EQUIPMENT SCHEDULE PHASE 1 LOWER GROUND FLOOR (SPLIT TYPE-FCU-FAN COIL UNIT) ITEM NO QTY. UNIT DESIG. 1 1 FLGF-1 2 2 FLGF-2 & FLGF-3 3 2 FLGF-4 & FLGF-5 AREA SERVED PRIVATE LECTURE ROOM PUBLIC HEALTH & TRAINING ROOM PUBLIC HEALTH & TRAINING ROOM NOMINAL CAPACITY TR HP BTU/HR AIR FLOW RATE CFM CMH FAN DATA OPERATING WT. SOUND LEVEL WATT VOLT PHASE CYCLE KGS. DBA FLOOR LEVEL TYPE LGF CEILING SUSPENDED 3.0 4.0 36,000 847 1,439 SIROCCO FAN 150 230 1 60 38 42 LGF CEILING SUSPENDED 2.0 2.5 24,000 600 1,020 SIROCCO FAN 117 230 1 60 32 38 LGF CEILING SUSPENDED 2.0 2.5 24,000 600 1,020 SIROCCO FAN 117 230 1 60 32 38 TYPE REMARKS UNIT SHALL BE INVERTER PACKAGE AIR C0NDITIOINING TYPE (CEILING SUSPENDED) COMPLETE WITH STANDARD ACCESSORIES UNIT SHALL BE INVERTER PACKAGE AIR C0NDITIOINING TYPE (CEILING SUSPENDED) COMPLETE WITH STANDARD ACCESSORIES. UNIT SHALL BE INVERTER PACKAGE AIR C0NDITIOINING TYPE (CEILING SUSPENDED) COMPLETE WITH STANDARD ACCESSORIES. LOWER GROUND FLOOR (SPLIT TYPE-ACCU-AIR COOLED CONDENSING UNIT) ITEM NO QTY. UNIT DESIG. 1 1 ALGF-1 2 2 ALGF-2 & ALGF-3 3 2 ALGF-4 & ALGF-5 AREA SERVED PRIVATE LECTURE ROOM PUBLIC HEALTH & TRAINING ROOM PUBLIC HEALTH & TRAINING ROOM NOMINAL CAPACITY TR HP BTU/HR 3.0 4.0 36,000 2.0 2.5 24,000 2.0 2.5 24,000 COMPRESSOR DATA TYPE KW HERMETICALLY SEALED SWING TYPE HERMETICALLY SEALED SWING TYPE HERMETICALLY SEALED SWING TYPE FAN DATA TYPE WATT CMH ELECTRICAL CHARACTERISTICS OPERATING WT. REF. PIPE SIZE MAX.PIPE LENGTH KW VOLT PHASE CYCLE KGS LIQUID GAS METERS 2.03 PROFELLER FAN 200 3,780 3.03 230 1 60 65 9.50 15.90 50 1.76 PROFELLER FAN 60 2,700 2.37 230 1 60 43 9.50 15.90 50 1.76 PROFELLER FAN 60 2,700 2.37 230 1 60 43 9.50 15.90 50 REMARKS 1. APPROPRIATE ACCU CLEARANCES SHALL BE BY MANUFACTURER'S INSTALLATION STANDARD. 2.APPROPRIATE ACCU FOOTING / MOUNTING BASE SUPPORT SHALL BE BY MANUFACTURER'S INSTALLATION STANDARD. 3.PROVIDE APPROPRIATE VIBRATION ISOLATOR FOR ACCU'S AND E MOTORS. 4.UNIT SHALL BE SUITABLE FOR OUTDOOR INSTALLATION C/W STD.ACCU'S. LOWER GROUND FLOOR - (VRF) ITEM NO QTY. UNIT DESIG. AREA SERVED FLOOR LEVEL 1 2 FLGF-A1,A2 RECEPTION / WAITING AREA LGF 2 1 FLGF-A3 COUNSELING ROOM LGF 3 1 FLGF-A4 COUNSELING ROOM LGF 4 1 FLGF-A5 5 1 FLGF-A6 PHU EXAMINATION ROOM 01 PHU EXAMINATION ROOM 02 6 1 FLGF-A7 PHU 01 LGF 7 1 FLGF-A8 PHU 02 LGF 8 1 FLGF-A9 PHU 03 LGF 9 1 FLGF-A10 PHU 04 LGF 10 1 FLGF-A11 PHU 05 LGF 11 1 FLGF-A12 PHU 06 LGF 12 1 FLGF-A13 PHU 07 LGF 13 1 FLGF-A14 PHU 8 LGF 14 1 FLGF-A15 PHU STAFF LOUNGE LGF 15 1 FLGF-A16 RECEPTION LGF 16 1 FLGF-A17 17 1 FLGF-A18 18 1 FLGF-A19 19 1 FLGF-A20 PHU ADMINITRATIVE OFFICE MEDICAL EDUC. GALLERY PH MED.TREATMENT EDUC.ROOM PHU LOBBY LGF LGF LGF LGF LGF LGF FAN COIL UNIT NOMINAL CAPACITY AIR FLOW RATE UNIT TYPE TR HP BTU/HR CFM CMH WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED WALL MOUNTED CEILING SUSPENDED WALL MOUNTED CEILING SUSPENDED CEILING MOUNTED CASSETTE ROUND FLOW CEILING MOUNTED CASSETTE ROUND FLOW CEILING MOUNTED CASSETTE ROUND FLOW 1.5 2 18,000 530 1020 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 1.0 1.5 12,000 300 510 3 4 36,000 883 1500 0.75 1 9,000 282 479 3 4 36,000 883 1500 3 4 36,000 1130 1921 3 4 36,000 1130 1921 3 4 36,000 1130 1921 FAN DATA ACCU(VRF TYPE) UNIT DESIG. WATTS VOLT PHASE CYCLE TYPE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE SIROCCO FAN DIRECT DRIVE CROSS FLOW FAN DIRECT DRIVE SIROCCO FAN DIRECT DRIVE TURBO FAN DIRECT DRIVE TURBO FAN DIRECT DRIVE TURBO FAN DIRECT DRIVE 33 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 40 230 1 60 130 230 1 60 40 230 1 60 130 230 1 60 120 230 1 60 120 230 1 60 120 230 1 60 AIR COOLED CONDENSING UNIT NOMINAL CAPACITY ELEC.CHARACTERISTICS HP BTU/HR KW VOLT PHASE CYCLE 40 ALGF - A 382,000 29.6 380 3 60 1. APPROPRIATE ACCU CLEARANCES SHALL BE BY MANUFACTURER'S INSTALLATION STANDARD. 2. APPROPRIATE ACCU FOOTING/ MOUNTING BASE SUPPORT SHALL BE BY MANUFACTURER'S INSTALLATION STANDARD. 3. PROVIDE APPROPRIATE VIBRATION ISOLATOR FOR BLOWERS, ACCU'S, AND E. MOTORS. 4.UNIT SHALL BE SUITABLE FOR OUTDOOR INSTALLATION C/W STD. ACC'S. LOWER GROUND FLOOR - VENTILATION SCHEDULE ITEM NO QTY. UNIT DESIG. AREA SERVED FLOOR LEVEL TYPE 1 7 TEF-LGF-1 TO 7 TOILET LGF 2 2 EF-LGF-1 & 2 AS SHOWN LGF CEILING CASSETTE CEILING CASSETTE 3 4 AC-LGF 1 TO 4 ENTRANCES LGF AIR CURTAIN AIR FLOW RATE CFM CMH TOTAL STATIC PRESSURE Pa. INCH CONSUMPTION WATTS ELEC.CHARACTERISTICS VOLT PHASE CYCLE 100 170 100 0.4 19 230 1 60 100 170 100 0.4 19 230 1 60 800 1360 N/A N/A 300 230 1 60 DENTAL UNIT AIR COMPRESSOR DATA REMARKS UNIT SHALL BE CEILING MOUNT CASSETTE TYPE SERVED AS TOILET EXHAUST FAN, MECHANICAL CONTRACTOR TO INSTALL WIRE AND MAKE UNIT OPERATIONAL. UNIT SHALL BE CEILING CASSETTE TYPE SERVED AS EXHAUST FAN, MECHANICAL CONTRACTOR TO INSTALL WIRE AND MAKE UNIT OPERATIONAL. MECHANICAL CONTRACTOR TO INSTALL WIRE AND MAKE UNIT OPERATIONAL. FAN SCHEDULE ITEM NO QTY. 1 REMARKS ITEM NO. 1 QTY. 5 UNIT DESIG. AIR COMPRESSOR AREA SERVED DENTAL UNIT 1 TO 5 FLOOR LEVEL UGF DENTAL OIL-LESS SILENT TYPE TYPE UNIT DESIG. AREA SERVED FLOOR LEVEL 7 OF-LGF 1 TO 7 AS SHOWN LGF 2 12 OF-GF 1 TO 12 AS SHOWN UGF 3 6 TF-GF1 TO 6 AS SHOWN UGF 4 2 HF-1 TO HF-2 UHS CENTRAL HALL 2F 5 2 OF-2F 1 TO 2 VIEWING AREA 2F TYPE CEILING MOUNTED ORBIT FAN CEILING MOUNTED ORBIT FAN CEILING MOUNTED TRANSFER FAN HELI FAN 5 AEROFOIL BLADES CEILING MOUNTED ORBIT FAN FAN DIAMETER INCH FT AIR FLOW CFM CMH MAX. RPM ELEC.CHARACTERISTICS VOLT PHASE CYCLE CONSUMPTION HP WATTS REMARKS 16 1.3 3,037 5162 1,410 0.10 75 230 1 60 COMPLETE WITH CEILING MOUNTED ON-OFF SWITCH. 16 1.3 3,037 5162 1,410 0.10 75 230 1 60 COMPLETE WITH CEILING MOUNTED ON-OFF SWITCH. N/A N/A 300 510 580 0.07 55 230 1 60 288 24 360,000 612,000 53 2 1,500 230 1 60 UNIT SHALL BE CEILING MOUNT CASSETTE TYPE SERVED AS TRANSFER FAN, MECHANICAL CONTRACTOR TO INSTALL WIRE AND MAKE UNIT OPERATIONAL. COMPLETE WITH CEILING MOUNTED ON-OFF SWITCH AND ACCESSORIES. 16 1.3 3,037 5162 1,410 75 230 1 60 COMPLETE WITH CEILING MOUNTED ON-OFF SWITCH. 0.10 UPPER GROUND FLOOR - BLOWERS SCHEDULE: AIR FLOW RATE CFM CMH TOTAL STATIC PRESSURE Pa. INCH MOTOR DRIVE HP ELEC.CHARACTERISTICS WATTS VOLT PHASE CYCLE ITEM NO QTY. UNIT DESIG. AREA SERVED FLOOR LEVEL 1 1 FAB1 GENERATOR ROOM UGF AXIAL BLOWER 9300 15800 250 1 3 800 380 3 60 2 1 ISO1 ISOLATION ROOM UGF NEGATIVE PRESSURE ISOLATION UNIT 582 990 N/A N/A 0.23 175 230 1 60 TYPE CAPACITY LITER TANK CAPACITY LITER SIZE LxWxH WT KGS MOTOR DRIVE HP ELEC. CHARACTERISTICS REMARKS UNIT SHALL BE COMPLETE PACKAGE WITH COMPLETE STANDARD ACCESSORIES. UNIT SHALL BE COMPLETE PACKAGE WITH STANDARD ACCESSORIES. REMARKS 165 35 410x410x600 27 1 WATTS VOLT PHASE 850 220 1 CYCLE 60 UNIT SHALL BE DENTAL OIL LESS AIR COMPRESSOR SILENT TYPE 1HP APPROVED OR EQUAL WITH COMPLETE STANDARD ACCESSORIES. EQUIPMENT SCHEDULE