HYDRAULIC CALCULATION FOR FOAM SYSTEM-WFF 5. As per NFPA 11, Clause no 10.7.3 Pressure restriction orifice are provided for the following tank bund protection in order to reduce the pressure. S.no Provided Foam system Protected Equipment / Area Pressure drop (Bar) Orifice diameter (mm) 1 Jet A-1 Storage Tank T201 Bund 1.8 161 2 Jet A-1 Storage Tank T202 Bund 1.0 181 3 Jet A-1 Storage Tank T203 Bund 1.3 173 4 Jet A-1 Storage Tank T204 Bund 0.6 194 5 Jet A-1 Storage Tank T205 Bund 1.3 170 6 Cross field pumps Bund 5.0 66 7 Refullers 3.0 50 8 WTAP Hydrant pumps 4.0 67 9 Test rig & fullers bay 2.8 73 10 Defuller 5.8 23 Bund Protection 6. As per the outcome of hydraulic calculation results the worst-case foam solution demand is 17914 Lpm (1075 m3/hr) for Jet A-1 Storage Tank T203 Bund fire and Foam Concentrate demand is 32.25 m3/hr (1075 X 0.03 = 32.25). Hence, the proposed foam concentrate pump capacity of 33 m3/hr is sufficient to cater the foam concentrate demand. 7. As per the outcome of hydraulic calculation results the worst-case foam solution demand is 17914 Lpm (1075 m3/hr) for Jet A-1 Storage Tank T203 Bund fire and the required foam concentrate for 30 minutes operation is 16.12 m3. Hence, the proposed foam concentrate tank capacity of 20 m3/hr is sufficient to cater foam concentrate demand. DOC. NO.: AC001-D6000-17-U0C-U-XXX0005 Rev 01 Page 23 of 45