ZESCO SPECIFICATION ===== SPECIFICATION 33/11kV POWER TRANSFORMER SPECIFICATION SCOPE This specification covers the design, manufacture, supply, delivery installation, testing and performance requirements of 33/11kV POWER TRANSFORMER Normative References The requirements of the following standards/ specifications shall be met where applicable unless otherwise stated in this specification. Specification / Standard Number Title IEC 76 Power Transformers IEC 137 Insulated bushings for alternating voltages above 1000V IEC 214 On-Load Tap Changers IEC 296 Specification for unused mineral insulating oils for transformers and switchgear IEC 529 Degrees of protection provided by enclosures IEC 551 Determination of Transformer and reactor sound level General Type of Transformer The transformer shall be double wound and be core type. The Transformer shall be suitable for outdoor use and shall have protection classification IP54W (IEC 529). IEC60076 recommendations shall be followed. The transformer shall be fitted with bushings which satisfy the requirements for creepage distance and for impulse levels for altitudes up to 1400 m, such that the transformer can be interchanged one with another at any site. Electrical Connections Unless otherwise approved, the direction of winding of the higher and lower voltage windings shall be such that they are of subtractive polarity. As specified in the Technical Schedules, tappings shall be provided on a three-phase set of transformer windings to provide an alternative ratio of transformation. The transformer shall be capable of delivering the rated power when connected for the alternative ratio and the unit must be capable of withstanding the specified test voltages when connected for the most severe condition. Duty Under Fault Condition Except where modified below, it is to be assumed that the amount of generation simultaneously connected is such that normal voltage will be maintained on one side of any transformer when there is a short circuit between phases or to earth on the other side. The transformer may be directly connected to an underground or overhead transmission circuit and switched into and out of service together with its associated transmission circuit. Cores The cores, framework, clamping arrangement and general structure of the transformer shall be of robust design capable of withstanding any shocks to which the transformer may be subjected during transport, installation and service. The magnetic circuit shall be of cold rolled grain orientated steel and the flux density shall be between 1.65...1.75 Tesla when the voltage applied to any tapping is not in excess of that for which the tapping was designed. All reasonable care shall be taken in the design and construction of the transformers to reduce noise and vibration to a minimum. Each core shall be earthed to the tank and securely fastened to prevent movement relative to the tank. Suitable hooks shall be provided to allow for the lifting of the core from the tank. The framework and core bolts shall be efficiently insulated from the core so as to reduce circulating current to a minimum. The core shall be earthed at one point only by means of a link or bolted connection which must be located in an accessible position requiring the minimum amount of oil to be drained from the tank. Preferably the link shall be brought to cover through a separate bushing and earthed through removable link for inspection purpose. Windings The windings shall be fully insulated for continuous working at the specified service voltage. The insulation of windings and all connections shall be of approved materials which shall not deteriorate under the action of hot oil or from other causes when the transformer is operated continuously at the maximum permissible loads. The windings shall be braced in an approved manner to withstand the effect of short circuit and shocks which may occur during transport. Tanks The tank (including the tank lid) of the transformer shall be of mild steel plate of sufficient thickness and it will have to stand static pressure up to 130 kPa Inspection openings shall be provided in the tank cover to give access to changeover links, bushing core earth links etc. and these inspection covers shall not weigh more than 25 kg each. Each tank is to be designed to prevent the collection of moisture on any part and shall be sufficient rigid to resist any permanent distortion when the transformer is lifted complete with oil and subjected to the rigors of road and sea transport. Tank covers shall be provided with lifting lugs or lifting eyebolts. The steel used shall comply with BS 4360 or corresponding ISO standard and must be of a quality suitable for deep drawing not prone to work hardness and accepting the welding processes used in the tank manufacture. The manufacturing process used shall not introduce any permanent elongation within the steel. The complete tank shall be pressure tested for oil tightness and tank rigidity and strength. Such testing shall be completed and proven satisfactory before the core and windings are installed. The methods of construction testing and quality control of the tanks shall be subject to the approval of the Engineer at all stages of construction. The Bidder shall submit comprehensive details of the methods of construction and testing procedures employed and shall be prepared to demonstrate to the Engineer the complete operation. Details shall be submitted of the standard method of packaging employed to protect the transformer from mechanical damage during transportation to site. The Bidder shall indicate in detail what additional packing will be provided to protect the transformer during shipping by sea and road and handling on sites due consideration being given to the limited resources available en route. Accessories Each transformer shall be fitted with the accessories specified in the Schedules. Earthing Terminal Stainless steel or mild steel earthing flag approximately 63 mm square with a thickness not less than 6 mm and a centre hole of 14 mm diameter shall be welded externally to the tank. Oil The transformer shall be supplied with a sufficient quantity of oil suitable in all respects for continuous service under tropical conditions. The oil shall be of approved grade and comply with IEC 296 Cl I or II. 31.5MVA TRANSFORMER SCHEDULE A: ZESCO MINIMUM TECHNICAL REQUIREMENTS S/N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 TECHNICAL DETAILS TYPE OF TRANSFORMER UNITS Rated power Nominal Primary Voltage Highest system voltage - primary Nominal Secondary Voltage Highest system voltage – secondary Vector Group Phases Type of cooling Type of insulating oil PCB content (attach specification without fail) Frequency Winding Material Impedance Temperature rise Winding limits at rated voltage and power Top oil Lightning impulse withstand level at primary Lightning impulse withstand level at secondary Power Frequency withstand voltage – primary Power Frequency withstand voltage – secondary Bushing Type Specific Bushing creepage distance Parallel transformer operation Equipped with Jacking pads Equipped with lifting lugs Buccholz for main transformer Temperature Gauges (Windings) Temperature Gauge (oil) Pressure Release Valve (oil tank) Skid under base TAP CHANGER DETAILS Tap changer Type MVA kV kV kV kV 31 Tapping range 32 Auxiliary supply to Tap changer controls DATA Free breathing oil immersed outdoor power transformers to IEC 60076 10 33 36 11 12 Dyn1 03 ONAN Mineral oil as per IEC 296 Nil Hz 50 Copper 7 65 % 0 C 0 C kV 60 200 kV 95 kV 70 kV 28 mm/kV Silicon 31 V ac OLTC Type-MRI Germany (with automatic and manual voltage regulation) 105% to 85% in steps of 1.25% ( 17 taps) 400 33 Visual position indicator of tap position 34 Buccholz for tap changer 35 Transformer secondary neutral earthing ENVIRONMENTAL CONDITIONS 36 Altitude above sea level 37 Relative humidity (maximum) 38 Operating ambient temperature 39 Applicable standards Solidly earthed m % 0 C IEC60076 1400 85 -1 to 40 IEC60076 NOTE: “” denotes that the item stated is required to be provided. OTHER REQUIREMENTS 1.0 TRANSFORMER SHOULD COME WITH NEUTRAL CTs FOR STANDBY EARTH & REF PROTECTION. Ratio: 150/1; Burden: 20VA; Class: 5P20 for standby earth fault protection and a 300/150/1 CT; Burden 20VA; Class X; Vk=300V for REF protection. 2.0 MARKINGS RATING AND DIAGRAM PLATES: To conform to IEC 60076 In addition, the following markings must appear on the rating plate Purchase Order No. Clearly indicate : “OIL contains NO PCB's” 3.0 Drawings, Test certificates/results and quality documents Tenderer shall provide drawings showing the dimensions of the transformers offered, the arrangement of connections and rating plate details Successful bidder shall provide routine test certificate on delivery of transformer SCHEDULE B: TO BE FULLY COMPLETED BY THE TENDERER S/ N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 TECHNICAL DETAILS TYPE OF TRANSFORMER Rated power Nominal Primary Voltage Highest system voltage - primary Nominal Secondary Voltage Highest system voltage – secondary Vector Group Phases Type of cooling Type of insulating oil PCB content (attach specification without fail) Frequency Winding Material Impedance Temperature rise limits at rated voltage and power Lightning impulse withstand level at primary Lightning impulse withstand level at secondary Power Frequency withstand voltage – primary Power Frequency withstand voltage – secondary Bushing Type Bushing creepage distance Parallel transformer operation Equipped with Jacking pads Equipped with lifting lugs Buccholz for main transformer Temperature Gauges (Windings) Temperature Gauge (oil) Pressure Release Valve (oil tank) Skid under base TAP CHANGER DETAILS Tap changer Type Tapping range Auxiliary supply to Tap changer Auxiliary supply to Tap changer controls Visual position indicator of tap position Buccholz for tap changer ENVIRONMENTAL CONDITIONS Altitude above sea level Relative humidity (maximum) Operating ambient temperature UNITS MVA kV kV kV kV Hz Winding Top oil % 0 C 0 C kV kV kV kV mm/kV M % 0 C DATA 39 Applicable standards IEC60076