Infectious aerosols transmission: Mitigation measures for heating, ventilating and airconditioning (HVAC) systems in operating and new hotels 4 July 2020 CONTENTS Infectious aerosols transmission: Mitigation measures for heating, ventilating and air-conditioning (HVAC) systems in operating and new hotels SECTION PAGE EXECUTIVE SUMMARY .................................................................................................. 2 INTRODUCTION .............................................................................................................. 3 PROPOSED MITIGATION MEASURES ........................................................................... 4 CONCLUSION .................................................................................................................. 9 ANNEX – INFORMATION OF AIR FILTRATION / CLEANING TECHNOLOGIES ..........11 REFERENCES ................................................................................................................13 1 EXECUTIVE SUMMARY Heating ventilating and air-conditioning (HVAC) systems can either promote or curtail the spread of infectious airborne aerosols. A well-designed and well-maintained HVAC system has a significant contribution to the protection of building occupants by disrupting the transmission path of infectious diseases and diluting the level of infection. In April 2020, Federation of European Heating, Ventilating and Air-conditioning Associations (REHVA) issued COVID-19 guidelines1. American Society for Heating, Refrigeration and Airconditioning Engineers (ASHRAE) also published a position document on infectious aerosols2. In May and June 2020, both U.S.3 and European4 Center for Disease Control and Prevention have respectively issued advisories stating that ventilation is essential in mitigating the spread of COVID-19. Based on the above-mentioned guidelines and published papers, this document outlines HVAC mitigation measures applicable for hotels. As proof of more mitigation measures become available, the recommendations can be updated. There needs to be flexibility and practicality applied as all buildings have their unique issues requiring different consideration. Currently, the most effective measures are summarised as below: Ensure ventilation is well distributed to all areas Maximise fresh air supply Control room relative humidity within the range of 40 - 60% Enhance filtration for high-risk (occupant-dense) areas 2 INTRODUCTION In 1979, a commercial airliner with 54 persons onboard was delayed on ground (due to engine failure) for 3 hours and the ventilation system was inoperative during the entire duration. 72 percent of passengers subsequently developed cough, fever and other symptoms of influenza. Scientists concluded that there was airborne transmission of the H3N2 virus5. In decades that followed, cases of outbreaks and scientific research6 continued to reinforce the point that airborne transmission of infectious diseases cannot be ignored. Pathogens spread through the air in the form of droplets or droplet nuclei (smaller than 10m or 10 x 10-6 m), also known as aerosols. Such droplets are emitted from the primary host by oral means such as coughing, sneezing or talking. Most large droplets will descend on surfaces due to self-weight within 1-2 meters from the source (see Figure 1). Some large droplets may reduce in size to become aerosols, due to evaporation (also known as desiccation). These aerosols are lightweight enough to suspend in the air and remain virulent for long periods of time ranging from several minutes to days. Figure 1 ( a) Comparative settling times by particle diameter 7 and ( b) Illustration of transmission of droplets and small airborne particles produced by an infected patient (courtesy of Yuguo Li) HVAC systems play an important role to prevent the spread of infectious aerosols within the building. While ventilation systems cannot prevent the settlement of large droplets, mitigation measures on HVAC systems can influence the transmissibility of infectious aerosols to a great extent. 3 PROPOSED MITIGATION MEASURES Provide minimum ventilation and exhaust for all areas as per ASHRAE8 or EN9 standards (For operating and new hotels) Inadequate ventilation increases the risks of airborne transmission of infectious aerosols. A minimum amount of outdoor air ventilation ensures that airborne contaminants do not accumulate to harmful concentration levels. Fresh air should be made available for all areas; bathroom exhausts should always be working. The windows of naturally ventilated premises should be kept open where practicable. The fresh air rates should be increased above these minimum levels wherever possible, even if only on a temporary basis. Avoid use of energy recovery ventilation systems that leak exhaust air into outdoor air supply (For operating and new hotels) Energy recovery systems such as heat recovery wheels are commonly used to harness the cooling potential of exhaust air for pre-cooling of outdoor air. The wheels rotate at low-speeds, constantly alternating contact with exhaust air and outdoor air (see Figure 2). Under certain circumstances, as much as 20% of polluted exhaust air side may carry over to outdoor supply air due to leakages at the joints. For operating hotels with heat recovery wheels, if leaks are suspected, adjustments or bypass are possible workaround solutions. For new hotels, alternative forms of energy recovery systems such as heat pipes should be considered. Figure 2: Leakages through heat recovery wheel 4 Maintain kitchen’s negative air pressure difference within acceptable limits (For operating and new hotels) A kitchen is typically designed to maintain negative air pressure difference in relation to dining area, with not more than 15 % of the amount of replacement air drawn from adjacent dining areas10. However, under certain circumstances, the negative air pressure difference becomes excessive and large amounts of air from dining area will constantly stream into the kitchen. If there is excessive negative air pressure difference, adjustments to the dampers of exhaust or supply fans are possible options to improve the situation. Ensure correct airflow patterns within indoor space; adjust supply air diffuser vanes, air damper settings and/or use portable air cleaners to supplement existing system (For operating and new hotels) Air distribution in any space should allow for a good continuous directional airflow through the space from supply air grille to return air grille, without any dead zone where air remains stagnant. To achieve this, (a) there should be appropriate separation distance between supply and return air grilles to prevent short-circuiting of air flows and (b) appropriate selection and placement of supply air grilles to ensure conditioned air reaches all areas; the same set of supply grilles with different vane directions results in a wide variety of air distribution patterns (see Figure 3). Thus, manufacturer’s recommendations should be closely followed. Figure 3 Illustration of depth of throw of conditioned air in relation to various grille deflections 5 For operating hotels with areas that are not well-ventilated with pockets of stagnant air, there are possible options such as (a) adjustments to supply air diffuser vanes and air dampers settings, and/or (b) use of portable high-efficiency particulate air (HEPA) air cleaners to supplement existing system. Enhance ventilation in elevators (For operating and new hotels) Elevators are enclosed occupant-dense areas. To improve ventilation, and where lift landing doors are not required to contribute to the protection of the building against fire, elevators could be programmed such that the doors are kept open when the elevators are idling. Ventilation fans should be sized such that the entire air volume of the elevator is replaced every hour, as per ASME standards11. Enhance air handling units (AHU) of high-risk (occupant-dense) areas (For operating and new hotels) Ballrooms, lobbies, pre-function areas, conference rooms – these occupant-dense areas have a high-risk of airborne transmissions. Below measures (Figure 4) should be considered: Figure 4: Enhancements for AHUs of high-risk (occupant- dense) areas 6 There are some points to take note before implementation of the enhancement measures: Use of higher-grade air filters results in higher pressure drop and reduced airflow. Depending on climatic conditions, fully opening outdoor air dampers and closing recirculation dampers may lead to a diminished heating/cooling capacity of the AHU. The room may not achieve designed temperature/humidity set-points and there may be acoustic noise issues due to larger amounts of air flowing through the outdoor air duct and grilles. If this measure is implemented, the temperature/humidity conditions of the indoor space needs to be carefully monitored and the occupancy of the space may have to be reduced accordingly. Control relative humidity (RH) within a range of 40 – 60%; adjust air-conditioning systems settings and/or use portable humidifiers to supplement existing system (For operating and new hotels) Typically, HVAC systems are designed to control humidity and in turn affect the transmissibility of pathogens. However, under certain circumstances, indoor environment’s RH may fall out of range. Studies show that indoor RH below 40% (see Figure 5) is associated with three factors that increases risk of infections: Aerosols shrink quickly to suspend in air much longer and gain the ability to travel further distances Many viruses have an increased survivability in low-RH conditions Humans become more susceptible due to dry air causing the protective mucous membranes of the nasal region to be impaired This measure is more relevant for very cold or desert climates where the outdoor air has low moisture content. For these operating hotels, it is important to verify that cooling, heating and humidification systems are operating at correct design parameters. Portable humidifier is an option to supplement existing system. 7 Figure 5: Indirect health effects of relative humidity in indoor environments 12 Ensure minimum 5 meters separation distance between all fresh air intake grilles and exhaust grilles (For operating and new hotels) Fresh air intakes and exhaust air grilles are typically located with a minimum 5 meters separation distance, as per ASHRAE recommendations. This helps prevent carry over of polluted exhaust air into fresh air intakes. Depending on the wind’s direction and speed, this distance may need to be extended further. For operating hotels, a site investigation should be carried out to determine how close/far the exhaust air grilles are to the supply air grilles. Mitigation measures such as extension of ducting or relocation of grilles may be necessary. Plan for re-commissioning of the ventilation systems for operating hotels; Enhance the commissioning of new ventilation systems for new hotels Commissioning13 is a quality-focused process aimed at verifying that systems are installed, tested, operated and maintained to meet specifications and standards. A typical commissioning for ventilation systems include testing and measurements, adjustments and balancing for all components of including AHU, fans, ducting, dampers and grilles. This process is typically completed by the general contractor before the premises are occupied. For operating hotels, a plan should be developed for a space-by-space re-commissioning, focused on identifying gaps and implementing measures to enhance the ventilation systems as highlighted previously. For new hotels, the commissioning process should have a renewed emphasis on indoor air quality. 8 CONCLUSION Applicability New Operating hotels hotels Proposed Mitigation Measure Provide minimum ventilation and exhaust for all areas as per ASHRAE or EN standard Avoid use of energy recovery ventilation systems that leak exhaust air into outdoor air supply Maintain kitchen’s negative air pressure difference within acceptable limits; adjust fans and air dampers Ensure correct airflow patterns within indoor spaces; Applicable areas All areas AHU and ventilation systems Kitchens and restaurants Adjust supply air diffuser vanes, air damper settings and/or use portable HEPA air cleaners to supplement All public areas, conference rooms and ballrooms existing system Enhance ventilation in elevators Elevators All public areas, conference rooms and Enhance AHU of high-risk (occupant-dense) areas: Fully open outdoor air damper, close re-circulating dampers, where indoor/outdoor conditions permit Disable demand-controlled ventilation Operate AHU for minimum 3-hours before and 3-hours after use Install higher-grade filters of minimum MERV-13 or F7 grade or higher Control relative humidity within 40 – 60 %; Adjust air-conditioning system settings and/or use of ballrooms All areas portable humidifiers to supplement existing system Ensure minimum 5 meters separation distance between fresh air intake grilles and exhaust grilles Plan for re-commissioning of ventilation systems; AHU and ventilation systems AHU and ventilation systems Enhance the commissioning of ventilation systems Table 1: Summary of mitigation measures and associated costs 9 Infectious aerosols can be transmitted within buildings through HVAC systems. Several measures are effective in disrupting transmission, including dilution, filtration, pressurisation, and having correct airflow patterns. All hotels should, as a minimum, continue to follow prevailing standards, guidelines and best practices in engineering design. Existing hotels should continue good maintenance practices such as filter cleaning/replacement, washing of cooling/heating coils, and ensuring HVAC equipment are in good working condition. Systems commissioning should have a renewed focus on indoor air quality. All above-mentioned HVAC mitigation measures (see Table 1) should be implemented, where appropriate, as they provide robust and effective level of control in HVAC systems together with planned preventative maintenance processes. The recommended measures do not incur capital cost for standards-compliant hotels; some measures will lead to a marginal increase in operating costs. Various countries and professional organisations are currently conducting research on how to enhance building codes and standards. There is also a lot of ongoing research and development on potentially workable solutions such as ultraviolet germicidal irradiator (UVGI) and electrostatic air cleaners. Broadly, several new technologies lack a test standard for verification of removal effectiveness and safety (see Annex). The situation will be closely monitored to identify proven strategies and solutions suitable for implementation in hotels. Prepared by: Joe Ong joe.ong@ihg.com Peer reviewed by: Barry Wormald b.wormald@aesg-me.com 10 ANNEX – INFORMATION OF AIR FILTRATION / CLEANING TECHNOLOGIES Air cleaning technology Fibrous filter Targeted pollutant Particles How does it work Collection: Fibrous or porous material to remove solid particulates such as dust, pollen, mould and bacteria. Rely on mechanical means to capture particles. Advantages Disadvantages Proven and widely used across all building types High-efficiency particulate air (HEPA) or ultra-low particulate air (ULPA) air filter can remove viral particles. HEPA/ULPA filters are used in critical facilities. Regular replacement is required HEPA/ULPA filters have high air pressure drop. Operating hotels fan motors are not sized to handle such pressure drops Electrostatictype fibrous filter Particles Collection: Air passing through the fibrous filter is statically charged. As air passes through subsequent layers, the charge is released, and particles are mechanically trapped in the filter. Proven and used in critical facilities Raises capture efficiency of mechanical filters with a much lower air pressure drop Higher capital cost Electrostatic precipitation (ESP) Particles Collection: Use of high voltage to charge up particles which collect on oppositely charged plates Low pressure drop Low maintenance High removal efficiency May have high ozone and nitrogen oxide generation rates. Both gases are indoor air pollutants Plates require cleaning May generate crackling noise as dust is accumulated Particle deposition in respiratory tract as particles become charged High power requirements Generates ozone Low effectiveness due to low airflow Ionisers Ultraviolet germicidal irradiation (UVGI) Particles Microbes Collection: Similar to ESP, electrically charge air molecules and generate ions to attach to airborne particles. Charged particles are then collected on oppositely charged plates in the air cleaner Destruction: UV-C light kills/inactivates airborne microbes Typically, low power draw requirements Low maintenance Effective with high dosage and sufficient exposure duration Typically used to inactivate microbes on cooling coils and surfaces, prevent biofilm formation Used in hospitals as upper-room air disinfection 11 Require minimum exposure duration to be effective In-duct airstream irradiation is not proven Potential for eye injury Susceptible to debris/dust Uncoated lamps generate ozone. Need to be mindful on lamp specifications Test standards and rating metrics Filters: ASHRAE Standard 52.2 (MERV) EN 779 ISO 16890 (for efficiency of particulate matter filters) ISO 29463 (HEPA) Portable air cleaners (HEPA): AHAM AC-1 Same as above ANSI/UL Standard 867 for electrical safety and ozone emissions Note: standard is only pass/fail; no rating metric None specified. Closest is ANSI/UL Standard 867 for electrical safety and ozone emissions Note: standard is only pass/fail; no rating metric Air irradiation: ASHRAE Standard 185.1 Surface irradiation: ASHRAE Standard 185.2 Air cleaning technology Activated carbon filters Targeted pollutant Gases How does it work Collection: Gases are adsorbed into the media Advantages Plasma bipolar ionisation Intentional ozone generation Gases Gases Conversion: Electric arc to ionise gas and break down chemical bonds of gas pollutants Conversion: Deliberate ozone production Disadvantages High removal efficiency of gaseous contaminants No by-product Preliminary information shows high removal efficiency Ozone is an effective air steriliser Photo catalytic oxidation (PCO) Gases Conversion: A high surface area media is coated with titanium dioxide; gases are adsorbed into the media and UV lamps activate the coating, causing a reaction with the adsorbed gases to transform them Can degrade a wide array of gaseous contaminants Not effective against viruses Regular replacement is required High pressure drops on sorbent media Standard test methods not widely used By-products are formed including particles, ozone, formaldehyde, carbon monoxide, nitrogen oxide. Needs to be used in tandem with other filtration such as activated carbon filters Ozone is an indoor air pollutant. Needs to be used in tandem with other less harmful means such as activated carbon filter to remove ozone. High amounts of by-products Can generate harmful by-product such as formaldehyde and ozone. Needs to be used in tandem with other less harmful means such as activated carbon filter to reduce harmful by-products. No standard test methods Lack of field studies to validate performance Note: The above table is closely referenced to: “Residential Air Cleaners – A Technical Summary” by US Environmental Protection Agency14 ASHRAE Position Document on Filtration and Air Cleaning, 201815 ASHRAE 2019 Handbook – HVAC Applications16 12 Test standards and rating metrics Media: ASHRAE Standard 145.1 In-duct air cleaners: ASHRAE Standard 145.2 Note: standards do not have any rating metric or effectiveness standards None specified. Closest is ANSI/UL Standard 867 for electrical safety and ozone emissions Note: standard is only pass/fail; no rating metric None specified. Closest is ANSI/UL Standard 867 for electrical safety and ozone emissions Note: standard is only pass/fail; no rating metric None specified. Closest is ANSI/UL Standard 867 for electrical safety and ozone emissions Note: standard is only pass/fail; no rating metric REFERENCES 1 REHVA. 2020. COVID-19 Guidance Document. https://www.rehva.eu/fileadmin/user_upload/REHVA_COVID19_guidance_document_ver2_20200403_1.pdf 2 ASHRAE. 2020. ASHRAE Position Document on Infectious Aerosols. https://www.ashrae.org/file%20library/about/position%20documents/pd_infectiousaerosols_2020.pdf 3 US CDC. 2020. Activities and Initiatives Supporting the COVID-19 Response https://www.cdc.gov/coronavirus/2019-ncov/downloads/php/CDC-Activities-Initiatives-for-COVID-19Response.pdf 4 European CDC. 2020. Heating, ventilation and air-conditioning systems in the context of COVID-19. https://www.ecdc.europa.eu/sites/default/files/documents/Ventilation-in-the-context-of-COVID-19.pdf 5 Moser, M.R., et al. 1979. An outbreak of influenza aboard a commercial airliner. American Journal of Epidemiology Volume 110(1): Page 1-6. 6 L. Morawska, et al. 2020. How can airborne transmission of COVID-19 indoors be minimised? Environment International. 7 Baron, P. n.d. Generation and Behaviour of Airborne Particles (Aerosols). Presentation published at CDC/NIOSH Topic Page: Aerosols, Center for Disease Control and Prevention. http://www.cdc.gov/niosh/topics/aerosols/pdfs/Aerosol_101.pdf 8 ASHRAE. 2019a. ANSI/ASHRAE Standard 62.1-2019, Ventilation for Acceptable Indoor Air Quality. Atlanta: ASHRAE. 9 EN. 2012. DIN EN 15251 Standard – Indoor Environmental Input Parameters. 10 HVCA. 2017. HVCA DW/172-2017, Specification for Kitchen Ventilation Systems. London: HVCA. 11 ASME. 2016. ASME A17.1-2016 – Safety Code for Elevators and Escalators. 12 Arundel, et al. 1986. Indirect Health Effects of Relative Humidity in Indoor Environments. Environmental Health Perspectives Volume 65: Page 351-361 13 CIBSE. 2006. CIBSE Commissioning Code A, Air Distribution Systems 14 US EPA. 2018. Residential Air Cleaners – A Technical Summary 3rd Edition https://www.epa.gov/sites/production/files/2018-07/documents/residential_air_cleaners__a_technical_summary_3rd_edition.pdf 15 ASHRAE. 2018. ASHRAE Position Document on Filtration and Air Cleaning https://www.ashrae.org/file%20library/about/position%20documents/filtration-and-air-cleaning-pd.pdf 16 ASHRAE. 2019. ASHRAE Handbook for HVAC Chapter 47: Air cleaners, Chapter 62: Ultraviolet air and surface treatment 13