AGLPlus 1 : Introduction to Airfield Ground Lighting AP1 – Module 13bis: CCR For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 1 13-04-22 Airport Ground Lighting AGL+1 Module 13bis Constant Current Regulators & Associated Equipments For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 2 13-04-22 The ADB MCR³ is a microprocessor controlled Constant Current Regulator specially designed for the supply of airport lighting series loops at various intensity levels. Secondary circuits Isolating Transformers I VTOTAL V2 V1 Primary circuit VTOT V1 V2 ...Vn For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 3 13-04-22 STANDARD COMPLIANCY & REF. DOCUMENTS Therefore the MCR³ has to be/is fully compliant with following standards: • • • • • ICAO: Areodrome Design Manual, Part 5, par. 3.2.1.4,5 & 6 FAA: AC 150/5345-10E & L829 IEC: IEC 61820 ADB ref. Documents: Installation Manual & Maintenance Manual ADB: Installation & Maintenance Manual For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 4 13-04-22 FACTS - FEATURES MAIN FEATURES • • • • • • • • Several PCB’s mounted separately in stead of 1 control module Control / parametering possible through LCD backlit display and pushbuttons (UI) Remote control is adaptable to customer needs J-bus & MW in same CCR for combined remote control CCR & CSM in same housing Distributed DC-supply Local Bus communication 2 types of Housing depending on the size For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 5 13-04-22 FACTS - FEATURES MAIN FEATURES • • • • • • • • Working principle: series thyristors controlled by μprocessor to obtain constant current Transformer principle to create high voltage and maintain constant current Remote control principle (J-bus, MW) Integrated HMI (Human Machine Interface) BASIC configuration through HMI Windows © compatible PC software Improved dynamic current regulation start-up = 0.5 sec max For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 6 13-04-22 SPECIFICATIONS SMALL HOUSING • • • • • • Power range 2,5/ 5 /7,5/ 10/ 12,5 kVA Input voltage ( single/bi-phase) 220/230/240/380/400 VAC (+/- 15%) 50/60Hz Output Current 6,6A Dimensions 400 x 600 x 930 Options: o selector (+ 500) o cut-out o wheels (+ 100) For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 7 13-04-22 SPECIFICATIONS BIG HOUSING • • • • • • Power range 15/ 20 / 25/ 30 kVA Input voltage ( single/bi-phase) 220/230/240/380/400 VAC (+/-15%) 50/60Hz Output Current 6,6A Dimensions 600 x 600 x 1260 (mm) Options: o selector (+ 500) o cut-out o wheels (+ 100) For internal use only Copyright © ADB 2009. All rights reserved. RAS-AGLP4-NDIA-ST1-Mod6 / Technical Support /ADB Belgium - 8 25 June 2012 SPECIFICATIONS Small cabinet + CSM+ wheels Big Cabinet + SCO + wheels For internal use only Copyright © ADB 2009. All rights reserved. RAS-AGLP4-NDIA-ST1-Mod6 / Technical Support /ADB Belgium - 9 25 June 2012 SPECIFICATIONS Ambient conditions All regulators are air-cooled without fans. Thus, all regulators must have a good airflow, especially if they operate near the maximum temperature. • • • Temperature : From -20 up to +55 °C Altitude : From 0 (sea level) up to 1000 meter Relative humidity : From 10 % up to 95 % RH without condensation For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 10 13-04-22 OPERATING PRINCIPLES The regulator is a microprocessor-controlled constant current regulator. The regulator supplies power to airport visual aid series circuits at different intensity levels. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 11 13-04-22 OPERATING PRINCIPLES For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 12 13-04-22 OPERATING PRINCIPLES The current regulator holds the output current constant by varying the output voltage to the series circuit. The voltage can be adapted by changing the conduction angle of the thyristors in both the positive and the negative difference of the input signal. - The TBM module fires the thyristors at the request of the CCL module. - The TBM module receives a signal from the remote control system. - The TMB module gives an output to a certain current level. - The CCL compares the requested step & actual output current level. - The CCL computes and sends the TBM a request to generate the required output voltage. This process will be maintained until no output is anymore demanded or if any of the safety features are triggered. The regulator stops immediately when triggered by a safety feature. The safety can only be reset at the TBM module. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 13 13-04-22 OPERATING PRINCIPLES – THE THYRISTOR + gate A thyristor with forward polarity will conduct a current, the moment a small voltage is applied to the gate. Thyristor Vgate I Short Pulse T Thyristor blocked With reverse polarity it will act as a diode and will not conduct, even with a voltage applied to the gate. The thyristor only requires a small voltage pulse at the gate and then it is thrust into saturation. It will continue to pass a current while the biasing is in the forward direction, even though the applied pulse has stopped. T For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 14 13-04-22 OPERATING PRINCIPLES – THE THYRISTOR V in Fig. a) V OUT Fig. b) V in V in Fig a) The thyristor can be used to chop an AC signal, but only passes current in the forward direction. V OUT Fig b) The thyristor only passes current in the reverse direction. Fig. c) Fig c) If the thyristors are connected in parallel then current will pass in both directions. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 15 13-04-22 OPERATING PRINCIPLES – THE THYRISTOR For Parallel circuit Vin t D D D The RMS voltage level of the wave can be controlled using the thyristors to chop the wave form. D Vgate t Vout The longer the thyristor circuit is conducting each cycle (time D), the higher the output RMS voltage. t For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 16 13-04-22 OPERATING PRINCIPLES BLOC K DIAGRAM OF A REGULATOR CONBTROLLED BY SERIAL THYRISTORS 7/8 V prim 6/8 V sec 4/8 2/8 I sec TI I prim. Tower (remote) Setpoint Local For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 17 13-04-22 OPERATING PRINCIPLES For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 18 13-04-22 CONSTANCY OF CURRENT Secondary power Psec = V sec * I sec Primary power Transformer ratio Pprim = V prim * I prim n = Vsec / V prim Due to the high efficiency off CCR (95 %) and with restive load load P =P sec prim V sec * I sec = V prim * I prim n* V prim * I sec = V prim * I prim I prim = n * I sec And this is independent of the load.... For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 19 13-04-22 BASIC PRINCIPLES OF A CCR CURRENT CONTROL AND OVERLOAD V I6.6 A Z 1 1 V I6.6 A Z 2 2 V 2 1/2 LOAD t 2 V 2 2 Vo V I 6.6 A Zo FULL LOAD t OVERLOAD t Assume max 6.6 A in secondary As load increases from half to full then feedback will trigger thyristors earlier in the cycle and so increase the voltage by factor of 2 in order to keep the current constant in the secondary. If the load increases after fullload then the voltage cannot be increased further and the current will start to fall. A constant current cannot be achieved and the system is in overload. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 20 13-04-22 COMPONENTS OUTSIDE REGULATOR HOUSING For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 21 13-04-22 COMPONENTS THE CCR consists mainly of two major parts: • High Voltage part, which includes: The Output transformer A fused input switch The measurements transformers The lighting arrestors • Low Voltage part, which includes: The power module with o the thyristor pack, o the input supply terminals o Contactors o Transformers, etc The control modules The EFD pcb Accessories for the LFD For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 22 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 23 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 24 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 25 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING LOW VOLTAGE For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 26 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING LOW VOLTAGE For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 27 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING LOW VOLTAGE For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 28 13-04-22 COMPONENTS INSIDE REGULATOR HOUSING HIGH VOLTAGE For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 29 13-04-22 COMPONENTS LMC – PCB 1513 Local Master Controller MASTER of the Local Bus communication Interface to MW, J-BUS for control & to laptop for SW configuration For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 30 13-04-22 COMPONENTS TBM – PCB 1517 Thyristor Block Module Produces the tyristor gate firing signals to obtain demanded conduction angle Over-current protection/ Assymetric output voltage monitoring Monitors input of Power transformer For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 31 13-04-22 COMPONENTS CCL – PCB 1516 Current Control Logic Requested & obtained current are compared & eventually adjusted by other conduction angle request to TBM Compute values from received measurements. Control contactor through PSL on startup & switch off , in case of OVC or OVL. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 32 13-04-22 COMPONENTS UI – PCB 1507 User interface LOCAL control of CCR & change parameters Indication of status (Vout, Vin, In , Iout, local/remote, EFD ,LFD) For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 33 13-04-22 COMPONENTS MW – PCB 1486 Multiwire interface board (2 for CCR control, 1 for CSM) 24 or 48 VDC external or internal supplied 8 Inputs / 8 outputs Value of I/O’s are set by default or configurable from SW For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 34 13-04-22 COMPONENTS JBUS – PCB 1502 J-bus interface module Dual or single, 2-wire or 4- wire connection J-bus type defined by factory SW configuration For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 35 13-04-22 COMPONENTS LFD – PCB 1519 (optional) Lamp fault detection Monitoring of Vout, Iout, Pout Optional -2 alarm levels possible/ LFD for CSM possible For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 36 13-04-22 COMPONENTS EFD – PCB 1514 & 1515 (optional) Earth fault detection Measurement of isolation resistance 2 alarm levels can be set Range from 10 kOhm – 250 MOhm For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 37 13-04-22 BRIGHTNESS STEPS 6.6 A OUTPUT CCR (in accordance with FAA specifications) Imax (A) Imin (A) Brightness step S1 S2 S3 S4 S5 S6 S7 S8 6.6 1.8 Nr of steps 3 4.8 5.5 6.6 “ “ “ “ “ 4 3.3 4.4 5.5 6.6 “ “ “ “ 5 2.8 3.4 4.1 5.2 6.6 “ “ “ 6 2.7 3.4 3.9 4.5 5.4 6.6 “ “ 7 2.2 2.8 3.4 4.1 5.2 6.4 6.6 “ 8 2.8 3.1 3.4 3.9 4.6 5.5 6.4 6.6 For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 38 13-04-22 MCR OUTPUT CIRCUIT VALUES Rated Output Max. powers current RMS (A) output voltage 2.5 kVA 4 kVA 5 kVA 7,5 kVA 10 kVA 12.5 kVA 15 kVA 20kVA 25kVA 30kVA 25kVA 30kVA 6,6 6,6 6,6 6,6 6,6 6,6 6,6 6,6 6,6 6,6 20 20 378 606 757 1136 1515 1894 2272 3030 3788 4545 1250 1500 Dielectric test on output circuit - V (1) Max. open Max. open circuit circuit peak voltage (3) RMS output volt.(2) 1895 3030 3790 5680 7575 9470 11360 15150 18940 22730 6250 7500 530 850 1060 1590 2120 2650 3180 4240 5300 6360 1750 2100 750 1200 1500 2250 3000 3740 4490 5990 7490 8990 2470 2970 1. 50 Hz- RMS voltage during 1 min 2. Under worst condition, considered 1.4 times max RMS output volt. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 39 13-04-22 OPERATING CHARACTERISTICS Current Regulation limitations Current regulation is guaranteed under the following conditions (±1.5 %): A minimum of 30 % of lamp transformers with an open circuit in their secondary side. This is for a range from half-load to full-load. For nominal input voltage: - IEC: ± 10 % - FAA: + 10 % / -5 % Operation from -5 % to -15 % (FAA) or from -10 % to -15 % (IEC) of nominal input voltage with full load can cause output current to be too low at the maximum brightness step. Operation at +15 % of the nominal input voltage is restricted to a maximum period of 1 hour. This helps to prevent that components become overheated or overstressed. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 40 13-04-22 OPERATING CHARACTERISTICS Features : Incorporates an open-circuit device which quickly locks out the primary voltage and requires resetting of the regulator Allows intensity settings to be changed without de-energising the regulator Incorporates a security device that sets the regulator out of service or assures a reduction of the current in case of an over current Indicate a ground fault while permitting the circuit to operate normally when a single fault prevails For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 41 13-04-22 POWER FACTOR AND EFFICIENCY • Efficiency : At nominal input power, nominal resistive load and maximum brightness: Power up to 10 KVA: 90% and Power above 10 KVA: 95% • Power Factor : At nominal input voltage and resistive load and max. brightness: 90 to 92%. • Taps: By means of output taps on the secondary (high voltage) side of the power transformer (PT) the power factor can be optimised versus the actual load at full brightness. The following taps are provided. 8/8 6/8 4/8 2/8 Benefits: The power factor will be optimised The main input current will decrease The harmonic content in the main input current and in the output current will decrease. The maximum output voltage in case of open-circuit will be lower. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 42 13-04-22 FINDING CIRCUIT LOADS AND SELECTING REGULATORS 1. Take for example a circuit using 45 Watt fittings. Then look at each individual isolating transformer and fitting. So from drawing below : value of lamp 1 = 45 W 2. Length ( l ) from transformer to fitting = 30 m If the section of wire used = 4mm² Resistance R in secondary circuit is 1 R sec 2 18 10-3 mm m 2 where resistivity Therefore Secondary circuit R sec 0.27 Losses in sec. cable = I²R= 6.6² x 0.27 = 11.76W l s 2 L 3 Isolating Transformer 4 3. Total Power at secondary = sum of 1 & 2 = 56.76W Primary circuit For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 43 13-04-22 FINDING CIRCUIT LOADS AND SELECTING REGULATORS 4. Power at primary side = power at secondary x 1.25 = 56.76 x 1.25 = 73.79 W ( 1.25 represents the isolating transformer characteristics ie. efficiency coefficient ) 5. If we take a series circuit containing 100 isolating transformers then: Total power of transformers = 73.79 x 100 = 7379 W 6. If the total length of the primary circuit is 8000 m, and the section of cable is 6mm² then the losses in this primary circuit will be : I²R = 6.6² x 24 = 1045 W where R prim l s 24 7. Total load on Regulator = sum of 5 + 6 = 8424 W For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 44 13-04-22 FINDING CIRCUIT LOADS AND SELECTING REGULATORS Therefore REMEMBER : A benchmark when choosing a regulator is to select a KVA rating which is somewhat greater than calculated so that 80% of this power rating is >= calculated load Look at the table of power ratings. If a 12.5 KVA regulator is chosen, then 80% of this value = 10000 VA and this is > the calculated load 8424 W, therefore O.K For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 45 13-04-22 MONITORING FUNCTIONS OF THE MCR Over current time Often a problem in the thyristor block MCR creates an alarm and switches off when output current is higher than one of two preset levels. 1st Level 4s Switches off, if current exceeds value >4% 0.4 s and <8% for duration 4 secs or current exceeds 8% for >0.4secs 2nd Level 4% >8% Over current Open Circuit Pulse stopped to thyristor and current falls within 20ms Main contactor open Locked position - must do a reset of the system For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 46 13-04-22 MONITORING FUNCTIONS OF THE MCR Mains Supply Voltage Monitoring V t t If mains supply voltage decreases then must increase thyristor triggering time t to keep output voltage and current constant. The time t can only be increased as far as t max. If the supply fall below a user adjustable level i.e 80% - then regulator will stop. V t Regulator will start again automatically if supply voltage increases again to 85-90% tmax For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 47 13-04-22 MONITORING FUNCTIONS OF THE MCR Capacitive Output Current Monitoring Capacitance Open circuit V Voltage rises as current falls Primary circuit A break in the series loop will normally cause the MCR to shut down on an open-circuit fault As the current falls below a minimum value. In long screened cables large capacitances can build up. The discharge of this capacitance to earth when there is a break in the cable could cause the output current to be greater than 1.8 Amps and so inhibit the open-circuit shut-down. The MCR monitors this situation, creates an alarm and switches off. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 48 13-04-22 MONITORING FUNCTIONS OF THE MCR Measuring for Asymmetry - Thyristor problem V t- Control module monitors conduction angle of both thyristors. If t+ does not equal t- then will get a DC component in transformer. If difference >10% for duration 100secs then MCR off. t t+ Monitoring of Overload 2 types of warning If installed load > nominal load then the regulator cannot supply a current at maximum rated 6.6A. If keep adding lamps above max for circuit, the current will diminish. MCR does not switch off but warning light blinks. Select: switch off if overload option For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 49 13-04-22 MONITORING FUNCTIONS OF THE MCR Monitoring Output surge Limitation Thyristor will switch OFF if output current reaches a value greater than twice the maximum peak value in normal operation. Thyristors remain in the OFF state for a period in which the firing angle goes smoothly from zero back to the normal value. Film cut-out MCR VTOTAL A Normal Peak Value t If the load suddenly short circuits such as in the case of a lamp cut-out then the output current will instantaneously rise. Usually the MCR monitors the RMS current which in this case would take longer to calculate and change than measuring the peak output. ie. a faster response to a sudden current change. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 50 13-04-22 SET-UP FOR EARTH FAULT DETECTOR ( EFD ) Maximum insulation leakage currrent based on the following: ICAO part 5 §3.9.4.7 Allow 2 μA for each series transformer Allow 1 A for each 100 metres of cable (this value includes for the normal number of connectors and splices ) Take for example a Runway centre-line circuit containing 133 light fixtures Maximum allowable leakage for transformers 2 133 266 A If length of the circuit is 10 KM then max.leakage for cable 10 000 100 100 A Total allowable leakage for circuit 366 A For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 51 13-04-22 SET-UP FOR EARTH FAULT DETECTOR ( EFD ) If testing with 5000 V then the resistance R must be 5000 13.7 MΩ 366 The recommended alarm levels are: level 1= 2 X calculated value = 27.4 megohms level 2 =0.5 X calculated value = 6.8 mega ohms If the calculated value = 150 mega ohms then do not multiply by 2 for the level 1 alarm For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 52 13-04-22 SET-UP FOR EARTH FAULT DETECTOR ( EFD ) Set-up delay : Because of the unknown capacity of the series circuit and the small current delivered by the 500V supply, it can take time to pull the circuit to the 500 V level. During this user determined time the EFD is inhibited. For a long circuit use a time of 60 to 120 seconds. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 53 13-04-22 SET-UP FOR LAMP FAULT DETECTOR ( LFD ) Important ! Calibration of the LFD must be carried out after the tap selection procedure and after any change made to the circuit Warm-up time Any change in the resistance affects the output voltage. Therefore on a long circuit there is a need to wait at least 30 seconds before doing the calibration. This warm-up time can be changed in the software. Affects of Capacitance and Inductance on the working of LFD •Normally a series circuit without any burned out lamps can be approximated to a pure resistance. The affect of too much capacitance and inductance in the circuit can mean that the LFD module is unable to calculate the no. of burned out lamps. •The LFD option is NOT available on the following types of circuits : •PVO’s (guidance signs) •Circuits with AGLAS modules •Circuits with saturated transformers For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 54 13-04-22 SCO CUT-OUT As an option, the regulator MCR can be delivered with a cutout SCO mounted onto the bottom part of the rear panel. The purpose is to isolate safely the series circuit from the CCR during maintenance or testing operations. It also allows periodical isolation resistance measurement series circuit to ground without disconnecting the series cable. Cutout Type SCO Cover Body Grounding terminals Iso. measurement Serie cables and Grounding Locking key Fasting holes Microswicth For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 55 13-04-22 SCO CUT-OUT For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 56 13-04-22 CIRCUIT SELECTOR SELECTOR LOW RANGE For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 57 13-04-22 CIRCUIT SELECTOR SELECTOR HIGH RANGE For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 58 13-04-22 CIRCUIT SELECTOR - APPLICATIONS Simultaneous supply of several taxiway tracks Alternate supply of PAPI systems For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 59 13-04-22 CIRCUIT SELECTOR – SIMULTANEOUS SUPPLY Simultaneous supply of several taxiway tracks FT D FT S 2 FTC 2 2 1 Taxiway track 1: Centreline lights MCR FTS FTS 2 2 1 1 CSM Taxiway track 2: Stop bars For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 60 13-04-22 CIRCUIT SELECTOR – ALTERNATE SUPPLY Alternate supply of PAPI systems 2 2 2 2 1 PAPI Runway end 12 MCR 2 2 2 2 1 CSM PAPI Runway end 30 For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 61 13-04-22 TAP SELECTION Tap Selection Target : Adaptation of the regulator to the installed load by using the right tap combination. The three methods possible are: 1 Measurement of the output voltage directly on the output terminals High Voltage! 2 Measurement of the primary voltage on the output transformer 3 Use of the MCR parameterisation For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 62 13-04-22 TAP SELECTION Example for a 5KVA CCR PARAMETER UNITS TAP 8/8 TAP 4/8 Thyristor conduction angle Deg 85 124 Mains Voltage Vrms 398 401 Mains Current Irms 14.6 7.42 Output Voltage Vrms 326 312 Output Current Irms 6.6 6.6 Mains power W 2605 2379 Mains power VA 5831 2979 Output Power W 2203 2096 Output Power VA 2450 2060 0.45 0.79 84.5 88.1 Power Factor (input) Efficiency % Table shows results taken from a practical trial using a 5 KVA MCR. Tap selection was undertaken using the 3 methods outlined in the previous slide For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 63 13-04-22 TAP SELECTION For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 64 13-04-22 TAP SELECTION Practical example for a 7,5 kVA CCR This example shows how to select and wire a tap for a 7.5 kVA regulator with a supply voltage of 380 A. The measured voltage reading on the terminals of fuse holder F3 is 210 V. 1. Find the correct tap selection table for a 7.5 kVA regulator. In this case, table 4 below. 2. Find in the table the voltage reading that you measured on the terminals of fuse holder F3. In this case, find the measured voltage 210 V under the supply voltage column 380 A. 3. Find the correct tap setting on the line that matches the measured voltage. In this case, the measured voltage was 210 V, so the correct tap setting is 6/8. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 65 13-04-22 TAP SELECTION Practical example for a 7,5 kVA CCR 3. Find the correct tap setting on the line that matches the measured voltage. In this case, the measured voltage was 210 V, so the correct tap setting is 6/8. 4. Find the wire diagram for tap 6/8 5. Wire the taps according to tap 6/8. For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 66 13-04-22 PC CONFIGURATION TOOL Optional configuration/ maintenance tool SW runs on windows XP through serial port of PC Demands power from the regulator For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 67 13-04-22 PC CONFIGURATION TOOL For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 68 13-04-22 DOCUMENTATION Installation Manual Maintenance Manual Drawings User Interface Flowchart Configuration Software MCR³ Database ADB Zaventem Technical Support: customerservice@adb-air.com For internal use only Copyright © ADB 2009. All rights reserved. Training Department/ AGP1- 13b - page 69 13-04-22