IECEx Certificate of Conformity INTERNATIONAL ELECTROTECHNICAL COMMISSION IEC Certification System for Explosive Atmospheres for rules and details of the IECEx Scheme visit www.iecex.com Certificate No.: IECEx CML 16.0004X Page 1 of 5 Status: Current Issue No: 1 Date of Issue: 2021-01-05 Applicant: Pepperl+Fuchs SE Lilienthalstrasse 200 68307 Mannheim Germany Equipment: GL Range of terminal enclosures Optional accessory: Type of Protection: Increased Safety, Intrinsic safety & Dust Protected Marking: Ex eb IIC T6/5/4 Gb Ex ia IIC T6/5/4 Ga Ex tb III C T80/95/130°C Db Ta (limits up to) = -50°C to +60°C Refer to Annex for all marking options. Approved for issue on behalf of the IECEx Certification Body: R C Marshall Position: Operations Manager Signature: (for printed version) Date: (for printed version) 1. This certificate and schedule may only be reproduced in full. 2. This certificate is not transferable and remains the property of the issuing body. 3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code. Certificate issued by: Eurofins E&E CML Limited Unit 1, Newport Business Park New Port Road Ellesmere Port, CH65 4LZ United Kingdom Certificate history: Issue 0 (2016-03-03) IECEx Certificate of Conformity Certificate No.: IECEx CML 16.0004X Page 2 of 5 Date of issue: 2021-01-05 Issue No: 1 Manufacturer: Pepperl+Fuchs SE Lilienthalstrasse 200 68307 Mannheim Germany Additional manufacturing locations: See following pages for more locations This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended STANDARDS : The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards IEC 60079-0:2011 Edition:6.0 Explosive atmospheres - Part 0: General requirements IEC 60079-11:2011 Edition:6.0 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i" IEC 60079-31:2013 Edition:2 Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure "t" IEC 60079-7:2015 Edition:5.0 Explosive atmospheres – Part 7: Equipment protection by increased safety ''e'' This Certificate does not indicate compliance with safety and performance requirements other than those expressly included in the Standards listed above. TEST & ASSESSMENT REPORTS: A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in: Test Reports: GB/CML/ExTR16.0005/00 GB/CML/ExTR20.0239/00 Quality Assessment Reports: DE/PTB/QAR06.0015/15 FR/INE/QAR12.0003/08 US/UL/QAR07.0005/15 IECEx Certificate of Conformity Certificate No.: IECEx CML 16.0004X Page 3 of 5 Date of issue: 2021-01-05 Issue No: 1 EQUIPMENT: Equipment and systems covered by this Certificate are as follows: The GL type junction boxes are a range of hazardous area, IP 66 terminal junction boxes. They comprise a glass fibre reinforced polyester enclosure, component certified under IECEx SIR 06.0105U, fitted with separately certified terminals and/or surface mount plug and socket connectors (DXN1, DXN3 or DXN6). Refer to Annex for full description and Conditions of Manufacture. SPECIFIC CONDITIONS OF USE: YES as shown below: Refer to Annex IECEx Certificate of Conformity Certificate No.: IECEx CML 16.0004X Page 4 of 5 Date of issue: 2021-01-05 Issue No: 1 DETAILS OF CERTIFICATE CHANGES (for issues 1 and above) i. Updating the Applicant ii.Updating the QAR iii. Updating the manufacturing locations IECEx Certificate of Conformity Certificate No.: IECEx CML 16.0004X Page 5 of 5 Date of issue: 2021-01-05 Issue No: 1 Additional manufacturing locations: Pepperl+Fuchs sri Via Galileo Galilei 1/B 1-20875 Burago (MB) Italy Pepperl+Fuchs SE Bussmatten 10-12 77815 Buehl/Baden Germany Pepperl+Fuchs Manufacturing (India) Private Limited Plot No. A-13 Sipcot Industrial Growth centre ORAGADAM TAMIL NADU 602105 India Pepperl+Fuchs (AUstralia) Pty Ltd. 131 - 149, Link Drive Campbellfield 3061 Victoria Australia Australia Pepperl+Fuchs (Shanghai) Automation Engineering Co. Ltd Nr. 269, Yuanzhong Rd. Huinan Town Pudong District Shanghai, 201399 China Pepperl+Fuchs Manufacturing Inc. 502 Cane Island Parkway, Katy, TX 77494 United States of America Annex: IECEx CML 16_0004X Annex iss 1.pdf Annexe to: IECEx CML 16.0004X Issue 1 Applicant: Pepperl+Fuchs SE Apparatus: GL Range of terminal enclosures Description The GL type junction boxes are a range of hazardous area, IP 66 terminal junction boxes. They comprise a glass fibre reinforced polyester enclosure, component certified under IECEx SIR 06.0105U, fitted with separately certified terminals and/or surface mount plug and socket connectors (DXN1, DXN3 or DXN6). The GL type range is available in 14 sizes designated GL1 to GL14D as shown in the table below. The sides of the enclosures may be drilled for entries by the manufacturer or in accordance to the manufacturer’s instructions. The enclosures are available with an optional earth continuity plate or earth stud fitted by the manufacturer. All enclosures sizes from the range may be fitted with separately certified terminals mounted on DIN rails fitted to the base of the enclosures. Enclosures GL11 to GL14D may be fitted with separately certified plug and socket connectors (DXN1, DXN3 or DXN6). These connectors may be installed to three of the four sides of the enclosure, with a maximum of two connecters per side. Only items from the Pepperl+Fuchs approved range may be fitted. Before they are installed, the maximum power dissipation shall be calculated in accordance with IEC 60079-7, Annex E.2 and shall not exceed the values given in the table below: GL Enclosure Maximum Power Dissipation (W) Type Size (WxHxD) T6/T80°C (-50°C to +40°C) T5/T95°C (-50°C to +55°C) T4/T130°C (-50°C to +60°C) GL1 GL2 GL3 GL4 GL5 GL6 GL7 GL8 GL9 GL10 GL11 GL11D GL12 GL13 GL14 GL14D 80x75x55 110x75x55 160x75x55 190x75x55 122x120x90 220x120x90 160x160x90 260x160x90 360x160x90 560x160x90 255x250x120 255x250x165 400x250x120 405x400x120 405x400x165 405x400x200 7.5 8.0 9.0 9.0 9.4 9.4 10.4 12.0 13.8 13.8 15.5 15.5 15.5 31.4 31.4 31.4 1 of 3 T6/T80°C -50°C to +50°C 1.6 2.0 3.0 3.0 3.5 3.5 4.3 5.0 6.2 6.2 6.4 6.4 6.4 11.2 11.2 11.2 Terminal enclosures may also be manufactured to sizes not specified in this table provided that any given dimension is not larger than the respective dimension of the largest enclosure or smaller than the respective dimension of the smallest enclosure. The power rating applied to a terminal enclosure of intermediate size is that of the next smallest enclosure. Marking There are several options that the equipment can be marked with, as specified below: T6 Marking Ex ia IIC T6 Ga -50°C to +40°C or +50°C Ex eb IIC T6 Gb Ex tb IIIC T80°C Db -50°C to +40°C or +50°C T5 Marking Ex ia IIC T5 Ga -50°C to +55°C Ex eb IIC T5 Gb Ex tb IIIC T95°C Db -50°C to +55°C T4 Marking Ex ia IIC T4 Ga -50°C to +60°C Ex eb IIC T4 Gb Ex tb IIIC T130°C Db -50°C to +60°C Ambient range limited to -40°C to +40°C when fitted with Marechal plugs/sockets Conditions of Manufacture i. ii. iii. iv. v. The equipment covered by this certificate incorporates the use of previously certified components, it is therefore the responsibility of the manufacturer to continually monitor the status of the certification associated with these components. The manufacturer shall notify CML of any modifications to the components that may impinge upon the explosion safety aspects of the GL range of terminal enclosures. The power rating marking on the label shall be allocated in accordance with the table detailed in the product description on the certificate. The manufacturer will take all reasonable steps to ensure that the power dissipated by the terminal box does not exceed the maximum value stipulated the table detailed in the Description, and shall supply all the relevant information that will allow the installer/user to calculate the power dissipation (Watts) in accordance with IEC 60079-7, Annex E, E.2 for each terminal box. When terminals are supplied with the enclosure, they shall be appropriately IECEx approved components, chosen from the Pepperl+Fuchs approved range as stated in document 16-1241CML-04 and having a minimum insulation temperature range of: • T6 =-50°C to +80°C • T5 =-50°C to +95°C • T4 =-50°C to +100°C. All terminals fitted shall be suitably Ex eb IIC Gb certified and installed in accordance with their certification requirements. Terminals are to be similar in size to the existing terminals listed and shall not reduce creepage and clearance. 2 of 3 vi. vii. viii. ix. x. All cable glands and plugs/stoppers for unused entries shall be suitable for use with the equipment and shall be: • certified as group II category 2 G D • have a minimum ingress protection of IP 66 When the GL Range Junction Boxes are fitted with the Marechal plug/sockets (as stated in document 16-1241CML-04) the equipment shall be marked for a maximum ambient range of -40°C to +40°C. Terminal enclosures may be manufactured to sizes not specified in the table in the description. Any given dimension shall not be larger than the respective dimension of the largest enclosure or smaller than the respective dimension of the smallest enclosure. The power rating applied to a terminal enclosure of intermediate size shall be that of the next smallest enclosure. If enclosures are supplied with wiring, a dielectric strength test is required at 2 x rated voltage +1000V with a minimum of 1500V for 60s in accordance with clause 7.1 of IEC 60079-7:2015 A metallic label shall be fitted to equipment marked with an ambient temperature below -40°C IECEx Conditions of Certification (IECEx Special Conditions for Safe Use) i. ii. Enclosures which are fitted with the Marechal Type DXN1, DXN3 and DXN6 sockets (as stated in document 16-1241CML-04) shall be protected from impacts of greater than 4 Joules. Non-metallic external surfaces may be a potential electrostatic charge hazard and shall therefore be cleaned only with a damp cloth. 3 of 3