Transformer Loss Calculation Rated Power Rated Frequency Rated Volatge (HV) Rated Volatge (LV) Rated Current (HV,Δ) Rated Current (LV,Y) Percentage Impedance = = = = = = = 26 50 33 11 263 1365 8.5 MVA Hz KV KV A Phase A Phase % Core Dia Total Weight of Core (G) Maxm. Flux Density Core Loss/Kg (p) Safety Factor (K) = = = = = 540 13539 1.68 0.8 1.1 mm Kg Tesla Watt/Kg No Load Loss (Po=K x p x G) = 12 KW = = = 729 570 649.5 mm mm mm HV Winding Inner Dia Outer Dia Mean Dia = = = 976 765 870.5 mm mm mm C (=πd) = 2040 mm C (=πd) = 2735 mm No. of Turns LT Winding Area Temperature Coefficient LV Resistance at 75°C = = = = No. of Turns HT Winding Area Temperature Coefficient HV Resistance at 75°C = = = = Winding Resistance Loss,LV (=3I²R) = 40 KW Winding Resistance Loss,HV (=3I²R) = 37 KW Weight of LV Winding = 2158 Kg Weight of LV Winding = 4128 Kg ii. Additional Loss Calculation Additional Loss,LV = 4 KW Additional Loss,HV = 3 KW iii. Lead Loss Calculation Lead Loss = 1 KW iv. Stray Loss Calculation Stray Loss (=K x Uk x Se x 100) = 9 KW = = = 5 0.5 3 Nos. KW KW Full Load Loss (Copper Loss) No Load Loss (Core Loss) Auxiliary Loss = = = 93 12 3 Nos. KW KW Total Loss = 108 KW Calculation of No Load Loss (Core Loss) Calculation of Full Load Loss (Copper Loss) i. Winding Resistance Loss Calculation LV Winding Inner Dia Outer Dia Mean Dia 80 491 mm² 0.02135 0.0071 Ω/Phase Auxiliary Loss of Transformer Total No. of Cooling Fan Rating of Each Fan Auxiliary Loss Summary 416 134.69 mm² 0.02135 0.1803 Ω/Phase