ON LOAD GEARS INSPECTION REPORT UNIT II 432, 433 SIDCO Estate, 88, Yadhaval Street, Ambattur, Chennai - 600 098. Description : Finger contact OLG QA/F. 11 Supplier : I/R No :1 I/R Date Spec./ Drg. No. : AQL % Sl. No. 5131700R2 : Qty. Supplied 2.5 Specification : Lot/Sample Qty. : : 5Nos D.C. No. : 5 Nos GRIN No. : Observations 1 2 3 4 5 6 7 8 Concl. 1 25.4 (±0.2) 25.80 25.70 25.80 25.60 25.70 Not Ok 2 31.8 (±0.3) 32.00 32.40 32.37 32.00 32.30 Not Ok 3 Radius 1.5 4 87±0.2 5 R32.7 6 45 deg 44.50 7 2.4 3.00 3.50 3.40 3,20 2.80 Not ok 8 Conductivity Min 97 76 76 76 78 76 Not Ok Not Found 9.15 9.5 9.19 15.04.22 REMARKS Not Ok 9.6 9.52 Not Ok Not Found 44.00 45.00 44.00 45.00 No radius at 45 deg 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Qty. Accepted Note : 1.Conductivity is 76 only instead of 98 2.Radius 1.5 at the base is important but not found Qty. Rejected 5 Inspected By K.Rajaselvam 15.04.2022 Approved By M.Pugazhendhi. 15.04.2022 Note : Please take back rejected / rework material from our works at your cost within two weeks from the date of Inspection Report. If material is not lifted beyond stipulated time limit, we shall not be held responsible in any manner whatsoever and any claim for the material or cost thereof will not be binding on us. All suppliers are requested to cooperate. DOC No. WQAD 13