Uploaded by Umar Hashmi

19

advertisement
EE 313: Power Distribution and
Utilization
(3 Credit Hours)
During the operation of power system, it is often desirable and
necessary to switch on or off the various circuits (e.g., transmission
lines, distributors, generating plants etc.) under both normal and
abnormal conditions.
With the advancement of power system, the lines and other
equipment operate at very high voltages and carry large
currents.
A circuit breaker can make or break a circuit either manually or
automatically under all conditions viz., no-load, full-load and shortcircuit conditions.
Circuit Breaker
A circuit breaker can
• Make or break a circuit either manually or by remote control under
normal conditions
• Break a circuit automatically under fault conditions
• Make a circuit either manually or by remote control under fault
conditions
Thus, a circuit breaker incorporates manual (or remote control) as well
as automatic control for switching functions. The latter control employs
relays and operates only under fault conditions.
Operating principle.
A circuit breaker essentially consists of fixed and moving contacts, called
electrodes. Under normal operating conditions, these contacts remain
closed and will not open automatically until and unless the system becomes
faulty.
The contacts can be opened manually or by remote control whenever
desired.
When a fault occurs on any part of the system, the trip coils of the circuit
breaker get energized and the moving contacts are pulled apart, thus
opening the circuit.
Isolator
It is one type of mechanical switch used to isolate a fraction of the
electrical circuit when it is required.
Isolator switches are used for opening an electrical circuit in the no-load
condition. It is not proposed to be opened while current flows through the
line.
Generally, these are employed on circuit breaker both the ends thus the
circuit breaker repair can be done easily without any risk.
Earthing Switch
Earthing switch is used to ground the residual charge in power lines
after disconnecting the line from source.
When a circuit is open by the circuit breaker and Isolator, there is a
residual charge remaining in the circuit. So to discharge the charge
Earthing switch is used.
This ensures the safety of the maintenance personnel during
maintenance and routine checking.
In normal condition, the isolators and circuit breakers are
closed but the earthing switch is opened.
During the maintenance period, the circuit breakers and
isolators are kept open and earthing switch kept closed.
In the Substations circuit breakers, isolators and earthing switches
are connected.
For the maintenance or any other purpose if we need to open the
circuit then we should follow a proper sequence for the operations
of circuit breakers, isolators and earthing switches.
If we follow the wrong sequence then it will be a danger for us as
well as equipment and circuits.
The sequence of operation of Isolator, Circuit Breaker, and
Earthing Switch:
While opening a circuit we should follow the below sequence
While closing a circuit we should follow the below sequence
What happened if we open the isolator before the circuit breaker?
We know that the Isolator is designed to operate under no load
condition, so if we open the isolator before the circuit breaker, that
means we open the isolator under live condition. So there will be
huge sparking between the contacts of the Isolator which is very
dangerous for us
Here a circuit diagram of 11KV/400V substation is shown. Here is one
incoming line and two outgoing line.
Suppose we need to the maintenance of the Transformer of the
second outgoing line.
So for the maintenance, first the transformer is to be
disconnected from the circuit. So below sequence should
be followed,
1. First circuit breakers A, B should be open.
2. Then the isolators C and D should be open.
3. Then the earthing switches E and F should be closed.
Now after complete the maintenance, to connect
again the Transformer to the line we should follow
the below sequence,
1. First Open the earthing switches E and F
2. Then close the isolators C and D
3. Then close the circuit breakers A and B
When the contacts of a circuit breaker are separated under
fault conditions, an arc is struck between them.
The current is thus able to continue until the discharge ceases.
The production of arc not only delays the current interruption
process but it also generates enormous heat which may
cause damage to the system or to the circuit breaker itself.
Therefore, the main problem in a circuit breaker is to
extinguish the arc within the shortest possible time so that
heat generated by it may not reach a dangerous value.
Classification of Circuit Breakers
The most general way of classification is on the basis of medium used for arc
extinction. The medium used for arc extinction is usually oil, air, sulphur
hexafluoride (SF6) or vacuum.
Accordingly, circuit breakers may be classified into :
• Oil circuit breakers which employ some insulating oil (e.g., transformer oil)
for arc extinction.
• Air-blast circuit breakers in which high pressure air-blast is used for
extinguishing the arc.
• Sulphur hexafluoride circuit breakers in which Sulphur hexafluoride (SF6)
gas is used for arc extinction.
• Vacuum circuit breakers in which vacuum is used for arc extinction.
Fuses
A fuse is a short piece of metal, inserted in the circuit, which
melts when excessive current flows through it and thus breaks
the circuit.
Battery Banks
A battery bank is the result of joining two or more batteries
together for a single application
By linking batteries together, we can increase the voltage, or
the Capacity (AH / Wh), or both
There are two primary ways to successfully connect
two or more batteries:
• Series
• Parallel
To connect batteries in a series, A wire is used to connect
the negative terminal of the first battery to the positive
terminal of the second battery
Connecting batteries in series adds the voltage of the two batteries,
but it keeps the same AH rating. For example, these two 6-volt
batteries joined in series now produce 12 volts, but they still have a
total capacity of 10 amps.
To join batteries in parallel, A wire is used to connect both the
positive terminals, and another wire is used to connect both the
negative terminals of both batteries to each other.
Negative to negative and positive to positive.
Parallel connections will increase capacity rating, but the voltage
will stay the same.
In the “Parallel” diagram, voltage is 6 volts, but the amps increase
to 20 AH.
It is also possible to connect batteries in series and parallel
configuration
If you have two sets of batteries already connected in
parallel, you can join them together to form a series to
create a series parallel battery bank.
In the diagram above, we have a battery bank that
produces 12 volts and has 20 amp hours.
Related documents
Download