Problem-1 A 3-phase delta-star connected, 30-MVA, 33/11kV transformer is protected by a differential relay. Calculate the relay setting for faults drawing up to 200% of rated current. The CT current ration on the primary side is 500:5, and that on the secondary side is 2000:5 The primary line current is MVA 30 106 IP 524.88 A 3 3KV 3 33 10 The sec ondary line current is Is 3 IP 3 524.88 1574.64 A The primary CT current is 5 I1 524.88 5.249 A 500 The sec ondary CT current is 5 I1 1574.64 3 6.818 A 2000 The relay current at 200% of the rated current I r 2 I 2 I1 2 6.818 5.249 3.3138 A Problem-2 A 3-phase delta-star connected, 15-MVA, 33/11kV transformer is protected by CTs. Calculate the CT ratios for differential protections such that the circulating current does not exceed 5A. The primary line current is MVA 15 106 IP 262.44 A 3 3KV 3 33 10 The sec ondary line current is Is 3 IP 3 262.44 787.30 A The CT ratio on high voltage side 787.3 CTratio 157.46 A 5 The CT ratio on low voltage side CTratio 262.44 (5) 757.6 A 3 Problem-3 If the fault current is 2000A, the relay setting is 50% and CT ratio is 400:5, then determine the plug setting multiplier (PSM). Fault Current PSM Re lay setting ( CT sec ondary current ) CT ratio 2000 10 0.5 5 80 Problem-4 A 3-phase 345/34.5kV transformer is rated at 50MVA and its short term emergency rating is 60 MVA. Using standard CT ratios available, determine the CT ratios, and the currents in the power transformer and the CTs. The 345kV is star connected, while the 34.5kV side is delta connected. The primary line current is MVA IP 3KV 60 10 100.4 A 3 3 345 10 6 The sec ondary line current is 60 10 1004.1A 3 3 34.5 10 6 The CT ratio of 1000 / 5 on 34.5kV voltage side 5 I r 1004 5A 1000 The CT ratio on 345kV voltage side 5 Ir 2.9 A 3 100.4 CTratio 34.64 2.9 The CT ratio of 200 / 5 on 345kV voltage side 5 I r 100.4 2.51A 200 The CT ratio on 34.5kV voltage side I r 5 3 4.35 A