IECEx Certificate
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Certificate No.:
IECEx CML 16.0004X
Page 1 of 5
Status:
Current
Issue No: 1
Date of Issue:
2021-01-05
Applicant:
Pepperl+Fuchs SE
Lilienthalstrasse 200
68307 Mannheim
Germany
Equipment:
GL Range of terminal enclosures
Optional accessory:
Type of Protection:
Increased Safety, Intrinsic safety & Dust Protected
Marking:
Ex eb IIC T6/5/4 Gb
Ex ia IIC T6/5/4 Ga
Ex tb III C T80/95/130°C Db
Ta (limits up to) = -50°C to +60°C
Refer to Annex for all marking options.
Approved for issue on behalf of the IECEx
Certification Body:
R C Marshall
Position:
Operations Manager
Signature:
(for printed version)
Date:
(for printed version)
1. This certificate and schedule may only be reproduced in full.
2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.
Certificate issued by:
Eurofins E&E CML Limited
Unit 1, Newport Business Park
New Port Road
Ellesmere Port, CH65 4LZ
United Kingdom
Certificate history:
Issue 0 (2016-03-03)
IECEx Certificate
of Conformity
Certificate No.:
IECEx CML 16.0004X
Page 2 of 5
Date of issue:
2021-01-05
Issue No: 1
Manufacturer:
Pepperl+Fuchs SE
Lilienthalstrasse 200
68307 Mannheim
Germany
Additional
manufacturing
locations:
See following pages for more locations
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended
STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards
IEC 60079-0:2011
Edition:6.0
Explosive atmospheres - Part 0: General requirements
IEC 60079-11:2011
Edition:6.0
Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
IEC 60079-31:2013
Edition:2
Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t"
IEC 60079-7:2015
Edition:5.0
Explosive atmospheres – Part 7: Equipment protection by increased safety ''e''
This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.
TEST & ASSESSMENT REPORTS:
A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:
Test Reports:
GB/CML/ExTR16.0005/00
GB/CML/ExTR20.0239/00
Quality Assessment Reports:
DE/PTB/QAR06.0015/15
FR/INE/QAR12.0003/08
US/UL/QAR07.0005/15
IECEx Certificate
of Conformity
Certificate No.:
IECEx CML 16.0004X
Page 3 of 5
Date of issue:
2021-01-05
Issue No: 1
EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:
The GL type junction boxes are a range of hazardous area, IP 66 terminal junction boxes. They comprise a glass fibre reinforced polyester enclosure, component certified
under IECEx SIR 06.0105U, fitted with separately certified terminals and/or surface mount plug and socket connectors (DXN1, DXN3 or DXN6).
Refer to Annex for full description and Conditions of Manufacture.
SPECIFIC CONDITIONS OF USE: YES as shown below:
Refer to Annex
IECEx Certificate
of Conformity
Certificate No.:
IECEx CML 16.0004X
Page 4 of 5
Date of issue:
2021-01-05
Issue No: 1
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above)
i. Updating the Applicant
ii.Updating the QAR
iii. Updating the manufacturing locations
IECEx Certificate
of Conformity
Certificate No.:
IECEx CML 16.0004X
Page 5 of 5
Date of issue:
2021-01-05
Issue No: 1
Additional manufacturing locations:
Pepperl+Fuchs sri
Via Galileo Galilei 1/B
1-20875 Burago (MB)
Italy
Pepperl+Fuchs SE
Bussmatten 10-12
77815 Buehl/Baden
Germany
Pepperl+Fuchs Manufacturing (India)
Private Limited
Plot No. A-13
Sipcot Industrial Growth centre
ORAGADAM TAMIL NADU 602105
India
Pepperl+Fuchs (AUstralia) Pty Ltd.
131 - 149, Link Drive
Campbellfield 3061
Victoria Australia
Australia
Pepperl+Fuchs (Shanghai) Automation
Engineering Co. Ltd
Nr. 269, Yuanzhong Rd.
Huinan Town
Pudong District
Shanghai, 201399
China
Pepperl+Fuchs Manufacturing Inc.
502 Cane Island Parkway, Katy, TX 77494
United States of America
Annex:
IECEx CML 16_0004X Annex iss 1.pdf
Annexe to:
IECEx CML 16.0004X Issue 1
Applicant:
Pepperl+Fuchs SE
Apparatus:
GL Range of terminal enclosures
Description
The GL type junction boxes are a range of hazardous area, IP 66 terminal junction boxes. They
comprise a glass fibre reinforced polyester enclosure, component certified under
IECEx SIR 06.0105U, fitted with separately certified terminals and/or surface mount plug and
socket connectors (DXN1, DXN3 or DXN6).
The GL type range is available in 14 sizes designated GL1 to GL14D as shown in the table below.
The sides of the enclosures may be drilled for entries by the manufacturer or in accordance to the
manufacturer’s instructions. The enclosures are available with an optional earth continuity plate or
earth stud fitted by the manufacturer.
All enclosures sizes from the range may be fitted with separately certified terminals mounted on
DIN rails fitted to the base of the enclosures.
Enclosures GL11 to GL14D may be fitted with separately certified plug and socket connectors
(DXN1, DXN3 or DXN6). These connectors may be installed to three of the four sides of the
enclosure, with a maximum of two connecters per side.
Only items from the Pepperl+Fuchs approved range may be fitted. Before they are installed, the
maximum power dissipation shall be calculated in accordance with IEC 60079-7, Annex E.2 and
shall not exceed the values given in the table below:
GL Enclosure
Maximum Power Dissipation (W)
Type
Size
(WxHxD)
T6/T80°C
(-50°C to +40°C)
T5/T95°C
(-50°C to +55°C)
T4/T130°C
(-50°C to +60°C)
GL1
GL2
GL3
GL4
GL5
GL6
GL7
GL8
GL9
GL10
GL11
GL11D
GL12
GL13
GL14
GL14D
80x75x55
110x75x55
160x75x55
190x75x55
122x120x90
220x120x90
160x160x90
260x160x90
360x160x90
560x160x90
255x250x120
255x250x165
400x250x120
405x400x120
405x400x165
405x400x200
7.5
8.0
9.0
9.0
9.4
9.4
10.4
12.0
13.8
13.8
15.5
15.5
15.5
31.4
31.4
31.4
1 of 3
T6/T80°C
-50°C to +50°C
1.6
2.0
3.0
3.0
3.5
3.5
4.3
5.0
6.2
6.2
6.4
6.4
6.4
11.2
11.2
11.2
Terminal enclosures may also be manufactured to sizes not specified in this table provided that any
given dimension is not larger than the respective dimension of the largest enclosure or smaller than
the respective dimension of the smallest enclosure. The power rating applied to a terminal
enclosure of intermediate size is that of the next smallest enclosure.
Marking
There are several options that the equipment can be marked with, as specified below:
T6 Marking
Ex ia IIC T6 Ga
-50°C to +40°C or +50°C
Ex eb IIC T6 Gb
Ex tb IIIC T80°C Db
-50°C to +40°C or +50°C
T5 Marking
Ex ia IIC T5 Ga
-50°C to +55°C
Ex eb IIC T5 Gb
Ex tb IIIC T95°C Db
-50°C to +55°C
T4 Marking
Ex ia IIC T4 Ga
-50°C to +60°C
Ex eb IIC T4 Gb
Ex tb IIIC T130°C Db
-50°C to +60°C
Ambient range limited to -40°C to +40°C when fitted with Marechal plugs/sockets
Conditions of Manufacture
i.
ii.
iii.
iv.
v.
The equipment covered by this certificate incorporates the use of previously certified
components, it is therefore the responsibility of the manufacturer to continually monitor the
status of the certification associated with these components. The manufacturer shall notify
CML of any modifications to the components that may impinge upon the explosion safety
aspects of the GL range of terminal enclosures.
The power rating marking on the label shall be allocated in accordance with the table
detailed in the product description on the certificate.
The manufacturer will take all reasonable steps to ensure that the power dissipated by the
terminal box does not exceed the maximum value stipulated the table detailed in the
Description, and shall supply all the relevant information that will allow the installer/user to
calculate the power dissipation (Watts) in accordance with IEC 60079-7, Annex E, E.2 for
each terminal box.
When terminals are supplied with the enclosure, they shall be appropriately IECEx
approved components, chosen from the Pepperl+Fuchs approved range as stated in
document 16-1241CML-04 and having a minimum insulation temperature range of:
• T6
=-50°C to +80°C
• T5
=-50°C to +95°C
• T4
=-50°C to +100°C.
All terminals fitted shall be suitably Ex eb IIC Gb certified and installed in accordance with
their certification requirements. Terminals are to be similar in size to the existing terminals
listed and shall not reduce creepage and clearance.
2 of 3
vi.
vii.
viii.
ix.
x.
All cable glands and plugs/stoppers for unused entries shall be suitable for use with the
equipment and shall be:
• certified as group II category 2 G D
• have a minimum ingress protection of IP 66
When the GL Range Junction Boxes are fitted with the Marechal plug/sockets (as stated in
document 16-1241CML-04) the equipment shall be marked for a maximum ambient range
of -40°C to +40°C.
Terminal enclosures may be manufactured to sizes not specified in the table in the
description. Any given dimension shall not be larger than the respective dimension of the
largest enclosure or smaller than the respective dimension of the smallest enclosure. The
power rating applied to a terminal enclosure of intermediate size shall be that of the next
smallest enclosure.
If enclosures are supplied with wiring, a dielectric strength test is required at 2 x rated
voltage +1000V with a minimum of 1500V for 60s in accordance with clause 7.1 of
IEC 60079-7:2015
A metallic label shall be fitted to equipment marked with an ambient temperature
below -40°C
IECEx Conditions of Certification (IECEx Special Conditions for Safe Use)
i.
ii.
Enclosures which are fitted with the Marechal Type DXN1, DXN3 and DXN6 sockets (as
stated in document 16-1241CML-04) shall be protected from impacts of greater than 4
Joules.
Non-metallic external surfaces may be a potential electrostatic charge hazard and shall
therefore be cleaned only with a damp cloth.