4 Poles) Phase Sequence(0 - RYB,1 - RBY) 1 1 1 1 1 1 1 1 Trip Record 1 Trip Record 2 Trip Record 3 Trip Record 4 Trip Record 5 Trip Record 6 Trip Record 7 Trip Record 8 Trip Record 9 Trip Record 10 44 44 44 44 44 44 44 44 44 44 System Frequency (0 - 50 Hz, 1- 60 Hz, 2 - 400 Hz) I_Frame(0 - 800A, 1 -1600A, 2 -3200A, 3 -4000A, 4 -6300 A) ^ Rated Current (In) Nominal Voltage(0-220V,1-240V, 2-400V,3-415V,4-440V) & 30324 30368 30412 30456 30500 30544 30588 30632 30676 30720 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF UNITS Interpretation Divisor/ Multiplier Each Record should be accessed separately(one at a time). Event Record ( 9Words ) * Source 30764 30773 30782 30791 30800 30809 30818 30827 30836 30845 30854 30863 30872 30881 30890 30899 30908 30917 30926 30935 30944 30953 30962 30971 30980 30989 30998 31007 31016 31025 31034 31043 31052 Size(in words) Event Type(String Value ALARM -1,TRIP -2,PICKUP- 3) Event Time - Year Event Time - Month Event Time - Date Event Time - Hour Event Time - Min Event Time - Sec Event Time - mSec 1 1 1 1 1 1 1 1 1 Event Record 1 Event Record 2 Event Record 3 Event Record 4 Event Record 5 Event Record 6 Event Record 7 Event Record 8 Event Record 9 Event Record 10 Event Record 11 Event Record 12 Event Record 13 Event Record 14 Event Record 15 Event Record 16 Event Record 17 Event Record 18 Event Record 19 Event Record 20 Event Record 21 Event Record 22 Event Record 23 Event Record 24 Event Record 25 Event Record 26 Event Record 27 Event Record 28 Event Record 29 Event Record 30 Event Record 31 Event Record 32 Event Record 33 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 14-7 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 70 OF 86 CD00965 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Address 31061 31070 31079 31088 31097 31106 31115 31124 31133 31142 31151 31160 31169 31178 31187 31196 31205 31214 31223 31232 31241 31250 31259 31268 31277 31286 31295 31304 31313 31322 31331 31340 31349 31358 31367 31376 31385 31394 31403 31412 31421 31430 31439 31448 31457 31466 31475 31484 31493 31502 31511 31520 31529 31538 31547 31556 31565 31574 31583 31592 31601 31610 31619 Size(in words) Parameter Event Record 34 Event Record 35 Event Record 36 Event Record 37 Event Record 38 Event Record 39 Event Record 40 Event Record 41 Event Record 42 Event Record 43 Event Record 44 Event Record 45 Event Record 46 Event Record 47 Event Record 48 Event Record 49 Event Record 50 Event Record 51 Event Record 52 Event Record 53 Event Record 54 Event Record 55 Event Record 56 Event Record 57 Event Record 58 Event Record 59 Event Record 60 Event Record 61 Event Record 62 Event Record 63 Event Record 64 Event Record 65 Event Record 66 Event Record 67 Event Record 68 Event Record 69 Event Record 70 Event Record 71 Event Record 72 Event Record 73 Event Record 74 Event Record 75 Event Record 76 Event Record 77 Event Record 78 Event Record 79 Event Record 80 Event Record 81 Event Record 82 Event Record 83 Event Record 84 Event Record 85 Event Record 86 Event Record 87 Event Record 88 Event Record 89 Event Record 90 Event Record 91 Event Record 92 Event Record 93 Event Record 94 Event Record 95 Event Record 96 UNITS Interpretation Divisor/ Multiplier 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 14-8 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY:HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 71 OF 86 CD00965 Address 31628 31637 31646 31655 31664 31673 31682 31691 31700 31709 31718 31727 31736 31745 31754 31763 31772 31781 31790 31799 31808 31817 31826 31835 31844 31853 31862 31871 31880 31889 31898 31907 Parameter Event Record 97 Event Record 98 Event Record 99 Event Record 100 Event Record 101 Event Record 102 Event Record 103 Event Record 104 Event Record 105 Event Record 106 Event Record 107 Event Record 108 Event Record 109 Event Record 110 Event Record 111 Event Record 112 Event Record 113 Event Record 114 Event Record 115 Event Record 116 Event Record 117 Event Record 118 Event Record 119 Event Record 120 Event Record 121 Event Record 122 Event Record 123 Event Record 124 Event Record 125 Event Record 126 Event Record 127 Event Record 128 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING UNITS Interpretation Divisor/ Multiplier 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 Maintenance Record (20Words ) Year Month Date Hour Minute Second Millisecond THIS DRAWING AND DESIGN IS THE PROPE RTY OF Size(in words) Each Record should be accessed separately(one at a time). 1 1 1 1 1 1 1 Maximum I2T Value 2 Phase Period Reserved Data 1 1 9 31916 31936 31956 31976 31996 Maintenance Record 1 Maintenance Record 2 Maintenance Record 3 Maintenance Record 4 Maintenance Record 5 20 20 20 20 20 32016 Running Record 20 Module Event Record ( 9Words ) Source Event Type Event Time - Year Event Time - Month Event Time - Date Event Time - Hour Event Time - Min Event Time - Sec Event Time - mSec Each Record should be accessed separately(one at a time). 1 1 1 1 1 1 1 1 1 Module ID:Module ID of the corresponding module.Eg: For display module 0x1A Event Type Strings:0 : Offline,1 : Online 14-9 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 72 OF 86 CD00965 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPERTY OF Address 32036 32045 32054 32063 32072 32081 32090 32099 32108 32117 32126 32135 32144 32153 32162 32171 32180 32189 32198 32207 32216 32225 32234 32243 32252 32261 32270 32279 32288 32297 32306 32315 32324 32333 32342 32351 32360 32369 32378 32387 32396 32405 32414 32423 32432 32441 32450 32459 32468 32477 32486 32495 32504 32513 32522 32531 32540 32549 32558 32567 32576 32585 32594 32603 Parameter Module Event Record 1 Module Event Record 2 Module Event Record 3 Module Event Record 4 Module Event Record 5 Module Event Record 6 Module Event Record 7 Module Event Record 8 Module Event Record 9 Module Event Record 10 Module Event Record 11 Module Event Record 12 Module Event Record 13 Module Event Record 14 Module Event Record 15 Module Event Record 16 Module Event Record 17 Module Event Record 18 Module Event Record 19 Module Event Record 20 Module Event Record 21 Module Event Record 22 Module Event Record 23 Module Event Record 24 Module Event Record 25 Module Event Record 26 Module Event Record 27 Module Event Record 28 Module Event Record 29 Module Event Record 30 Module Event Record 31 Module Event Record 32 Module Event Record 33 Module Event Record 34 Module Event Record 35 Module Event Record 36 Module Event Record 37 Module Event Record 38 Module Event Record 39 Module Event Record 40 Module Event Record 41 Module Event Record 42 Module Event Record 43 Module Event Record 44 Module Event Record 45 Module Event Record 46 Module Event Record 47 Module Event Record 48 Module Event Record 49 Module Event Record 50 Module Event Record 51 Module Event Record 52 Module Event Record 53 Module Event Record 54 Module Event Record 55 Module Event Record 56 Module Event Record 57 Module Event Record 58 Module Event Record 59 Module Event Record 60 Module Event Record 61 Module Event Record 62 Module Event Record 63 Module Event Record 64 Size(in words) UNITS Interpretation Divisor/ Multiplier 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 14-10 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 73 OF 86 CD00965 Address Size(in words) Parameter UNITS Interpretation Divisor/ Multiplier Each Record should be accessed separately(one at a time). Other Event Record ( 9Words ) 1 Source(1 - SG2 To SG1, 2 - SG1 To SG2 Event Type(1 - Auto SG Change,2 - Manual SG Change) 1 Event Time - Year 1 Event Time - Month 1 Event Time - Date 1 Event Time - Hour 1 Event Time - Min 1 Event Time - Sec 1 Event Time - mSec 1 32612 32621 32630 32639 32648 32657 32666 32675 32684 32693 9 9 9 9 9 9 9 9 9 9 SetGroupChangeEvent Record 1 SetGroupChangeEvent Record 2 SetGroupChangeEvent Record 3 SetGroupChangeEvent Record 4 SetGroupChangeEvent Record 5 SetGroupChangeEvent Record 6 SetGroupChangeEvent Record 7 SetGroupChangeEvent Record 8 SetGroupChangeEvent Record 9 SetGroupChangeEvent Record 10 Read/Write parameters Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 In (Amp) 1 1/100 0 150 1 1500 1 10 1 10 1 1 1 - 1 1 1 0 1 0 1 3 1 1 1 1 1 1 1 Set Group 1 Instantaneous 40001 40002 Protection(0: Disable,1: Enable) Pickup Earth Fault 40003 40004 40005 40006 40008 40009 40011 40013 40014 Protection(0: Disable,1: Enable) Mode(1 : Alarm, 2 : Trip, 3 : Both) Cold Load feature(0 : OFF, 1 : ON) Cold Load Delay Low Word Cold Load Delay High Word Pickup IDMT Off Delay Low Word IDMT Off Delay High Word IDMT On Delay Low Word IDMT On Delay High Word E/F Characteristic (IDMT) Prealarm 2 mSec 1.25 80 4000 80 80 1 In (Amp) 1/100 20 60 10 10 2 mSec 1.25 80 800 80 80 2 mSec 1.25 80 320 80 80 1 1 Ig (Amp) 1 1/100 0 50 1 95 1 5 1 5 1 1 1 1 1 1 Is (Amp) - 1 1 1 1 1/100 1 0 0 0 0 50 0 1 1 1 0 95 1 1 1 1 0 5 1 1 1 1 0 5 1 Short Circuit Portection 40015 40016 40017 40018 40019 40020 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 40021 40023 40024 40025 40027 Protection(0: Disable,1: Enable) Double Selective I2T Reserved Prealarm Cold Load feature Cold Load Delay Low Word Cold Load DelayHigh Word Pickup High Pickup low Delay High Low Word Delay High HIgh Word Delay Low Low Word Delay Low Low Word 2 mSec 1.25 80 8000 80 80 1 1 In (Amp) In (Amp) 1/100 1/100 60 60 1200 1200 5 5 5 5 2 mS 1.25 16 320 64 80 2 mS 1.25 16 320 64 80 14-11 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 74 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size 1 1 1 1 1 1 Id (Amp) - 1 1 1 1 1/100 1 0 0 0 0 50 0 1 1 1 0 95 1 1 1 1 0 5 1 1 1 1 0 5 1 80 Further Step Size Directional Short Circuit Protection 40029 40030 40031 40032 40033 40034 40035 40037 40038 Protection Direction I2T Reserved Prealarm Cold Load feature Cold Load Delay Low Word Cold Load Delay High Word Pickup Delay Low Word Delay High Word 2 mSec 1.25 80 8000 80 1 In (Amp) 1/100 60 1200 5 5 2 mS 1.25 16 320 64 80 1 1 1 1 Ir (Amp) - 1 1 1/100 1 0 0 50 0 1 1 95 4 1 1 5 1 1 1 5 1 OverLoad Protection 40040 40041 40042 40043 40044 40046 Protection Thermal Memory Prealarm O/L Characteristic Delay Low Word Delay High Word Pickup 2 mSec 1 0 8 1 1 1 In (Amp) 1/100 40 100 5 5 1 1 1 Ir (Amp) Intrl (Amp) 1 1/100 1/100 0 50 50 1 200 95 1 5 5 1 5 5 1 1 1 - 1 1 1 0 1 0 1 3 1 1 1 1 1 1 1 OverLoad(Neutral) 40047 40048 40049 Protection Pickup Prealarm Restricted Earth Fault 40050 40051 40052 40053 40055 40056 40058 40060 40061 Protection Mode Cold Load feature Cold Load Delay Low Word Cold Load Delay High Word Pickup IDMT Off Delay Low Word IDMT Off Delay High Word IDMT On Delay Low Word IDMT On Delay High Word RE/F Characteristic Prealarm 2 mSec 1.25 48 8000 16 16 1 In (Amp) 1/100 10 60 10 10 2 mSec 1.25 80 4000 80 80 2 mSec 1.25 80 320 80 80 1 1 Iref (Amp) 1 1/100 0 50 1 95 1 5 1 5 1 1 1 Amp mS 1 1 1/10 0 1 3 1 3 300 1 1 1 1 1 1 1.25 80 400 80 80 1 1 1 Ir (Amp) 1 1 1/100 0 1 20 1 3 80 1 1 5 1 1 5 2 mSec 1.25 800 204000 800 800 1 1 1 % 1 1 1 0 1 10 1 3 90 1 1 5 1 1 5 2 mSec 1.25 400 48000 400 400 1 - 1 0 1 1 1 1 1 1 Vn (Volts) 1 1 1/100 0 1 70 1 3 95 1 1 1 1 1 1 Earth Leakage 40062 40063 40064 40065 Protection Mode Pickup Delay Low Word Delay High Word 2 Under Current 40067 40068 40069 40070 Protection Mode Pickup Delay Low Word Delay High Word Curent Unbalance 40072 40073 40074 40075 40077 Protection Mode Pickup Delay Low Word Delay High Word IEC/ANSI Under Voltage 40078 40079 40080 40081 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 40083 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage 2 mS / Sec 1.25 80 4000 80 80 1 Vuv (Volts) 1/100 101 105 1 1 1 1 1 Vn (Volts) 1 1 1/100 0 1 105 1 3 150 1 1 1 1 1 1 Over Voltage 40084 40085 40086 40087 40089 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage 2 mSec 1.25 80 4000 80 80 1 Vov (Volts) 1/100 95 99 1 1 14-12 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 75 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 1 % 1 1 1 0 1 5 1 3 20 1 1 1 1 1 1 2 mSec 1.25 400 48000 400 400 1 V 1/100 95 99 1 1 1 1 1 Vn (Volts) 1 1 1/100 0 1 5 1 3 40 1 1 5 1 1 5 Voltage Unbalance 40090 40091 40092 40093 40095 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage Residual Voltage 40096 40097 40098 40099 40101 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage 2 mSec 1.25 80 4000 80 80 1 Vrv (Volts) 1/100 95 99 1 1 1 1 1 Hz 1 1 1/100 0 1 4500 1 3 6000 1 1 10 1 1 10 2 mSec 1.25 800 24000 100 100 1 Fn 1/100 101 105 1 1 2 Sec 1.25 800 160000 800 800 1 1 1 Hz 1 1 1/100 0 1 4500 1 3 6500 1 1 10 1 1 10 2 mSec 100 Under Frequency 40102 40103 40104 40105 40107 40108 Protection Mode Pickup Delay Low Word Delay High Word Reset Frequency Clod Load Delay Low Word Clod Load Delay High Word Over Frequency 40110 40111 40112 40113 40115 40116 Protection Mode Pickup Delay Low Word Delay High Word Reset Frequency Clod Load Delay Low Word Clod Load Delay High Word 1 1.25 800 24000 100 1/100 95 99 1 1 2 mSec 1.25 800 160000 800 800 1 1 1 Pn (kW) 1 1 1/100 0 1 5 1 3 40 1 1 1 1 1 1 2 mS / Sec 1.25 80 16000 80 80 1 1 1 PF 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 mSec 1.25 800 4000 800 800 1 1 1 PF 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 mSec 1.25 800 4000 800 800 1 1 1 - 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 Sec 1.25 800 4000 800 800 1 1 1 - 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 Sec 1.25 800 4000 800 800 1 1 - 1 1 0 1 1 3 1 1 1 1 - 0 1 0 40 1 3 1 100 1 1 1 1 1 1 1 1 0 0 0 0 Reverse Power 40118 40119 40120 40121 Protection Mode Pickup Delay Low Word Delay High Word Leading Power Factor 40123 40124 40125 40126 Protection Mode Pickup Delay Low Word Delay High Word Lagging Power Factor 40128 40129 40130 40131 Protection Mode Pickup Delay Low Word Delay High Word Peak Factor 40133 40134 40135 40136 Protection Mode Pickup Delay Low Word Delay High Word Form Factor 40138 40139 40140 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPERTY OF 40141 Protection Mode Pickup Delay Low Word Delay High Word Trip Circuit Supervision 40143 40144 Protection Mode Max Demand Energy (Active) 40145 40146 40147 40148 Protection Mode Type Pickup 1 1 1 1 KW 1 1 1 1/100 40149 Reserved 2 - 1 14-13 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY:AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 76 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size - 0 1 0 40 1 3 1 100 1 1 1 1 1 1 1 1 Max Demand Energy (Reactive) 40151 40152 40153 40154 Protection Mode Type Pickup 1 1 1 1 KW 1 1 1 1/100 40155 Reserved 2 - 1 0 0 0 0 - 0 1 0 40 1 3 1 100 1 1 1 1 1 1 1 1 Max Demand Energy (Apparent) 40157 40158 40159 40160 Protection Mode Type Pickup 1 1 1 1 KW 1 1 1 1/100 40161 Reserved 2 - 1 0 0 0 0 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 Reserved 40163 40164 40165 40166 40167 Reserved Reserved Reserved Reserved Reserved Reserved Phase Sequence 40169 40170 40171 Protection Mode Delay Low Word Delay High Word 1 1 - 1 1 0 1 1 3 1 1 1 1 2 mSec 1.25 80 4000 20 20 Braker Failure 40173 40174 Protection Delay Low Word Delay High Word 1 - 1 0 1 1 1 2 mSec 1.25 40 1600 40 40 1 1 1 1 - 1 1 1 1/100 0 0 1 500 1 1 3 5000 1 1 1 100 1 1 1 100 2 mSec 1.25 800 12000 800 800 1 1 1 1 Vn 1 1 1 1 0 0 1 5 1 1 3 50 1 1 1 1 1 1 1 1 2 mSec 1.25 800 12000 800 800 0 0 0 0 0 Total Harmonics Distance Current 40176 40177 40178 40179 40180 Protection Based On Mode Pickup Delay Low Word Delay High Word Total Harmonics Distance Voltage 40182 40183 40184 40185 40186 40188 Protection Based On Mode Pickup Delay Low Word Delay High Word Reserved 1 Set Group 2 Instantaneous 40201 40202 Protection Pickup 1 1 In (Amp) 1 1/100 0 150 1 1500 1 10 1 10 1 1 1 - 1 1 1 0 1 0 1 3 1 1 1 1 1 1 1 Earth Fault 40203 40204 40205 40206 40208 LARSEN & TOUBRO LIMITED 40211 AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 40209 40213 40214 Protection Mode Cold Load feature Cold Load Delay Low Word Cold Load Delay High Word Pickup IDMT Off Delay Low Word IDMT Off Delay High Word IDMT On Delay Low Word IDMT On Delay High Word E/F Characteristic (IDMT) Prealarm 2 mSec 1.25 80 4000 80 80 1 In (Amp) 1/100 20 60 10 10 2 mSec 1.25 80 800 80 80 2 mSec 1.25 80 320 80 80 1 1 Ig (Amp) 1 1/100 0 50 1 95 1 5 1 5 14-14 REVISIONS LARSEN & TOUBRO LIMITED, DATE MTX RELEASE USERS MANUAL SCALE 08.02.2010 ENGINEERS,MUMBAI. - U-POWER DEPT: DRAWN BY: HRA CHECKED BY: AnS APPROVED BY: SSK 300202311 PROJECTION CD00965 SHEET 77 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 1 1 1 1 Is (Amp) - 1 1 1 1 1/100 1 0 0 0 0 50 0 1 1 1 0 95 1 1 1 1 0 5 1 1 1 1 0 5 1 Short Circuit Portection 40215 40216 40217 40218 40219 40220 40221 40223 40224 40225 40227 Protection Double Selective I2T Reserved Prealarm Cold Load feature Cold Load Delay Low Word Cold Load DelayHigh Word Pickup High Pickup low Delay High Low Word Delay High HIgh Word Delay Low Low Word Delay Low Low Word 2 mSec 1.25 80 8000 80 80 1 1 In (Amp) In (Amp) 1/100 1/100 60 60 1200 1200 5 5 5 5 2 mS 1.25 16 320 64 80 2 mS 1.25 16 320 64 80 1 1 1 1 1 1 Id (Amp) - 1 1 1 0 1/100 1 0 0 0 0 50 0 1 1 1 0 95 1 1 1 1 0 5 1 1 1 1 0 5 1 80 Directional Short Circuit Protection 40229 40230 40231 40232 40233 40234 40235 40237 40238 Protection Direction I2T Reserved Prealarm Cold Load feature Cold Load Delay Low Word Cold Load Delay High Word Pickup Delay Low Word Delay High Word 2 mSec 1.25 80 8000 80 1 In (Amp) 1/100 60 1200 5 5 2 mS 1.25 16 320 64 80 1 1 1 1 Ir (Amp) - 1 1 1/100 1 0 0 50 0 1 1 95 4 1 1 5 1 1 1 5 1 OverLoad Protection 40240 40241 40242 40243 40244 40246 Protection Thermal Memory Prealarm O/L Characteristic Delay Low Word Delay High Word Pickup 2 mSec 1 0 8 1 1 1 In (Amp) 1/100 40 100 5 5 1 1 1 Ir (Amp) Intrl (Amp) 1 1/100 1/100 0 50 50 1 200 95 1 5 5 1 5 5 1 1 1 - 1 1 1 0 1 0 1 3 1 1 1 1 1 1 1 OverLoad(Neutral) 40247 40248 40249 Protection Pickup Prealarm Restricted Earth Fault 40250 40251 40252 40253 40255 40256 40258 40260 40261 Protection Mode Cold Load feature Cold Load Delay Low Word Cold Load Delay High Word Pickup IDMT Off Delay Low Word IDMT Off Delay High Word IDMT On Delay Low Word IDMT On Delay High Word RE/F Characteristic Prealarm 2 mSec 1.25 48 8000 16 16 1 In (Amp) 1/100 10 60 10 10 2 mSec 1.25 80 4000 80 80 2 mSec 1.25 80 320 80 80 1 1 Iref (Amp) 1 1/100 0 50 1 95 1 5 1 5 1 1 1 Amp mS 1 1 1/10 0 1 3 1 3 300 1 1 1 1 1 1 1.25 80 400 80 80 1 1 1 Ir (Amp) 1 1 1/100 0 1 20 1 3 80 1 1 5 1 1 5 2 mSec 1.25 800 204000 800 800 1 1 1 % 1 1 1 0 1 10 1 3 90 1 1 5 1 1 5 2 mSec 1.25 400 48000 400 400 1 - 1 0 1 1 1 Earth Leakage 40262 40263 40264 40265 Protection Mode Pickup Delay Low Word Delay High Word 2 Under Current 40267 40268 40269 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHOUT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 40270 Protection Mode Pickup Delay Low Word Delay High Word Curent Unbalance 40272 40273 40274 40275 40277 Protection Mode Pickup Delay Low Word Delay High Word IEC/ANSI 14-15 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 78 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 1 Vn (Volts) 1 1 1/100 0 1 70 1 3 95 1 1 1 1 1 1 Under Voltage 40278 40279 40280 40281 40283 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage 2 mS / Sec 1.25 80 4000 80 80 1 Vuv (Volts) 1/100 101 105 1 1 1 1 1 Vn (Volts) 1 1 1/100 0 1 105 1 3 150 1 1 1 1 1 1 Over Voltage 40284 40285 40286 40287 40289 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage 2 mSec 1.25 80 4000 80 80 1 Vov (Volts) 1/100 95 99 1 1 1 1 1 % 1 1 1 0 1 5 1 3 20 1 1 1 1 1 1 2 mSec 1.25 400 48000 400 400 1 V 1/100 95 99 1 1 1 1 1 Vn (Volts) 1 1 1/100 0 1 5 1 3 40 1 1 5 1 1 5 Voltage Unbalance 40290 40291 40292 40293 40295 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage Residual Voltage 40296 40297 40298 40299 40301 Protection Mode Pickup Delay Low Word Delay High Word Reset Voltage 2 mS / Sec 1.25 80 4000 80 80 1 Vrv (Volts) 1/100 95 99 1 1 1 1 1 Hz 1 1 1/100 0 1 4500 1 3 6000 1 1 10 1 1 10 2 mSec 1.25 800 24000 100 100 1 Fn 1/100 101 105 1 1 2 Sec 1.25 800 160000 800 800 1 1 1 Hz 1 1 1/100 0 1 4500 1 3 6500 1 1 10 1 1 10 2 mSec 100 Under Frequency 40302 40303 40304 40305 40307 40308 Protection Mode Pickup Delay Low Word Delay High Word Reset Frequency Clod Load Delay Low Word Clod Load Delay High Word Over Frequency 40310 40311 40312 40313 40315 40316 Protection Mode Pickup Delay Low Word Delay High Word Reset Frequency Clod Load Delay Low Word Clod Load Delay High Word 1 1.25 800 24000 100 1/100 95 99 1 1 2 mSec 1.25 800 160000 800 800 1 1 1 Pn (kW) 1 1 1/100 0 1 5 1 3 40 1 1 1 1 1 1 2 mS / Sec 1.25 80 16000 80 80 1 1 1 Pf 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 mSec 1.25 800 4000 800 800 1 1 1 Pf 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 mSec 1.25 800 4000 800 800 1 1 1 - 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 mSec 1.25 800 4000 800 800 Reverse Power 40318 40319 40320 40321 Protection Mode Pickup Delay Low Word Delay High Word Leading Power Factor 40323 40324 40325 40326 Protection Mode Pickup Delay Low Word Delay High Word LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Lagging Power Factor 40328 40329 40330 40331 Protection Mode Pickup Delay Low Word Delay High Word Peak Factor 40333 40334 40335 40336 Protection Mode Pickup Delay Low Word Delay High Word 14-16 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 79 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value 1 1 1 - 1 1 1/100 0 1 50 1 3 99 1 1 1 1 1 1 2 mSec 1.25 800 4000 800 800 1 1 - 1 1 0 1 1 3 1 1 1 1 - 0 1 0 40 1 3 1 100 1 1 1 1 1 1 1 1 First Step Size Further Step Size Form Factor 40338 40339 40340 40341 Protection Mode Pickup Delay Low Word Delay High Word Trip Circuit Supervision 40343 40344 Protection Mode Max Demand Energy (Active) 40345 40346 40347 40348 Protection Mode Type Pickup 1 1 1 1 KW 1 1 1 1/100 40349 Reserved 2 - 1 0 0 0 0 - 0 1 0 40 1 3 1 100 1 1 1 1 1 1 1 1 Max Demand Energy (Reactive) 40351 40352 40353 40354 Protection Mode Type Pickup 1 1 1 1 KW 1 1 1 1/100 40355 Reserved 2 - 1 0 0 0 0 - 0 1 0 40 1 3 1 100 1 1 1 1 1 1 1 1 Max Demand Energy (Apparent) 40357 40358 40359 40360 Protection Mode Type Pickup 1 1 1 1 KW 1 1 1 1/100 40361 Reserved 2 - 1 0 0 0 0 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 Reserved 40363 40364 40365 40366 40367 Reserved Reserved Reserved Reserved Reserved Reserved Phase Sequence 40369 40370 40371 Protection Mode Delay Low Word Delay High Word 1 1 - 1 1 0 1 1 3 1 1 1 1 2 mSec 1.25 80 4000 20 20 Braker Failure 40373 40374 Protection Delay Low Word Delay High Word 1 - 1 0 1 1 1 2 mSec 1.25 40 1600 40 40 1 1 1 1 - 1 1 1 1/100 0 0 1 500 1 1 3 5000 1 1 1 100 1 1 1 100 2 mSec 1.25 800 12000 800 800 1 1 1 1 Vn 1 1 1 1 0 0 1 5 1 1 3 50 1 1 1 1 1 1 1 1 2 mSec 1.25 800 12000 800 800 0 0 0 0 0 Total Harmonics Distance Current 40376 40377 40378 40379 40380 Protection Based On Mode Pickup Delay Low Word Delay High Word Total Harmonics Distance Voltage 40382 40383 40384 40385 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 40386 40388 Protection Based On Mode Pickup Delay Low Word Delay High Word Reserved 1 14-17 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 80 OF 86 CD00965 Address Size(in Words) Parameter UNITS Divisor/ Multiplier Min Value Max Value First Step Size Hz A A V Month(s) - Refer Comment Refer Comment Refer Comment Refer Comment Refer Comment Refer Comment Refer Comment Refer Comment Refer Comment 0 0 0 0 0 0 0 0 0 2 4 14 4 5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 1 1 0 0 0 59 59 23 0 31 12 99 0 0 1 1 1 0 1 1 1 0 0 1 1 1 0 1 1 1 0 0 1 1 1 1 1 1 1 1 1 0 0 0 126 0 0 0 1 0 0 0 1 0 0 0 Further Step Size System Settings 40400 40401 40402 40403 40404 40405 40406 40407 40408 Frequency I_Frame Rated Current (In) Nominal Voltage Maintenance Period Maintenance Enable/Disable Incoming Poles Phase Sequence 1 1 1 1 1 1 1 1 1 Poles Unit Settings DateTime 40415 40416 40417 40418 40419 40420 40421 40422 40423 Seconds Minutes Hour Reserved Date Month Year Reserved Reserved Local Communication Setting(1107 Protocol) 40424 40425 40426 40427 Device ID Reserved Reserved Reserved EventRecorder 40428 40429 40430 40431 40432 40433 40434 EventPickup EventTrip EventAlarm ModuleConnected Module Removed RelayModuleInputs DigitalInputOutputModule 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 40435 Metering Sign Convention 1 1 0 2 1 1 1 1 1 1 0 0 1 1 1 1 1 1 Oscillography Settings 40436 40437 Oscillography Enable/ Disable Trigger Source Maximum Demand 40438 40439 40440 Reserved MD Integration Period MD Sliding Interval 1 1 1 Minutes Minutes 1 1 0 0 0 0 1 2 0 1 1 0 1 1 Minutes 1 1 0 0 3 2 1 1 1 1 Load Profile 40441 40442 LP Active Configuration Interval 1 1 40443 Logo Display 1 1 0 1 1 1 40444 Setting Password 1 1 0 9999 1 1 40445 Command Password 1 1 0 9999 1 1 1 1 1 1 1 1 0 13 0 2 63 0 1 1 0 1 1 0 2 1 0 0 0 0 2 1 0 0 0 0 Display Settings 40446 40447 40448 40449 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF 40451 Language Contrast Reserved Reserved Reserved Reserved Reserved 40453 AutoChange SET GROUP Enable / Disable 1 1 0 1 1 1 40454 40455 40456 SG1 To SG2 Hour Minutes Reserved 1 1 1 1 1 1 0 0 0 23 59 0 1 0 1 0 40457 40458 40459 SG2 To SG1 Hour Minutes Reserved 1 1 1 1 1 1 0 0 0 23 59 0 1 1 0 1 1 0 14-18 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 81 OF 86 CD00965 Size(in Words) Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 1 1 1 1 0 1 1 99 12 31 1 1 1 1 1 1 DayLight Saving Time(DST) DST Enable / Disable 1 1 0 1 1 1 40464 40465 40466 40467 Start DST Setting Start DST Month Start DST Date Start DST Hour Start DST Minute 4 1 1 1 1 1 1 1 1 1 1 0 0 12 31 23 59 1 1 1 1 1 1 1 1 40468 40469 40470 40471 End DST Setting End DST Month End DST Date End DST Hour End DST Minute 4 1 1 1 1 1 1 1 1 1 1 0 0 12 31 23 59 1 1 1 1 1 1 1 1 Argument 2 0x00 - Active Set Group1 0x00 0x00 0x00 0x00 0x00 0x00 0x00 0x00 0x00 96 106 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Address Parameter 40460 40461 40462 Installation Date Year Month Date 40463 UNITS Commands 40500 Command Change SetGroup Restore Factory Defaults Clear MD Clear max current value Clear max voltage value Clear Energy Open breaker Close breaker Breaker maintenance done EF test 2 Argument 1 0x60 0x61 0x62 0x63 0x64 0x65 0x66 0x67 0x68 0x6A Module Settings DIO Module1 40600 40601 40602 40603 40604 40605 40606 40607 40608 40609 DIO1 Enable Input 1 Enable Input 2 Enable Input 3 Enable Input 4 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Input Type DIO Module2 40610 40611 40612 40613 40614 40615 40616 40617 40618 40619 DIO2 Enable Input 1 Enable Input 2 Enable Input 3 Enable Input 4 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Input Type LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF DIO Module3 40620 40621 40622 40623 40624 40625 40626 40627 40628 40629 DIO3 Enable Input 1 Enable Input 2 Enable Input 3 Enable Input 4 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Input Type DIO Module4 40630 40631 40632 40633 40634 40635 40636 40637 40638 40639 DIO4 Enable Input 1 Enable Input 2 Enable Input 3 Enable Input 4 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Input Type 14-19 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 82 OF 86 CD00965 Address Parameter Size(in Words) Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 1 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1/100 0.100 0 0 0 1 50 850 1 1 1 3 95 1150 1 1 1 1 5 1 1 1 1 1 5 1 2 1 0 15 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 1 1 2 1 1 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 1 14 14 14 14 0 0 0 0 1 1 1 1 1 0 0 0 0 1 1 1 1 1 0 0 0 0 1 1 1 1 1 1 0 0 0 1 1 3 1 1 1 1 1 1 1.25 48 320 8 8 1 0 0 0 1 0 1 0 1 0 UNITS Relay Module 1 40640 40641 40642 40643 40644 Relay1 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Relay Module 2 40645 40646 40647 40648 40649 Relay2 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Relay Module 3 40650 40651 40652 40653 40654 Relay3 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Relay Module 4 40655 40656 40657 40658 40659 Relay4 Enable Output 1 Enable Output 2 Enable Output 3 Enable Output 4 Enable Thermistor Module 40660 40661 40662 40663 40664 40665 40666 Temp Module 1 Enable Temp Module 2 Enable Protection Mode Prealarm Pickup Temp TemperatureDelay_LW TemperatureDelay_HW Modbus Module 40668 40669 40670 40671 40672 40673 Modbus Module Enable Modbus Protocol Type Parity Stop bit Baud rate Type Baud rate bps Configurator Module 40674 Configurator Module Enable AnalogOutputModule 40675 40676 40677 40678 40679 40680 40681 40682 40683 Analog Module Enable Output Parameter 0 Output Parameter 1 Output Parameter 2 Output Parameter 3 Reserved Reserved Reserved Reserved ZSI Module 40684 40685 40686 40687 ZSI Module Enable Directional ZSI Configuration ZSIDelay LW ZSIDelay HW mSec Profibus Module LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF #VALUE! Profibus Module Enable #VALUE! Reserved 1 1 14-20 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 83 OF 86 CD00965 Address Parameter Size(in Words) UNITS Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 1 1 1 1 In 1 1 1 1/100 0 0 1 20 1 1 3 60 1 1 1 1 1 1 1 1 2 mSec 1.25 80 800 80 80 2 mSec 1.25 80 800 80 80 1 1 1 1/100 0 50 1 95 1 5 1 5 1 1 1 1 Amps 1 1 1 1/100 0 0 1 30 1 1 3 3000 1 1 1 20 1 1 1 50 2 mSec 1.25 80 4000 80 80 1 1 1 1 1 1 0 0 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1 0 11 0 1 26 999 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 REF Module 40760 40761 40762 40763 40764 40766 40768 40769 REF Module Enable PROTECTION MODE PICKUP I2T OFF DELAY LOW WORD I2T OFF DELAY HIGH WORD I2T ON DELAY LOW WORD I2T ON DELAY HIGH WORD REF CHARACTERISTIC RESERVED EL Module 40770 40771 40772 40773 40774 EL Module Enable PROTECTION MODE PICKUP DELAY LW (in ticks, 1 tick = 1.25mS) DELAY HW (in ticks, 1 tick = 1.25mS) TCS Module 40776 40777 40778 TCS Module Enable PROTECTION MODE Zigbee Module 40779 40780 40781 ZIGBEEModuleEnable Frequency Channel Select PAN ID RelayBoolean Equations Relay 1 40800 40803 40806 40809 40812 40815 40818 40821 40824 40827 40830 40833 40836 40839 40842 40845 Relay Out 1.1.1 Relay Out 1.1.2 Relay Out 1.1.3 Relay Out 1.1.4 Relay Out 1.2.1 Relay Out 1.2.2 Relay Out 1.2.3 Relay Out 1.2.4 Relay Out 1.3.1 Relay Out 1.3.2 Relay Out 1.3.3 Relay Out 1.3.4 Relay Out 1.4.1 Relay Out 1.4.2 Relay Out 1.4.3 Relay Out 1.4.4 Relay 2 40848 40851 40854 40857 40860 40863 40866 40869 40872 40875 40878 40881 40884 40887 40890 40893 Relay Out 2.1.1 Relay Out 2.1.2 Relay Out 2.1.3 Relay Out 2.1.4 Relay Out 2.2.1 Relay Out 2.2.2 Relay Out 2.2.3 Relay Out 2.2.4 Relay Out 2.3.1 Relay Out 2.3.2 Relay Out 2.3.3 Relay Out 2.3.4 Relay Out 2.4.1 Relay Out 2.4.2 Relay Out 2.4.3 Relay Out 2.4.4 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF Relay 3 40896 40899 40902 40905 40908 40911 40914 40917 40920 40923 40926 40929 40932 40935 40938 40941 Relay Out 3.1.1 Relay Out 3.1.2 Relay Out 3.1.3 Relay Out 3.1.4 Relay Out 3.2.1 Relay Out 3.2.2 Relay Out 3.2.3 Relay Out 3.2.4 Relay Out 3.3.1 Relay Out 3.3.2 Relay Out 3.3.3 Relay Out 3.3.4 Relay Out 3.4.1 Relay Out 3.4.2 Relay Out 3.4.3 Relay Out 3.4.4 14-21 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 84 OF 86 CD00965 Address Parameter Size(in Words) Divisor/ Multiplier Min Value Max Value First Step Size Further Step Size 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 UNITS Relay 4 40944 40947 40950 40953 40956 40959 40962 40965 40968 40971 40974 40977 40980 40983 40986 40989 Relay Out 4.1.1 Relay Out 4.1.2 Relay Out 4.1.3 Relay Out 4.1.4 Relay Out 4.2.1 Relay Out 4.2.2 Relay Out 4.2.3 Relay Out 4.2.4 Relay Out 4.3.1 Relay Out 4.3.2 Relay Out 4.3.3 Relay Out 4.3.4 Relay Out 4.4.1 Relay Out 4.4.2 Relay Out 4.4.3 Relay Out 4.4.4 DIO Boolean Equations DIO 1 41000 41003 41006 41009 41012 41015 41018 41021 41024 41027 41030 41033 41036 41039 41042 41045 DIO Out 1.1.1 DIO Out 1.1.2 DIO Out 1.1.3 DIO Out 1.1.4 DIO Out 1.2.1 DIO Out 1.2.2 DIO Out 1.2.3 DIO Out 1.2.4 DIO Out 1.3.1 DIO Out 1.3.2 DIO Out 1.3.3 DIO Out 1.3.4 DIO Out 1.4.1 DIO Out 1.4.2 DIO Out 1.4.3 DIO Out 1.4.4 DIO 2 41048 41051 41054 41057 41060 41063 41066 41069 41072 41075 41078 41081 41084 41087 41090 41093 DIO Out 2.1.1 DIO Out 2.1.2 DIO Out 2.1.3 DIO Out 2.1.4 DIO Out 2.2.1 DIO Out 2.2.2 DIO Out 2.2.3 DIO Out 2.2.4 DIO Out 2.3.1 DIO Out 2.3.2 DIO Out 2.3.3 DIO Out 2.3.4 DIO Out 2.4.1 DIO Out 2.4.2 DIO Out 2.4.3 DIO Out 2.4.4 DIO 3 41096 41099 41102 41105 41108 41111 41114 41117 41120 41123 41126 41129 41132 41135 41138 41141 DIO Out 3.1.1 DIO Out 3.1.2 DIO Out 3.1.3 DIO Out 3.1.4 DIO Out 3.2.1 DIO Out 3.2.2 DIO Out 3.2.3 DIO Out 3.2.4 DIO Out 3.3.1 DIO Out 3.3.2 DIO Out 3.3.3 DIO Out 3.3.4 DIO Out 3.4.1 DIO Out 3.4.2 DIO Out 3.4.3 DIO Out 3.4.4 LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF DIO 4 41144 41147 41150 41153 41156 41159 41162 41165 41168 41171 41174 41177 41180 41183 41186 41189 DIO Out 4.1.1 DIO Out 4.1.2 DIO Out 4.1.3 DIO Out 4.1.4 DIO Out 4.2.1 DIO Out 4.2.2 DIO Out 4.2.3 DIO Out 4.2.4 DIO Out 4.3.1 DIO Out 4.3.2 DIO Out 4.3.3 DIO Out 4.3.4 DIO Out 4.4.1 DIO Out 4.4.2 DIO Out 4.4.3 DIO Out 4.4.4 14-22 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 85 OF 86 CD00965 Address 40752 Size(in Words) Parameter Third Party S/W Login Address UNITS Divisor/ Multiplier Queries Query from Third Party Software. For login query Device Id : Write Function Code : Add High: Add Low: No of regs High: No of regs Low: No of bytes: Login And logout query First Step Size Max Value Further Step Size Response to Third Party Software. Error Response to Third Party Software. For logout query 0x10 0x02 0xF0 0x00 0x02 0x04 0x00 0x01 Login ID 0x00 0x00 0x00 0x00 Password High: Password Low: CRC Low : CRC High : Queries Min Value 2 Device Id : Write Function Code : Add High : Add Low : No of regs High : No of regs Low : CRC Low : CRC High : 0x10 0x02 0xF0 0x00 0x02 Device Id : Function Code : Error Code CRC Low : CRC High : 0x80 | 0x10 Response From Third Party Software. Device Id : Write Function Code : Add High: Add Low: No of regs High: No of regs Low: No of bytes: Changing password Login ID 0x10 0x02 0xF0 0x00 0x02 0x04 0x00 0x02 New Password High: New Password Low: CRC Low : CRC High : * Trip Cause,Event Cause 1 - Instantaneous 2 - Earth Fault 3 - Short Circuit 4 - Directional Short Circuit 5 - Overload 6 - Neutral Overload 7 - ZSI Earth Fault 8 - ZSI Short Circuit 9 - Phase Sequence 10 - Restricted Earth Fault 11 - Earth Leakage # Pickup Setting String LARSEN & TOUBRO LIMITED AND MUST NOT BE COPIED OR LENT WITHO UT THEIR PERMISSION IN WRITING THIS DRAWING AND DESIGN IS THE PROPE RTY OF C1447: String 22 - Lead Power Factor 23 - Lag Power Factor 24 - Peak Factor 25 - Form Factor 26 - MD ActIve 27 - MD Reactive 28 - MD Apparent 29 - THD 30 - Terminal Temperature 31 - Earth Fault Test ^ Rated Current (In) & Maintenance Period If I_FRAME = X then Rated_Current should list the following values Value BLANK AMPERES VOLTS PERCENT PS_RYB PS_RBY KW KVAR KVA DEG_C HERTZ 12 - Current Unbalance 13 - Under Current 14 - Under Voltage 15 - Over Voltage 16 - Voltage Unbalance 17 - Residual Voltage 18 - Under Frequency 19 - Over Frequency 20 - Reverse Power 21 - Trip Circuit Supervision X 0 1 2 3 4 5 6 7 8 9 10 800 1600 3200 4000 6300 Rated_Current 0 - 400, 1 - 630, 2 - 800 3 - 1000, 4 - 1250, 5 - 1600 6 - 2000, 7 - 2500, 8 - 3200 9 - 2000, 10 - 2500, 11 - 3200, 12 - 4000 13 - 5000, 14 - 6300 0 - 1 Month 1 - 2 Months 2 - 3 Months 3 - 4 Months 4 - 5 Months 5 - 6 Months 6 - 7 Months 7 - 8 Months 8 - 9 Months 9 - 10 Months 10 -11 Months 11 -12 Months 14-22 REVISIONS LARSEN & TOUBRO LIMITED, DATE SCALE 08.02.2010 - ENGINEERS,MUMBAI. MTX RELEASE USERS MANUAL U-POWER DEPT: DRAWN BY:HRA CHECKED BY:AnS APPROVED BY:SSK 300202311 PROJECTION CD00965 SHEET 86 OF 86