Uploaded by a.hansen

TP48120A-HD09A1

advertisement
Outdoor Power System
TP48120A-HD09A1
Introduction
TP48120A-HD09A1 is a small outdoor cabinet to supply power for
wireless site. It configures 30A/50A rectifier modules to supply
rated of 120A output current, with heat exchange cooling for
equipment cabin and fan cooling for battery cabin. The cabinet is
compactly designed and support various installation scenarios
such as wall mounted, pole mounted or grounding. It has excellent
performance such as wide range of AC input voltage, high power
efficiency, surge protection, intelligent temperature and battery
management, and remote management.
Features
 High protection level:IP55
 High efficiency of rectifier module: >96%
 Super temperature performance for rectifiers with range from
-40℃ to 75℃
 The power module supports hot-swapping, easy to install and
maintain
 Temperature control system built-in door, easy to maintain,
clean, replace
 Strong anti-theft design: Door embedded, hinge hidden, 3point lock, door sensor, support padlock
 Intelligent battery management, prolong battery lifespan
Pole Mounted
(Pole size:Φ114~220mm)
 Support battery anti-reverse function, reducing operating risk
 Support remote management, reducing customer operating
cost
Application Scenarios
 Outdoor wireless site
 Outdoor enterprise communication network
Wall Mounted
Specifications
System
AC
Distribution
Dimension
650mm(W)×650mm(D)×900mm(H) (excluding base)
Weight
≤75kg (without rectifier module and battery)
Cooling mode
Heat exchange(equipment cabin) +Fan cooling(battery cabin)
Cooling capacity
1500W
Heater
500W(optional)
Installation mode
On ground\Wall mounted\Pole mounted
Cabling mode
At the bottom, inlet/outlet downwards
Maintenance mode
In front
Noise
ETS300 753 4.1E standard
Protection level
IP55
Battery space
8U (100AH)
User space
8U
MTBF
200,000 hours
Input mode
Three phase, single phase
Input voltage
85VAC~300VAC, rated: 220VAC;
Input frequency
45~65Hz, rated value: 50Hz/60Hz
Input capacity
1×63A/3P
SPD
20kA/40kA, 8/20μs
Maintenance socket(AC output) Universal
Three phase/single phase:
1×16A/1P(maintenance socket)
AC output
1×16A/1P
DC
Distribution
Rectifier
Output voltage
42~58VDC, rated value: 53.5VDC
Maximum capacity
120A
Battery branch
1x125A MCB
LLVD branch
1×80A MCB, 3×30A FUSE
BLVD branch
3×30A FUSE
SPD
10kA/20kA, 8/20μs
Input voltage
85VAC~300VAC, rated 220VAC
Rated power
30A/50A
Working temperature
-40℃~+75℃
Weight
<2kg
Power factor
≥0.99
THD
≤5%
Signal input
Controller
Environment
3 AI(battery temp., ambient temp., ambient humidity)
9 DI(water, smoke, gate, 6 common DI)
Alarm output
8 dry contact
Communication port
RS232, RS485, SNMP
Storage capacity
Up to 1000 historical records
Display mode
LCD
Operating temperature
-40℃~+45℃ (+ solar radiation)
Storage temperature
-40℃~+70℃
Operating humidity
5%~95%(non-condensing)
Altitude
0~4000m
Copyright © Huawei Technologies Co., Ltd. 2014. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com
Outdoor Power System
TP48200A-HD15A6
Introduction
TP48200A-HD15A6 is an AC/DC outdoor power system that configures 1U
48V/50A rectifier modules to supply rated of 200A output current, with heat
exchanger in power cabin and direct ventilation in battery cabin . The system
has excellent performance such as wide range of AC input voltage, high
power efficiency, surge protection, intelligent temperature and battery
management, and remote management. The TP48200A-HD15A6 is used in
class C environment for various outdoor scenarios.
Features
 High protection level: IP55 for power cabin, IP45 for battery cabin
 Super temperature performance for rectifiers with range from
-40℃ to 75℃
 The power module supports hot-swapping, easy to install and maintain
 Temperature control system built-in door, easy to maintain, clean and replace
 Strong anti-theft design: door embedded, hinge hidden, 3-point lock, door sensor and
supporting padlock
 Intelligent battery management prolongs battery lifespan
 Support battery anti-reverse function, reducing operating risk
 Support remote management, reducing customer operating cost
Application Scenarios
 Outdoor wireless site
 Outdoor enterprise communication network
Specifications
Dimension
650mm(W)×650mm(D)×1500mm(H) (excluding base)
Weight
≤100kg (without rectifier module)
Cooling mode
System
DC
Distribution
Rectifier
Grounding\rooftop\wall against
Cabling mode
At the bottom, inlet/outlet downwards
Maintenance mode
In front
Noise level
Satisfied GR487, noise≤65dBA@1.5m
Environment
Power cabin: IP55
Battery cabin: IP45
Battery space
16U (Maximum 2*190Ah)
User space
9U
MTBF
200,000 hours
Input mode
Three phase compatible with single phase
Input voltage
380V/220VAC
Input frequency
45~65Hz, rated value: 50Hz/60Hz
Input capacity
1×63A/3P
SPD
20kA/40kA, 8/20μs
Maintenance socket
Universal 220Vac socket (with 16A MCB protection)
AC output
1*16A/1P MCB, 220Vac output
Output voltage
42~58VDC, rated value: 53.5VDC
Maximum capacity
12kW (4*3000W)
Battery branch
2*125A MCB
LLVD branch
2*63A MCB, 2*32A MCB
BLVD branch
2*16A MCB, 1*10A MCB
SPD
10kA/20kA, 8/20μs
Input voltage
85VAC~300VAC, rated 220VAC
Rated power
3000W(>96%)
Working temperature
-40℃~+75℃
Dimensions
105mm(W)×281mm(D)×40.8mm(H)
Weight
<2kg
Power factor
≥0.99
THD
≤5%
Signal input
Controller
Battery cabin: direct ventilation
Installation mode
Protection level
AC
Distribution
Power cabin: Heat exchange 850W
3 AI(battery temp., ambient temp., ambient humidity)
9 DI(water, smoke, gate, 6 common DI)
Alarm output
8 dry contact
Communication port
RS232, RS485, SNMP
Storage capacity
Up to 50000 historical records
Display mode
LCD
Operating temperature
-10℃~+45℃ (+ solar radiation)
Storage temperature
-40℃~+70℃
Operating humidity
5%~95%(non-condensing)
Altitude
0~4000m
Remark: normal efficiency(>94%, 3000W) rectifier is optional
Copyright © Huawei Technologies Co., Ltd. 2014. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com
Outdoor Power System
TP48200A-HD15A7
Introduction
TP48200A-HD15A7 is an AC/DC outdoor power system that configures 1U
48V/50A rectifier modules to supply rated of 200A output current, with heat
exchanger in power cabin and direct ventilation in battery cabin . The system
has excellent performance such as wide range of AC input voltage, high
power efficiency, surge protection, intelligent temperature and battery
management, and remote management. The TP48200A-HD15A7 is used in
class B environment for various outdoor scenarios.
Features
 High protection level: IP55 for power cabin, IP45 for battery cabin
 Super temperature performance for rectifiers with range from
-40℃ to 75℃
 The power module supports hot-swapping, easy to install and maintain
 Temperature control system built-in door, easy to maintain, clean and replace
 Strong anti-theft design: door embedded, hinge hidden, 3-point lock, door sensor and
supporting padlock
 Intelligent battery management prolongs battery lifespan
 Support battery anti-reverse function, reducing operating risk
 Support remote management, reducing customer operating cost
Application Scenarios
 Outdoor wireless site
 Outdoor enterprise communication network
Specifications
Dimension
650mm(W)×650mm(D)×1500mm(H) (excluding base)
Weight
≤100kg (without rectifier module)
Cooling mode
System
DC
Distribution
Rectifier
Grounding\rooftop\wall against
Cabling mode
At the bottom, inlet/outlet downwards
Maintenance mode
In front
Noise level
Satisfied GR487, noise≤65dBA@1.5m
Environment
Power cabin: IP55
Battery cabin: IP45
Battery space
16U (Maximum 2*190Ah)
User space
9U
MTBF
200,000 hours
Input mode
Dual live wire
Input voltage
110V/220VAC
Input frequency
45~65Hz, rated value: 50Hz/60Hz
Input capacity
1×125A/2P
SPD
30kA/60kA, 8/20μs
Maintenance socket
Universal 110Vac socket (with 10A RCD protection)
AC output
1*16A/2P MCB, 220Vac output
Output voltage
42~58VDC, rated value: 53.5VDC
Maximum capacity
12kW (4*3000W)
Battery branch
2*125A MCB
LLVD branch
1*80A MCB, 6*32A MCB
BLVD branch
1*80A MCB, 2*32A MCB, 1*10A MCB
SPD
10kA/20kA, 8/20μs
Input voltage
85VAC~300VAC, rated 220VAC
Rated power
3000W(>96%)
Working temperature
-40℃~+75℃
Dimensions
105mm(W)×281mm(D)×40.8mm(H)
Weight
<2kg
Power factor
≥0.99
THD
≤5%
Signal input
Controller
Battery cabin: direct ventilation
Installation mode
Protection level
AC
Distribution
Power cabin: Heat exchange 850W
3 AI(battery temp., ambient temp., ambient humidity)
9 DI(water, smoke, gate, 6 common DI)
Alarm output
8 dry contact
Communication port
RS232, RS485, SNMP
Storage capacity
Not less than 1000 historical records
Display mode
LCD
Operating temperature
-10℃~+45℃ (+ solar radiation)
Storage temperature
-40℃~+70℃
Operating humidity
5%~95%(non-condensing)
Altitude
0~4000m
Remark: normal efficiency(>94%, 3000W) rectifier is optional
Copyright © Huawei Technologies Co., Ltd. 2014. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
General Disclaimer
The information in this document may contain predictive statements including,without limitation, statements regarding the future
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com
Download