27 kV MASTERCLAD® Medium Voltage Metal-Clad Switchgear with Type VR Vacuum Circuit Breakers Class 6055 CONTENTS Description Page Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Product Description RATINGS • • • • • • 16.5 to 27 kV 1200-2000 Amperes Continuous Ratings 16, 25 and 40 kA Symmetrical Interrupting Capacity 125 kV BIL, peak (impulse) dielectric withstand 60 kV, rms 1 minute 60 Hz dielectric withstand NEMA Type 1 – Indoor enclosure APPLICATIONS AND STANDARDS MASTERCLAD® medium voltage metal-clad switchgear is used in a wide variety of switching, control and protective applications including electric utility generation and distribution systems, industrial plants, commercial buildings, hospitals, municipal pumping stations, wastewater treatment plants, transportation systems and pipeline stations. MASTERCLAD offers a standard two-high breaker arrangement, incorporating a series of basic modular units, control packages and instrumentation that can be assembled in combinations as needed to satisfy user application requirements. MASTERCLAD switchgear with VR circuit breakers meets or exceeds the design standards of ANSI, IEEE, NEMA and IEC. The switchgear is tested in accordance with both ANSI C37.20.2 and IEC 298. The VR circuit breakers are tested per ANSI C37.09 and IEC 56. STANDARD FEATURES Metal-Clad Switchgear as defined by ANSI C37.20.2 includes: • • • • • • • • • Removable (Drawout) Circuit Breaker Fully Compartmented Construction Grounded Metal Barriers enclose all live parts Automatic Shutters over primary contacts Fluidized-Bed Epoxy Insulated Bus Mechanical Interlocks Disconnect Type Voltage Transformers Fixed Control Power Transformer with Drawout Primary Fuses Grounded Breaker Truck in and between Test-Disconnected and Connected Positions • Low Voltage Instrument/Control Compartment isolated from primary voltage areas 2 © 2000 Schneider Electric All Rights Reserved 1/00 Dimensions 27 kV LAYOUT DIMENSIONS/CONFIGURATION GUIDE Vertical sections are 36” wide 1.75 95.12 (44) (242) 1.75 95.12 (44) (242) 36.35 36.35 (923) (923) 1.00 (25) 58.25 1.00 16.06 (1480) (25) (408) 58.25 16.06 (1480) (408) 110.50 110.50 (2807) (2807) AUX VT/Circuit Breaker Section 1200/2000 A, 2000/1200 A Circuit Breaker Section 1.75 95.12 (44) (242) 95.12 (242) Bus to Incoming Line 36.35 (923) 1.00 (25) 58.25 16.06 (1480) (408) .80 (20) 110.50 58.25 (1480) 110.50 (2807) (2807) Blank/Circuit Breaker Section 95.12 AUX VT/AUX VT Section 95.12 (242) (242) Bus to Incoming Line 1.00 (25) 110.50 58.25 (2807) (1480) 110.50 AUX CPT Section (2807) Blank/AUX Section Dimensions are in inches (millimeters). 3 1/00 © 2000 Schneider Electric All Rights Reserved Ratings VR 27 kV Vacuum Circuit Breakers Rating Table on Symmetrical Current Rating Basis Description Preferred Ratings per ANSI C37.06-1997 q Insulation Level Rated Withstand Rated PermisRated VoltInterImpulse sible Max. age rupting Low 1.2 x Tripping Voltage Range Time Freq. 50 µs Delay kV rms Factor k Cycles kV kV Y rms Crest Sec. a Rated Transient Current Values Recovery Voltage Circuit Breaker Catalog Number Rated Rated Short (Ref.) Cont. Circuit Three Current Current Phase 60 Hz (at rated MVA A rms Max. kV) kA rms Rated Crest Voltage E2 kV Crest Rated Time to Crest T2 MicroSec Maximum Sym. Interrupting Capability kA rms 3 Sec. ShortTime Current Carrying Capability kA rms Close and Latch Rating Momentary kA Crest f VR2701612 750 1200 16 27 1.0 3 60 125 2 51 105 16 16 43 VR2701620 750 2000 16 27 1.0 3 60 125 2 51 105 16 16 43 VR2702512 1250 1200 25 27 1.0 3 60 125 2 51 105 25 25 68 VR2702520 1250 2000 25 27 1.0 3 60 125 2 51 105 25 25 68 VR2704012 2000 1200 40 27 1.0 3 60 125 2 51 105 40 40 108 VR2704020 2000 2000 40 27 1.0 3 60 125 2 51 105 40 40 108 q a f Also tested per IEC 56 These values apply with circuit breaker in or out of enclosure. Close and Latch Rating (Momentary) Amperes rms = 2.7 k (Rated Short Circuit Current) Breaker Identification 36.00 4.50 27.00 (114) 4.50 (686) (914) Rear Aisle 8.00 (203) 20.00 (508) (114) 8.00 VR 27 025 12 3.50 (203) (89) Continuous Current Rating Top Breaker Below Bottom Circuit Breaker Above (Conduit Area) kA Rating 9.00 Voltage Rating (229) 53.30 (279) 28.00 4.00 (711) (102) Circuit Breaker Type 11.00 (1354) 1.00 (25) 4.00 (102) Top Breaker Above Bottom Circuit Breaker Below (Conduit Area) 110.50 Weight (Approximate) Section (less circuit breaker) 2600 lbs. (1179 kgs.) (2807) (6) .75 Dia. Mounting Holes 1200 A circuit breaker 600 lbs. (272 kgs.) 2000 A circuit breaker 630 lbs. (286 kgs.) Recommended 4.00 Mounting Channels (3) Places (By Customer) 54.70 (1389) Control Conduit Area (Bottom) 8.00 (203) 1.00 2.00 (51) (25) Door 1.75 8.00 (44) (203) 1.50 2.50 72.00 (38) (64) 64.00 (23) (1829) Front Aisle (1626) (Minimum) 34.20 (869) .90 2.00 .90 (561) (23) 36.00 (914) NOT FOR CONSTRUCTION Typical Indoor 1200/2000 A Floor Plan 2.50 (64) Control Conduit Area (Top) Dimensions are in inches (millimeters). Square D Company 330 Weakley Road Smyrna, TN 37167 615-459-5026 1-888 Square D (1-888-778-2733) www.squared.com Catalog No. 6055CT9901 January 2000