Automatic Three Phase Load Balancing System by Using Fast Switching Relay in Three Phase Distribution System Sajid Ul Haq Department of Electrical Engineering COMSATS Institute of Information Technology Islamabad Pakistan engrsajid857@gmail.com Bilal Arif Department of Electrical Engineering COMSATS Institute of Information Technology Islamabad Pakistan bilalarifmail@gmail.com Asif Khan Department of Electrical Engineering ABASYN University Islamabad Campus Islamabad Pakistan khanasif109@gmail.com Junaid Ahmed Department of Electrical Engineering COMSATS Institute of Information Technology Islamabad Pakistan junaid@comsats.edu.pk Abstract—In three phase distribution system the unbalance phenomenon occurs due to single-phase loads and unequal sharing of loads in each phase. To overcome this problem, distribution systems require equal sharing of load in each phase. This is possible by automatic three phase load balancing technique. The automatic three phase load balancing system is possible by the proposed hardware which is micro-controller and relay based hardware. This hardware is installed in the incoming of three phase lines and will accordingly switch the domestic load to the least loaded phase using fast switching relays. The single full house load is connected to the phase that is least loaded by relay switching ON/OFF. The result of the proposed hardware and simulation shows that microcontroller and relays switching is effective in reducing the unbalancing in three phase lines and also reducing the current in the neutral wire of the system. In addition, it retains voltage regulation and stability in the all three phase. The phases are normally called red, yellow and blue. Three phases distribution systems suffer from power fluctuations and non-zeros neutral currents due to unbalanced loads. The unbalanced loading in distribution systems mostly occur due to the following reasons. • • • • • When there is a phase imbalance, due to the basic laws of circuits, current increases in the neutral wire of three phase system. The flow of neutral wire current is a hazard, it creates safety problems and can cause fire. In addition it also decreases the electrical power system efficiency, tripping (relays) protection devices of the system, and damaging network equipment. The grids are designed as three phase electrical power systems. Various problems arise in the electrical power distribution grids because consumer loads are not perfectly predictable and do not balance out when different loads are distributed over the three phases. Faults in the distribution system can cause over-loading in some areas and under-loading in others. So to prevent these unbalance conditions, power and loads are required to be controlled in real time. This real time controlling technique is called load balancing technique. In other words, load balancing is the process to avoid the power systems from overloading and underloaded situation. In [1] an intelligent consumers load transfer scheme is proposed that dynamically reduces voltage unbalance (VU). In this scheme to minimize VU in the distribution feeders, consumers loads are transferred from one phase to another without disconnection of phases. In [2] Scott transformers are used in a low voltage radial feeder to balance the distribution Keywords:Voltage unbalance, electric spring, electric vehicle, STATCOM. I. I NTRODUCTION Many domestic loads and small industries are supplied by a single phase AC with a phase and neutral wire. However, power is generated and transmitted in 3-phase AC. A single phase generator has single coil rotating in magnetic field, while 3-phase generators have fixed coils that are separated by 120◦ from each other. These three voltages are out of phase from each other by 120◦ . A set of balance 3-phase voltages form,in terms of the time domain as, √ VRed = 2Vm cos(wt + φ) (1) √ VY ellow = 2Vm cos(wt + φ − 120◦ ) (2) √ ◦ VBlue = 2Vm cos(wt + φ − 240 ) (3) In three phase balance system the neutral current will be zero. I N = IR + I Y + I B , I N = 0 Overloading of single phase. Manual switching of the phases. Unequal sharing of single phase loads on 3-phase system. Unbalanced three phase loads. Asymmetrical transmission impedance. (4) 978-1-5386-5482-8/18/$31.00 ©2018 IEEE 1 Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 07,2022 at 09:14:42 UTC from IEEE Xplore. Restrictions apply. system. In this scheme, unbalanced 3 phase power supply is converted to unbalanced 2 phase supply and then converted back to a balanced 3 phase power supply using Scott transformers. In the scheme proposed by [3] the unbalancing of a three phase system can be controlled by electric vehicle (EV) chargers and photovoltaic (PV) inverters. A new 3phase electric spring (ES) circuit can also be used to decreases power unbalance in a 3-phase system as proposed by [4]. In [5] a high realization control method is proposed using cascade Static compensator (STATCOM) with (star)Y configuration under unbalanced three phase conditions. In conventional distributions, single-phase electrical loads are equally distributed among three phases. However, daily loadflow variation is ignored, causing unbalancing in the three phase distribution system. In [6] a new method is proposed for equal sharing of load and balancing the three phases in a 0.4 KV distributions grid. They also simulated daily load flow using MATLAB/Simulink models. In [7] a new phasing identification system is proposed that measures voltage phase of underground distribution transformers at the secondary side to determine the phase load and indicate unbalancing. However, no proposal is given to reduce the unbalancing. In [8] a new technique is developed for identifying automatically the phase each domestic loads is connected to, this information can be used by the distribution systems for phase rebalancing. In this technique voltage information from the energy meters and phase information from the transformers is collected over time and then correlated to determine each customer’s phase. In [9] a stochastic method is proposed to calculate the increasing of a single-phase photovoltaic inverter (PVI) to voltage unbalancing in LV distribution networks. The ambiguity in location and phase is included in a serial number of stochastic indicators. This technique is used in induction motors, electric vehicle charging (EVC) and single-phase loads. In this paper we present an automatic 3-phase load balancing device that balances 3-phase load using microcontrollers and relays. This paper explains the details of automatic three load balancing system and steps for how to design and implement an automatic load balancing in power distribution network. PT otal (6) (7) i 3Vp2 2R By changing phase voltage to RMS votage, √ Vrms = 2Vp PT otal = (8) (9) 2 3V (10) R 2) Power for Non-Resistive loads: When the load is non resistive, it may be written as, PT otal = Z = Zejϕ (11) The peak value of the current, Ip = Vp |Z| (12) The instantaneous current of all phases are given as, IR = Ip sin(θ − ϕ) 2 IY = Ip sin(θ − π − ϕ) 3 4 IB = Ip sin(θ − π − ϕ) 3 Calculating power from the above current equations, PR = VR IR = Vp Ip sin(θ)sin(θ − ϕ) (13) (14) (15) (16) 2 2 PY = VY IY = Vp Ip sin(θ − π)sin(θ − π − ϕ) (17) 3 3 4 4 PB = VB IB = Vp Ip sin(θ − π)sin(θ − π − ϕ) (18) 3 3 Using trigonometric functions we simplified the above power equtions, can be simplified as, Vp Ip PR = [cos(θ) − cos(2θ − ϕ)] (19) 2 4 V p Ip [cos(θ) − cos(2θ − π − ϕ)] (20) PY = 2 3 8 V p Ip [cos(θ) − cos(2θ − π − ϕ)] (21) PB = 2 3 Adding equations (19-21) we obtain, 3Vp Ip PT otal = cos(ϕ) (22) 2 II. BALANCE AND UNBALANCE LOAD DEFINITION In 3-phase distribution sytem, electical loads are distributed between the phases. The parameter power, voltage and current are balanced among all 3-phases. The flow of the current in the neutral wire is zero in balance condition. PT otal = 3Vp Ip 2 [cos(3ϕ) − [cos(2θ) +cos(2θ − 43 π − ϕ) + cos(2θ − 83 π − ϕ)]] A. BALANCE LOADS 3Vp2 cos(ϕ) 2 By changing phase voltage to RMS votage, √ Vrms = 2Vp In a three-phase balanced power system, the voltage phasor components have same magnitudes but are 120 degrees differ from each other. 1) Power for Resistive loads: In case of resistive loads the instantaneous powers is constant all time, P =VI V L i2 R PLi = PLi = PT otal = PT otal = (5) 3V 2 cos(ϕ) Z (23) (24) (25) 2 Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 07,2022 at 09:14:42 UTC from IEEE Xplore. Restrictions apply. 3) No neutral current in Balance 3-phase system: No neutral current be obtained by equal sharing of loads on each of the 3-phases. Therefore the net current is zero in the neutral wire of the three phase balnce system, IR = VR − N R (26) IY = VY − N R (27) IB = VB − N R (28) −IN = IR + IY + IB Fig. 1. Transposition of 3-phase System 3) Neutral phase shift: Neutral phase shift is created when unbalanced phenomena occurs in current of the power system. In this case, the distribution phases are not balanced to each other; at load side the line to neutral voltages have different magnitudes and phases. The magnitudes of current in this situation in all three phases are different, which results in different voltage drops which further cause the neutral phase shift. Arcing and dielectric breakdown of insulation is produced by neutral phase shifts. (29) As we know non-dimensionalized current, can be written as i= IN R Vp 2 2 inon−dimension = sin(θ) + sin(θ − π) + sin(θ + π) 3 3 (30) 2 (31) inon−dimension = sin(θ) + 2sin(θ)cos( π) 3 inon−dimension = sin(θ) − sin(θ) III. DECOMPOSITION OF ASYMMETRICAL COMPONENTS IN LV DISTRIBUTION NETWORK In an unbalanced 3-phase system, the magnitudes and phases of the voltage phasor components are different from each other in LV network. Decompsing the voltage phasor component into a complete set of symmetrical component helps evaluate the system as well as any imbalance. A vector of three phase voltage is, ⎡ ⎤ Vr Vryb = ⎣ Vy ⎦ Vb ⎡ ⎤ ⎡ ⎤ ⎡ ⎤ ⎡ ⎤ Vr Vr,0 Vr,1 Vr,2 ⎣ Vy ⎦ = ⎣ Vy,0 ⎦ + ⎣ Vy,1 ⎦ + ⎣ Vy,2 ⎦ Vb Vb,0 Vb,1 Vb,3 (32) inon−dimension = 0 B. UNBALANCED LOADS When the amplitude of three phase voltages and current is different and the angle between the phases is shifted by 120◦ it is called unbalanced or asymmetrical. The power system is called unbalanced or asymmetrical. In balanced condition no neutral current flows. Unbalance system occurs due to nonlinear loads. 1) Neutral Current: By adding the three phase currents together as complex numbers and then converting form rectangular to polar co-ordinates form which determined neutral current of the 3-phase unbalanced system . If the three-phase root mean square (RMS) currents are, The subscripts 0, 1 and 2 shows respectively 0, +ive and -ive sequence components. The zero sequence components have same magnitude and are phase with each other, I R , IY , IB V0 = Vr,0 = Vy,0 = Vb,0 the neutral RMS current is: IN = IR + IY cos( 23 π) + jIY sin( 23 π) +IB cos( 43 π) + jIB sin( 32 π) But phase sequences of the positive and negative sequences have the same magnitudes, but their phases difference by 120◦ (33) V1 = Vr,1 = αVy,1 = α2 Vb,1 V2 = Vr,2 = α2 Vy,2 = αVb,2 which simplify to √ 1 1 3 − IB + j (IY − IB ) (34) 2 2 2 2) Asymmetrical transmission impedances: The impedance of the transmission line varies therefore faults occur in the balance three phase power system. Due to this fault the system goes to unbalanced condition. Without transposition of the transmission line, asymmetrical phenomena increases which creates asymmetrical impedance in power systems.Transposition show in given ”Fig. 1”. alpha is a phasor rotation, which rotates a phasor vector by 120◦ with counterclockwise, IN IR − IY 2 α = e 3 πi (35) after decomposition the vector in three symmetrical components gives the following form, ⎡ ⎤ ⎡ ⎤ ⎡ ⎤ V0 V1 V2 Vryb = ⎣ V0 ⎦ + ⎣ α2 V1 ⎦ + ⎣ αV2 ⎦ V0 αV1 α 2 V2 3 Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 07,2022 at 09:14:42 UTC from IEEE Xplore. Restrictions apply. ⎡ Vryb 1 =⎣ 1 1 1 α2 α ⎤⎡ ⎤ 1 V0 α ⎦ ⎣ V1 ⎦ V2 α2 = AV012 where, ⎡ Vryb ⎤ ⎡ V0 1 = ⎣ V1 ⎦ , A = ⎣ 1 V2 1 ⎡ 1 1 1 A−1 = ⎣ 1 α2 3 1 α 1 α2 α ⎤ 1 α ⎦ α2 ⎤ 1 α ⎦ α2 by these equations we convert an asymmetrical set of three phasors to symmetrical components set of three phasors. By this conversion VU phenomene is rare in symmetrical components. Three phase connected load are efficiently working during symetrical conditon and flow of neutral current in the neutral wire is vanish and the stability of the power system is attained. Fig. 3. Proteus simulation Design IV. P ROPOSED H ARDWARE The design of the proposed hardware will made using Proteus software. First of all we implemented this automatic three phase load balancing system in Proteus simulation and took the results from it and then designed hardware of the proposed system which is shown in ”Fig. 3”. The hardware is divided into three main circuits and each circuit consists of electrical components which are given in ”Fig. 2”, • Current sensing circuit • Relay operating circuit • Controller circuit In ”Fig. 3” shows the whole simulation of automatic three phase load balancing system and also shows each component and his electrical symbol and names. The simulation is possible with proteus software This simulation is start from three phases input and terminated with single phase output. Our desired to swiping the three phase loads and our single phase full house load is connected to that phase which is least loaded among it. The display show any instant of the parameter variation like voltage, current and connected output status of phases. This hardware is prototype and experimental design for three phase distribution system show in ”Fig. 4”. In currently this hardware design is very helpful to overcome three phase unbalancing, near distribution transformer. In nowadays mostly urban area is feeding a long radial distribution network, LV side is connected with single full house loads which creates the problem. By this hardware our single phase load is swiping to the least loaded phases among three phase in LV network, maintain the power system stability and also improve the efficiency of the distribution transformer. Fig. 4. Hardware Design Fig. 2. Proposed Design 4 Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 07,2022 at 09:14:42 UTC from IEEE Xplore. Restrictions apply. V. C ALCULATION OF R ELAY OPERATION Where PS is plug sitting, so PS is 200%,when the fault current is 1000A in the CT primary. Hence, fault current is calculated on the secondary side of CT is, 1000 * 5/200 = 25A, The relay used in hardware design is Inverse Definite Minimum Time (IDMT) overcurrent relay. In an over current relay, the ideal inverse time characteristics can not be achived. The secondray current of current transformer (CT) is directly proportionally to the system current. The actuating quantity in IDMTis only current, there is current operated element in the relay, no voltage coil are required to construct this protective relay. In IDMT,near pick-up value the operating time is inversely proportional to the fault current of the relay. Above the pickup value of relay becomes considerably slightly constant, as shown in the ”Fig. 5”. This is obtained when current slightly greater than the pick-up current and using a core of the electromagnet which gets saturated. The mathematical relation between the the operating time and current of IDMT characteristic can be written as toperating = 0.14 ∗ (T M S) (P M S) 0.02 −1 25 = 12.5. (44) 2 An electromechanical relay when we set the time of travelling distance is called time setting. This adjustment is commonly known as time setting multiplier (TMS) of relay. The TMS calibrated range is from 0 to 1 in steps 0.05 sec .The fastest operation is obtaind when TMS is selected as 0.1. Putting the values in equation no (2). P SM = toperating = (36) VI. R ESULTS The single phase output load is keept constant and the loads of three phase input line varied. The single full house load is connected to that phase which is least loaded by relays. The varying loads range from 0 W to 1000 W in each phase. We continuously checked the display phase swiping between output load and incoming three phases according to load situation at different loads and noticed different phase swiping at different loads. Tables given below show the phase swiping, and load currents of each phase. Table I and table II show results. We took experimental data from display show in ”Fig. 6”, our single phase full house load is connected by default Red phase show in display denoted by phase1 and A1, A2, A3 show load of each phase. In ”Fig. 7” the load connected in each phase is given, this load variation is sensing by Arduino nano and give signal to the fast switching relay to connect our desired single full house load to least loaded phase among three phase LV network. There is no flow of neutral current to variation of load from 0W to 1000W on each phase, in ”Fig. 8” load variation is (37) The value of IDMT is 10A; the CT ratio is 200:5 the PSM and TMS is given below, P ick up current = 10A, PS = pick up current ∗ 100%, Rated secondray current of CT Current sitting = P SM = pick up current , Rated secondray current (45) The operating time of the relay is most important because when the domestic load switched to the least loaded phase, it required sufficient delay time for its operation. The 0.27s is more suitable relay operating time and the power system will be stable during this time. where PSM is plug-sitting multiplier, TMS is time multiplier sitting The maximum load current of IDMT is 10A, assuming 25 % overload, maximum overload can be calculated as 10A + (0.25 + 10A) = 12.5A (0.14) ∗ (0.1) = 0.27sec (12.5)0.02 − 1 (38) (39) (40) F ault current in relay coil , Rtaed CT secondray current ∗ current sitting (41) 10 ∗ 100% = 200%, (42) PS = 5 10A = 2, (43) Current sitting = 5A Fig. 5. Various characteristics of over current relays Fig. 6. Result on Display 5 Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 07,2022 at 09:14:42 UTC from IEEE Xplore. Restrictions apply. TABLE I C ONNECTED LOADS ON EACH PHASE . No Red(W) Yellow(W) 1 0W 0W Blue(W) 0W 2 400W 315W 320W 3 100W 215W 60W 4 300W 215W 260W 5 100W 315W 120W Fig. 8. Three Phase Current (A) loaded phase using fast switching relays. The single full house load is connected to that phase which is least loaded by relay switching ON/OFF. The hardware and simulation result shows that the microcontroller and relays switching is effective in reducing the unbalancing in three phase line. In addition, it retains voltage regulation and stability in the all three phase. Fig. 7. Connected loads on each pahse R EFERENCES [1] F. Shahnia, P. Wolfs, and A. Ghosh, Voltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases, vol. 5, no. 3, pp. 13181327, 2013 [2] Y. Li and P. a Crossley, Voltage balancing in lowvoltage radial feeders using Scott transformers, IET Gener. Transm. Distrib., vol. 8, no. February, pp. 14891498, 2014 [3] S. Weckx and J. Driesen, Load Balancing with EV Chargers and PV Inverters in Unbalanced Distribution Grids, IEEE Trans. Sustain. Energy, vol. 6, no. 2, pp. 635643, 2015 [4] Q. Wang, M. Cheng, and Y. Jiang, Harmonics Suppression for Critical Loads Using Electric Springs with Current-Source Inverters, IEEE J. Emerg. Sel. Top. Power Electron., vol. 1, no. c, pp. 18, 2016. [5] L. Tan, S. Wang, P. Wang, Y. Li, Q. Ge, H. Ren, and P. Song, High Performance Controller with Effective Voltage Balance Regulation for a Cascade STATCOM with Star Configuration Under Unbalanced Conditions, IEEE Trans. Ind. Appl., vol. 5, no. June, pp. 110, 2015. [6] K. Mansouri, M. Ben Hamed, L. Sbita, and M. Dhaoui, Three-phase balancing in a LV distribution smart-grids using electrical load flow variation: L.F.B.M., 16th Int. Conf. Sci. Tech. Autom. Control Comput. Eng. STA 2015, no. 1, pp. 427431, 2016 [7] C. S. Chen, T. T. Ku, and C. H. Lin, Design of phase identification system to support three-phase loading balance of distribution feeders, IEEE Trans. Ind. Appl., vol. 48, no. 1, pp. 191198, 2012. [8] H. Pezeshki and P. Wolfs, Correlation based method for phase identification in a three phase LV distribution network, IEEE ISGT Eur. 2012, no. July 2011, pp. 17, 2012. [9] M. Osama, B. Shakeel, S. A. Jaffar, M. F. Ali, and S. Sajjad, 74 . LV Three Phase Automatic Load Balancing System, vol. 2016, no. Eesd, 2016. TABLE II E ACH PHASE CURRENT AND CONNECTED STATUS OF SINGLE PHASE LOAD . No Red(A) Yellow(A) Blue(A) Connected Output Status 1 0A 0A 0A Red 2 1.86A 1.41A 1.47A Yellow 3 0.45A 0.97A 0.27A Blue 4 1.42A 0.96A 1.19A Yellow 5 0.46A 1.52A 0.54A Red give with taken by different readings. With the above range of variation there will be no neutral flow of current, the system will be stable.This hardware is design upto 5A load variation, we also change equipments and its rating for higher load variation, according to our requirements. VII. C ONCLUSION Domestic load is single phase while connected to three phase distribution network. The three phase distribution system suffers from unbalancing due to overloading of one phase as comparing to the remaining two phases. To overcome this problem, distribution system requires equal sharing of load on each phase. When equal sharing is obtained, due to which in 3-pahse unbalancing, energy losses, overload situation and return current flow in neutral is reduced. The automatic three phase load balancing system is possible by the proposed hardware which is micro-controller and relay based hardware. The hardware is installed in the incoming of three phase lines and will accordingly switch the domestic load to the least 6 Authorized licensed use limited to: NWFP UNIV OF ENGINEERING AND TECHNOLOGY. Downloaded on April 07,2022 at 09:14:42 UTC from IEEE Xplore. Restrictions apply.