Angle Stability component failure, etc. However, it is important that system operators do everything possible to ensure as many regulators are in automatic mode as possible. This action helps ensure adequate reactive power support and may help avoid system instability. 7.6 Transient Stability/Instability This section describes transient stability and instability and presents several illustrated examples. 7.6.1 Process of Transient Stability The transient environment is characterized by a system that undergoes a sudden, severe disturbance. In contrast to the steady state environment where changes occur gradually, the transient environment involves rapid changes. Figure 7-13 illustrates the power system used to illustrate transient stability and instability. This system has remote generation feeding through two high voltage transmission lines into a large power system. A remote generator tied to a large power system is used to keep our description simple. The large power system is not impacted significantly by what happens to the generator or the two-line transmission system. Figure 7-13. Power System for Transient Stability & Instability The top portion of Figure 7-14 contains the initial or pre-disturbance power system. The remote generator is initially producing 1,000 MW. This MW is transmitted to a large power system via two transmission lines. The large system has 101,000 MW of load, 100,000 MW of which is fed from local generation. A disturbance is created in this power system to study the transient stability of the system. The circuit breakers at both ends of one of the transmission lines are opened. From the generator perspective, once a line is opened the generator suddenly has to transmit its mechanical power input across a much higher impedance system. The generator must now work harder to transmit its MW across the transmission system to the load area. The bottom portion of Figure 7-14 contains power-angle curves for this system. There are two curves; one for pre-disturbance conditions and one for after the line 7-20 11697808 Angle Stability opens (post-disturbance). Note the pre-disturbance power-angle curve has a higher PMAX. Once the line is opened the transmission path has sharply higher impedance that results in a lower PMAX. Note in Figure 7-14 that the postdisturbance curve has a significantly lower peak than the pre-disturbance curve. Transient stability is a rapid event. From the initial disturbance to the peak of the angle swing is, at most, a few seconds. Figure 7-14. Power-Angle Curves for 1,000 MW Generator Loading Initially the power system is operating at point “A” in Figure 7-14. When the line opens the operating point instantly shifts from point “A” to a position on the postdisturbance power-angle curve at point “B”. When at point “B”, the generator must accelerate since its mechanical power input is now greater than the electrical power the generator can push out. As the generator accelerates it turns faster than synchronous speed. The angle increases due to this relative acceleration and slides from point “B” towards “C”. When the operating point reaches “C”, the generator’s MW output is again equal to the mechanical power input. However, the angle cannot stop increasing. The whole time the generator operated below the mechanical power input line it was storing energy in its rotor. The generator is now spinning faster than synchronous 7-21 11697808 Angle Stability If the generator had not slowed down to synchronous speed by the time it reached point “F” it would have been transiently unstable. This possibility is addressed in the next section. speed. The angle keeps increasing as long as the generator’s speed is greater than synchronous speed. The generator must rid itself of the excess stored energy before it can return to synchronous speed and stop the angle increase. As the operating point rises above point “C”, the generator starts to slow down. The generator slows because it is now sending out more electrical power than it is taking in mechanical power. The generator rises above point “C” until it slows down to synchronous speed. This occurs at point “D” in Figure 7-14. If the generator had not slowed down to synchronous speed by the time it reached point “F” it would have gone unstable. Equal Area Criterion for Transient Stability Immediately following the line opening the operating point shifted from point “A” on the pre-disturbance curve to point “B” on the post-disturbance curve. This movement represented an immediate reduction in MW transfer due to the opening of the line. The angle then increased from “B” through “C” and on to “D”. The angle stopped increasing at “D”. As the operating point moved, there were two areas created bounded by the points “A-B-C” and “C-D-E”. These two areas are shaded and labeled “1” and “2” in Figure 7-14. The two areas represent the accelerating and decelerating periods of the generator. Area “1” represents the accelerating period of the generator. The size of area “1” is equivalent to the energy stored in the rotor. Area “2” represents the decelerating period of the generator. The size of area “2” is equivalent to the energy removed from the rotor. The operating point rose above point “C” until area “2” was the same size as area “1”. This is called the equal area criterion for transient stability. If area “2” is not equal to area “1” by the time point “F” is reached, the power system enter a period of instability. Area “1” represents the energy that is absorbed by the rotor as a result of the reduced MW transfer across the system. This absorbed energy is what causes the rotor to speed-up and the angle to increase. Area “2” represents the energy released by the rotor as it decelerates due to the electrical power output exceeding the mechanical power input. The equal area criterion basically states that the amount of energy required to slow the rotor to synchronous speed is equal to the amount of energy that was added to accelerate it from synchronous speed. If the decelerate area cannot match the accelerate area, instability occurs. Maximum Angle Our angle stability descriptions to this point have stated that the angle difference between any two adjoining points in the power system can never stabilize at a value greater than 90°. Note that we have emphasized, “stabilize” at a value. The angle can exceed 90° for short periods of time as long as its final value returns to less than 90°. This can happen if the angle is oscillating about a point that is less than 90°. 7-22 11697808 Angle Stability Note that the angle in Figure 7-14 could have swung all the way to point “F” as long as it did not pass through point “F”. Once the operating point has passed point “F”, the system is unstable. Once past point “F”, the electrical power output is again less than the mechanical power input. The angle must increase, as energy is again stored in the rotor. As the angle is already greater than 90° when past point “F” the only option is a further angle increase and eventual angle instability. Figure 7-15 illustrates the same information as Figure 7-14 but in a different format. Points “A”, “B”, “C” and “D” are labeled on Figure 7-15. These labeled points correspond to the labeled areas on Figure 7-14. Note that once disturbed the MW output of the generator oscillates about 1,000 MW before finally settling down at 1,000 MW. In this example of transient stability the MW output starts and ends at 1,000 MW. During the oscillation the output may swing between 1,500 to 500 MW. Note the time frames in Figure 7-15. Once the angle started to reduce from point “D”, it indicates that the system was transiently stable. It took approximately 1 second to determine whether this system was transiently stable or unstable. It takes only a few seconds to determine if the angle recovers from the first swings. However, the oscillations that follow the first few swings may last for many more seconds. When the oscillations finally settle down or dampen, the operating point is at “C”. The angle at point “C” is greater than the initial angle at point “A”. This is expected since the system has lost a line and the path impedance is now greater. For transient stability we are only concerned with the first several swings. Oscillatory stability concerns itself with subsequent swings. 7-23 11697808 Angle Stability Several points are labeled “C” in this figure. This is intentional as the operating point swings through point “C” several times before finally settling at point “C”. Figure 7-15. Strip Chart Equivalent of Figure 7-11 7.6.2 Process of Transient Instability The top of Figure 7-16 is the same power system as was used in Figure 7-14 with the exception of the loading on the system. Figure 7-14 had a loading of 1,000 MW on the remote generator. When one of the lines was opened the system remained transiently stable. Figure 7-16 has a loading of 1,500 MW on the remote generator. One of the two lines is again opened. The shock to the system is greater since larger amounts of MW flow and a larger initial angle are involved. The power-angle curve at the bottom of Figure 7-16 illustrates that the operating point shifts from its initial location at point “A” to “B” once the line is opened. The remote generator now has more mechanical power input than electrical power output and must accelerate. As the generator accelerates the angle increases. The angle keeps increasing until the generator can again return to synchronous speed. If the generator does not return to synchronous speed by the time the operating point reaches “F”, the system is transiently unstable. 7-24 11697808 Angle Stability Since the decelerating area (area #2) is smaller than the accelerating area (area #1) this generator goes out-of-step with the larger power system. Figure 7-16. Power Angle Curve for Transient Instability A close inspection of Figure 7-16 reveals that this generator goes out-of-step as predicted by the equal area criterion. The important point to note is that area “2” is smaller than area “1”. This means there is not enough decelerating energy to return the generator’s rotor to synchronous speed before reaching point “F”. Since the generator is still above synchronous speed after point “F” is reached, the angle continues to increase. The electrical output again drops below the mechanical power input line. This causes the generator to further accelerate and go out-of-step. The system illustrated in Figure 7-16 is transiently unstable. The generator never recovered from the initial angle swing. Once the generator passed through point “F” it accelerated at a faster and faster rate. Once the angle passes 180°, the generator starts motoring (absorbing MW) and accelerates even faster. Generator protection systems are sometimes designed to detect out-of-step conditions and trip the generator before damage occurs. 7-25 11697808 Angle Stability 7.6.3 Transient Stability Following a Fault The top of Figure 7-17 illustrates the same system and generation levels as Figure 7-14 but now, instead of just opening a line’s circuit breakers, a fault occurs. With a fault occurrence there are three power-angle curves instead of two. One curve is for the pre-fault conditions, one curve is for post-fault conditions, and one curve is for the period of time during which the fault is applied. The fault is cleared by the transmission line’s protective relays. While the fault is applied to the system, voltages are depressed due to the large rush of reactive current to the fault. The depressed voltage is represented by the low peak (low PMAX) of the power-angle curve while the fault is applied. Immediately after the fault is applied, the operating point shifts from the pre-fault curve at point “A” to the fault curve at point “B”. The angle then increases along the fault curve until the fault is cleared at point “J”. The size of the accelerating area (area “1”) is directly related to the fault clearing time. When the fault is cleared the operating point shifts to the post-fault curve. The post-fault curve is smaller then the pre-fault curve because one of the transmission lines is out-of-service. The power-angle curves of Figure 7-17 indicate that the system is transiently stable as the generator reached synchronous speed at point “D”. The operating point then oscillates back and forth before finally settling at point “C”. Figure 7-17 follows on the next page. 7-26 11697808 Angle Stability The faulted system curve is the smallest of the three curves as system voltage is depressed during the fault. Figure 7-17. Transient Stability and a Fault 3F Fault and an Extended Power Angle Curve The top of Figure 7-18 again illustrates our simple power system. A 3Φ fault is now applied at the remote generator’s high side bus. Three phase faults are generally the most severe type of fault. While this 3Φ fault is applied, no MW can leave the generator. All of the generator’s mechanical power input is stored in and accelerates the rotor. The bottom of Figure 7-18 contains an extended power angle curve. Instead of illustrating only 180° this figure illustrates several alternations of the sine curve. Note the size of the accelerating area (area “1”) in Figure 7-18. The decelerating area (area “2”) is no match for the accelerating area and the generator pulls outof-step from the larger power system. 7-27 11697808 Angle Stability Figure 7-18. Extended Power-Angle Curve After the operating point passes through point “G” the generator becomes a motor. While motoring the generator absorbs MW from the system, which further accelerates the generator’s rotor. The combination of the mechanical power input to the generator and the generator acting as a motor creates a second large accelerating area “3”. The decelerating area “4” is again no match for the accelerating area “3” and the generator continues its out-of-step operation. Throughout our description of transient stability we assumed that the mechanical power input stays constant. This is a reasonable assumption as it is very difficult to rapidly change the mechanical power input. In Figure 7-18 note that after a few seconds mechanical power input is slowly reduced. However, the reduction is too little too late and the generator is unstable. In the next section several methods for achieving rapid, and effective reductions in mechanical power input are described. 7-28 11697808 Angle Stability 7.6.4 Further Observations with Power-Angle Curves Benefits of High Speed Reclosing Several additional concepts can be illustrated on a power-angle curve. One concept is the benefit of high-speed reclosing following faults. Assume that the fault in Figure 7-17 was a line-to-ground fault. Further assume that the faulted transmission line was equipped with high speed reclosing. If this reclosing had been successful, instead of shifting from the faulted conditions power-angle curve to the post-fault curve, the system would have shifted back to the larger pre-fault curve with two lines in service. With two lines available to draw MW out of the generator the chances of remaining stable are greatly increased. If high speed reclosing had been successfully used, area “1” in Figure 7-17 would be slightly smaller. Area #2 would not need to be as large and, if required, area #2 would have more room to grow. The maximum angle growth (point “D”) would therefore not be as large. A risk of high speed reclosing is the chance of closing back into the fault and ending up worse off than just letting the line trip. The effect of closing back into the fault as seen in Figure 7-17 would be a much larger area “1” with the distance from points “B” to “J” being greater. As we now know, the larger area “1” is, the higher the risk of instability. Need for High Speed Protective Relaying Power-angle curves also illustrate the need for high-speed protective relays in the transmission system. The faster the fault is cleared, the smaller the accelerating area. The smaller the accelerating area, the less the angle grows and the better the chances to remain angle stable. Use of Fast Valving Earlier sections have stated that it is difficult to make rapid changes to the mechanical power input. While it may be difficult to accomplish, this type of action could be well worth the effort. Note the position of the mechanical power input line in Figure 7-18. If following a disturbance, a rapid movement downward could be made to the position of this line, the accelerating area would be reduced and the decelerating area increased. A rapid adjustment to mechanical power input could save a system from transient instability. Steam turbine/generators may use a process called “fast valving” to achieve a rapid reduction in mechanical power input. Figure 7-19 illustrates the fast valving process. The steam flows to the intermediate and low-pressure turbine stages through the intercept valve. A fast valving system is designed to rapidly shut the intercept valve when the generator is at risk of transient instability. When the intercept valve is quickly shut possibly two-thirds of the generator’s mechanical power input is suddenly removed. This action greatly reduces the accelerating energy in the system and possibly avoids instability. 7-29 11697808 While many steam units have the ability to use fast valving, few actually implement the scheme due to the possible harmful impact to the boiler. Angle Stability Following a severe disturbance it may take ½ second to shut the intercept valve. The valve then remains closed for a few seconds. Ideally no steam is vented and the generator is rapidly brought back to initial loading. Figure 7-19. Fast Valving in Steam Units Hydro units cannot utilize fast valving but a hydro-based system can employ a process with a similar purpose. Braking resistors are sometimes installed in hydro-based systems. Braking resistors are large resistive loads. The braking resistor control logic monitors system parameters to determine if the local power system is accelerating. If all the conditions are met, the braking resistor is placed in-service. The braking resistor remains in-service for only a short time, perhaps 20 cycles. While it is in-service the braking resistor slows the system down. This deceleration may be sufficient to avoid instability. British Columbia Hydro also has a braking resistor installed adjacent to their northern most hydro generation. Figure 7-20 is a picture of the Bonneville Power Administration (BPA) braking resistor. This large brake (rated 230 kV & 1,400 MW) is located in the Pacific Northwest. The brake is inserted if the Pacific Northwest power system accelerates with respect to the rest of the Western Interconnection. While inserted the brake slows down the Pacific Northwest system and helps reduce the angle growth. 7-30 11697808 Angle Stability The three towers in the picture form the braking resistor. The towers contain approximately 10 miles of ½ inch stainless-steel wire stretching from the towers to ground. These wires form the brake’s resistance. 230 kV transmission lines connect the towers to the power system via circuit breakers. When the brake is needed to stop acceleration, the circuit breakers are closed and the brake is placed inservice for ½ second Figure 7-20. The BPA Braking Resistor Generator Dropping An additional option for rapidly reducing the power system’s accelerating energy is to quickly trip generation. Generator dropping refers to the intentional tripping of generating units. Generators may be tripped to avoid an accelerating condition that could lead to instability. NERC utilities drop both steam and hydro generation. However the dropping of hydro generation has definite advantages, as it is often simple and rapid process to re-synchronize a hydro unit. In contrast, there are many events that could occur which could delay the re-synchronizing of a steam unit. 7.7 Oscillatory Stability/Instability This section describes oscillatory stability and instability and presents several illustrated examples. The oscillatory environment is characterized by a system that is constantly changing. MW, Mvar, voltage magnitudes, angles, and frequency may be oscillating. The study of oscillatory stability is similar to steady state stability in that no severe triggering event is required. A system may enter into a period of oscillatory instability as the result of a minor disturbance such as a line switching operation. Oscillatory instability may be a slowly developing event. A system may begin a period of oscillations that last for several seconds, minutes, or even 7-31 11697808 The causes, effects, and control of the oscillations that accompany oscillatory stability and instability are further addressed Chapter 8.