Single-core 90°C thermosetting insulated cables, non-armoured, with or without sheath (COPPER CONDUCTORS) CURRENT-CARRYING CAPACITY (amperes): Reference Method A (enclosed in conduit in thermally insulating wall etc) Conductor crosssectional area 2 cables, single3 or 4 cables, threephase AC or DC phase AC Ambient temperature: 30°C Conductor operating temperature: 90°C Reference Method B (enclosed in conduit on a wall or in trunking etc) 2 cables, singlephase AC or DC Reference Method C (clipped direct) 3 or 4 cables, three2 cables, single- 3 or 4 cables, threephase AC phase AC or DC flat phase AC flat and and touching Reference Method F (in free air or on a perforated cable tray etc horizontral or vertical etc Touching Reference Method G (in free air) spaced by one cable diameter 2 cables, singlephase AC or DC flat 3 cables, threephase AC flat 3 cables, threephase AC trefoil 2 cables, single-phase AC or DC or 3 cables three-phase AC flat Horizontal Vertical 8 (A) 9 (A) 10 (A) 11 (A) 12 (A) 1 (mm²) 1 1.5 2 (A) 14 19 3 (A) 13 17 4 (A) 17 23 5 (A) 15 20 6 (A) 19 25 7 (A) 17.5 23 2.5 4 6 10 16 26 35 45 61 81 23 31 40 54 73 31 42 54 75 100 28 37 48 66 88 34 46 59 81 109 31 41 54 74 99 25 35 50 70 95 106 131 158 200 241 95 117 141 179 216 133 164 198 253 306 117 144 175 222 269 143 176 228 293 355 130 161 209 268 326 161 200 242 310 377 141 176 216 279 342 135 169 207 268 328 182 226 275 353 430 161 201 246 318 389 120 150 185 240 300 278 318 362 424 486 249 285 324 380 435 354 393 449 528 603 312 342 384 450 514 413 476 545 644 743 379 436 500 590 681 437 504 575 679 783 400 464 533 634 736 383 444 510 607 703 500 577 661 781 902 454 527 605 719 833 683 783 900 584 666 764 868 990 1130 1288 1443 793 904 1033 1179 1323 940 1083 1254 1358 1520 868 998 1151 1275 1436 823 946 1088 1214 1349 1085 1253 1454 1581 1775 1008 1169 1362 1485 1671 400 500 630 800 1000 029290 887222 www.ayjaygroup.co.uk DISCLAIMER: This PDF is for information only and Ayjay Group Ltd and can not be held liable for any information therein.