Transformer Test Report Product Model: 3150kVA/34.5kV Product No: Test conclusion: Test date: Inspector: SUNGROW POWER SUPPLY Co.,Ltd Confidential 1 Description Name of Product Type of Product Serial No. Drawing No. 2 Technical Specification Power Rating 3.15 MVA Cooling Type KNAN Rated Voltage (34.5±2×2.5%)/0.63 kV Number of Phases 3 Phases Rated Current 52.7/2887A Rated Frequency 60Hz Vector Group Dy1 3 Applicable Standards ANSI/IEEE C57.12.00 ANSI/IEEE C57.12.90 ANSI/IEEE C57.12.80 ANSI/IEEE C57.100 ANSI/IEEE C57.136 ASTM D 6871 AWS NEMA NFPA SSPC General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformer Test Code for Liquid-Immersed Distribution, Power and Regulating Transformers Standard Terminology for Power and Distribution Transformers IEEE Standard Test Procedure for Thermal Evaluation of Liquid-Immersed Distribution and Power Transformers IEEE Guide For Sound Level Abatement & Determination For Liquid-Immersed Power Transformer & Shunt Reactors Rated Over 500 KVA Standard Specification for Natural (Vegetable Oil) Ester Fluids Used in Electrical Apparatus American Welding Society National Electrical Manufacturers Association TO National Fire Protection Association National Electrical Code The Society for Protective Coatings Paint Application Specification NO.2 4 Test Items and Test Results TEST ITEMS Acceptance Criteria Test Result 34.5kV/0.63kV, Dy1, Error Tolerance shall be ≤±0.5% Measurement of 4.1 voltage ratio and check of phase displacement Tap Position HV (V) LV (V) A 36225 57.50 B 35363 56.13 C 34500 D 33638 53.39 E 32775 52.02 630 Nominal A B 54.76 HV Winding (Ω) Measurement of 4.2 Tap Position winding A resistance B C H1-H2 H2-H3 H3-H1 C Confidential D E LV Winding (Ω) Tap Position X1-X2 X2-X3 X3-X1 / 4.3 Measure of Measured insulation Between windings 4.5 Voltage (V) R15 2500 Measured Between Test Voltage (kV) Test Frequency (HZ) Duration (s) HV 50 60 60 LV 10 60 60 test Induced voltage withstand test Tap Test Supplied short-circuit Supplied C HV LV 4.10 7200 Test Current (%) No-load Loss (W) Required Measured Required ≤0.5 Test Voltage Test Current (V) (V) Measured ≤4450+8% Impedance (%) Required Measured 5.75±7.5% Load loss (W) Required Measured ≤27500 Tank pressure Applied Pressure (MPa) Duration of Test (h) (leakage) test 0.04 6 Lightning impulse HV Test Voltage 150kV test LV Test Voltage 30KV Paint film thickness test insulation oil (Optional) Measure of 4.12 Duration(cycles) Test Voltage (V) impedance and Testing of 4.11 Induced 1260 load loss 4.9 Induced Position Winding Terminal Voltage(V) Voltage (kV) Multiple no-load current Measurement of 4.8 R60/R15 LV~HV & Earth and no-load loss 4.7 R60 HV~LV & Earth Applied voltage Measurement of 4.6 Absorptance resistance to earth of the 4.4 Insulation Resistance (MΩ) Breakdown voltage (kV) ≥45 Measured Between capacitance and dissipation loss HV~LV & Earth factor (Optional) LV~HV & Earth Water content (ppm) ≤200 Dielectric Loss Factor tgδ (%) Dielectric dissipation Dissolved gas factor @100℃(%) analysis ≤4 Capacitance Cx (pF) Voltage (kV) Confidential HV/LV~Earth Average Measurement of 4.13 sound levels (Type Test) 4.14 4.15 Lightning Impulse Test (Type Test) Temperature Rise Test (Type Test) Noise Level of Trans. Average Noise Level Backgroun Difference d Noise Level Background Noise Level A Surface A Sounding Between Trans. Modification And Background Noise Power Level (X) Tap Positon Full Wave Chopped Wave HV Test Voltage 150kV 165kV LV Test Voltage 30KV 33kV Top Oil Temp. Rise Required Value (K) Actual Measured Value (K) Average Oil Temp. Rise ≤65 HV Winding Temp. Rise ≤65 LV Winding Temp. Rise ≤65