Outdoor Blade Power
DPU40D-N06A3 Datasheet
Introduction
The DPU is a blade power module that uses natural heat dissipation.
It can be installed on a pole or wall. Easy installation, fast deployment,
high reliability, and maintenance-free. Supports parallel system power
expansion to meet 5G evolution requirements.
Features
 Simple Deployment
• Fast installation, 1 hour by 2 person
DPU40D-N06A3
• Multiple input modes: AC/HVDC
 Easy O&M
• Fan-free design, 4-6 years routine maintenance-free
 Reliable Power Supply
• Protect level:IP65
• working temperature:-40℃ to +55℃
Specifications
Distributed Power Unit for DC Load Scenarios
DPU40D-N06A3
Product Type
System
Dimension (W×D×H)
50 mm × 300 mm × 400 mm
Weight
≤7.5 kg
Installation Mode
Wall-mounted, pole-mounted, tower installation
Rated Power
2000 W
Parallel Number
4
Cabling Mode
Bottom inlet and outlet
Protection Level
IP65
Working Temperature
−40℃ to +55℃ (without solar radiation)
Cooling Mode
Natural heat dissipation
Operating Environment
Class C*
Grid Environment
1st/ 2nd/ 3rd rate grid*
Note: Any datasheet issued previously is invalid when new version releases.
www.huawei.com
Issue date of this version: 2020-7-16
Specifications
Environment
Storage Temperature
−40℃ to +70℃
Operating Humidity
5% to 95% (non-condensing)
Altitude
-60 to 4000 m (From 2000~4000m, each 200m increases in altitude will decrease
the working temperature by 1℃)
Power Input Mode
220 V AC single-phase
110 V AC dual-live wire
HVDC
Input Voltage
AC: 85 - 300 V AC
HVDC: 90 - 400 V DC
Input Frequency
45 Hz - 65 Hz
AC Input
1× 16 A
AC SPD
20 kA/20 kA, 8/20 µs
Output Power
2000 W
Output Voltage
-54.5V DC (default), adaptable to 57V DC
DC Output
3×40 A Quick plug terminals with replaceable fuse
Battery Branch
1x40 A Quick plug terminals
DC SPD
10 kA/20 kA, 8/20 µs
Power Input
Load Output
Maximum efficiency ≥96%
Efficiency
Others
Safe
IEC62368-1,IEC/EN 60950-22,IEC60950-1,GB4943-2011,YD/T 1436-2014
Certified
CE,RCM,ETL,TUV,KCC,FCC,IC,TLC
MBTF
≥500,000 小时(@25℃)
*Remark:
RS485 interface supports telecom protocol / NetEco / U2000/M2000
Internal Communication: DPU supports in-band communication with 5th generation Huawei RRU.
Grid classification standard:
1st rate grid: power outage < 10hrs per month; 2nd rate grid: power outage < 10hrs per week; 3rd rate grid: power outage 2-8hrs per
day
Operating environment definitions:
Class C-Sea environments or outdoor land environments (with simple shielding measures) near pollution sources. If a site is near a
pollution source, it is at most 3.7 km away from salt water such as the sea and salt lakes, 3 km away from heavy pollution sources such
as smelteries, coal mines, and thermal power plants, 2 km away from medium pollution sources such as chemical, rubber, and
galvanization industries, or 1 km away from light pollution sources such as packing houses, tanneries, and boiler rooms.
Class D-Environments within 500 m away from the seashore. Class D environments are special Class C environments
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei
Technologies Co., Ltd.
General Disclaimer
The information in this document may contain predictive statements including, without limitation, statements regarding the future financial
and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and
developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for
reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.
Note: Any datasheet issued previously is invalid when new version releases.
www.huawei.com
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Industrial Base
Bantian Longgang
Shenzhen 518129, P.R. China
Tel: +86-755-28780808
www.huawei.com
Issue date of this version: 2020-7-16