www.reinhausen.com OILTAP® M On-Load Tap-Changer for Regulating Transformers On-Load Tap-Changer OILTAP® M model M III 500 Y, Um = 123 kV, 500 A, ±9 steps The OILTAP® M on-load tap-changer is used to vary the ratio of oil-immersed transformers under load. In general it is designed for network transformer as well as industrial transformer applications. The tap-changers comprise a diverter switch and a tap selector in a single column design and represent the most recent state of technology. The tap-changers offer both transformer manufacturer and user a great number of essential advantages. Versatility – three-pole design for neutral application at 350 A, 500 A and 600 A ratings for three-phase wye-connected windings – single-pole designs at 350 A, 500 A, 600 A, 800 A, 1200 A and 1500 A ratings for auto connected windings or single-phase transformers – available with ±9, ±11, ±13, ±15, ±17 steps – insulation to ground and tap selector size can be selected independently of one another – convenient for bell-type tank installation – additional devices for potential tie-in of tap winding during change-over operation of the change-over selector (tie-in resistors, potential contact) Compactness – high speed transition resistor type diverter switch with arc extinction at the first current zero – diverter switch uses snap-action mechanics by energy accumulator mounted directly on the diverter switch – minimum possible tap selector dimensions because four available sizes ensure matched impulse voltage withstandability – radial dimensions of the tap selector are reduced by special shaping of all parts on high potential, distances between tap selector bars determined by actual voltage stress – optimised integration of the change-over selector into the fine selector contact circle Robustness – long life – rapid tap change operation, low thermal stress on the transition resistors – diverter switch arcing contacts made of tungsten-copper alloy at 500 A and above – simple tap selector design, effective contact cooling, high short-circuit withstandability – tap selector gear with steady torque during the tap-changer operation Easy to install – cost saving – oil-immersed installation of the entire tap-changer in the transformer main tank – simple to connect – drive shaft and pipe connections easy to orientate – straight forward coupling to motor drive unit Reduced maintenance – long contact life – quick and easy to disassemble diverter switch insert – simple to adjust and control – oil suction pipe built-in – diverter switch contacts easy to replace www.reinhausen.com © Maschinenfabrik Reinhausen GmbH Falkensteinstrasse 8 93059 Regensburg, Germany Phone (+49) 9 41/40 90-0 Fax (+49) 9 41/40 90-1 11 E-mail sales@reinhausen.com Technical data The technical data of type M have been verified in type tests according to the IEC International Standard 60214-1. Moreover, they meet all corresponding National Standards. Detailed information and comprehensive data for selecting a type M for a particular application are contained in our printing matter TD 50. On-Load tap-changer M III 350 Y M III 500 Y M III 600 Y M I 351 M I 501 M I 601 M I 802 M I 1203 M I 1503 Number of poles 3 3 3 1 1 1 1 1 1 and application (neutral point) (neutral point) (neutral point) Max. rated through-current 350 500 600 350 500 600 800 1200 1500 Ium (in A) Rated short-time withstand 6 8 8 6 8 8 16 24 24 current (in kA) Rated short-circuit duration 3 3 3 3 3 3 3 3 3 (in s) Rated peak withstand 15 20 20 15 20 20 40 60 60 current (in kA) Max. rated step voltage 3300 3300 3300 3300 3300 3300 3300 3300 3300 Uim (in V) 1000 1400 1500 1000 1400 1500 2000 3100 3500 Step capacity (PStN) (in kVA) Rated frequency (in Hz) 50 to 60 Operating positions Without change-over selector: max. of 18, with change-over selector: max. of 35 Rating insulation level Highest voltage for 72.5 123 170 245 300 equipment Um (in kV) Highest operating voltage 55 79 145 170 245 Ub (phase-phase) on diverter switch (in kV) Rated lightning impulse 350 550 750 1050 1050 withstand voltage (in kV, 1,2/50) Rated switching impulse 850 withstand voltage (in kV) AC withstand voltage 140 230 325 460 460 (in kV, 50 Hz, 1min.) Tap selector 4 different tap selector sizes (B, C, D, DE) available Oil compartment Pressure-proof up to 0.3 bar continuous difference pressure (test pressure 0.6 bar), head and cover of the on-load tap-changer are vacuum-proof. Oil suction pipe Installed as standard (for details, see BA 18) Temperature range The on-load tap-changer OILTAP® M can be operated in the rated load range with oil temperatures of -25°C to +105°C. Please note: The data in our publications may differ from the data of devices delivered. We reserve the right to make changes without notice. IN258/01en – 0305/1500 – 258/01/01/0 – F0132700 · dp · Printed in Germany