— A P P L I C AT I O N N OT E 2 .0 Transformers Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge arresters in medium-voltage systems. Each APPLICATION NOTE gives in a concentrated form additional and more detailed information for the selection and application of MO surge arresters in general or for a specific equipment. First published December 2018 3 O V E R V O LTA G E P R OT E C T I O N — Overvoltage protection of transformers All transformers in high-voltage and medium-voltage systems must be protected against transient overvoltages resulting from lightning and switching events. 1 Introduction The most efficient protection against overvoltages is the installation of gapless MO surge ­arresters on both sides (primary and secondary side) of the transformer. The MO surge arresters must be installed as close as possible to the bushings. In medium-voltage distribution systems mainly lightning incidents are critical. Figure 1 shows a medium-voltage transformer in a very simplified way. The transformer is in star connection with open star point on the mediumvoltage side (3phase, three-wire system) and the low-voltage side (3phase, five-wire system). — Figure 1: Principle outline of a mediumvoltage transformer in star connection Overvoltage protection has to be considered for: • The bushings and insulation on the mediumvoltage side • The neutral of the transformer (star point) • The bushings and lines on the low-voltage side. Concentrating on the medium-voltage side we have the situation shown in Figure 2 with MO surge arresters between phase and earth (phase arresters) and between neutral and earth (neutral arrester). The possible coupling of transient overvoltages from the medium-voltage side to the low-voltage side is shown in Figure 3 and described below. Trafo L1 i MV LV i L1 L2 L2 L3 L3 U N P U Mp, neutral — Figure 2: Mediumvoltage transformer in star connection Trafo L1 Mp L2 L3 neutral arrester phase arrester 4 A P P L I C AT I O N N O T E T R A N S F O R M E R S 2 Coupling of transient overvoltages through a transformer This potential difference is also to be found on the low-voltage side between the conductor and the earthing system. Up to 40% of fast front overvoltages (e.g. lightning overvoltages) can be transmitted capacitive from the primary to the secondary side. That is why it is necessary to protect the secondary side, even though the line on this side may not be directly lightning endangered. The resistive coupling of the overvoltage in a substation is also to be taken into account. Depending on the execution of the earthing at the medium-voltage and the low-voltage side, overvoltages can be transmitted from one side to the other over the earthing system. In Figure 3 the possible voltage transmissions are depicted in a strongly simplified manner. Capacitive coupling The height of the possible transmitted impulse voltage can be roughly estimated with a simple observation. In a system having a maximum ­system voltage of Us = 24 kV and an insulated neutral, the MO surge arrester with, for example, a continuous operating voltage Uc = 24 kV is directly connected at the medium voltage bushing of the transformer. This arrester may have a ­t ypical lightning impulse protection level of Upl = 80 kV (POLIM-K). Therefore, the insulation of the transformer with LIWV = 125 kV is very well protected on the medium-voltage side. If 40% of the voltage is coupled through the transformer, an overvoltage of theoretical 32 kV occurs on the low-voltage side. The insulation of the transformer is not likely to be endangered, but the bushings on the low-voltage side and the connected lines can be destroyed or a flash over may occur. Resistive coupling Let us consider the possible resistive transmission of the overvoltage. The lightning current of In = 10 kA peak value flows according to the Figure 3 through the arrester and over the earthing resistance RE to earth. If we take a typical earthing resistance of RE = 10 Ω, a temporary potential rise of the transformer housing of 100 kV occurs. — Figure 3: Coupling of a lightning overvoltage through a medium-voltage transformer This very simplified examinations do not provide an absolute statement about the level of the overvoltages that are transmitted, but explain the problems very well. Therefore, overvoltages on both sides of the transformer are to be considered in any case. 3 Selection of the MO surge arresters The MO surge arresters have to be selected as described in the Application Guidelines and the Application Notes, see Application Note 1.1. The examples given below guide through the principle of the selection process step by step. Other system configurations are possible and have to be considered from case to case. Depending on the expected stresses, electrical and environmental, and the importance of the equipment to be protected it is necessary to decide which characteristics of the MO surge arresters are most important to provide best protection. In this way the type of arrester (arrester class etc.) can be chosen from the beginning. In the example below high thunderstorm activity is mentioned, and consequently an MO surge arrester with sufficient energy handling capability should be chosen, in this case the type POLIM-K. The following practical example guides through the selection process for the arresters. 3.1 Selection example: Transformer protection in an outdoor substation Supplied information • System voltage Us = 24 kV • Star point high ohmic insulated with automatic earth fault clearing after a maximum of 60 s • Installation at 3 600 m above sea level • High thunderstorm activity, seasonally ­dependent • Line discharge class 2 LV MV C 0.4 Ures i Ures i RE i U U 5 O V E R V O LTA G E P R OT E C T I O N Assumptions First: Line discharge class 2 is the old arrester classification acc. IEC 60099-4, Ed. 2.2! Application Note 1.1 gives us the equivalent of line discharge class 2: arrester class SL acc. IEC 60099-4, Ed.3.0 is the correct choice. If no further information is provided we have to assume • Um = 24 kV • LIWV = 125 kV (see Application Note 1.1) or IEC 60071-1 • Duration of the earth fault t = 60 s • Nominal discharge current In = 10 kA • Short circuit current of the system Is = 20 kA • Degree of pollution: light POLIM-K is an MO surge arrester with arrester class SL (station low) with • Repetitive charge transfer rating Qrs = 1.0 C and • Rated thermal energy Wth = 5.6 kJ/kVUc , see data sheet. Step e) Check lightning impulse protection level Upl and withstand voltage LIWV Control of the protection level. Required is: Upl ≤ LIWV / Ks With LIWV = 125 kV and Ks = 1.15, the maximum allowed voltage at the electrical equipment results in 108.7 kV. 3.2 Phase arresters Following the steps given in selection flow chart Application Note 1.1 A1 it follows: Step a) Continuous operating voltage Uc The choice of the continuous operating voltage according to Application Note 1.2 is Us Uc ≥ ---T The type POLIM-K is chosen with the assumption of arrester class SL (station low) on the basis of increased thunderstorm activity. For t = 60 s, this results in a factor of T = 1.275 out of the TOV curve for POLIM-K. The continuous voltage is thus calculated as: 24 kV Uc ≥ ---- -- --- = 18.8 kV 1.275 Adding a safety margin for Uc of 10% this results in Uc = 20.7 kV Therefore, chosen is (according data sheet): POLIM-K with Uc = 21 kV Step b) Rated voltage Ur According data sheet the rated voltage is Ur = 26.3 kV Step c) Nominal discharge current In The nominal discharge current for MO surge arresters class DH, SL, SM is In = 10 kA, for class SH the nominal discharge current is In = 20 kA. The type POLIM-K is of class SL with In = 10 kA. See also data sheet. Step d) Charge and thermal rating Qrs and Wth Based on the given information “high thunderstorm activity” the type POLIM-K was chosen ­instead of the type POLIM-D. The POLIM-K 21 has an Upl of 70.0 kV and meets the demands with a good additional safety margin. With the steps a) to e) the active part of the MO surge arrester is selected. Now follows the selection of the arrester housing and confirmation of mechanical data. Step f) Creepage distance According to the assumption, there is low pollution (pollution class b-light acc. IEC/TS 60815-1) to be considered. Therefore the minimum recommended specific creepage distance between phase and earth is 27.8 mm/kV. — Note: In previous definitions the creepage distance was related to the system voltage phase-to-phase and defined as “specific creepage distance” SCD. In this case the SCD would be 27.8/√3 = 16 mm/kV. 6 A P P L I C AT I O N N O T E T R A N S F O R M E R S Pollution effects on insulators or housings are long term effects. Short TOVs as for instance for 60 s need not to be considered. Therefore, the needed creepage distance in this example can be based on the phase-to-earth voltage Us/√3 = 24 kV/√3 = 13.8 kV. This results in a minimum requirement of 384 mm creepage distance. With silicone housing and light pollution (pollution class b, see Table 4 in the ­APPLICATION GUIDELINES), the creepage distance can be reduced by 30%. This ultimately ­results in a creepage distance of 269 mm. The P ­ OLIM-K 21-50 has a creepage distance of 745 mm according to the datasheet and offers large reserves here as well. Step g) Flashover distance The minimum necessary withstand values of the empty arrester housing are calculated according to IEC 60099-4, Ed. 3.0 as: Lightning voltage impulse 1.2/50 μs: 1.3 × Upl = 1.3 × 70.0 kV = 91.0 kV a.c. voltage test 1 min., wet: 1.06 × Ups (switching current impulse 500 A => Ups = 53.8 kV) = Utest ,pv = 57.1 kV,pv This results in a withstand value of 57.1 kV / √2 = 40.3 kV, rms, 1 min., wet The proved withstand values according to the datasheet are: a.c. voltage tests 1 min., wet: 40.3 kV rms. An increase of 18% results in 47.6 kV rms Both calculated values according to the altitude correction lie below the proved withstand values. Therefore, it is not necessary to extend the housing. Step h) Consider short circuit rating Is The POLIM-K 21-50 is proved with a short circuit current of 50 kA and easily meets the demands for a short circuit current of 20 kA, as it was assumed. Step i) Consider mechanical loads Special requirements for mechanical loads are not given. Therefore, no further considerations necessary. — It follows: the POLIM-K 21-50 is the right arrester from all points of view for this application. 3.3 Neutral arrester One of the most widely used special application of MO surge arresters is for the protection of transformer neutrals. Each not directly earthed neutral brought out through a bushing should be protected against lightning and switching overvoltages by an arrester. Without protection, the neutral insulation may be overstressed by overvoltages due to lightning events or to asymmetrical faults or switching operations in the power system. Lightning discharge voltage 1.2/50 μs: 180 kV a.c. voltage test: 80 kV, rms, 1 min. wet. Therefore, the housing of POLIM-K 21-50 has higher withstand values than are required according to IEC. Taking into consideration the installation height of 3600 m, it must be checked whether an increasing of the flash over distance of the arrester housing is necessary. According the guide lines for altitude correction, the flash over distance should be increased with 10% per 1000 m above an installation height of 1800 m, which means that a corresponding higher withstand voltage must be proven. Thus, for installation in an altitude of 3600 m a correction factor of 18% has to be considered. For the minimum required withstand voltage, this results in: Lightning discharge voltage 1.2/50 μs: 91.0 kV. An increase of 18% results in 107.4 kV. The charge transfer rating or the energy handling capability of neutral arresters should be at least the same as required for the phase-to-earth arresters. The selection of the neutral arrester has, in prin­ ciple, to be done in the same way as for the phase arresters. But, as said above, the neutral arrester should have the same specific ratings as the phase arresters. Therefore, we have to go for a POLIM-K. Step a) Continuous operating voltage Uc The power frequency voltage at the neutral ­cannot be higher than Us/√3. It follows for continuous operating voltage of the neutral arrester US Uc ≥ ---------T x √3 The continuous voltage for the phase arrester was calculated to Uc = 20.7 kV. This includes ­already a safety margin of 10%, so we can write Uc,neutral = Uc,phase /√3 = 20.7 kV / √3 = 11.95 kV. From the data sheet follows POLIM-K 12-20. O V E R V O LTA G E P R OT E C T I O N 7 Step b) Rated voltage Ur According data sheet the rated voltage is Ur = 15.0 kV The proved withstand values according to the datasheet are: Lightning discharge voltage 1.2/50 μs: 110 kV. Step c) Nominal discharge current In In = 10 kA for type POLIM-K a.c. voltage test: 50 kV, rms, 1 min. wet. Step d) Charge and thermal rating Qrs and Wth Repetitive charge transfer rating Qrs = 1.0 C, and Rated thermal energy Wth = 5.6 kJ/kVUc Step e) Check lightning impulse protection level Upl and withstand voltage LIWV If no further information is given one can assume that the lightning and switching impulse withstand voltages of the neutral insulation are the same as for the phases. Control of the protection level. Required is: Upl ≤ LIWV / Ks With LIWV = 125 kV and Ks = 1.15, the maximum allowed voltage at the electrical equipment results in 108.7 kV. The POLIM-K 12 has an Upl of 40.0 kV and the demands with a good additional safety margin. Step f) Creepage distance According to the assumption, there is low pollution (pollution class b-light acc. IEC /TS 60815-1) to be considered. Therefore, the minimum recommended specific creepage distance between ­neutral and earth is theoretical 27.8 mm/kV. In our example the voltage between neutral and earth is virtually zero, except for a short UTOV = 13.8 kV for 60 s As pollution effects are long term effects we don’t need to worry about the creepage distance for the neutral arrester. Step g) Flashover distance The minimum necessary withstand values of the empty arrester housing are calculated according to IEC 60099-4, Ed. 3.0 as: Lightning voltage impulse 1.2/50 μs: 1.3 × Upl = 1.3 × 40.0 kV = 52.0 kV a.c. voltage test 1 min., wet: 1.06 × Ups (switching current impulse 500 A => Ups = 30.8 kV) = Utest ,pv = 32.7 kV,pv. This results in a withstand value of 32.7 kV / √2 = 23.1 kV, rms, 1 min., wet. Therefore, the housing of POLIM-K 12-20 has higher withstand values than are required according to IEC. Taking into consideration the installation height of 3600 m, it must be checked whether an increasing of the flash over distance of the arrester housing is necessary. According the guide lines for altitude correction, the flash over distance should be increased with 10% per 1,000 m above an installation height of 1800 m, which means that a corresponding higher withstand voltage must be proved. Thus, at 3600 m it must be corrected by 18%. For the minimum required withstand voltage, this results in: Lightning discharge voltage 1.2/50 μs: 52.0 kV. An increase of 18% results in 61.36 kV. a.c. voltage tests 1 min., wet: 23.1 kV rms. An increase of 18% results in 27.26 kV rms Both calculated values according to the altitude correction lie below the proved withstand values. Therefore, it is not necessary to extend the housing. Step h) Consider short circuit rating Is The POLIM-K 12-20 is proved with a short circuit current of 50 kA and easily meets the demands for a short circuit current of 20 kA, as it was ­assumed. Step i) Consider mechanical loads Special requirements for mechanical loads are not given. Therefore, no further considerations necessary. — It follows: the POLIM-K 12-20 is the right arrester from all points of view for this application. 8 A P P L I C AT I O N N O T E T R A N S F O R M E R S 4 Low-voltage arresters Overvoltage protection in buildings and structures (including lightning protection structur) starts at the meter and is to be done according to the IEC 61643 series, and not subject to the ABB application guidelines. However, some special ­applications as for instance protection of transformer bushings on the low-voltage side, motors, cable sheath, low-voltage overhead lines etc. are considered in separate application notes. High-voltage and medium-voltage arresters are designed and tested according the IEC 60099 ­series. The scope of the 60099 series is limited to MO surge arresters for AC power circuits with Us above 1 kV. Therefore, the IEC 60099 series are not applicable for low-voltage arresters. For low-voltage systems IEC 61643-11 “Low-voltage surge protective devices - Part 11: surge protective devices connected to low-voltage power systems – Requirements and test methods”, and other standards of the 61643 series are applicable. Figure 4 illustrates the situation. Typical low-voltage power systems are threephase four-wire systems with system voltages 230/400 V and 400/690 V. 5 Application considerations The practice for overvoltage protection of the low-voltage side of the transformer (protection of the bushings and connected lines) is the same adopted for medium-voltage overhead lines. Information about the assembling and installation, maintenance, transport, storage and disposal of MO surge arresters is to be found in the operating instructions (manual) for each surge arrester. There are some points to be especially observed so that a MO surge arrester can fulfill correctly its function. — Figure 4: Principle of overvoltage protection in a medium-voltage and low-voltage power system. IEC 60099-series IEC 61643-series LPS Overhead line LPZ0 MVSA LPZ1 LVSA SPDs MVSA: Medium-voltage MO surge arrester LVSA: Low-voltage MO surge arrester SPD: Surge protective device LPS: Lightning protection structure LPZ0 and LPZ1: Lightning protection zones — Figure 5: Examples of good and poor connection principles for MO surge arresters in distribution systems. Overhead line T T C C 1: Poor. The connection leads are too long and the transformer and the MO surge arrester do not have the same earthing point. 2: Good. Common earth of MO surge arrester and transformer. The connection leads are much shorter. 1 2 T C 3 3: Very good. The MO surge arrester is earthed directly at the transformer tank. The loop is very short. In this way the inductance is kept to a minimum. O V E R V O LTA G E P R OT E C T I O N 9 5.1 Connections At distribution levels the MO surge arresters often can be located very close to the equipment to be protected, e.g. transformers. The connections must be as short and straight as possible, on the medium-voltage side as well as on the earth side. This is because inductive voltages appear at each conductor due to the self-inductivity of the leads during the flowing of the impulse current. The specified residual voltages, which are given in the data sheets, are always the voltages between the arrester terminals only. The additional inductive voltage drop Ui is to be calculated as Ui = L × di/dt. L is the inductance of the loop and di/dt the rate of rise of the impulse current. Figure 5 gives hints for good and poor connection principles. If possible connection principle 3 should be used. In no case connections as in 1 should be made. Additional information about connecting MO surge arresters and induced voltages is provided in Technical Note 2.3. 6 Summary The provided information in the example was ­limited to some basics. Sometimes specifications refer to old standards, which are not applicable anymore. Therefore, assumptions have to be made. In any case, it must be clear with the offer on which information and assumptions the offer is based. For our example the technical data of the phase arresters are summarized below. For completion, the data for the neutral arrester and some information for the overvoltage protection on the low-voltage side is given as well. Based on the information provided and the assumptions made, the technical data for the chosen MO surge arrester are, see Table 1: 5.2 Earthing considerations Low earth resistance is essential, and it should be as low as possible in order to limit the earth ­potential rise at the earth terminal, and hence mitigate safety hazards and flash over on the low-voltage side of the transformer. A value for earth resistance of 10 Ω or less is considered to be sufficient. See also Figure 3. — Table 1: Technical data of selected MO surge arresters Information and assumptions Technical data Comments Phase arresters Highest system voltage Us = 24 kV, k = √3 Fault clearing time 60 s Nominal discharge current LD 2 => old arrester class Repetitive charge transfer rating Rated thermal energy Lightning protection level Um = 24 kV Uc = 21 kV Ur = 26.3 kV In = 10 kA new class: SL (station low) selected POLIM-K 21-50 Qrs = 1.0 C according data sheet W th = 5.6 kJ/kV Uc according data sheet Upl = 70 kV according data sheet LIWV = 125 kV assumed acc. AN 1.1 A2 All other technical data according datasheet. Neutral arrester Uc = 12 kV Ur = 15 kV In = 10 kA class SL selected POLIM-K 12-20 Qrs = 1.0 C W th = 5.6 kJ/kV Uc Upl = 40 kV Um = 24 kV LIWV = 125 kV assumed acc. AN 1.1 A2 All other technical data according datasheet Low-voltage arresters If MO surge arresters for the protection of the low-voltage bushings and connected installations are required, the types MVR or POLIM-R..N can be a solution. For a 230/400 V low-voltage system MO surge arresters with Uc = 440 V are recommended. — ABB Switzerland Ltd. PGHV Surge Arresters Jurastrasse 45 CH-5430 Wettingen/Switzerland Tel. + 41 58585 2911 Fax + 41 58585 5570 Email: sales.sa@ch.abb.com abb.com/arrestersonline We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. © Copyright 2018 ABB. All rights reserved Specifications subject to change without notice 1HC0138866 EN AA Additional information We reserve the right to make technical changes or modify the content of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.