SWA Cable (Steel Wire Armoured) BS5467 Application: Steel Wire Armour cable BS5467 (SWA) is a hard-wearing power cable, with mechanical protection, designed for the supply of mains electricity. SWA is suitable for indoors and outdoors, in cable ducts or directly buried in the ground. Multi-core steel wire armoured cable can also be used for auxiliary control. Technical Data: 1 Conductor Class 2 pain stranded copper conductor to BS EN 60228:2005 2 Insulation XPLE (Cross Linked Polyethylene) 3 Bedding PVC (Polyvinyl Chloride) 4 Armouring Multi-core: SWA (Steel Wire Armour) 5 Sheath PVC (Polyvinyl Chloride) Voltage Rating 600/1000V Conductor Operating Temperature 00C to +900C Core Identification 1 Core: Brown 2 Cores: Brown, Blue 3 Cores: Brown, Black, Grey or Brown, Blue, Green/Yellow 4 Cores: Brown, Black, Grey, Blue 5 Cores: Brown, Black, Grey, Blue, Green/Yellow Alternative Core Identification: White cores with black numbers Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 1 of 7 Sizes and Dimensions - 2 core Part No. No. Cores Conduct or Cross Section Area (mm²) Cable Cross Section Area (mm²) 6942X 1.5 6942X 2.5 6942X 4 6942X 6 6942X 10 6942X 16 6942X 25 6942X 35 6942X 50 6942X 70 6942X 95 6942X 120 6942X 150 6942X 185 6942X 240 6942X 300 6942X 400 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 114.93 145.19 169.63 198.46 254.34 326.69 455.94 426.17 522.53 660.19 860.05 1023.02 1212.42 1568.50 1884.79 2246.87 2732.59 Actual Armour Cross Section Area (mm²) 15 17 19 22 26 42 42 60 68 80 113 125 138 191 215 235 265 Overall Gland Diameter Size (mm) 12.1 13.6 14.7 15.9 18.0 20.4 24.1 23.3 25.8 29.0 33.1 36.1 39.3 44.7 49.0 53.5 59.0 20S 20S 20S 20 20 25 25 25 32 32 40 40 40 50 50 63 63 Cleat Size Nominal Weight (kg/km) 5 6 6 7 8 9 10 10 11 12 14 16 18 20 T9 T9 T10 302 346 410 499 648 978 1290 1500 1890 2450 330 4020 4750 5800 7280 8750 10700 Resistance of Copper Conductor (Ω/Km) at 200C 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 NB: Actual Armour Cross Section Area (mm²) Red shows SWA too small to be used as protective conductor. Taken from table 54G in 17th Edition of the IET Wiring Regulations (but may comply by calculation). Black shows SWA adequate to use as protective conductor. Taken from table 54G in 17th Edition of the IET Wiring Regulations. The information contained within this datasheet is for guidance only. Please note the actual cable dimensions may very due to manufacturing tolerence. Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 2 of 7 Sizes and Dimensions - 3 core Part No. No. Cores Conduct or Cross Section Area (mm²) Cable Cross Section Area (mm²) 6943X 1.5 6943X 2.5 6943X 4 6943X 6 6943X 10 6943X 16 6943X 25 6943X 35 6943X 50 6943X 70 6943X 95 6943X 120 6943X 150 6943X 185 6943X 240 6943X 300 6943X 400 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 124.63 156.07 183.76 216.31 298.50 366.25 510.45 615.44 637.62 813.92 1074.67 1281.25 1625.15 1946.83 2383.27 2844.87 3481.91 Actual Armour Cross Section Area (mm²) 16 19 20 23 39 45 62 68 78 90 128 141 201 220 250 269 304 Overall Diameter (mm) Gland Size Cleat Size Nominal Weight (kg/km) Resistance of Copper Conductor (Ω/Km) at 200C 12.6 14.1 15.3 16.6 19.5 21.6 25.5 28.0 28.5 32.2 37.0 40.4 45.5 49.8 55.1 60.2 66.6 20s 20s 20s 20 20 25 32 32 32 40 40 50 50 50 63 63 75 6 6 6 7 8 10 11 11 12 14 16 16 18 20 T9 T10 T11 330 390 464 568 866 1152 1800 2230 2490 3290 4440 5470 6930 8350 10400 12600 14600 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 NB: Actual Armour Cross Section Area (mm²) Red shows SWA too small to be used as protective conductor. Taken from table 54G in 17th Edition of the IET Wiring Regulations (but may comply by calculation). Black shows SWA adequate to use as protective conductor. Taken from table 54G in 17th Edition of the IET Wiring Regulations. The information contained within this datasheet is for guidance only. Please note the actual cable dimensions may very due to manufacturing tolerence. Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 3 of 7 Sizes and Dimensions - 4 core Part No. No. Cores Conduct or Cross Section Area (mm²) Cable Cross Section Area (mm²) 6944X 1.5 6944X 2.5 6944X 4 6944X 6 6944X 10 6944X 16 6944X 25 6944X 35 6944X 50 6944X 70 6944X 95 6944X 120 6944X 150 6944X 185 6944X 240 6944X 300 6944X 400 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 143.07 176.63 211.13 274.51 349.49 411.66 597.98 725.47 803.84 1115.71 1365.03 1741.45 2073.94 2514.79 3115.75 3715.75 4788.19 Actual Armour Cross Section Area (mm²) 17 20 23 36 43 49 70 78 90 131 147 206 230 255 289 319 452 Overall Diameter (mm) Gland Size Cleat Size Nominal Weight (kg/km) Resistance of Copper Conductor (Ω/Km) at 200C 13.5 15.0 16.4 18.7 21.1 22.9 27.6 30.4 32.0 37.7 41.7 47.1 51.4 56.6 63.0 68.8 78.1 20s 20s 20 20 25 25 32 32 32 40 50 50 50 63 63 75 75 6 6 7 8 9 11 12 12 14 16 18 20 TC9 TC10 TC11 TC12 TC14 365 438 532 764 1013 1360 2160 2690 3130 4500 5600 7400 8780 10630 13390 16290 19800 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 NB: Actual Armour Cross Section Area (mm²) Red shows SWA too small to be used as protective conductor. Taken from table 54G in 17th Edition of the IET Wiring Regulations (but may comply by calculation). Black shows SWA adequate to use as protective conductor. Taken from table 54G in 17th Edition of the IET Wiring Regulations. Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 4 of 7 Sizes and Dimensions - 5 core Part No. No. Cores Conduct or Cross Section Area (mm²) Cable Cross Section Area (mm²) 6945X 1.5 6945X 2.5 6945X 4 6945X 6 6945X 10 6945X 16 6945X 25 6945X 35 6945X 50 5 5 5 5 5 5 5 5 5 1.5 2.5 4 6 10 16 25 35 50 143.07 176.63 211.13 274.51 349.49 411.66 655.64 808.87 1133.54 Actual Armour Cross Section Area (mm²) 19 22 25 40 46 72 88 100 144 Overall Diameter (mm) Gland Size 13.5 15.0 16.4 18.7 21.1 22.9 28.9 32.1 38.0 Cleat Size Nominal Weight (kg/km) Resistance of Copper Conductor (Ω/Km) at 200C 6 7 7 8 9 10 12 14 16 390 465 579 820 1090 1400 2100 2580 3850 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 Sizes and Dimensions - Multi core Part No. No. Cores Conduct or Cross Section Area (mm²) Cable Cross Section Area (mm²) 6945X 1.5 6947X 1.5 694/12X 1.5 694/19X 1.5 694/27X 1.5 694/37X 1.5 6945X 2.5 6947X 2.5 694/12X 2.5 694/19X 2.5 694/27X 2.5 694/37X 2.5 5 7 12 19 27 37 5 7 12 19 27 37 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 143.07 181.37 295.44 386.88 559.62 660.19 176.63 229.54 393.88 555.43 739.85 896.82 Actual Armour Cross Section Area (mm²) 19 20 39 45 70 78 22 24 45 70 84 94 Overall Diameter (mm) Gland Size Cleat Size Nominal Weight (kg/km) Resistance of Copper Conductor (Ω/Km) at 200C 13.5 15.2 19.4 22.2 26.7 29.0 15.0 17.1 22.4 26.6 30.7 33.8 20S 20S 20 25 25 32 20S 20 25 25 25 32 6 6 8 9 10 12 7 7 9 10 12 14 390 470 780 1000 1500 1800 465 600 1000 1540 1950 2350 12.1 12.1 12.1 12.1 12.1 12.1 7.41 7.41 7.41 7.41 7.41 7.41 The information contained within this datasheet is for guidance only. Please note the actual cable dimensions may very due to manufacturing tolerence. Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 5 of 7 Conductor Cross Sectional area (mm²) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 Reference Method C (Clipped Direct) 1 Two core cable, singlephase a.c. or d.c. (A) 27 36 49 62 85 110 146 180 219 279 338 392 451 515 607 698 787 1 three- or 1 four-core cable, three phase a.c. (A) 23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599 673 Reference Method E (In free air on a perforated cable tray etc, horizontal or vertical) 1 two core 1 three or cable, single1 four-core phase a.c. or cable, three d.c. phase a.c. (A) (A) 29 25 39 33 52 44 66 56 90 78 115 99 152 131 188 162 228 193 291 251 354 304 410 353 472 406 539 463 636 546 732 628 847 728 Reference Method D (Direct in ground or in ducting in ground, in or around buildings) 1 two core cable, singlephase a.c. or d.c. (A) 25 33 43 53 71 91 116 139 164 203 239 271 306 343 395 446 - 1 three or 1 four core cable, three-phase a.c. (A) 21 2 36 44 58 75 96 115 135 167 197 223 251 281 324 365 - This table above is in accordance with Table 4E4A of the 17th Edition of IET Wiring Regulations Notes: 1. Where is it intended to connect the cables in this table to the equipment or accessories designed to operate at a temperature lower than the maximum operating temperature of the cable, the cable should be rated at the maximum operating temperature of the equipment or accessory (see Regulation 512.1.5). 2. Where it is intended to group a cable in the table with other cables, the cables should be rated at the lowest of the maximum operating temperature of any of the cables in the group (see Regulation 512.1.5). Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 6 of 7 Conductor Cross Sectional Area (mm²) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 Two Core Cable, d.c (mV/A/m) 31 19 12 7.9 4.7 2.9 1.85 1.35 0.98 0.67 0.49 0.39 0.31 0.25 0.195 0.155 0.120 Two Core. Single Phase a.c. (mV/A/m) 31 19 12 7.9 4.7 2.9 r x z 1.85 0.160 1.90 1.35 0.155 1.35 0.99 0.155 1.00 0.67 0.150 0.69 0.50 0.150 0.52 0.40 0.145 0.42 0.32 0.145 0.35 0.26 0.145 0.29 0.20 0.140 0.24 0.16 0.140 0.21 0.13 0.140 0.190 Three- or Four-core cable, three-phase a.c. (mV/A/m) 27 16 10 6.8 4.0 2.5 r x z 1.60 0.140 1.65 1.15 0.135 1.15 0.86 0.135 0.87 0.59 0.130 0.60 0.43 0.130 0.45 0.34 0.130 0.37 0.28 0.125 0.30 0.22 0.125 0.26 0.175 0.125 0.21 0.140 0.120 0.185 0.115 0.120 0.165 This table above is in accordance with Table 4E4B of the 17th Edition of IET Wiring Regulations Dungannon Electrical Wholesale Tel: +44 28 87729787 Page 7 of 7